Uploaded by Anirudhan sadagopan bharath

Internship-Report-sample

advertisement
INTERNSHIP REPORT
USE OF IEC 61850 FOR ASSET MANAGEMENT
IN LOW VOLTAGE MICROGRIDS
T.G. PHAM (s1164163)
MSc Telematics, EEMCS
01-11-2012 to 28-02-2013
Alliander
Utrechtseweg 68
6812 AH Arnhem
The Netherlands
Supervisor
Frans Campfens
Senior Innovative Manager
frans.campfens@alliander.com
University of Twente
PO Box 217
7500 AE Enschede
The Netherlands
Academic supervisor
Dr. ir. Georgios Karagiannis
karagian@cs.utwente.nl
Preface and acknowledgement
For four months from November 2012 till February 2013, I did an internship at Alliander, an
energy distribution company which covers large areas in the Netherlands. Alliander core
business involves distributing gas and electricity to a huge amount of customers which is
about nearly a third of the Netherland’s population. This internship project is a part of my 2year master program which I conduct at University of Twente, the Netherlands.
Figure 0.1 – Alliander electricity and gas distribution grid, copied from [12]
I worked on an assignment project to investigate the use of the IEC 61850 standard for asset
management of LV Microgrids. The main content of the project is to use the IEC 61850
standardized data model and services to model the smart electrical equipment, and investigate
the interaction between different components within a network topology for Microgrids asset
management. This topic suits my major in telematics, and also brought me to a very new and
interesting area of using communication technologies in electricity network. Through the
assignment, I did not only gain a lot of knowledge but more importantly, I also had a great
chance to sharpen my skills in a professional working environment. Not less important than
the communication technologies that I have learnt is the communication skills that I have
i
been trained and practiced through giving presentations, discussing with the supervisors,
experts in the field and other staffs within and outside the company.
I am very appreciated to Mr. Frans Campfens, my supervisor at Alliander. Frans gave me
very in-time valuable instructions and put me in contact with experts in the field like Mr.
Marco Janssen, president and CEO at UTInnovative, who gave me extensive guidance
regarding many practical issues. I also would like to express my gratitude to Dr. ir. G.
Karagiannis for his permission to be my academic supervisor and more importantly for his
enthusiastic encouragements and precious instructions during my internship period. He gave
me in-time feedback on my research and helped to organize an interesting presentation in
which I could present my ideas and achievements to other professors and researchers of the
faculty.
Throughout the internship, I have also learnt many things about the Dutch culture whose
benefits are far beyond what I could learn in a normal project. In short, I would like to thank
Alliander and University of Twente, Internship Office for introducing me to this great
opportunity in which I have developed myself both academically, professionally and socially.
ii
Table of contents
List of Figures ....................................................................................................................... v
List of Tables ...................................................................................................................... vii
List of Abbreviations.......................................................................................................... viii
Chapter 1: Introduction ...................................................................................................... 1
1.1 Problem statement and research objectives ................................................................... 2
1.1.1 Problem statement ................................................................................................. 2
1.1.2 Research Objectives .............................................................................................. 2
1.2 Organisation of this report ........................................................................................... 3
Chapter 2: Technical descriptions ...................................................................................... 4
2.1 Description of IEC 61850 ............................................................................................ 4
2.1.1 Scope of IEC 61850 .............................................................................................. 4
2.1.2 Standardization approach....................................................................................... 5
2.1.3 Content of the IEC 61850 series ............................................................................ 6
2.1.4 Extensibility of IEC 61850 .................................................................................... 8
2.1.5 IEC 61850 data modelling principle ...................................................................... 8
2.1.6 IEC 61850 communication services ..................................................................... 10
2.1.7 Specific communication service mapping ............................................................ 13
2.2 Smart Grid and Microgrids ........................................................................................ 20
2.2.1 Smart Grid........................................................................................................... 21
2.3. Summary .................................................................................................................. 22
2.2.2 Microgrids ........................................................................................................... 23
Chapter 3: IEC 61850 network designing and data modelling for microgrids
components ........................................................................................................................ 25
3.1 Communication network designing ............................................................................ 25
3.1.1 Microgrids power diagram................................................................................... 25
3.1.2 Communication network topology for LV Microgrids power control and asset
management ................................................................................................................. 26
3.2 IEC 61850 data modelling ......................................................................................... 29
3.2.1 Extension rule for logical nodes ........................................................................... 30
iii
3.2.2 IEC 61850 data modelling for Microgrids components ........................................ 31
3.3 Summary ................................................................................................................... 37
Chapter 4: Applying IEC 61850 data models and services for microgrids for LV
microgrid asset management ............................................................................................ 39
4.1 Overview on asset management ................................................................................. 39
4.2 Asset management use case ....................................................................................... 42
4.2.1 Description of the Use Case ................................................................................. 42
4.2.2 Actor (Stakeholder) Roles ................................................................................... 43
4.2.3 Information exchanged ........................................................................................ 43
4.2.4 Step by Step Analysis of Function ....................................................................... 44
4.3 Realization of use case with IEC 61850 ..................................................................... 49
4.3.1 Scenario 1 ........................................................................................................... 49
4.3.2 Scenario 2 ........................................................................................................... 63
4.3.3 Mapping ACSI services to MMS ......................................................................... 66
4.4. Summary .................................................................................................................. 68
Chapter 5: Conclusion and future work .......................................................................... 69
References.......................................................................................................................... 71
iv
List of Figures
Figure 2.1 – Scope of application of IEC 61850, copied from [1] .......................................... 5
Figure 2.2 – Links between IEC 61850 parts, copied from [1] ............................................... 7
Figure 2.3 – IEC 61850 specifying approach, copied from [1] ............................................... 8
Figure 2.4 – Relationship between functions, logical nodes and physical nodes, copied from
[1] ......................................................................................................................................... 9
Figure 2.5 – Overview of IEC 61850 functionality and profiles, copied from [4] ................. 14
Figure 2.6 – GOOSE and SV peer-to-peer data value publishing model, copied from [4] .... 18
Figure 2.7 – Sampled value mapped to serial unidirectional multidrop point to point link,
copied from [23] ................................................................................................................. 19
Figure 2.8 – Transformation from traditional to future electricity grid, copied from [12] ..... 21
Figure 2.9 – Conceptual model of smart grid, copied from [13] ........................................... 22
Figure 2.10 – Microgrids architecture, copied from [16] ...................................................... 23
Figure 3.1 – LV microgrids diagram ................................................................................... 26
Figure 3.2 – Communication network topology for LV Microgrids power control and asset
management ........................................................................................................................ 28
Figure 3.3 – IEC 61850 data modeling, copied from [1] ...................................................... 29
Figure 3.4 – Basic extension rules diagram, copied from [3]................................................ 30
Figure 3.5 – Conceptual organization of DER logical devices and logical nodes, copied from
[7] ....................................................................................................................................... 32
Figure 3.6: Logical devices in proxies or gateways .............................................................. 37
Figure 4.1: Message flow for Scenario 1 of Asset Management use case ............................. 46
Figure 4.2: Message flow for Scenario 2 of Asset Management use case ............................. 48
Figure 4.3: TWO-PARTY-APPLICATION-ASSOCIATION (TPAA) class syntax [4] ....... 49
Figure 4.4: Relations between classes in an IEC 61850 server ............................................. 50
Figure 4.5: Instantiation of generic classes .......................................................................... 51
Figure 4.6: IEC 61850 server structure and the related services ........................................... 52
Figure 4.7: Example of GetServerDirectory and GetServerDirectory service used by HCMC
........................................................................................................................................... 54
Figure 4.8: A reference with a functional constraint ............................................................ 56
v
Figure 4.9: Example of GetDataValues service used by HCMC .......................................... 57
Figure 4.10: Example of GetAllDataValues service used by HCMC.................................... 59
Figure 4.11: HCMC retrieves device name plate information .............................................. 61
Figure 4.12: An example of report service configuration ..................................................... 63
Figure 4.13: HCMC performs health monitoring using GetDataValues service.................... 64
Figure 4.14: HCMC uses reporting services on the device to perform health monitoring ..... 65
Figure 4.15: HCMC uses reporting service on a switch to detect communication problems . 66
Figure 4.16: Mapping GetDataValues to MMS Read service to get measurement value ...... 68
vi
List of Tables
Table 2.1 – ACSI classes [4] ............................................................................................... 11
Table 2.2 – Service and protocols for GSE management and GOOSE communication Aprofile [8] ............................................................................................................................ 16
Table 2.3 – GOOSE/GSE T-profile [8] ................................................................................ 17
Table 2.4 – Time Sync A-Profile [8] ................................................................................... 20
Table 3.1 – Smart household appliances and their typical characteristics ............................. 33
Table 3.2 – ZAPL class ....................................................................................................... 34
Table 3.3 – Extension to STMP class .................................................................................. 35
Table 3.4 – ZHCM class...................................................................................................... 36
Table 4.1: Additional Bridge-data objects in LPHDB added to LN LPHD [17] ................... 41
Table 4.2: Additional Bridge-data objects in LCCHB added to LN LCCH [17] ................... 41
Table 4.3: Actor (Stakeholder) Roles................................................................................... 43
Table 4.4: Information exchanged between actors ............................................................... 43
Table 4.5: Preconditions and Assumptions .......................................................................... 44
Table 4.6: Steps to implement function - Scenario 1 ............................................................ 45
Table 4.7: Steps to implement function - Scenario 2 ............................................................ 47
Table 4.8: MMS objects and services, copied from [8] ........................................................ 67
Table 4.9: Mapping of GetDataValues service parameters, copied from [8] ......................... 67
vii
List of Abbreviations
ASN-1
Abstract Syntax Notation Number One
ACSI
Abstract Communication Service Interface
BRCB
BUFFERED-REPORT-CONTROL-BLOCK
CT
Current Transformer
DER
Distributed Energy Resource
DPWS
Devices Profile for Web Services
EPRI
Electric Power Research Institute
ES
Energy Storage
EV
Electric Vehicle
GOOSE
Generic Object Oriented Substation Events
GSE
Generic Substation Event
GSSE
Generic Substation State Event
HCMC
Home Control and Management Centre
HI
Hybrid Inverter
HMI
Human Machine Interface
ICMP
Internet Control Message Protocol
IEC
International Electrotechnical Committee
IED
Intelligent Electronics Device
IEEE
Institute of Electrical and Electronics Engineers
IP
Internet Protocol
LN
Logical Node
LD
Logical Device
LV
Low Voltage
MMS
Manufacturing Message Specification
MV
Medium Voltage
viii
OSI
Open System Interconnection
PUAS
Power Utility Automation System
PV
Photovoltaic
RCMC
Regional Control and Management Centre
RTU
Remote Terminal Unit
SCADA
Supervisory Control and Data Acquisition
SCSM
Specific Communication Service Mapping
SG3
Smart Grid Strategy Group
SNTP
Simple Network Time Protocol
SOE
Sequence of Event
TC57
Technical Committee 57
TCP
Transmission Control Protocol
UCA
Utility Communication Architecture
UDP
User Datagram Protocol
uPNP
Universal Plug and Play
URCB
UNBUFFERED-REPORT-CONTROL-BLOCK
VT
Voltage Transformer
ix
Chapter 1
Introduction
Many believe that there is a need for the current power grid to undergo a profound change to
evolve into a more modern grid. The current one-way power distribution infrastructure has
existed for several decades and cannot cope with the emerging challenges nowadays, for
examples, the penetration of distributed energy resources (DERs), electric vehicles (EVs), the
need for higher resiliency against failures, better security and protection, etc. This
modernized grid, often termed as "Smart Grid", "IntelliGrid", "GridWise", etc. [19], [20], is
considered the future of the electricity grid with the integration of advanced information
communication technologies (ICT) in order to efficiently deliver sustainable, economic and
secure electricity supplies [1].
In fact, communication networks have been in existence for several decades along with the
power grid for monitoring and protection control, but the network architecture has not
changed much since the first day [21]. Power utilities still do not have much insight into
distribution network, where nearly 90% of all power problems come from [16].
In the distribution network, the low-voltage (LV) part (less than 1kV) is a challenge for the
control and management of the power grid as it involves the participation of households with
their various private assets, such as DERs, storages, EVs. A household may form a cluster
known as "microgrid" which includes the local generators, storages, loads and control. These
microgrids may be integrated into a larger grid when power and information exchange among
them are available [16].
IEC 61850 emerges as the promising protocol for the future smart grid. It was designed to
ensure interoperability of the communication between Intelligent Electronic Devices (IEDs)
in substation automation systems. An IED is the microprocessor based device that performs
several protective, control, and similar functions. The main idea of IEC 61850 to break down
the functions of IEDs into core functions called Logical Nodes (LNs). Several logical nodes
can be grouped into a Logical Device (LD) which provides communication access point of
IEDs. By standardizing the common information model for each LN and the associated
services, IEC 61850 provides the interoperability among IEDs of different manufacturers in
substation automation systems.
1
IEC 61850 has been extended outside the scope of substation automation systems to cover
DERs, EVs, and the communication to control centre. Therefore it can potentially be applied
to the power control and asset management of LV microgrids, where private assets like
DERs, EVs are present.
Power control functions are important in LV microgrids as the system performs the
modulation of the equipment energy consumptions/generations. Power control within LV
microgrids also supports Demand Response for dynamic load operation. On the other hand,
asset management involves the tasks of the system to obtain an overall status of the
equipment participating in the microgrid, such as the list of devices within the scope and their
capabilities, the health monitoring of the devices and alarm handling.
1.1 Problem statement and research objectives
1.1.1 Problem statement
As briefly described, IEC 61850 was originally designed for communication in substation
automation systems and later was developed to support communication to DER and to
control centre with the objective of solving the interoperability problem caused by the coexistence of multiple proprietary communication protocols. However, in the progress of
transforming from the traditional centralized grid to distributed smart gird, the energy
consumers also play a not-less-important role than the energy producers. According to
European Technology Platform definition of smart grid [13] – the future electricity grid,
smart grid should "allow consumers to play a part in optimizing the operation of the system".
Nevertheless in the area of communication in home automation systems and microgrids, there
are still many different protocols for control and management of the smart appliances;
therefore, interoperability is still a serious problem to be solved.
1.1.2 Research Objectives
Based on the observation that IEC 61850 has great flexibility and extensibility, the main
research objective of this assignment is to use IEC61850 for low voltage Microgrids asset
management. The goal is to apply the concepts of IEC 61850 to a different domain, the LV
microgrid, to perform inventory management, configuration management, device monitoring
and alarm handling.
The main objective above can be decomposed to 3 smaller objectives:
2

