SPECIFICATION DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Title: Distribution current transformers: specific requirements for current transformers manufactured in accordance with NRS 029, up to and including 132kV Reference: Revision: Effective date: Total pages: Revision date: DSP0013 5 MARCH 2006 15 MARCH 2009 COMPILED BY TESCOD APPROVED FUNCTIONAL RESP APPROVED BY AUTHORISED BY Signed _ _ _ _ _ _ _ _ Signed _ _ _ _ _ _ _ _ Signed _ _ _ _ _ _ _ _ Signed _ _ _ _ _ _ _ _ I F SIBEKO Engineer B MEYER "SC Chairperson" A BEKKER for TESCOD MN BAILEY CMDT for MD (Dx) Content Page 1. Foreword....................................................................................................................2 2. Requirements.............................................................................................................2 3. Supporting Clauses....................................................................................................3 4. Revisions ...................................................................................................................4 5. Annex A Core arrangements and tapping requirements............................................6 6. Annex B Technical schedules A and B ......................................................................14 7. Annex C Impact assessment .....................................................................................15 JFScholtz/Mar’06 (Rev 5) to ensure traceability DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 2 of 15 and including 132kV 1. Foreword The HV/MV Substation Design Work Group comprising the following members prepared this specification: N Laubscher H Prinsloo B Meyer R Maitland-Stuart F Wahl C Foley J Peyper J Jordaan C Clark V Naidoo N Weber Western Region Northern Region Western Region Eastern Region Northern Region Northern Region North Western Region Northern Region Distribution Technology Central Region Southern Region The Protection Design Work Group comprising the following members D Kehrberg P Gerber R Kleinhans Central Region Central Region North West Region The Metering Design Work Group represented by: E Louw Western Region And the Manufacturer Interest Group represented by: K Gilbert J Ferreira-Netto A Calvino 2. Alstom ETC Alstom Requirements Distribution current transformers shall comply with the requirements of NRS 029, and Eskom’s specific requirements as set out in annex A and schedule A of an enquiry document. Current transformers shall be manufactured and tested in accordance with NRS 029. The only distribution current transformers used by Eskom are in the following voltage ranges: 22 kV, 33 kV, 66 kV and 132 kV. Corrosion protection shall be in accordance with SCSSCAAP9. The tenderer shall complete technical schedule B of the enquiry document When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 3 of 15 and including 132kV 3. Supporting Clauses No section should be deleted: if not applicable, simply insert “NOT APPLICABLE”. 3.1. Index of Supporting Clauses Content ...................................................................................................................................... Page 3.1. Content Page........................................................................................................................... 3 3.2. Scope....................................................................................................................................... 3 3.3. Normative/Informative References.......................................................................................... 3 3.4. Definitions................................................................................................................................ 3 3.5. Abbreviations........................................................................................................................... 4 3.2. Scope This specification sets out the specific requirements relevant to distribution current transformers. 3.3. Normative References The following documents contain provisions that, through reference in the text, constitute requirements of this specification. At the time of publication, the editions indicated were valid. All standards and specifications are subject to revision, and parties to agreements based on this specification are encouraged to investigate the possibility of applying the most recent editions of the documents listed below. Information on currently valid national and international standards and specifications can be obtained from the Information Centre and Technology Standardisation Department at Megawatt Park. 3.3.1. Normative IEC 60044-4:1996, Instrument transformers – Part 1: Current transformers. IEC 60044-4:1980, Instrument transformers – Part 4: Measurement of partial discharge. SANS 60044-6:1992, Instrument transformers – Part 6: Requirements for protective current transformers for transient performance. SANS 60815: Guide for selection of insulators in respect of polluted conditions. NRS 029:2002, Current transformers for rated a.c. voltages from 3,6 kV up to and including 420kV(maximum voltage for equipment). SCSSCAAP9: Rev 1, Corrosion protection specification for distribution equipment manufactured from 3CR12 stainless steel and mild steel (Draft). SCSPVAC13: Rev 3, KIPTS natural ageing and pollution performance test procedure for outdoor insulation products Section 0- General requirements. SCSPVAC14: Rev 1, KIPTS natural ageing and pollution performance test procedure for outdoor insulation products Section 1- Particular requirements for Post, Longrod and Stand-off insulators. NRS 057-4:2001, Electricity metering – Part 4: Code of practice. 3.4. Definitions The definitions and abbreviations in NRS 029 shall apply, in addition to the following. When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 4 of 15 and including 132kV 3.5. Abbreviations 3.5.1. MR: Multi Ratio 3.5.2. T: Turns 3.5.3. BZ: Bus zone 4. Revisions DATE Jul’96 Jul’99 Jul’99 Feb2000 REV. NO. 0 1 2 2A NOTES Original issue. Various changes Changes made to tables 3.1, 3.2, 3.3 and 3.4 in annex A. Changes made to schedules A and B and these are listed below. 