Objective 1: Designing a communication network topology in LV Microgrids.

Objective 2: Modelling LV Microgrids electrical components

Objective 3: Applying IEC 61850 services for asset management in LV Microgrids
A well-designed network topology is required for seamless communication between various
kinds of smart electrical components in a typical microgrid such as the Regional/Home
control and management centre, the controllable Distributed Energy Resources (DER)
including Photovoltaic (PV) panel, wind turbine, energy storage (ES), electric vehicle
(EV)…and the smart household appliances.
To allow those devices communicate with each other using IEC61850 protocol, those devices
needs to be modelled as IEC61850 data objects. The data objects which defined in a
standardized way also allow interoperable actions between different equipment inside a
microgrid. Because the initial scope of IEC61580 is for substation automation, many data
objects needed for smart appliances have not been defined yet and modelling those devices is
an important task in this project.
Finally, when the network topology and data objects of the equipment are available, the
IEC61850 services will be applied to perform all the management functions such as getting
device information, configuring reporting service on the device, etc. To illustrate how those
services can be applied for these tasks, a use case will be firstly defined explain the capability
of the IEC61850 protocol to support asset management in LV microgrids.
1.2 Organisation of this report
The report is organized as follows. Chapter 2 will introduce a technical description about the
related concepts such as IEC61850 standard, smart gird and microgrids. Chapter 3 is about
communication network topology of LV Microgrids components. Chapter 4 gives a specific
use case to demonstrate the usage of these models and services for asset management of LV
Microgrids. The conclusion and future work will be given in Chapter 5.
Chapters 2 and 3 in both the Internship reports of T.G. Pham and A.D. Nguyen are exactly
the same, since they have been developed and written by both authors of these two reports.
The reason of this is that the students worked during their Internship on solving issues
focussing on similar research areas, and where the first part of their research activity was
identical.
3
Chapter 2
Technical descriptions
This chapter describes the concept and architecture of IEC 61850, as well as the motivation
of transforming from the conventional centralized electricity grid to a distributed intelligent
electricity grid of the future which is called Smart Grid. An important part of the Smart Grid
which supports the distribution automation of the Smart Grid is called Microgrids will also be
explained within this chapter. This chapter is based largely on the official documents of the
international standard IEC 61850 [1, 8] and a published document by the Smart Grid Strategy
Group – SG3 about the roadmap of Smart Grid [11].
This chapter is organized as follows: Section 2.1 describes the IEC 61850 standards. Section
2.2 explains the concept of Smart Grid and the origin of Smart Grid designing decision.
Section 2.3 gives a description about Microgrids and the structure of a Microgrid. Finally
Section 2.4 summarizes the technical descriptions provided in this chapter.
2.1 Description of IEC 61850
2.1.1 Scope of IEC 61850
IEC 61850 was initially designed for communication in substation automation systems by
Institute of Electrical and Electronics Engineers – IEEE/Electric Power Research Institute –
EPRI Utility Communication Architecture (UCA) and the working group "Substation Control
and Protection Interfaces" within the International Electrotechnical Committee (IEC)
Technical Committee (TC) 57. The development of advanced and powerful microprocessors
supported the possibility for building Power Utility Automation System (PUAS) [1], and
consequently several Intelligent Electronics Devices (IEDs) was created each of which
support proprietary communication protocol from its manufacturer. However, the co-existing
of various proprietary communication protocols led to the big challenge of interoperability,
and therefore required investment for complicated and costly protocol converter when using
IEDs from different vendors [1].
IEC 61850 was initialized to solve the interoperability problem by defining standard
semantics, abstract communication services which can be mapped to different protocols,
4
configuration descriptions and engineering processes [1]. From the original scope of
communication within substation automation systems, IEC 61850 standard has been extended
to support communication to Distributed Energy Resources (DER) and are being developed
for communication to control centre and feeder automation domain [1].
Figure 2.1 – Scope of application of IEC 61850, copied from [1]
Figure 2.1 represents the scope of the IEC 61850 with updates about the possible extension of
the protocol in the future. It shows that currently, IEC 61850 has been adopted for the
communications inside substation and from control centre (SCADA – Supervisory Control
and Data Acquisition) to the Remote Terminal Unit – RTU and to the DERs. In the future,
the standard will be extended to support the communications between the Control Centre and
Power Utility substation as well as to the Medium Voltage – MV network.
2.1.2 Standardization approach
IEC 61850 provides a huge variety of communication functions which allow telecontrol,
teleprotection, supervision and monitoring between different IEDs in an electric power
5
system. The standardization approach of IEC 61850 series as mentioned in IEC 61850-part 1
[1] is to blend the strength of three methods:

Functional decomposition: is used to understand the logical relationship between
components of a distributed function which is decomposed and represented as Logical
Nodes (LNs)

Data flow modelling: is used to understand the communication interfaces that must
support the exchange of information between distributed functional components and
the functional performance requirements.

Information modelling: is used to define the abstract syntax and semantics of the
information exchanged
In short, IEC 61850 decomposes and standardizes the functions as logical nodes, classified
the communication interfaces between different functional levels and models the information
exchange in term of data objects, data attributes and abstract communication services.
2.1.3 Content of the IEC 61850 series
IEC 61850 consists of many parts which explain the standard step-by-step from general
information such as the introduction and overview in part 1, the glossary in part 2, the general
requirements in part 3, system and project management in part 4 to the communication
requirements and specifications in part 5, part 6 and part 7-1 to 7-4.
As IEC 61850 is an internationally standardized abstract method of communication and
integration between multi-vendor IEDs, it’s needed to be mapped to specific protocols to
support different functional requirements for protection, control, supervision, and monitoring.
Therefore, parts 8-1, 9-1, 9-2 of the standard define the specific communication mapping.
Additionally, the standard also defines guidelines of using the logical nodes to models the
functions of a substation automation system (part 7-500), a hydro power plant (part 7-510)
and distributed energy resources (part 7-520). The object models for hydro power plant and
distributed energy resources are defined respectively in part 7-410 and 7-420.
As the standard is still in development, it’s going to cover more areas such as power inverters
for DER systems (part 90-7), for electric mobility (part 90-8), for storage (part 90-9), DER
scheduling (part 90-10). Figure 2.2 shows the overall structure of IEC 61850 standard.
In short the basis rule of setting the numbers to documents in IEC 61850 is [1]:
6

7-4xx documents are normative definition of domain specific name spaces

7-5xx documents are informative application guidelines of the 7-x documents, i.e.
providing guidance on how to model application functions based on part 7-x.

8-x documents are normative definitions of the ACSI mapping (except
communication services related to sample values)

9-x documents are normative definitions of the ACSI mapping dedicated to
communication services related to sample values

80-x documents are additional informative Technical Specifications related to
communication mapping

90-x are additional informative Technical Reports for further enhancement/extensions
of the IEC 61850 domains
Figure 2.2 – Links between IEC 61850 parts, copied from [1]
7
2.1.4 Extensibility of IEC 61850
A significant advantage of IEC 61850 is the split between the communication and application
as illustrated in Figure 2.3. By specifying a set of abstract services and objects, IEC 61850
allows the user to design different applications without relying on the specific protocols. As a
consequence, the data models defined in IEC 61850 can be used on the diversity of
communication solutions.
This fact is the source of motivation for me to propose an extension of IEC 61850 to support
communication between control centre and smart appliances and DERs which has not yet
been proposed by any parts or technical reports within IEC 61850 series. The method of
using IEC 61850 data models and abstract services to manage microgrids electrical
components will be described in details in chapter 3 and 4.
Figure 2.3 – IEC 61850 specifying approach, copied from [1]
2.1.5 IEC 61850 data modelling principle
An important remark of applying IEC 61850 is the data modelling process which brings the
advantage of interoperability to IEC 61850 by modelling all the data in a standardized syntax
and format following an object-oriented method.
There are two main levels of modelling [1]:
8

The breakdown of a real device (physical device) into logical devices.

The breakdown of logical device into logical nodes, data objects and attributes.
Logical device is the first level of breaking down the functions supported by a physical
device i.e. an IED. A logical device usually represents a group of typical automation,
protection or other functions [1]. The Logical Device hosts communication access point of
IEDs and related communications services and provides information about the physical
devices they use as host (nameplate and health) or about external devices that are controlled
by the logical device (external equipment nameplate and health).
Logical nodes are the smallest entities decomposed from the application functions and are
used to exchange information. It supports the free allocation of those entities on dedicated
devices (IEDs). It is illustrated in Figure 2.4.
Based on their functionality, a logical node contains a list of data with dedicated data
attributes which have a structure and well-defined semantic.
Figure 2.4 – Relationship between functions, logical nodes and physical nodes, copied
from [1]
Figure 2.4 illustrates the decomposition of an application functions to multiple logical nodes
which represents the smallest entities to exchange information. It also represents the
9
allocation of logical nodes to physical devices. For example the Distance protection function
can be decomposed to 6 different logical nodes which are the Human Machine Interface
(HMI) to represent the data to user, the Distance Protection and Overcurrent protection
logical nodes – Dist.Prot. and O/C Prot. to perform protection action , the breaker to break the
circuit and the Bay Current Transformer (CT) and Voltage Transformer (VT) to provide
measurement data for identifying the problem. These logical nodes can be placed on
individual devices such as HMI on station computer (physical device 1), breaker on Bay
control unit (physical device 4), and Bay CT and Bay VT on current and voltage transformer
respectively. Or more than one logical node can be allocated in the same physical device such
as the Distance protection and Overcurrent protection logical nodes located on the same
physical device 3: Distance protection unit with integrated overcurrent function.
Many definitions of the typical logical nodes for substation automation systems can be found
in IEC 61850-7-4 [6] and further details about the data attributes are explained within IEC
61850-7-3 [5].
2.1.6 IEC 61850 communication services
Besides standardizing the data format in an object-oriented manner, IEC 61850 also defines a
set of abstract services for exchanging information among components of a Power Utility
Automation System. These services are described in details in part 7-2 of the standard [4]
The categories of services are as follows [1]:

retrieving the self-description of a device,

fast and reliable peer-to-peer exchange of status information (tripping or blocking of
functions or devices),

reporting of any set of data (data attributes), Sequence of Event SoE – cyclic and
event triggered,

logging and retrieving of any set of data (data attributes) – cyclic and event,

substitution,

handling and setting of parameter setting groups,

transmission of sampled values from sensors,

time synchronization,
10

file transfer,

control devices (operate service),

Online configuration
The complete Abstract Communication Service Interface – ACSI services are shown in Table
2.1. The description of these classes can be found in [4].
Table 2.1 – ACSI classes, copied from [4]
GenServer model
GetServerDirectory
Association model
Associate
Abort
Release
GenLogicalDeviceClass model
GetLogicalDeviceDirectory
GenLogicalNodeClass model
GetLogicalNodeDirectory
GetAllDataValues
GenDataObjectClass model
GetDataValues
SetDataValues
GetDataDirectory
GetDataDefinition
DATA-SET model
GetDataSetValues
SetDataSetValues
CreateDataSet
DeleteDataSet
GetDataSetDirectory
LOG-CONTROL-BLOCK model:
GetLCBValues
SetLCBValues
QueryLogByTime
QueryLogAfter
GetLogStatusValues
Generic substation event model –
GSE
GOOSE
SendGOOSEMessage
GetGoReference
GetGOOSEElementNumber
GetGoCBValues
SetGoCBValues
Transmission of sampled values model
MULTICAST-SAMPLE-VALUECONTROL-BLOCK:
SendMSVMessage
GetMSVCBValues
SetMSVCBValues
UNICAST-SAMPLE-VALUECONTROL-BLOCK:
SendUSVMessage
GetUSVCBValues
SetUSVCBValues
11
SETTING-GROUP-CONTROL-BLOCK
model
SelectActiveSG
Control model
Select
SelectWithValue
SelectEditSG
SetSGValues
ConfirmEditSGValues
GetSGValues
Cancel
Operate
CommandTermination
TimeActivatedOperate
GetSGCBValues
REPORT-CONTROL-BLOCK and LOGCONTROLBLOCK model
BUFFERED-REPORT-CONTROLBLOCK:
Report
GetBRCBValues
Time and time synchronization
TimeSynchronization
FILE transfer model
GetFile
SetFile
DeleteFile
GetFileAttributeValues
SetBRCBValues
UNBUFFERED-REPORT-CONTROLBLOCK:
Report
GetURCBValues
SetURCBValues

Data Set – permit grouping of data objects and data attributes

Substitution – support replacement of a process value by another value

Setting group control – defines how to switch from one set of setting values to
another one and how to edit setting groups

Report control and logging – defines conditions for generating report and log. There
are two classes of report control: BUFFERED-REPORT-CONTROL-BLOCK
(BRCB) and UNBUFFERED-REPORT-CONTROL-BLOCK (URCB). For BRCB
the internal events that trigger the report will be buffered so that it will not be lost due
to transport flow control constraints or loss of connection. For URCB internal events
issues immediate sending of reports on a "best effort" basis i.e. if no association exits,
or if the transport data flow is not fast enough, events may be lost.
12

Control blocks for generic substation event (GSE) – supports a fast and reliable
system-wide distribution of input or output data values; peer-to-peer exchange of IED
binary status information, for example, a trip signal.

Control block for transmission of sampled values – fast and cyclic transfer of
samples, for example, of instrument transformers.

Control – describes the services to control, for example, a device.

Time and time synchronization – provides the time base for the device and system

File system – defines the exchange of large data blocks such as programs.
For implementation, the abstract services will be mapped on different protocol profiles; the
selection of an appropriate mapping depends on the functional and performance requirements
and will be described in the next section.
2.1.7 Specific communication service mapping
As stated above, the mapping of the services to different protocol profiles is based on the
functional and performance requirements. Due to the different requirements for transfer time
of difference functions inside the substation, IEC 61850 classifies the messages exchanged
between the devices to several types [4]:

Type 1 (Fast messages)

Type 1A (Trip)

Type 2 (Medium speed messages)

Type 3 (Low speed messages)

Type 4 (Raw data messages)

Type 5 (File transfer functions)

Type 6 (Time synchronisation messages)
The required transfer times rely upon the requirements of the function, for example, the "trip"
message to open the circuit breaker for protection is very time critical (3 ms) in order to
prevent damage to the system; however, the transfer time for file transfer functions to transfer
a large amount of data is non-time-critical (can be 10000 ms).
13
Figure 2.5 provides the mapping of these messages to different protocol profiles. Messages of
type 1, 1A, and type 4 which are time-critical are mapped directly on Ethernet. Messages of
type 2, 3 and 5 which are used for automation, auto-control functions, transmission of event
records, reading and changing set-points…etc. require message oriented services [2, 4]. The
Manufacturing Message Specification – MMS provides exactly the information modelling
methods and services required by the ACSI. MMS services and protocol can operate over the
full OSI and TCP/IP compliant communication profiles [4]. This is also the only protocol that
easily supports the complex naming and services models of IEC 61850 [22]. This protocol
also includes the exchange of real-time data, indications, control operations, and report
notifications. This mapping of ACSI to MMS defines how the concepts, objects, and services
of the ACSI are to be implemented using MMS concepts, objects, and services. This mapping
allows interoperability across functions implemented by different manufacturers [4].
Figure 2.5 – Overview of IEC 61850 functionality and profiles, copied from [4]
2.1.7.1 Manufacturing message specification – MMS
MMS is a client/server communication model. MMS defines difference between the entity
that establishes the application association and the entity that accepted the application
14
association. The entity that establishes the association is the client and the one that accepts
the association is the server.
Due to the client/server model, the client can request for the data at any point of time when
the association is valid. The message exchanged will follow a request/response manner.
MMS also supports the report service. For the report service, instances of a report control
blocks which include the values of the data object to be reported to the client, are configured
in the server at configuration time. The server can restrict access to an instance of a report
control block to one or more clients.
The report will be triggered based on the configured triggered conditions which represented
by the attribute TrgOp. Some typical trigger options for report generation are data-change
which relates to the change in a value of DataAttribute representing the process-related value
of the data object; quality-change which relates to a change in the quality value of a
DataAttribute; and data-update which relates to a freeze event in a value of a DataAttribute
representing a freeze value of the data object (for example, frozen counters) or to an event
triggered by updating the value of a DataAttribute [4].
The data-update triggered condition can be used to provide periodic report generation with
the statistics values that may be calculated or updated periodically.
In MMS, the triggered conditions are encoded as a PACKET_LIST with the data-type bitstring which represents an ordered set of values defined when the type is used.