22 Kv CTs 1/2400 MR 1) Item1 Numbering changed. 2) Item 6a) 2500/1 MR changed to 2400/1 MR. 3) Item 19 Are electrogalvanizing, sherardizing etc. changed to Finish. 4) Item23 Yes changed to No. 22 Kv CTs 1/1600 MR 1) Item1 Numbering changed. 2) Item 4k) 1570 (min) changed to 150 (min). 3) Item 12 Missing text added. 4) Item 19 Are electrogalvanizing, sherardizing etc. changed to Finish. 5) Item23 Yes changed to No. 33 Kv CTs 1/1600 MR 1) Item1 Numbering changed. 2) Item 4k) 170 (min) changed to 200 (min). 3) Item 12 Missing text added. 4) Item 19 Are electrogalvanizing, sherardizing etc. changed to Finish. 5) Item23 Yes changed to No. 66 Kv CTs 1/1600 MR 1) Item1 Numbering changed. 2) Item 4k) 325 (min) changed to 350 (min). 3) Item 20 Are electrogalvanizing, sherardizing etc. changed to Finish. 4) Item24 Yes changed to No. Apr’04 3(A) Nov’04 4 132 Kv CTs 1/1600 MR 1) Item1 Numbering changed. 2) Item 20 Are electrogalvanizing, sherardizing etc. changed to Finish. 1) Change stems to pads 2) Add KIPTS – General requirements. Document reference number changed from SCS to DIS. Document approved. When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 5 of 15 and including 132kV Aug’05 4A Feb’06 Ar’06 4A 5 1) Requirements. 2) Metering ratios on the 2400/1 to align with NRS 029. 3) Tables updated. 4) Update schedules in accordance with NRS 029. 5) Routine tests certificates to be supplied with each unit. Comments. Document approved. When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 6 of 15 and including 132kV 5. 5.1. Annex A Core arrangements and tapping requirements Core arrangements: The core arrangements are shown in A.1.1 and A.1.2. It is important to note the primary polarity markings with respect to the core arrangement. The six-core arrangement will be used primarily on phase 1 and phase 2 protection schemes. It will also be used on existing stations with High Impedance busbar protection schemes with main and check zone configuration. It will also be used where metering dictates a requirement for a main and back-up metering core arrangement (i.e. – interregional tariff metering or bulk supply metering points) 5.1.1. Six-core arrangement: P1 P CORE 1 5.1.2. BZ CORE 2 CORE 3 P CORE 4 M CORE 5 M P2 CORE 6 Four-core arrangement: P1 P P CORE 1 5.2. BZ M M CORE 2 P2 CORE 4 CORE 3 Core tapping requirements: Core tapping for protection and metering shall be provided as specified in A.2.1 to A.2.4. 5.2.1. Protection Multi-ratio 1/1600 T PROTECTION: MR 1/1600T 200 S1 5.2.2. 600 S2 400 S3 400 S4 S5 Protection multi-ratio 1/2400 T PROTECTION: MR 1/2400T 400 S1 200 S2 1000 S3 800 S4 S5 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 7 of 15 and including 132kV 5.2.3. Metering multi-ratio 1/2400: METERING: MR 2400/1 400 S1 5.2.4. S2 200 S3 800 1000 S5 S4 Metering multi-ratio 1600/1: METERING: MR 1600/1 S1 5.2.5. 400 600 200 S2 400 S5 S4 S3 Bus zone multi-ratio 1/1600: BUS ZONE: MR 1/1600 1000 ……….. S1 5.3. 200 S2 400 S3 S4 Specifications: The specifications listed below are coupled with IEC 60044-4 and SANS 60044-6: only the relevant output data are given below. In the case of Class TPS CTs all specifications are given at the maximum tap and can be interpolated linearly upwards (i.e. I magnetisation in mA). In the case of metering CTs all specifications are given at the lowest tap and can be interpolated upward (i.e. Rated output in VA). When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 8 of 15 and including 132kV 5.4. Four-core, 22 kV current transformer 2400/1: Table A.5.1 CORE No. 1&2 3&4 TAPPING RATIO CLASS S2 – S3 S1 – S2 S1 – S3 S4 – S5 S3 – S4 S2 – S4 S1 – S4 S3 – S5 S2 – S5 S1 – S5 S1 – S2 S3 – S4 S2 – S3 S1 – S3 S2 – S4 S1 – S5 1/200T 1/400T 1/600T 1/800T 1/1000T 1/1200T 1/1600T 1/1800T 1/2000T 1/2400T 400/1 800/1 1200/1 1600/1 2000/1 2400/1 TPS TPS TPS TPS TPS TPS TPS TPS TPS TPS 0,2 0,2 0,2 0,2 0,2 0,2 Vknee Min or VA 200 400 600 800 1000 1200 1600 1800 2000 2400 5VA 10VA 10VA 10VA 10VA 10VA Imag Max 504mA 420mA 378mA 336mA 252mA 210mA 168mA 126mA 84mA 42mA - Rct (Ω) @ 75°C 0,8 1,6 2,4 3,2 4,0 4,8 6,4 7,2 8,0 9,6 - Notes : Imag Max values : [mA] : Manufacturer to concur with IEC 60044 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 9 of 15 and including 132kV 5.4.1. Data table, Four-core, 33kV & 22 kV current transformer 1600/1: Table A.5.2 CORE No. 1&2 3&4 TAPPING RATIO CLASS S1 – S2 S3 – S4 S2 – S3 S1 – S3 S2 – S4 S1 – S4 S2 – S5 S1 – S5 S1 – S2 S3 – S4 S2 – S3 S1 – S3 S2 – S4 S1 – S4 S2 – S5 S1 – S5 1/200T 1/400T 1/600T 1/800T 1/1000T 1/1200T 1/1400T 1/1600T 200/1 400/1 600/1 800/1 1000/1 1200/1 1400/1 1600/1 TPS TPS TPS TPS TPS TPS TPS TPS 0,5 0,2 0,2 0,2 0,2 0,2 0,2 0,2 Vknee Min or VA 200 400 600 800 1000 1200 1400 1600 5VA 10VA 10VA 10VA 10VA 10VA 10VA 10VA Imag Max 504mA 441mA 378mA 315mA 252mA 189mA 126mA 63mA - Rct (Ω) @ 75°C 0,8 1,6 2,4 3,2 4,0 4,8 5,6 6,4 - Notes : Imag Max values : [mA] : Manufacturer to concur with IEC 60044 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 10 of 15 and including 132kV 5.4.2. Buszone 1/500T fixed ratio 66kV current transformer: Table A.5.3 CORE No. 1&4 2&3 5&6 Imag Max TPS TPS TPS TPS TPS TPS TPS TPS Vknee Min or VA 200 400 600 800 1000 1200 1400 1600 504mA 441mA 378mA 315mA 252mA 189mA 126mA 63mA Rct (Ω) @ 75°C 0,8 1,6 2,4 3,2 4,0 4,8 5,6 6,4 1/500T TPS 550 50mA 2,0 200/1 400/1 600/1 800/1 1000/1 1200/1 1400/1 1600/1 0,5 0,2 0,2 0,2 0,2 0,2 0,2 0,2 5VA 10VA 10VA 10VA 10VA 10VA 10VA 10VA - - TAPPING RATIO CLASS S1 – S2 S3 – S4 S2 – S3 S1 – S3 S2 – S4 S1 – S4 S2 – S5 S1 – S5 1/200T 1/400T 1/600T 1/800T 1/1000T 1/1200T 1/1400T 1/1600T S1 – S2 S1 – S2 S3 – S4 S2 – S3 S1 – S3 S2 – S4 S1 – S4 S2 – S5 S1 – S5 Notes : Imag Max values : [mA] : Manufacturer to concur with IEC 60044 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 11 of 15 and including 132kV 5.4.3. Multi-ratio Buszone 66kV current transformer: Table A.4 Imag Max Rct (Ω) @ Vknee Min or VA 75°C S1 – S2 1/200T TPS 200 504mA 0,8 S3 – S4 1/400T TPS 400 441mA 1,6 