Bit 0 reserved

Bit 1 data-change

Bit 2 quality-change

Bit 3 data-update

Bit 4 integrity

Bit 5 general-interrogation
MMS is based on Open System Interconnection (OSI) model with an adaptation layer (RFC
1006) layer for emulating OSI services over TCP/IP [22]. MMS application protocol is
specified in Abstract Syntax Notation Number One (ASN-1) format that is a notation for
describing the data structure.
15
2.1.7.2 GOOSE services communication profile
The Generic Object Oriented Substation Events – GOOSE provides fast and reliable systemwide distribution of data, based on a publisher-subscriber mechanism (Generic Substation
Event – GSE management). GOOSE is one of the two control classes within the GSE control
model (the other is Generic Substation State Events – GSSE).
GOOSE uses Data-set to group the data to be published. The use of Data-set allows grouping
many different data and data attributes. Table 2.2 shows the application profile (A-profile) of
GSE/GOOSE services:
Table 2.2 – Service and protocols for GSE management and GOOSE communication Aprofile, copied from [8]
Instead of mapping to the TCP/IP profile like MMS, GOOSE is mapped directly to Ethernet.
The transport profile (T-profile) for GSE/GOOSE can be found in table 2.3
16
Table 2.3 – GOOSE/GSE T-profile, copied from [8]
GOOSE provides an efficient method of simultaneously delivery of the same generic
substation event information to more than one physical device through the use of multicast
services. GOOSE messages contain information that allows the receiving device to know that
a status has changed and the time of the last status change [8]. GOOSE sending is triggered
by the server by issuing SendGOOSEmessage service. The event that causes the server to
invoke a SendGOOSEmessage service is a local application issue as defined in [4], such as
detecting a fault by a protection relay.
2.1.7.3 Sampled Value
Sampled Value or Samples of Measured Values (SMV) is the protocol for transmission of
digitized analogue measurement from sensors (temperature, current transformer, voltage
transformer).
Sampled value messages are exchanged in a peer-to-peer publisher/subscriber mechanism
like GOOSE messages. However GOOSE uses the multicast model while SMV can be
unicast or multicast. Figure 2.6 sketches the comparison between GOOSE and SMV
communication models.
17
Figure 2.6 – GOOSE and SV peer-to-peer data value publishing model, copied from [4]
The transmission of sampled value is controlled by the MULTICAST-SAMPLE-VALUECONTROL-BLOCK – MSVCB if multicast is used; and by the UNICAST-SAMPLEVALUE-CONTROL-BLOCK – USVCB if unicast is used.
The transmission rate of the sampled value can be altered by configuring the Data Attribute
SmpMod which specifies the definition of units of samples i.e. unit of samples per nominal
period, samples per second or seconds per sample; and the SmpRate which specifies the
sample rate with the definition of units of sample defined by SmpMod.
Basically SMV can be mapped to Ethernet with different configuration as defined in part 9-1
[23] and part 9-2 [24] of the IEC 61850 series.
Part 9-1 maps the Sampled Value to a fixed link with pre-configure Data-set. Figure 2.8
presents the communication profile defined in part 9-1
18
Figure 2.7 – Sampled value mapped to serial unidirectional multidrop point to point
link, copied from [23]
Part 9-2 provides a more flexible implementation of SMV data transfer by allowing a userconfigurable Data-set in which the data values of various sizes and types can be integrated
together.
2.1.7.4 Generic Substation State Events – GSSE
This control model is similar to GOOSE. However, the GSSE only supports a fixed structure
of status data to be published; meanwhile the data for the GOOSE message is configurable by
applying data sets referencing any data [4].
2.1.7.5 Time Sync
The time synchronization model must provide accurate time to all IEDs in a power utility
system for data time stamping with various ranges of accuracy, e.g. millisecond range for
reporting, logging and control and microsecond range for sample values [4].
19
Time synchronization protocol used by IEC 61850 to provide synchronization between IEDs
is Simple Network Time Protocol – SNTP. Table 2.4 shows the application profile of the
Time Sync service
Table 2.4 – Time Sync A-Profile, copied from [8]
The transport layer uses the Internet Control Message Protocol (ICMP) and User Datagram
Protocol (UDP) over IP and Ethernet.
2.2 Smart Grid and Microgrids
Traditionally, the electricity grid was built as a centralized control network with the
unidirectional power flow from the massive electricity generation like hydro/thermal power
plants via the transmission grids and distribution grids to the customers [13]. This centralized
control network was suitable with the clear separation between customers who were almost
pure consumers and the massive power plants which generated all electricity for both
domestic and industrial demands.
However, the traditional energy resources such as gas, oil and coal are non-renewable. The
massive electricity production has led to a global decline of gas, oil and other natural
resources. The rapid development of many developing countries alongside with the
population explosion led to the severe energy shortages in the late of 20th century. More
importantly using these energy resources has led to seriously negative effects on human like
including CO2 pollution, global warming, climate change and etc. For example, the climate
change caused more than 36 million of displacement and evacuation in 2008 according to
United Nations Office for the Coordination of Humanitarian Affairs and the Internal Displace
ment Monitoring Centre [14]
As it was vital to find new energy resources for a sustainable future, many renewable energy
resources have been explored during the last few decades including the wind turbine,
Photovoltaic panel, heat pump…leading to a great transformation of the electricity grid from
unidirectional power flow with centralized control network to bi-directional power flow with
distributed control centres.
20
Figure 2.8 – Transformation from traditional to future electricity grid, copied from [12]
Figure 2.8 illustrates the transform from a traditional electricity grid to an intelligent
electricity grid. The traditional grid shown in the figure only requires the one-way
communication due to the unidirectional energy flow from the centralized power plants to the
consumers. However, with the rapid growth of the Distributed Energy Resources – DERs
such as wind farms, solar panels, the contribution of those distributed generations is
considerable. It is desired to utilize these resources which provide many advantages such as
renewable and environment-friendly nature. However using these resources also introduces
new issues such as voltage stabilizing, energy balancing, pricing and so on. These problems
require the construction of a bidirectional communication network to support all the
automation, supervision and control as well as monitoring functions. Therefore the second
generation of the electricity grid is being designed with a new communication infrastructure
to support the two-way communications between all the active intelligent components within
the grid and to the control centres.
2.2.1 Smart Grid
According to European Technology Platform Smart Grid, the definition of Smart grid is [13]:
"A Smart Grid is an electricity network that can intelligently integrate the actions of all users
connected to it – generators, consumers and those that do both – in order to efficiently deliver
sustainable, economic and secure electricity supplies."
21
Smart grid consists of the smart elements from customer / prosumer such as smart
consumption which enable demand response or home automation systems, building
automation systems, to bulk generation with increased use of power electronics and power
grid (Transmission and Distribution) including substation automation systems, power
monitoring system, energy management system, asset management system and condition
monitoring, distribution automation and protection [13]. Figure 2.9 provides an overall
architecture of the Smart grid with the participation of many elements from the energy
generation, the transmission/distribution networks to the customers with the services and
managements from the markets, operations and service provider.
2.3. Summary
This chapter provided an overall picture of IEC 61850 standard including the scope of the
standard, data models, abstract services, communication protocols and communication
profiles mapping. These theories will be applied to achieve the objectives of the research in
chapter 3 and chapter 4. Moreover, descriptions of the Smart Grid and Microgrids were also
described in this chapter. This background information will help to clarify the new domain of
IEC 61850 proposed by this research.
Figure 2.9 – Conceptual model of smart grid, copied from [13]
22
In short, the key idea of smart grid is the use of more and more intelligent controllable
devices with high level of interoperability to build a sustainable, economic and secure
electricity network.
2.2.2 Microgrids
Microgrids " describe the concepts of managing energy supply and demand using an isolated
grid that can island or connect to the utility’s distribution Smart Grid" [15]. Therefore,
Microgrids are crucial part in order to achieve an overall Smart Grid with the participation of
consumers.
From the above definition of Microgrids, we can decompose the three main parts of a
Microgrid as: energy supply, load and the control part for managing the energy supply and
demand. It is illustrated in Figure 2.10.
An important objective of building Microgrids is to create self-contained cells with use of
distributed energy resources in order to help assure energy supply in distribution grids even
when the transmission grid has a blackout [11]
Figure 2.10 – Microgrids architecture, copied from [16]
Basically, there are three elements for control and management within a microgrid: the
distributed energy generators, the energy storages, and the household appliances which
23
consume energy. The design of the control algorithm and management system should be able
to provide best energy efficiency and resilience to failures.
In addition to the energy-related issues, another very important aspect to be considered is the
privacy and convenience for the customers. Therefore, the functions like access control have
to be taken into consideration.
24
Chapter 3
IEC 61850 network designing and
data modelling for microgrids
components
Chapter 3 describes the communication network designing and data modelling processes
which are the two very important research tasks in order to allow power control and asset
management of Microgrids through using IEC 61850 data models and services. As being
emphasized above, the current covering areas of IEC 61580 include communication in
substation automation systems, between substations and to DERs. Therefore, for microgrids
distribution automation and home automation systems, before we can use the IEC 61850
services for communication between devices, we have to model those devices as IEC 61850
data models and design a network topology to support seamless communication between
different components. Moreover, although IEC 61850 facilitates modelling a lot by giving
many object models for common functions like measurement, metering, monitoring…etc.,
there are still some missing pieces for building a diversity of functions for household
appliances like tuning the temperature of an electric heater or refrigerator. This chapter will
explain how to model new devices and new functions as IEC 61850 models.
3.1 Communication network designing
In this part, a simple but typical communication network will be presented to allow the
communication between different actors in a Microgrid which support the use of IEC 61850
data models and services for power control and asset management.
3.1.1 Microgrids power diagram
Normally, LV Microgrids consist of three building blocks: the DERs including energy
distributed generators like PV panel and energy storage, and the electrical loads which
consumes energy. LV Microgrids can operate in islanding mode or grid connected mode but
25
the latter is chosen for the scope of this research. Therefore, a typical LV Microgrid can be
illustrated in the following figure:
Figure 3.1 – LV microgrids diagram
Figure 3.1 illustrates a typical LV Microgrid which consists of the Smart houses and the
public Distributed Energy Resources (DERs). In this case, the components of this LV
Microgrid can be classified to three types: energy consumers, energy generators and energy
storages. The energy consumers are the household electrical appliances inside the houses.
The energy generators are the public Low voltage DERs such as wind turbine or PV panel
and the possible DERs in the houses. The energy storages which can be a controllable battery
systems are used to store the energy that can be used for emergency or other future plans. A
special component here is the Electric vehicle (EV) which can be seen as both the energy
load and energy storage.
3.1.2 Communication network topology for LV Microgrids power control and
asset management
According to the current version of IEC 61850, the underlying communication network
infrastructure is standardized is Ethernet. Therefore, we need to build an Ethernet-based
26
communication network to connect all the Microgrids equipment. Within this research, a
network topology was designed for that purpose.
According to the current version of IEC 61850, the standardized underlying communication
network infrastructure is Ethernet. Therefore, we need to build an Ethernet-based
communication network to connect all the Microgrids equipment.
This network was designed as a hierarchical topology in which each Smart house will be
represented as a subnet and these subnets create a kind of field area network. The control and
management part of this regional microgrid is the Regional control and management centre
(RCMC) which is also connected to the field area network. Physically, the each subnet and
RCMC should connect to an Ethernet switch to establish communication links between
RCMC and each subnet.
There can also be some public DERs, Electric vehicles that should be managed by the RCMC
and therefore, they should have an Ethernet connection with RCMC through connecting to
the Ethernet switch.
Another important aspect is protection which is handled by the protection device and the
Circuit breaker (modelled by XCBR Logical Node). However, because the messages for
protection are very time-critical, they are handled by another protocol (GOOSE) instead of
the protocol for control and management purposes (MMS) which produces higher delay.
Due to the scope of this research, the protection part will not be analysed. The protection
device and circuit breaker in Figure 3.2 is just for illustration of a typical LV Microgrid with
the control, protection, and asset management functions.
27
Figure 3.2 – Communication network topology for LV Microgrids power control and
asset management
As shown in Figure 3.2, within a smart home, there is a Home control and management
centre (HCMC) which is in charge of controlling and managing all the in-home private DERs
and smart household appliances.
There are some motivations behind this hierarchical topology. First, by having HCMC
control and manage in-home the equipment, we achieve a highly distributed management
layer which reduces the amount of information to be kept at the regional level. Second, the
users have their control over the information they share with the utility. A HCMC can work
as a proxy or gateway in the home-neighbourhood boundary using the IEC 61850 proxy
feature that will be discussed later in this chapter.
The Home control and management centre can handle the Demand Response Signal sent
from the Regional control and management centre to manage the energy
consumption/production of the house. HCMC can control the household appliances to
modulate their energy consumption and the DERs to modify their power production ability.
RCMC is capable of monitor and if permissible manage the HCMCs in order to efficiently
utilize the available energy of the grid.
28
3.2 IEC 61850 data modelling
The main idea of IEC 61850 is to breakdown a physical device in to logical devices each of
which will be further broken down into logical nodes, data objects and data attributes [1].
The Logical Device hosts communication access point of IEDs and related communication
services and is hosted by a single IED. However, there’s no rule on how to arrange Logical
Devices into a physical device which brings a great flexibility to the user.
Logical Nodes are the smallest entities which are derived from the application functions.
Logical nodes are the building blocks of the standard since they represents the smallest
functions of the device. The scope of this project is about microgrids control and asset
management which is very different from the scope of substation automation systems;
therefore, many new functions must be modelled. The next clause will describe how to model
a new function as IEC 61850 Logical Nodes.
Figure 3.3 – IEC 61850 data modelling, copied from [1]
Figure 3.3 illustrates the principle of IEC 61850 data modelling. In this case, a physical
device IEDx is composed of a logical device LDx in which there are two different logical
nodes XCBR and MMXU. XCBR1 and MMXU1 are the two instances of the logical node
class XCBR and MMXU which represent the circuit breaker and the measurement unit
respectively.
29
Each logical node is composed of many data object. In this example, logical node XCBR1
contains the data object Pos which represents the position of the circuit breaker. This data
object consists of many data attribute among which are StVal attribute for setting the position
of the breaker to open or close, q attribute stands for quality of the data and t stands for time
of operating the function.
3.2.1 Extension rule for logical nodes
The rule for extension or definition of new logical nodes is defined in IEC 61850 part 7-1 [3]
Figure 3.4 – Basic extension rules diagram, copied from [3]
The rules modelled in Figure 3.4 can be briefly summarized as follow [3]:

If there is any Logical Nodes Class which fits the function to be modelled, an instance
of this logical node shall be used with all its mandatory data (M).
30

If there are dedicated versions of this function with the same basic data different
instances of this Logical Node Class shall be used.

If there are no Logical Nodes Classes which fit to the function to be modelled, a new
logical node shall be created according to the rules for new Logical Nodes.
3.2.2 IEC 61850 data modelling for Microgrids components
There are 3 types of equipment to be modelled in a typical LV Microgrid:

Distributed energy resources (DER): Photovoltaic – PV panel, electric vehicle, energy
storage…

Smart household appliances: LCD TV, electric heater, refrigerator…

Control and management centres: Regional/Home control and management centre.
3.2.2.1 Distributed energy resources
Following the extension rule for logical nodes above, we mostly utilize the existing logical
nodes defined in the standard part 7-420 [7], the draft technical reports part 90-7 [9] and part
90-8 [10] for modelling the DERs. Additionally, the object models for wind turbine can be
found in series IEC 61400-25: "Communications for monitoring and control of wind power
plants". In Figure 3.5, we can see many existing logical nodes defined for substation
automation systems were applied for DERs, and also many new logical nodes defined to
represent the new functions of DERs.
31
Figure 3.5 – Conceptual organization of DER logical devices and logical nodes, copied
from [7]
Because there’s no strict rule on the arrangement of logical devices on physical device, it’s
not necessary to implement all of the logical nodes in Figure 3.5 to a DER. Actually, depend
on the specific locations and application requirements of the DER, only respective logical
nodes should be added.
For simplification in home automation systems, only the PV panel is used as the distributed
generator and the energy storage is the battery which also connects to the PV through a
hybrid inverter for charging purpose. The hybrid inverter allows the reverse flow of power
from the PV and energy storage to the grid in case of emergency or in response to the
Demand Response signal issued by the RCMC as a consequence of peak demand periods.
3.2.2.2 Smart household appliances
As the household appliances are the very new devices to be modelled within IEC 61850, the
first step of modelling should be identification of their characteristics. There are hundreds of
32
different household appliances; therefore, we only take into account the appliances that
consume much energy. Table 3.1 summarizes the typical energy-consuming appliances and
their significant characteristics to be modelled.
Television
Electric cooker
Cooker Hood
Microwave
Electric Stove
Dishwasher
Refrigerator
Washing machine
Clothes Dryer
Bread maker
Coffeemaker
Air conditioner
Fan
Electric heater
Dishwasher
Electric water heater
Printer
Kettle
Lighting system
Table 3.1 – Smart household appliances and their typical characteristics
On/Off
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Voltage
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Current
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Frequency
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Energy consumption
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Household Electric
Appliances
Properties
Product information
(serial number,
manufacturer…)
Temperature
X
X
X
Speed
X
X
X
X
X
X
Energy modulation
X
X
X
X
X
X
X
X
X
Regarding to the appliances parameters listed above, the basic functions required for control
and management of household appliances should be:

switching ON/OFF the equipment

monitoring the device status

measuring/monitoring the energy-related parameters (current, voltage, frequency,
energy consumption)

monitoring other parameters (e.g. temperature)

moderating the energy consumption by alternating the operation modes of the devices
33
Firstly, we can see that IEC 61850 provides the two Logical Nodes MMXN and MMTN for
measurement and monitoring of single-phase voltage, current, frequency and energy
consumption [6]. Therefore, we should utilize these Logical Nodes to model the energy selfmeasuring and monitoring functions of the household appliances.
Secondly, for monitoring the devices in term of physical/product information, IEC 61850
defines the Logical Node LPHD [6] consist of the physical information of the equipment
which is mandatory for all IEDs. Therefore, with the Get and Report services it is possible to
get this kind of information for management purposes.
Similarly for monitoring other operational parameters such as fan speed, temperature,
pressure, heat…of the devices, IEC 61850 also provisions the corresponding Logical Nodes
KFAN, STMP, MPRS, MHET… [7].
Although there are many Logical Nodes existing in the standard that are applicable, some
functions for control services not been defined due to the difference in scope between
substation automation systems and home automation systems. Energy modulation is the most
important function needed to be modelled but it lacks from the standard. Therefore, a new
general logical node for all smart appliances named ZAPL was defined as table 3.2
Table 3.2 – ZAPL class
This new Logical Node allows retrieving information about the operation status of the
corresponding appliance such as the operation status and operating mode i.e. the appliance is
working autonomously or following a schedule or being controlled by the user.
The function of turning ON/OFF the device is also modelled in ZAPL Logical Node since it
is a basic and mandatory function for all devices.
34
This Logical Node represents the energy tuning function which is indispensable to manage
the energy consumption of the appliances in order to assure energy efficiency. By setting the
load target set-point, the Home control and management centre or the user can modulate the
energy consumption of the appliances.
By setting the load target, HCMC can manage the energy consumption of all smart
appliances; however, another way to tune the energy consumption of a device is to directly
change its operational threshold like changing the speed of a fan, or the temperature of a
heater or refrigerator.
IEC 61850-7-4 defines a Logical Node called STMP for temperature supervision, so it is
convenient to utilize this Logical Node and add more data objects to model the temperature
tuning function.
Table 3.3 – Extension to STMP class
As shown in Table 3.3, a temperature set-point to the STMP class was added to control the
temperature. Therefore, an instance of the STMP class with TmpSpt allows tuning the
energy consumption of a heater or refrigerator by changing its output temperature.
3.2.2.3 Control and management centre
Within the scope of this research, management of the in home automation systems is the main
issue for concentration. HCMC can use IEC 61850 services for communication with the
Logical Nodes in smart appliances to perform management tasks. The models for the smart
appliances have been defined in the section above.
35
In the regional area, it is necessary to model the data and function of HCMC that RCMC can
access and manage. For this purpose, a new Logical Node ZHCM has been defined as in table
3.4.
Table 3.4 – ZHCM class
ZHCM class
Data Object
Name
LNName
Data Objects
EEHealth
EEName
OpTmh
Status
Oper
OperMod
Common
Data Class
Explanation
M
/O
/C
Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
ENS
DPL
INS
External equipment health
External equipment name plate
Operation time
O
O
O
SPS
ENS
Operation status of the Home control and management center
Operating mode
M
M
Value
1
2
99
Settings
MaxWh
T
ASG
Explanation
Autonomous
Controllable
Other
Set-point of maximum energy consumption
O
In this Logical Node, there is a data object OperMod which represents the operating mode of
HCMC. If HCMC is configured to be controllable then RCMC can use the data object
MaxWh to change the allowed maximum energy consumption of the house.
If there is no error and the control function succeeds, HCMC will then control the in-home
DERs and appliances to reduce the energy consumption in response to the Demand response
signal sent from RCMC.
As stated earlier in this chapter, HCMC can be used to control the amount of information that
the users want to share with their utility. HCMC can act as a gateway/proxy by "hosting" the
logical devices that it permits the outside world to see. An illustration of this feature is shown
in Figure 3.6.
36
Figure 3.6: Logical devices in proxies or gateways
The HCMC can be viewed as the physical device D in the figure. A, B and C can be different
smart appliances or DER within the home system. If HCMC permits the devices to be viewed
by the outside world, it can "copy" the logical device from them. As only HCMC should
connect with the RCMC, this feature can be employed to provide privacy for the users.
3.3 Summary
This chapter fulfilled the two first objectives of the research: Objective 1 – Designing a
communication network topology in LV Microgrids; and Objective 2 – Modelling LV
Microgrids electrical components for power control and asset management.
In section 3.1, a communication network topology was designed to allow the information
transmissions among the Home Control and Management Centre – HCMC to all the Smart
37
appliances inside the smart houses as well as connecting all the HCMCs and public DERs to
the Regional Control and Management Centre at regional domain. Due to the current version
of IEC 61850 that standardizes Ethernet as the layer 2 protocol, this network was built over
Ethernet. However, it is also possible for future research on applying another underlying
protocol for transmitting the IEC 61850 information such as wireless or cellular networks.
Section 3.2 gives a further details about IEC 61850 data modelling principles which were
mentioned in chapter 2. More importantly, this section described how to use those principles
in practice by modelling the LV microgrid electrical components with IEC 61850 data
objects. This section also defined some new logical nodes to represent for the very important
control and management functions such as ZAPL and ZHCM logical nodes. However, it is
crucial to realize that this research has utilized almost the existing logical nodes defined in
IEC 61850 documents to model very different components in a very different area with the
substation automation systems. This shows the great possibility of extending the scope of IEC
61850 to other area in order to provide interoperability to the future Smart Grid.
38
Chapter 4
Applying IEC 61850 data models
and services for microgrids for LV
microgrid asset management
The goal of this chapter is to apply the IEC 61850 services on the object models that have
been defined in chapter 3 in order to support asset management within the LV microgrids in a
specific use case.
The use case is not meant to cover all the functionalities of LV microgrid management tasks,
as there have to be hundreds of use cases to achieve this. Instead, the use case is provided to
illustrate some typical behaviours and interactions of the components within smart home
system (considered as a LV microgrid) for the specific management tasks. In the use case, the
management tasks are performed by the Home Control and Management Centre (HCMC). It
is the entity that manages other equipment in the home system, such as smart appliances,
DER, and also networking devices. The advantage of this design is the HCMC has an overall
picture of the equipment to be managed inside the home, and provides a single portal for the
users to keep track of their equipment (e.g. health, operation status and settings), and notifies
the users when a problem happens via the alarm handling functions.
IEC 61850 has been applied for the IEDs within substation automation systems and had
tremendous success. Its object models have been extended to cover also DERs, EVs, power
plants, etc. The main contribution of this chapter and also of this report is to demonstrate that
with the IEC 61850 models defined in chapter 3 and the existing IEC 61850 services, IEC
61850 is capable of performing management tasks, which is a new application in a new
domain for IEC 61850.
4.1 Overview on asset management
An asset management system is a crucial part in an electrical system as it provides a
systematic way to maintain and ensure normal operation of physical assets, and also provides
an information base for other applications, such as smart control, system planning, etc.
39
In this report, asset management is defined as the composition of the following tasks:

Inventory management: the management system keeps track of the list of devices to
be managed together with their related information, e.g. vendor, serial number,
location, etc.

Configuration management: the management system maintains the configuration and
settings of the devices.

Device monitoring: the management system acquires the current status of the devices,
e.g. device health, measurement data, etc.