S2 – S3 1/600T TPS 600 378mA 2,4 1&4 S1 – S3 1/800T TPS 800 315mA 3,2 S2 – S4 1/1000T TPS 1000 252mA 4,0 S1 – S4 1/1200T TPS 1200 189mA 4,8 S2 – S5 1/1400T TPS 1400 126mA 5,6 S1 – S5 1/1600T TPS 1600 63mA 6,4 S1 – S2 1/1000T TPS* 550 50mA 2 2&3 S1 – S3 1/1200T TPS* 660 42mA 2,4 S1 – S4 1/1600T TPS* 880 31mA 3,2 S1 – S2 200/1 0,5 5VA S3 – S4 400/1 0,2 10VA 5&6 S2 – S3 600/1 0,2 10VA S1 – S3 800/1 0,2 10VA S2 – S4 1000/1 0,2 10VA S1 – S4 1200/1 0,2 10VA S2 – S5 1400/1 0,2 10VA S1 – S5 1600/1 0,2 10VA TPS* - definition of kneepoint : 10% increase of voltage, 50% increase of Imag, r.m.s. values CORE No. TAPPING RATIO CLASS Notes : Imag Max values : [mA] : Manufacturer to concur with IEC 60044 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 12 of 15 and including 132kV 5.4.4. Buszone 1/500T fixed ratio 132kV current transformer: Table A.5 CORE No. 1&4 2&3 5&6 Imag Max TPS TPS TPS TPS TPS TPS TPS TPS TPS TPS Vknee Min or VA 200 400 600 800 1000 1200 1600 1800 2000 2400 504mA 420mA 378mA 336mA 252mA 210mA 168mA 126mA 84mA 42mA Rct (Ω) @ 75°C 0,8 1,6 2,4 3,2 4,0 4,8 6,4 7,2 8,0 9,6 1/500T TPS 550 50mA 2,0 400/1 800/1 1200/1 1600/1 2000/1 2400/1 0,2 0,2 0,2 0,2 0,2 0,2 5VA 10VA 10VA 10VA 10VA 10VA - - TAPPING RATIO CLASS S2 – S3 S1 – S2 S1 – S3 S4 – S5 S3 – S4 S2 – S4 S1 – S4 S3 – S5 S2 – S5 S1 – S5 1/200T 1/400T 1/600T 1/800T 1/1000T 1/1200T 1/1600T 1/1800T 1/2000T 1/2400T S1 – S2 S1 – S2 S3 – S4 S2 – S3 S1 – S3 S2 – S4 S1 – S4 Notes : Imag Max values : [mA] : Manufacturer to concur with IEC 60044 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 13 of 15 and including 132kV 5.4.5. Buszone Multi-ratio ratio 132kV current transformer: Table A.6 Imag Max Rct (Ω) @ Vknee Min or VA 75°C S2 – S3 1/200T TPS 200 504mA 0,8 S1 – S2 1/400T TPS 400 420mA 1,6 S1 – S3 1/600T TPS 600 378mA 2,4 S4 – S5 1/800T TPS 800 336mA 3,2 1&4 S3 – S4 1/1000T TPS 1000 252mA 4,0 S2 – S4 1/1200T TPS 1200 210mA 4,8 S1 – S4 1/1600T TPS 1600 168mA 6,4 S3 – S5 1/1800T TPS 1800 126mA 7,2 S2 – S5 1/2000T TPS 2000 84mA 8,0 S1 – S5 1/2400T TPS 2400 42mA 9,6 S1 – S2 1/1000T TPS* 550 50mA 2 2&3 S1 – S3 1/1200T TPS* 660 42mA 2,4 S1 – S4 1/1600T TPS* 880 31mA 3,2 S1 – S2 400/1 0,2 5VA S3 – S4 800/1 0,2 10VA 5&6 S2 – S3 1200/1 0,2 10VA S1 – S3 1600/1 0,2 10VA S2 – S4 2000/1 0,2 10VA S1 – S4 2400/1 0,2 10VA TPS* - definition of kneepoint : 10% increase of voltage, 50% increase of Imag, r.m.s. values CORE No. TAPPING RATIO CLASS Notes : Imag Max values : [mA] : Manufacturer to concur with IEC 60044 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 14 of 15 and including 132kV 6. Annex B Technical schedules A and B The schedules A and B are provided for purchasing current transformers. The purchaser’s technical requirements are in schedule A. Schedule B is for the suppliers to fill in with the guarantees and technical details of the offered products. The following list serves as an index of the schedules A and B: Measuring core Protection core Bus zone core SAP number 22 kV for use in medium pollution conditions (20 mm/kV) Current transformer 2400/1 MR 1/2400T MR – 0008742 22 kV for use in very heavy pollution conditions (31 mm/kV) 2400/1 MR 1/2400T MR – 0180088 22 kV for use in medium pollution conditions (20 mm/kV) 1600/1 MR 1/1600T MR – 0008743 22 kV for use in very heavy pollution conditions (31 mm/kV) 1600/1 MR 1/1600T MR – 0180087 33 kV for use in medium pollution conditions (20 mm/kV) 1600/1 MR 1/1600T MR – 0017521 33 kV for use in very heavy pollution conditions (31 mm/kV) 1600/1 MR 1/1600T MR – 0180038 66 kV for use in medium pollution conditions (20 mm/kV) 1600/1 MR 1/1600T MR 1/1600T MR 0180036 66 kV for use in very heavy pollution conditions (31 mm/kV) 1600/1 MR 1/1600T MR 1/1600T MR 0180037 66 kV for use in medium pollution conditions (20 mm/kV) 1600/1 MR 1/1600T MR 1/500T 0017520 66 kV for use in very heavy pollution conditions (31 mm/kV) 1600/1 MR 1/1600T MR 1/500T 0180035 132 kV for use in medium pollution conditions (20 mm/kV) 2400/1 MR 1/2400T MR 1/1600T MR 0180033 132 kV for use in very heavy pollution conditions (31 mm/kV) 2400/1 MR 1/2400T MR 1/1600T MR 0180034 132 kV for use in medium pollution conditions (20 mm/kV) 2400/1 MR 1/2400T MR 1/500T 0008653 132 kV for use in very heavy pollution conditions (31 mm/kV) 2400/1 MR 1/2400T MR 1/500T 0180031 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. DOCUMENT CLASSIFICATION: CONTROLLED DISCLOSURE Reference: Distribution current transformers: specific Revision: requirements for current transformers manufactured in accordance with NRS 029, up to Page: DSP0013 5 15 of 15 and including 132kV 7. Annex C Impact assessment Impact assessment Document title: Document no: Distribution current transformer: specific requirements for current transformers manufactured in accordance with NRS 029, up to and including 132kV Revision no: DSP0013 5 Activity Detail What training is required to implement this document? (e.g. Awareness training, practical / on job, module.) Who will require training? (State designations.) What prerequisites are needed for students? What equipment will be required for training? (Computers etc.) What special tools will be required for training? What special requirements are needed for the trainer? Time period for training to be completed? What special tools / equipment will be needed to be purchased by the Region to effectively implement? Are there stock numbers available for the new equipment? Does the document affect the budget? Time period for implementation of requirements after training is completed? Does the Buyers Guide or Buyers List need updating? What Buyer’s Guides have been created? Was Training & Development consulted w.r.t training requirements? Were the critical points in the document determined? Is any training material available on the subject in this document? Was the document SCSPVABE0 adhered to? N/A No N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Yes Total implementation period Total training cost Total cost of tools / equipment Total cost involved Comments: Assessment Compiled by: Name: Designation: Dept: Date: I F Sibeko Engineer Plant Techn. IARC October 2005 Recommended by (Functional Responsibility): Name: B Meyer Designation: Project Engineering Man Dept: Western Region Date: October 2005 When downloaded from the IARC Web, this document is uncontrolled and the responsibility rests with the user to ensure it is in line with the authorised version on the Web. ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) Measuring core ratio: 2400/1 MR Protection core ratio: 2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Inland Medium Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 22 b) Maximum system voltage (line-to-line) voltage (Um) kV 24 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 2500 f) Nominal short time current (Thermal) kA 25 g) Nominal short time current (Dynamic) kA 64 s 3 j) Power frequency short-duration withstand voltage kV 50 (min) k) kV 150 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 b) size mm c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxx Diameter of the holes mm 18 xxxxxxxxx 100/120/20 xxxxxxxxx xxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Schedule B Drawings and literature required with tender 6 xxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxx Details of CT cores a) Number of cores b) Number of measuring cores c) Number of protection cores for 4 2M ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item C.15 Subclause 4.2.2 Description Schedule A General purposes Bus zone 2P xxxxxxxxxx Differential xxxxxxxxxx Details of measuring core Details of core number Core 3 & 4 a) Nominal ratio A/A 2400/1 MR b) Rated burden VA 10 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx 1) Instrument security factor at 400/1 ratio C.16 4.2.3 Schedule B xxxxxxxxx 20 2) Are core steel details required? Yes xxxxxxxxx 3) Is B/H curve of annealed core required? Yes xxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 2 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/2400T MR 2500 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve 1) Are core steel details required? 2) Is B/H curve of annealed core required? xxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxx xxxxxxxxx Copper xxxxxxxxx Flat xxxxxxxxx 50 × 3 xxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate Schedule B kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are valid type test certificates available? xxxxxxxxxx If No, are type tests to be carried out? Yes xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 20 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No For ratios for multi-ratio (MR) measuring and protection current transformers see annex A of DSP0013. ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) Measuring core ratio: 2400/1 MR Protection core ratio: 2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Humid salt air Very heavy Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 22 b) Maximum system voltage (line-to-line) voltage (Um) kV 24 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 2500 f) Nominal short time current (Thermal) kA 25 g) Nominal short time current (Dynamic) kA 64 s 3 j) Power frequency short-duration withstand voltage kV 50 (min) k) kV 150 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Schedule B Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause Description Schedule A Schedule B Details of CT cores a) Number of cores 4 b) Number of measuring cores 2M c) Number of protection cores for General purposes Bus zone 2P xxxxxxxxxx Differential C.15 4.2.2 xxxxxxxxxx Details of measuring core Details of core number Core 3 & 4 a) Nominal ratio A/A b) Rated burden VA c) Accuracy class xxxxxxxx See annex A e) Means used to effect ratio changes if required xxxxxxxxx Instrument security factor at 400/1 ratio 4.2.3 10 0,2 d) Ratio for which (b) and (c) apply C.16 2400/1 MR 20 Are core steel details required? Yes xxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 2 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/2400T MR 2500 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxx xxxxxxxx Copper xxxxxxxx Flat xxxxxxxx 50 × 3 xxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate Schedule B kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 31 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No For ratios for multi-ratio (MR) measuring and protection current transformers see annex A of DISSCAAF4. ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Inland Medium Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 22 b) Maximum system voltage (line-to-line) voltage (Um) kV 24 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 50 (min) k) kV 150 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxx b) Manufacturer type designation xxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Schedule B Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three Details of CT cores a) Number of cores b) Number of measuring cores c) Number of protection cores for General purposes Bus zone 4 2M 2P xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Differential C.15 4.2.2 xxxxxxxxxx Details of measuring core Details of core number Core 3 & 4 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 Schedule B xxxxxxxx 20 Are core steel details required? Yes xxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 2 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/1600T MR 1600 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxx xxxxxxxx Copper xxxxxxxx Flat xxxxxxxx 50 × 3 xxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Schedule B xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate kA l 20 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 20 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C.20 C.21 Description Schedule B High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 Schedule A 5.3 At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No For ratios for multi-ratio (MR) measuring and protection current transformers see annex A of DISSCAAF4. ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Humid salt air Very heavy Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 22 b) Maximum system voltage (line-to-line) voltage (Um) kV 24 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 50 (min) k) kV 150 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Schedule B Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx Details of CT cores a) Number of cores 4 b) Number of measuring cores 2M c) Number of protection cores for General purposes 2P ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Differential C.15 4.2.2 xxxxxxxxxx Details of measuring core Details of core number Core 3 & 4 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 Schedule B xxxxxxxx 20 Are core steel details required? Yes xxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 2 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/1600T MR 1600 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxx xxxxxxxx Copper xxxxxxxx Flat xxxxxxxx 50 × 3 xxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate Schedule B kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 31 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 22 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No For ratios for multi-ratio (MR) measuring and protection current transformers see annex A of DSP0013. ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in medium pollution conditions (20mm/kV) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Inland Medium Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 33 b) Maximum system voltage (line-to-line) voltage (Um) kV 36 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 70 (min) k) kV 200 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Schedule B Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx Details of CT cores a) Number of cores b) Number of measuring cores c) Number of protection cores for General purposes Bus zone 4 2M 2P xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Differential C.15 4.2.2 xxxxxxxxxx Details of measuring core Details of core number Core 3 & 4 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 200/1 ratio C.16 4.2.3 Schedule B xxxxxxxx 20 Are core steel details required? Yes xxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 2 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/1600T MR 1600 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxx xxxxxxxx Copper xxxxxxxx Flat xxxxxxxx 50 × 3 xxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate Schedule B kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 20 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. chnical schedules A and B for 33 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions Humid salt air Very heavy c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 33 b) Maximum system voltage (line-to-line) voltage (Um) kV 36 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 70 (min) k) kV 200 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Schedule B Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx Details of CT cores a) Number of cores 4 b) Number of measuring cores 2M c) Number of protection cores for General purposes 2P ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Differential C.15 4.2.2 xxxxxxxxxx Details of measuring core Details of core number Core 3 & 4 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 Schedule B xxxxxxxxxx 20 Are core steel details required? Yes xxxxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 2 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/1600T MR 1600 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper xxxxxxxxxx Flat xxxxxxxxxx 50 × 3 xxxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate Schedule B kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 31 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 33 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Bus zone core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Inland Medium Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 66 b) Maximum system voltage (line-to-line) voltage (Um) kV 72,5 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 140 (min) k) kV 350 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxx b) Manufacturer type designation xxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Schedule B Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx Details of CT cores a) Number of cores b) Number of measuring cores c) Number of protection cores for 4 2M ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item C.15 Subclause 4.2.2 Description Schedule A General purposes Bus zone 2P xxxxxxxxxx Differential xxxxxxxxxx Details of measuring core Details of core number Core 5 & 6 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 Schedule B xxxxxxxxxx 20 Are core steel details required? Yes xxxxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 4 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/1600T MR 1600 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper xxxxxxxxxx Flat xxxxxxxxxx 50 × 3 xxxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A xxxxxxxxxx Manufacturer of HV porcelain insulators kA 25 l xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx Total mass of current transformer kg xxxxxxxxxx Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate Schedule B c) Overall dimensions of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 20 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Bus zone core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Humid salt air Very heavy Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 66 b) Maximum system voltage (line-to-line) voltage (Um) kV 72,5 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 140 (min) k) kV 350 (min) h) Time for which thermal applies C.4 C.5 4.1 4.1.4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx Details of insulation materials xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause 4.1.4.2 Description Schedule A Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator C6 C.7 4.1.5 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Yes Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 b) size mm