Alarm management: the management system handles the alarm generated by the
devices when certain problems occur.
Within a smart home context, the devices to be managed are smart appliances, DERs and also
networking devices (such as switches). In order to do the management of these assets, there
are two possible approaches [17]:
The first approach is the HCMC uses SNMP for management tasks. SNMP is a well-known
protocol and is supported by almost all networking devices. The management information is
structured into Management Information Base (MIB) objects. SNMP an extensible protocol
as different vendors can define their private MIBs beside the list of standard MIBs. To follow
this approach, data objects and attributes of smart appliances and DERs need to be mapped to
SNMP MIBs, and HCMC has to implement SNMP.
The second approach is to use IEC 61850 MMS protocol for management tasks. This
alternative to SNMP protocol requires the networking equipment to support IEC 61850, and
models for these devices have to be defined.
The following sections will further describe the second approach, which is using IEC 61850
MMS services for management tasks. Considering IEC 61850 has been used for the control
functions, using the same protocol for management tasks would enable the simpler design
and implementation of the system. It also allows seamless integration of networking devices,
smart appliances and DERs for both control and management functions.
As stated above, models for networking devices have to be defined. IEC 61850-90-4
describes the extension to existing Logical Nodes (LPHD, LCCH) to support information
models for the physical bridge (LPHDB), bridge ports (LCCHB) and also the information
that these models contain in relation with SNMP MIB objects. Some of these models are
listed in Table 4.1 and 4.2.
40
Table 4.1: Additional Bridge-data objects in LPHDB added to LN LPHD [17]
In Table 4.1, the existing logical node LPHD is extended to add additional physical
characteristics of a bridge, e.g. whether the bridge is the root of the layer 2 spanning tree, or
the settings of VLAN ID or Mac address filtering.
Table 4.2: Additional Bridge-data objects in LCCHB added to LN LCCH [17]
41
Table 4.2 provides some extensions to the existing LN LCCH (Physical Communications
Channel Supervision) including the port status (bit rate, duplex mode, port VLAN ID, etc.)
These additions shown in Table 4.1 and 4.2 are important especially for large layer 2 Ethernet
network, where maintaining the forwarding spanning tree is important. Within smart home
automation, what we are interested in is the status of the bridge port connected to IEDs. The
status is contained in the existing data object ChLiv (physical channel status) in LN LCCH.
4.2 Asset management use case
The scope of this use case is about the management of smart appliances, networking devices,
DERs (referred to as "managed devices", or "devices" for the rest of this chapter) within
Smart Home Automation system. The management system is implemented in the HCMC.
The information exchange using IEC 61850 data models and services among the devices will
also be specified.
4.2.1 Description of the Use Case
In IEC 61850, the configuration of devices must be done offline using engineering tools.
Currently IEC 61850 does not specify the auto-configuration or auto-discovery of the
devices. This is considered disadvantages of IEC 61850 when applied to the Smart Home
domain, where ideally the equipment should have the "plug-and-play" capability. This feature
is being proposed by [18], in which the combination of Universal Plug and Play (uPnP) and
Devices Profile for Web Services (DPWS) is investigated for a plug-and-play reference
architecture of IEC 61850.
This Use Case presumes that the HCMC and the managed device have been configured to be
able to exchange information, and the Use Case is divided into two scenarios:
In the first scenario, the HCMC obtains the capabilities of the new managed device, creates a
database entry for it and configures the device for additional services such as reporting. This
is an important task for asset management as it provides a database of devices that are
working within the smart home context. This information can then be used for other tasks
such as power control.
42
In the second scenario, the configured managed device interacts with the HCMC. HCMC
keeps an up-to-date database of the device when there is change to ensure normal operation.
The HCMC generates alarms under abnormal conditions.
4.2.2 Actor (Stakeholder) Roles
Below are the actors within this use case. These are the entities that have interaction through
information exchange to perform the use case.
Table 4.3: Actor (Stakeholder) Roles
Actor Description
Actor
Name
Actor Type (person,
HCMC
Subsystem
Home Control and Management Centre
controls and manages DERs, Smart
Appliances, network devices
Managed
device
Device
The device to be managed (smart appliances,
DER, network devices)
organization, device, system,
or subsystem)
4.2.3 Information exchanged
The information exchange among the actors is listed in the table below.
Table 4.4: Information exchanged between actors
Information Object
Name
Information Object Description
DeviceCapability
request
The request from HCMC to a managed device to obtain its
capabilities
DeviceCapability
response
The capabilities of a managed device sent to HCMC
NamePlateData request
The request from the HCMC to the device to get name plate
information of the device.
NamePlateData
The name plate information provided by the devices to the
43
Information Object
Name
Information Object Description
response
HCMC. This information is defined in the IEC 61850 object
models. The name plate contains information about the vendor,
serial number, location, etc. of the devices.
StatusSetting request
A command sent from the HCMC to request the status and
settings of the device.
StatusSettingData
A message which contains information about the status and
settings of the device.
Configuration
A command sent from the HCMC to configure the device (e.g.
reporting services)
ConfigurationConfirm
A message which contains confirmation about the current
configuration of the device.
Report
A report contains a set of data attributes that are configured to be
sent from the device to the HCMC
4.2.4 Step by Step Analysis of Function
4.2.4.1 Step to implement function – Scenario 1
In order to perform the function listed in Scenario 1, there are preconditions and assumptions
for HCMC and device, see Table 4.5.
Table 4.5: Preconditions and Assumptions
Actor/System/Information/Contract Preconditions or Assumptions
Managed device
Has been implemented with auto-discovery
functions to join, discover and self-configure to
work with HCMC.
HCMC
Has known the existence of the device (e.g. having
the IP address of the device by the discovering
process) and needs to connect to the device to
acquire more information.
44
The step-by-step analysis of the activities needed to perform the defined task in Scenario 1 is
shown in Table 4.6.
Table 4.6: Steps to implement function - Scenario 1
Name of
Process/Ac
tivity
Description of
Process/Activity
Informati
on
Producer
Informa
Name of Info
tion
Exchanged
Receiver
Browses
device
capabilities
HCMC browses
device for its
capabilities
HCMC
Managed
device
DeviceCapability
request
Managed device
returns its capabilities
to HCMC
Managed
device
HCMC
DeviceCapability
response
HCMC
Managed
device
NamePlateData
request
Managed Responds
Managed device
device
with name
responds with name
plate information
plate
information
Managed
device
HCMC
NamePlateData
response
1.5
HCMC
Checks for
duplicate
devices
HCMC checks the
database for existing
device entry
HCMC
HCMC
1.6
HCMC
Creates a
database
entry for
the device
HCMC creates a
database entry for the
device
HCMC
HCMC
1.7
HCMC
Requests
status and
settings of
the device
HCMC polls the
device for status and
settings using an IEC
61850 browser
HCMC
Managed
device
StatusSettings
request
1.8
Managed Responds
Device responds with
device
with status status information
information
Managed
device
HCMC
StatusSettings
Data
1.9
HCMC
HCMC
HCMC
#
Primary
Actor
1.1
HCMC
1.2
Managed Returns
device
device
capabilities
1.3
HCMC
1.4
Requests
HCMC polls the
name plate device for name plate
information information using an
IEC 61850 browser
Updates the HCMC updates the
device
status and settings of
the device in the DB
status and
settings in
the DB
45
#
Primary
Actor
1.10 HCMC
Name of
Process/Ac
tivity
Configures
additional
service on
the device
1.11 Managed Confirms
device
the new
configurati
ons
Informati
on
Producer
Informa
Name of Info
tion
Exchanged
Receiver
HCMC configures
additional service on
the device
HCMC
Managed
device
Configuration
Data
Managed device
confirms the new
configurations
Managed
device
HCMC
Configuration
Confirm
Description of
Process/Activity
Figure 4.1 shows the interaction between the actors with the activities defined in Table 4.6.
Managed device
HCMC
1.1 Obtains device capabilities
1.2 Device capabilities
1.3 Request name plate information
1.4 Response name plate information
1.5 Check for duplication
1.6 Creates a database entry for the device
1.7 Requests status and settings of the device
1.8 Status and settings
1.9 Updates the device status in the DB
1.10 Send device configurations
1.11 Confirmation
Figure 4.1: Message flow for Scenario 1 of Asset Management use case
46
4.2.4.2 Step to implement function – Scenario 2
The step-by-step analysis of the activities needed to perform the defined task in Scenario 2 is
shown in Table 4.7
Table 4.7: Steps to implement function - Scenario 2
Description of
Process/Activity
Informa
tion
Produce
r
1.1A.1
Managed Managed device sends report
device
to HCMC
1.1B.1
HCMC
1.1B.2
Informa
tion
Receiver
Name of Info
Exchanged
Managed
device
HCMC
Report
HCMC
Managed
device
StatusSettings
request
Managed Managed device responds with
device
status information
Managed
device
HCMC
StatusSettings
Data
1.2
HCMC
HCMC updates the status and
settings of the device in the
DB
HCMC
HCMC
1.3
HCMC
HCMC notifies the user if an
alarm is detected
HCMC
HCMC
1.4
HCMC
HCMC loses communicate
with the managed device
HCMC
HCMC
1.5
HCMC
HCMC waits for a hold-down
timer
HCMC
HCMC
1.6
HCMC
HCMC deletes the device
entry from the database
HCMC
HCMC
#
Primary
Actor
HCMC polls devices for status
and settings
(*) HCMC detects a time-out for communication link, or get an alarm from network devices.
(**) This is to prevent frequent database delete/insert when there is a frequent change in
communication link between HCMC and the managed device.
47
Figure 4.2 shows the interaction between the actors with the activities defined in Table 4.7.
HCMC
Managed device
1.1A.1 Sends reports (event-trigger, alarms, etc.)
1.1B.1 (Periodic) Requests status and settings of the device
1.1B.2 Responses with status and settings information
1.2 Updates the device status and settings in the DB
1.3 Notifies users after an alarm is detected
<Communication error>
1.4 Detects the communication link problems
1.5 Waits for a hold-down timer
1.6 Deletes the device entry from database
Figure 4.2: Message flow for Scenario 2 of Asset Management use case
48
4.3 Realization of use case with IEC 61850
This section is the core of the chapter in which it describes how the IEC 61850 object models
defined in chapter 3 and existing IEC 61850 services can be integrated to realize the
management tasks in the 2 scenarios the use case. An example will be given to show the
interaction between the HCMC and some managed devices working in a home automation
system using IEC 61850. The mapping between IEC 61850 models to underlying protocol is
also described.
4.3.1 Scenario 1
In this scenario, HCMC has to retrieve information about managed device to build the entries
for its device database. IEC 61850-7-2 provides multiple services to retrieve data. However,
before performing these services, an application association needed to be established.
An Application association can be considered an agreement between two parties in which the
party that sends "associate" message will be the client and the other will be the server. In IEC
61850, the method of establishing an application association follows the TWO-PARTYAPPLICATION-ASSOCIATION (TPAA) class syntax defined in part IEC 61850-7-2 [4].
Figure 4.3: TWO-PARTY-APPLICATION-ASSOCIATION (TPAA) class syntax [4]
Figure 4.3 shows the communication pattern of an IEC61850 client and server. In this case,
the managed device acts as an IEC 61850 server and the HCMC is the client within the
context of the Smart Home automation system. The client can request data from the server in
a request/response fashion (confirmed method), or the server can send data to the client
49
without the client initiating the request (unconfirmed method). The confirmed method can be
used when the HCMC wants to get specific information from the devices, such as polling the
operation status or getting the current settings on the devices. The unconfirmed method can
be used in the reporting services, where the manage devices are configured to send some
specific data to the client without having to wait for the client request.
The structure of a server implementation is depicted in Figure 4.4.
Figure 4.4: Relations between classes in an IEC 61850 server
The Meta Model in IEC 61850-7-2 part defines several generic classes, such as
GenServerClass, GenLogicalDeviceClass, GenLogicalNodeClass, GenDataObjectClass
50
for the servers (7), logical devices (9), Logical Nodes (10) and data objects (11, 12), as well
as services that are supported for each class.
One important notice in IEC 61850 is that the services operate on instances of classes only.
The generic classes have to be instantiated into entities that have unique identities (termed
instances, or objects). Figure 4.5 shows some specific instances of generic classes. MMXN1
is an instance of a generic logical node class MMXN, the data object Amp is an instance of
the Common Data Class MV (Measured Values), etc.
GenLogicalNodeClass
GenCommonDataClass
instance
GenDataAttributeClass
MMXN1
MMXN
Amp
LN instance
MV
mag
f
Sub Data Attributes
...
Data Attributes
FLOAT32
...
...
Data Object class
AnalogueValue
Basic Type
Figure 4.5: Instantiation of generic classes
An IEC 61850 server (e.g. a washing machine) has an access point that determines how it can
be reached. The server can serve one or more clients (associations). A server can host several
logical device instances, each has different logical nodes instances (functions as defined in
chapter 3). For example, a washing machine can have a logical device instance WM01 which
is broken down into logical nodes instances LPHD1, LLN0, MMXN1, MMTN1, ZAPL1.
Each of these LN has its own data objects and attributes. These attributes can be put in data
sets which can be used for other services such as MMS Services, GOOSE, SV, etc.
The next sections will described in details how IEC 61850 services can operate on these
instances to support information exchange as described in Scenario 1.
4.3.1.1 Device capabilities
As logical nodes represent specific functions of a device, the HCMC can obtain the list of
LNs within a device to get its functional capabilities. This is made possible thanks to the selfdescription of IEC 61850, in which several GetXXDirectory and GetXXDefinition services
51
are supported. The services that are supported in each level of the information object tree is
shown in Figure 4.6.
Figure 4.6: IEC 61850 server structure and the related services
The HCMC (client) can use the GetServerDirectory service to retrieve a list of the names of
all logical devices made visible on the washing machine (server). The parameters needed to
perform the GetServerDirectory service include:
Request:
- ObjectClass: shall contain an identification of the
selected class. The client shall select one of the
following classes: LOGICAL-DEVICE or FILESYSTEM
Response+: shall indicate that the service request
succeeded. A successful result shall return the
following parameter.
- Reference [0..n]: shall contain the ObjectReference of the logical devices and file
systems. Response-:
52
Response-: The parameter Response– shall indicate that the service request failed. The
appropriate ServiceError shall be returned
After retrieving the list of logical device instances on the device, the HCMC shall use the
GetLogicalDeviceDirectory service to retrieve the list of the ObjectReferences of all
Logical Nodes made visible and thus accessible to the HCMC by the referenced logical
device. The parameters needed to perform the GetLogicalDeviceDirectory service include:
Request:
- LDName: shall contain the object name of a logical
device.
Response+: shall indicate that the service request
succeeded. A successful result shall return the
following parameter.
- LNReference
ObjectReference of the logical devices and file systems.
[1..n]:
shall
contain
the
Response-: The parameter Response– shall indicate that the service request failed. The
appropriate ServiceError shall be returned
Assuming that there are no errors with these 2 GetServerDirectory and GetLogicalDeviceDirectory requests, the HCMC obtains the list of logical nodes of the device; hence it knows
its functional capabilities of the device. Figure 4.7 shows an example of the interaction
between the HCMC with a washing machine, an electric fan, and an electric heater whose
logical nodes are different.
53
HCMC
Washing machine
Fan
Heater
GetServerDirectory Request
Param: ObjectClass = LOGICAL-DEVICE
GetServerDirectory.Response+
Param: Reference[0..n] = WM01
GetLogicalDeviceDirectory Request
Param: LDName = WM01
GetLogicalDeviceDirectory.Response+
Param: LNReference[1..n] = [WM01/
LLN0; WM01/MMXN1; WM01/
MMTN1; WM01/ZAPL1]
GetServerDirectory Request
Param: ObjectClass = LOGICAL-DEVICE
GetServerDirectory.Response+
Param: Reference[0..n] = FAN01
GetLogicalDeviceDirectory Request
Param: LDName = FAN01
GetLogicalDeviceDirectory.Response+
Param: LNReference[1..n] = [FAN01/
LLN0, FAN01/MMXN1, FAN01/
MMTN1, FAN01/KFAN1]
GetServerDirectory Request
Param: ObjectClass = LOGICAL-DEVICE
GetServerDirectory.Response+
Param: Reference[0..n] = HEATER01
GetLogicalDeviceDirectory Request
Param: LDName = HEATER01
GetLogicalDeviceDirectory.Response+
Param: LNReference[1..n] = [HEATER01/
LLN0, HEATER01/MMXN1, HEATER01/
MMTN1, HEATER01/STMP1]
Figure 4.7: Example of GetServerDirectory and GetServerDirectory service used by
HCMC
54
4.3.1.2 Device status and settings
After retrieving the list of Logical Node instances on the device, the HCMC has several
options to retrieve the status and settings of the device.
Option 1: HCMC uses GetDataValues service to retrieve individual data object value
A logical node may have many different data objects, each with many data attributes. This
option is suitable when HCMC only needs a single value for a particular data attribute (e.g.
only current power usage, or the load set-points of the device). This option provides the
selectivity for the data retrieval from HCMC and also suits the bandwidth-limited network.
Currently Ethernet bandwidth is sufficient, but in the future when the protocol is mapped
onto lower bandwidth protocol such as ZigBee, this option will help reduce the bandwidth
consumption. The parameters needed to perform the GetDataValues service.
Request:
- Reference: shall define the functional constrained
data (FCD) or functional constrained data attributes
(FCDA) of the data object whose data attribute values
are to be retrieved. The Reference shall be FCD or
FCDA
Response+: shall indicate that the service request
succeeded.
- DataAttributeValue [1..n]: The parameter
DataAttributeValue [1..n] shall contain the values of
all data attributes of a data object referenced by FCD;
or the value of a data attribute referenced by FCDA.
Response-: shall indicate that the service request
failed. The appropriate ServiceError shall be returned.
The Reference in the GetDataValues Request should have the functional constraint (FC) set.
Functional constraint is the property of a data attribute that indicates the services, e.g. read
55
value, write value, substitute value, etc. that may be applied to that data attribute. Figure 4.8
shows a data attribute reference WM01/MMXN.Watt.mag that represents the power
consumption for the washing machine in Figure 4.7. This attribute has FC=MX which means
the attribute represent a measurand information whose value may be read, substituted,
reported, and logged but shall not be writeable.
Instance of MMXN
Data Attribute
WM01/MMXN1.Watt.mag [MX]
LDName
MX Functional constraint data attribute (FCDA)
DataObject
Functional
constraint
Figure 4.8: A reference with a functional constraint
For example, the HCMC uses GetDataValues service to retrieve the power usage and
operation status of the washing machine, the speed set point of the fan and the temperature
set point of the heater. These values are contained in the logical nodes of the appliances that
have been defined in Chapter 3. Specifically, the power usage of the washing machine can be
obtained by getting the value of the Watt data object in LN MMXN; the operation status is
visible by getting the Oper data object in LN ZAPL (newly defined); the speed set point of
the fan is represented by the Spd data object in LN KFAN; and the temperature set point is
included in TmpSpt data object in LN STMP (extended from existing LN). The message
flows and parameters are shown in Figure 4.9.
56
HCMC
Washing machine
Fan
Heater
GetDataValues.Request
Param: Reference = WM01/MMXN1.Watt.mag [MX]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [700] (700 Watts)
GetDataValues.Request
Param: Reference = WM01/ZAPL1.Oper.stVal [ST]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [TRUE]
GetDataValues.Request
Param: Reference = FAN01/KFAN1.Spd.mag [MX]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [10] (10 rotations per second)
GetDataValues.Request
Param: Reference = HEATER01/STMP1.TmpSpt.setMag [SP]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [24] (24 degrees)
Figure 4.9: Example of GetDataValues service used by HCMC
The HCMC can recursively use the GetDataValues service to get the needed data values.
However this is not a very effective method as the HCMC typically needs a lot more data
object values. Therefore it can use the GetAllDataValues service (Option 2).
Option 2: HCMC uses GetAllDataValues service in GenLogicalNodeClass to retrieve all
data object values of a Logical Node instance in the washing machine.
57
The parameters needed to perform the GetAllDataValues service include:
Request:
- LNReference: shall contain the ObjectReference of
the
Logical
Node
(which
shall
be
LDName/LNName)
FunctionalConstraint (FC): shall contain the
functional constraint parameter (FC) to filter the
respective data attributes of all data objects contained
in the Logical Node.
Response+:
shall
indicate
the
request
succeeded/failed
- DataAttributeReference [1..n]: shall contain the ObjectReference of a data attribute
contained in the Logical Node that shall be returned according to the value of the
FunctionalConstraint received in the request.
- DataAttributeValue [1..n]: shall contain the value of a data attribute of the data object
contained in the referenced Logical Node. If the parameter FunctionalConstraint is present
in the service request then only values of those data attributes that have the Functional
Constraint as given in the service request shall be returned.
Response-: shall indicate that the service request failed. The appropriate ServiceError shall
be returned.
For example, Figure 4.10 illustrates the the HCMC using GetAllDataValues service to
retrieve all the measurand values of the measurement function (Functional Constraint = MX)
from Logical Node instance MMXN1 of the washing machine, KFAN1 of the fan, and
STMP1 of the heater.
58
HCMC
Washing machine
Fan
Heater
GetAllDataValues.Request
Param: LNReference = WM01/MMXN1
FunctionalConstraint [0..1] = [MX]
GetAllDataValues.Response+
Param: LNReference = WM01/MMXN1
DataAttributeReference [1..n] = [
WM01/MMXN1.Amp.mag; WM01/MMXN1.Amp.q;
WM01/MMXN1.Ampt;
WM01/MMXN1.Vol.mag; WM01/MMXN1.Vol.q;
WM01/MMXN1.Volt;
WM01/MMXN1.Watt.mag; WM01/MMXN1.Watt.q;
WM01/MMXN1.Watt.t; etc. ]
DataAttributeValue[1..n] = [3; <quality_1>; <time_1>;
220; <quality_2>; <time_2>;
600; <quality_3>; <time_3>; etc.] (*)
GetAllDataValues.Request
Param: LNReference = FAN01/KFAN1
FunctionalConstraint [0..1] = [MX]
GetAllDataValues.Response+
Param: LNReference = FAN01/KFAN1
DataAttributeReference [1..n] = [
FAN01/KFAN1.Spd.mag; FAN01/KFAN1.Spd.q;
FAN01/KFAN1.Spd.t]
DataAttributeValue[1..n] = [10; <quality_4>;
<time_4>;] (*)
GetAllDataValues.Request
Param: LNReference = HEATER01/STMP1
FunctionalConstraint [0..1] = [MX]
GetAllDataValues.Response+
Param: LNReference = HEATER01/STMP1
DataAttributeReference [1..n] = [
HEATER01/STMP1.Tmp.mag; HEATER01/
STMP1.Tmp.q; HEATER01/STMP1.Tmp.t]
DataAttributeValue[1..n] = [24; <quality_5>;
<time_5>] (*)