c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx 100/120/20 xxxxxxxxxx xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Schedule B Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause Description Schedule A Schedule B Details of CT cores a) Number of cores 4 b) Number of measuring cores 2M c) Number of protection cores for General purposes Bus zone 2P xxxxxxxxxx Differential C.15 4.2.2 xxxxxxxxxx Details of measuring core Details of core number Core 3 & 4 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 xxxxxxxxxx 20 Are core steel details required? Yes xxxxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 2 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/2400T MR 2500 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper xxxxxxxxxx Flat xxxxxxxxxx 50 × 3 xxxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Schedule B xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 31 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Bus zone core ratio: 1/500T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Inland Medium Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 66 b) Maximum system voltage (line-to-line) voltage (Um) kV 72,5 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 140 (min) k) kV 350 (min) h) Time for which thermal applies C.4 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Sub-clause C.5 Description Schedule A Schedule B 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator C6 C.7 4.1.5 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Yes Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Details of CT cores 4 a) Number of cores 2M Schedule B b) Number of measuring cores c) Number of protection cores for General purposes C.15 4.2.2 2P Bus zone xxxxxxxxxx Differential xxxxxxxxxx Details of measuring core Details of core number Core 5 & 6 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 xxxxxxxxxx 20 Are core steel details required? Yes xxxxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 4 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? 1/1600T MR 1600 2 TPS V See annex A mA Ω See annex A See annex A xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper xxxxxxxxxx Flat xxxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description c) Size Schedule A Schedule B mm Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate xxxxxxxxxx xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith 50 × 3 kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 20 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Bus zone core ratio: 1/500T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Humid salt air Medium Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 66 b) Maximum system voltage (line-to-line) voltage (Um) kV 72,5 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 140 (min) k) kV 350 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 b) size mm c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx 100/120/20 xxxxxxxxxx xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Schedule B Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx Details of CT cores a) Number of cores 4 b) Number of measuring cores 2M c) Number of protection cores for General purposes 2P ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item C.15 Subclause 4.2.2 Description Schedule A Bus zone xxxxxxxxxx Differential xxxxxxxxxx Details of measuring core Details of core number Core 5 & 6 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 Schedule B xxxxxxxxxx 20 Are core steel details required? Yes xxxxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 4 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/1600T MR 1600 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper xxxxxxxxxx Flat xxxxxxxxxx 50 × 3 xxxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Schedule B xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 20 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 66 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 1600/1 MR Protection core ratio: 1/1600T MR Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Bus zone core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Inland Medium Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 66 b) Maximum system voltage (line-to-line) voltage (Um) kV 72,5 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 1600 f) Nominal short time current (Thermal) kA 20 g) Nominal short time current (Dynamic) kA 51 s 3 j) Power frequency short-duration withstand voltage kV 140 (min) k) kV 350 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 b) size mm c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx 100/120/20 xxxxxxxxxx xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Schedule B Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Schedule B Details of CT cores a) Number of cores 4 b) Number of measuring cores 2M c) Number of protection cores for General purposes C.15 4.2.2 2P Bus zone xxxxxxxxxx Differential xxxxxxxxxx Details of measuring core Details of core number Core 5 & 6 a) Nominal ratio A/A 1600/1 MR b) Rated burden VA 5 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 xxxxxxxxxx 20 Are core steel details required? Yes xxxxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 4 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/1600T MR 1600 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper xxxxxxxxxx Flat xxxxxxxxxx 50 × 3 xxxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate Schedule B kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 20 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Bus zone core ratio: 1/1600T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Inland Medium Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 132 b) Maximum system voltage (line-to-line) voltage (Um) kV 145 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 2500 f) Nominal short time current (Thermal) kA 25 g) Nominal short time current (Dynamic) kA 64 s 3 j) Power frequency short-duration withstand voltage kV 230 (min) k) kV 550 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Schedule B Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx Details of CT cores a) Number of cores b) Number of measuring cores c) Number of protection cores for 4 2M ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause Description Schedule A General purposes C.15 4.2.2 2P Bus zone xxxxxxxxxx Differential xxxxxxxxxx Details of measuring core Details of core number Core 5 & 6 a) Nominal ratio A/A 2400/1 MR b) Rated burden VA 10 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 Schedule B xxxxxxxxxx 20 Are core steel details required? Yes xxxxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 4 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/2400T MR 2500 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper xxxxxxxxxx Flat xxxxxxxxxx 50 × 3 xxxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause Description Schedule A Schedule B xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 31 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Bus zone core ratio: 1/500T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.1 1.2 Description Schedule A Schedule B Service conditions a) Altitude m b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required Humid salt air Very heavy Yes a) Access to site by Road b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position Yes No m e) Nature of ground to be traversed f) Rise to fall 1800 300 Soft earth m g) Erection prepared steel support structures 3 Yes h) Construction power supply available Yes/No j) Is mounting structure to be provided by the supplier? C.3 4.1 General requirements a) Nominal system voltage (line-to-line) voltage (Un) kV 132 b) Maximum system voltage (line-to-line) voltage (Um) kV 145 c) Frequency Hz 50 xxxxxxxxxx 3 xxxxxxxxxx d) Number of phases e) Nominal continuous primary current A 2500 f) Nominal short time current (Thermal) kA 25 g) Nominal short time current (Dynamic) kA 64 s 3 j) Power frequency short-duration withstand voltage kV 230 (min) k) kV 550 (min) h) Time for which thermal applies C.4 C.5 4.1 Lightning impulse withstand voltage Type of current transformers offered a) Manufacturer of current transformer xxxxxxxxxx b) Manufacturer type designation xxxxxxxxxx 4.1.4.1 Details of insulation materials xxxxxxxxxx 4.1.4.2 Manufacturer of HV porcelain insulators xxxxxxxxxx Detailed drawing of insulator Yes ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/500T MR Item Subclause C6 4.1.5 C.7 4.1.6 4.1.6.5 C.8 C.10 C.11 C.12 C.13 4.1.3 4.3.5 4.3.6 4.4 Description Schedule A Schedule B Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method xxxxxxxxxx b) Sealing arrangements xxxxxxxxxx c) Oil-level indicators xxxxxxxxxx Gas-insulated current transformers Method of sealing xxxxxxxxxx Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes mm 4x14 xxxxxxxxxx b) size mm 100/120/20 xxxxxxxxxx c) hole centres mm 50x50 Holding down bolts to be arranged to fall within a square of maximum dimensions mm 706 × 706 xxxxxxxxxx Diameter of the holes mm 18 xxxxxxxxxx Mounting arrangement Finish Finish offered on ferrous parts xxxxxxxxxx Finish offered on non-ferrous parts xxxxxxxxxx Rating and diagram plates 4.4.1 a) Materials used for rating plates xxxxxxxxxx 4.4.5 b) Material used for diagram plates xxxxxxxxxx 4.4.5 c) Method of fixing diagram and rating plates xxxxxxxxxx 4.5 Drawings and literature required with tender 6 xxxxxxxxxx Number of instruction books required if other than three 6 xxxxxxxxxx Number of descriptive pamphlets required if other than three 6 xxxxxxxxxx Details of CT cores a) Number of cores b) Number of measuring cores c) Number of protection cores for 4 2M ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/500T MR Item Subclause Description Schedule A General purposes C.15 4.2.2 2P Bus zone xxxxxxxxxx Differential xxxxxxxxxx Details of measuring core Details of core number Core 5 & 6 a) Nominal ratio A/A 2400/1 MR b) Rated burden VA 10 c) Accuracy class 0,2 d) Ratio for which (b) and (c) apply See annex A e) Means used to effect ratio changes if required Xxxxxxxxxx Instrument security factor at 400/1 ratio C.16 4.2.3 Schedule B xxxxxxxxxx 20 Are core steel details required? Yes xxxxxxxxxx Is B/H curve of annealed core required? Yes xxxxxxxxxx Details of protection core a) Details core number b) Nominal turns ratio c) Continuous current rating 1) Primary 2) Secondary Core 1 & 4 Turns A A d) Accuracy class e) Rated knee-point voltage Vk f) Magnetising current j) Maximum total secondary winding resistance Ri 1/2400T MR 2500 2 TPS V See annex A mA Ω See annex A See annex A k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? xxxxxxxxxx xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper xxxxxxxxxx Flat xxxxxxxxxx 50 × 3 xxxxxxxxxx Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause Description Schedule A Schedule B xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV Tests Are type test results available? xxxxxxxxxx Yes/No If No, are type tests to be carried out? Yes xxxxxxxxxx xxxxxxxxxx If required where are the type tests to be carried out? C.19 5.12 20 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in medium pollution conditions (20mm/kV) (concluded) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No For ratios for multi-ratio (MR) measuring protection and bus zone current transformers see annex A of DSP0013. ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 1 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Bus zone core ratio: 1/500T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item SubDescription clause 1.2 C.1 Service conditions a) Altitude b) Climate conditions c) Level of pollution that equipment will be subjected to d) Lightning area When erection is required a) Access to site by b) To be off-loaded from transport by supplier? c) Crane available for off-loading? d) Distance from off-loading point to operation position e) Nature of ground to be traversed f) Rise to fall g) Erection prepared steel support structures h) Construction power supply available j) Is mounting structure to be provided by the supplier? 4.1 C.3 General requirements a) Nominal system voltage (line-to-line) voltage (Un) b) Maximum system voltage (line-to-line) voltage (Um) c) Frequency d) Number of phases e) Nominal continuous primary current f) Nominal short time current (Thermal) g) Nominal short time current (Dynamic) h) Time for which thermal applies j) Power frequency short-duration withstand voltage k) Lightning impulse withstand voltage 4.1 Type of current transformers offered C.4 C.5 4.1.4.1 4.1.4.2 a) Manufacturer of current transformer b) Manufacturer type designation Details of insulation materials Manufacturer of HV porcelain insulators Detailed drawing of insulator Schedule A m m m kV kV Hz A kA kA s kV kV Schedule B 1800 Humid salt air Medium Yes Road Yes No 300 Soft earth 3 Yes Yes/No 66 72,5 50 3 1600 20 51 3 140 (min) 350 (min) xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx Yes xxxxxxxxxx xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 2 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item C6 C.7 C.8 C.10 C.11 C.12 C.13 Subclause 4.1.5 4.1.6 4.1.6.5 4.1.3 4.3.5 4.3.6 4.4 4.4.1 4.4.5 4.4.5 4.5 Description Details of oil-insulated current transformers to be submitted for approval a) Expansion accommodation method b) Sealing arrangements c) Oil-level indicators Gas-insulated current transformers Method of sealing Each main terminal to be electrotinned copper flat pad of the following dimensions a) Diameter holes b) size c) hole centres Mounting arrangement Holding down bolts to be arranged to fall within a square of maximum dimensions Diameter of the holes Finish Finish offered on ferrous parts Finish offered on non-ferrous parts Rating and diagram plates a) Materials used for rating plates b) Material used for diagram plates c) Method of fixing diagram and rating plates Drawings and literature required with tender Number of instruction books required if other than three Number of descriptive pamphlets required if other than three Details of CT cores a) Number of cores b) Number of measuring cores c) Number of protection cores for Schedule A Schedule B xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx mm mm mm 4x14 100/120/20 50x50 xxxxxxxxxx xxxxxxxxxx mm mm 706 × 706 18 xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx 6 6 6 4 2M xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 3 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (continued) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Schedule A: Purchaser’s specific requirements Schedule B: Guarantees and technical particulars of equipment offered Item SubDescription clause General purposes Bus zone Differential 4.2.2 C.15 Details of measuring core Details of core number a) Nominal ratio A/A b) Rated burden VA c) Accuracy class d) Ratio for which (b) and (c) apply e) Means used to effect ratio changes if required Instrument security factor at 400/1 ratio Are core steel details required? Is B/H curve of annealed core required? 4.2.3 C.16 Details of protection core a) Details core number b) Nominal turns ratio Turns c) Continuous current rating 1) Primary A 2) Secondary A d) Accuracy class e) Rated knee-point voltage Vk V f) Magnetising current mA j) Maximum total secondary winding resistance Ri Ω k) Drawing number of magnetisation curve Are core steel details required? Is B/H curve of annealed core required? Earth terminal to be provided with a clamp suitable for a) Material b) Type c) Size mm Schedule A Schedule B 2P xxxxxxxxxx xxxxxxxxxx Core 5 & 6 1600/1 MR 5 0,2 See annex A Xxxxxxxxxx 20 Yes Yes xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx Core 1 & 4 1/1600T MR 1600 2 TPS See annex A See annex A See annex A xxxxxxxxxx Yes Yes xxxxxxxxxx xxxxxxxxxx Copper Flat 50 × 3 xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx xxxxxxxxxx ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 4 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause Description Schedule A Schedule B xxxxxxxxxx Manufacturer of HV porcelain insulators Rated short-duration primary current Ith Miscellaneous a) Oil quantity b) Minimum effective gland area of terminal box table gland plate kA l 25 xxxxxxxxxx mm 130 × 75 Height mm xxxxxxxxxx Length mm xxxxxxxxxx Width Mm xxxxxxxxxx kg xxxxxxxxxx c) Overall dimensions of current transformer Total mass of current transformer d) Type of terminal box Creepage distance Minimum Creepage distance for other than medium pollution level (heavy) / very heavy (IEC 60815) C.18 5.1.1 xxxxxxxxxx mm/kV 31 Tests Results of routine tests to be included into the terminal box (water proof packaging) C.19 5.12 Characteristic of impulse wave Results of routine tests to be included into the terminal box (water proof packaging) µs 1/50, 1,2/50 or 1,5/50 ESKOM DISTRIBUTION GROUP Specification reference number: DSP0013 Page 5 Enquiry No.: ………………………………… Tenderer’s name: …………………………………. Project Name: ……………………………………………………… Date: …………………….. Technical schedules A and B for 132 kV distribution current transformers for use in very heavy pollution conditions (31mm/kV) (concluded) Measuring core ratio: 2400/1 MR Protection core ratio: 1/2400T MR Item Subclause C.20 C.21 Description Schedule A Schedule B At the lowest tap See annex A xxxxxxxxxx xxxxxxxxxx Yes/No Are tangent delta measurements to be made? Yes xxxxxxxxxx Are special tests required? No xxxxxxxxxx xxxxxxxxxx Yes/No Yes xxxxxxxxxx High voltage power frequency withstand tests 5.1.5 Minimum 60 s power-frequency wet withstand kV Minimum 60 s power-frequency dry withstand kV Short-time current test a) short-time withstand current A b) time s C.22 5.2.6.1 Ratio for accuracy test C.23 5.2.7.2 Are details of procedure for determination of the rate of gas leakage submitted for approval? C.24 5.3 Are valid type test certificates available? If No, are type tests to be performed? If required where are the type tests to be carried out? xxxxxxxxxx 5.3.1 Impulse test Yes/No 5.3.2 Mechanical strength and sealing test Yes/No 5.3.3 Dielectric dissipation factor test Yes/No 5.3.4 Long duration voltage test Yes/No 5.3.5 Chopped impulse test Yes/No 5.3.6 Internal arc withstand capability test Yes/No