Figure 4.10: Example of GetAllDataValues service used by HCMC
59
(*) The represented values are for illustrative purposes only. The actual data format has to
conform to specific data types defined in IEC 61850--3 Common Data Classes.
4.3.1.3 Device name plate
The name plate (information about vendor, serial number, hardware/software revision, etc.)
of the washing machine is included in the LPHD and LLN0 Logical Nodes. This information
will be used to keep track of the device in the database. The HCMC can use the
GetDataValues or GetAllDataValues services that have been described in section 3.3.1.2 to
retrieve the name plate information of the device.
For example, the HCMC can retrieve the information about the vendor and serial number of
the washing machine, fan and heater (Figure 4.11)
60
HCMC
Washing machine
Fan
Heater
GetDataValues.Request
Param: Reference = WM01/LPHD1.PhyNam.vendor [DC]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [“Toshiba”]
GetDataValues.Request
Param: Reference = WM01/LPHD1.PhyNam.serNum [DC]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [“TOWM1234”]
GetDataValues.Request
Param: Reference = FAN01/LPHD1.PhyNam.vendor [DC]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [“Philips”]
GetDataValues.Request
Param: Reference = FAN01/LPHD1.PhyNam.serNum [DC]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [“PLFA0001”]
GetDataValues.Request
Param: Reference = HEATER01/LPHD1.PhyNam.vendor [DC]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [“Philips”]
GetDataValues.Request
Param: Reference = WM01/LPHD1.PhyNam.serNum [DC]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [“PLHT1234”]
Figure 4.11: HCMC retrieves device name plate information
4.3.1.4 Device configuration
This section only discusses the reporting service configuration of the device. It is because the
configuration of the operating status and set points is in the scope of equipment control
within home automation system, not asset management. The reporting service is important
because it does not require the HCMC to keep polling the devices to get data values. Instead,
if a report control block is configured in the device (this is the presumption described in
section 3.2.1), HCMC can use ACSI services to change the configuration of the report control
block, so that when a triggering event happens, the reports are sent automatically to the
61
HCMC. However, HCMC cannot create a new report control block in the device, as this has
to be done by IEC 61850 engineering tools. This is considered a disadvantage of IEC 61850.
We assume there is an UNBUFFERED-REPORT-CONTROL-BLOCK (URCB)
configured in the device. Then the HCMC can use the SetURCBValues service to change
some parameters for this URCB:
- RptEna: enabling or disabling the report service on the device
- TrgOps: triggering options of the report, whether it is due to data change, data update,
quality change of the attributes.
- DatSet: the data set that comprises of different data attributes which are of interest to be
included in the report.
For example, the HCMC can enable the report with data change triggering options and a data
set on the heater so that when a temperature rises above the defined threshold, a report is sent.
(See Figure 4.12)
62
HCMC
Heater
SetURCBValues
URCBRef = HEATER01/
LLN0.AlmRpt
rptEna = TRUE
DatSet = HEATER01/
STMP1.DS1
TrgOps = data-change
(Reporting service configured)
Alarm Temperature Value set point = 30 deg
Current Temperature Value = 31 deg
Report
RptID = AlmRpt1
OptFlds
sequence-number = 123
report-time-stamp = 14:31:58
reason-for-inclusion = data-change
data-set
data-set-reference = HEATER01/STMP1.DS1
entry-data
DataAttRef = HEATER01/STMP1.Alm.stVal [ST]
Value = <TRUE>
Figure 4.12: An example of report service configuration
4.3.2 Scenario 2
In Scenario 2, the HCMC monitors the operation status of the devices (by polling or by
receiving reports from the devices). The HCMC generates alarms under abnormal conditions.
In this Scenario, the HCMC also has to monitor the communication link to the devices and
update the device database accordingly.
4.3.2.1 Device health monitoring
Health monitoring is a critical task within asset management, as it ensures the normal
operation of the devices. The devices have the capability to self-assess and report the current
63
problem it might have, e.g. with the physical (hardware) or logical (software) aspects. This
information is contained in PhyHealth data object in LN LPHD and Health data object in
LN LLN0, which can be value 1 (OK - "green" - no problems, normal operation), 2 (Warning
- "yellow" - minor problems, but in safe operation) or 3 (Alarm - "red" - severe problem, no
operation possible).
The HCMC can use the GetDataValues or GetAllDataValues services for health monitoring
of the devices by retrieving the attributes values of the health data objects.
HCMC
Washing machine
Fan
Heater
GetDataValues.Request
Param: Reference = WM01/LPHD1.PhyHealth.stVal [ST]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [1]
(OK)
GetDataValues.Request
Param: Reference = FAN01/LPHD1.PhyHealth.stVal [ST]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [2]
(Warning)
Notifies the user about the warning
GetDataValues.Request
Param: Reference = FAN01/LPHD1.PhyHealth.stVal [ST]
GetDataValues.Response+
Param: DataAttributeValue [1..n] = [3]
(Alarm)
Notifies the user about the alarm
Figure 4.13: HCMC performs health monitoring using GetDataValues service
If the HCMC can use reporting services for health monitoring of the devices by including the
health data object attributes in the report. In this case, whenever there is a change to the
health data object attribute, the device will send reports to the HCMC. This option brings less
overhead for the health monitoring, as only the changes are sent and the HCMC does not
have to perform polling. This method is illustrated in Figure 4.14.
64
HCMC
Heater
Device health: OK
Device health: Warning
Report
RptID = AlmRpt1
OptFlds
sequence-number = 234
report-time-stamp = 17:31:58
reason-for-inclusion = data-change
data-set
data-set-reference = HEATER01/LPHD1.DS1
entry-data
DataAttRef = HEATER01/LPHD1.PhyHealth.stVal
[ST]
Value = <2>
Figure 4.14: HCMC uses reporting services on the device to perform health monitoring
4.3.2.2 Communication link monitoring
Communication links from the HCMC to the devices have to be continuously monitored to
ensure normal operation of the system. The HCMC has to know whether it can reach the
devices it manages. If a device is unplugged from the network, then the HCMC has to notice
that as well. The HCMC can employ the existing keep-alive mechanisms of the transporting
protocol in order to detect link failures with the devices.
The HCMC can also detect layer 1 and layer 2 problems via communicating with the switch
using IEC 61850. We assume that the switch supports IEC 61850, and it has LN LCCH
implemented as described in section 4.1. The switch has an instance of LN LCCH for every
switch port, and then can represent the communication status of the ports connecting to the
devices. The data object attributes ChLiv in the LN LCCH instances can be put in a data set
and be sent as report to the HCMC when there is any change to the data value (port status
changes). Upon receiving this report, the HCMC knows of the changes in the communication
links.
Figure 4.15 shows an example in which the washing machine is unplugged from the network.
The HCMC notices the communication link is broken after receiving the report from the
switch.
65
HCMC
Switch
Washing Machine
SW01/LCCH1.ChLiv.stVal = TRUE
Data-change
In LN
LCCH1.ChLiv
Unplugged
Report
RptID = SwRpt1
OptFlds
sequence-number = 1
report-time-stamp = 19:31:58
reason-for-inclusion = data-change
data-set
data-set-reference = SW01/LCCH1.DS1
entry-data
DataAttRef = SW01/LCCH1.LCCH1.ChLiv.stVal
[ST]
Value = <FALSE>
Figure 4.15: HCMC uses reporting service on a switch to detect communication problems
4.3.3 Mapping ACSI services to MMS
In section 3.3.2, we have seen that the ACSI services of IEC 61850 are capable of performing
management tasks within the home automation system. Since ACSI services are abstract
services, they must be mapped to an underlying protocol to allow communication between
HCMC and the devices. As described in chapter 2, there are several message types within
IEC 61850. Because management service does not require fast message exchange, and
employs the client/server interaction between the HCMC and the managed devices, the ACSI
services are mapped to MMS services as shown in Table 4.8 [8].
66
Table 4.8: MMS objects and services, copied from [8]
Mapping of IEC 61850-7-2 and IEC 61850-7-3 data attributes can also be found in IEC
61850-8-1 [8]. For example, Table 4.9 lists the mapping of the GetDataValues service to
MMS Read service.
Table 4.9: Mapping of GetDataValues service parameters, copied from [8]
67
HCMC
Parameters:
- Presentation Address
- ACSI Authentication Value
Washing Machine
initiate-Request
initiate-Response
Initiate
Parameter:
PresentationEndPoint
VariableAccessSpecification
mmsWM01/MMXN1$Watt$mag
Read-request
Read-response
Data
listOfAccessResult = 700
Conclude-Request
Conclude
Conclude-Response
Figure 4.16: Mapping GetDataValues to MMS Read service to get measurement value
Figure 4.16 sketches the mapping of ACSI GetDataValues service to MMS Read service
that allows the HCMC to establish a two-party association with the washing machine and
retrieve the power consumption in the logical node instance MMXN1. For other services used
in this use case such as GetAllDataValues service, SetURCBValues, etc. a detailed
mapping can be found in IEC 61850-8-1 [8]. The MMS PDU (Protocol Data Unit) will be
encoded using ASN.1 to have the format of TLV (Tag, Length, Value) and will be
transported through communication links by the TCP/IP transport profile (T-Profile) that
MMS supports [8].
4.4. Summary
This chapter is the core of the report, where a typical management tasks are introduced in a
specific use case. IEC 61850 services are applied on the object models that have been defined
in chapter 3 in order to support asset management within the LV microgrids, including the
inventory management, health monitoring, device reporting service configuration, and alarm
handling functions.
68
Chapter 5
Conclusion and future work
IEC 61850 is an extensible protocol to support a growing demand in different domains.
Initially it was designed for interoperability of different IEDs within Substation Automation
Systems, and then was further extended to support object models for power plants, DER and
inter-substation communication.
The main goal of the research is to apply the concepts of IEC 61850 to a different domain,
the LV microgrid, to perform inventory management, configuration management, device
monitoring and alarm handling. Each chapter has fulfilled a specific objective to achieve the
main goal.
Specifically, a communication network topology is presented in chapter 3, which allows for
the distributed control and management of the LV microgrid with user privacy taken into
account. The object models for the components within the LV microgrid are also analysed in
chapter 3. Some of the existing logical nodes for substation domain can be reused, while the
missing models are defined either by extending the data objects of the existing logical nodes,
or defined as new logical nodes.
Based on the defined logical nodes in chapter 3, the IEC 61850 services shown in chapter 4
allow the asset management of the LV microgrid components in a specific use case that
covers typical management tasks. The IEC 61850 services that can be used to fulfil these
management tasks are also presented in chapter 4 with the associated parameters of the
services and the mapping to the communication protocol.
This research contributes to the development of IEC 61850 by introducing a new domain that
the standard has not yet covered: the low voltage network microgrid. Within the research,
IEC 61850, originally used for substation automation, is shown to be capable of performing
asset management within the LV microgrid.
There is room for improvement of the standard within the scope of LV microgrid asset
management. Future work can define more use cases for different purposes, such as voltage
stabilization, microgrid islanding, etc. to see whether IEC 61850 can be used to support these
use cases.
69
One shortage of IEC 61850 is the lack of auto-configuration and device discovery process
that have been described in chapter 4. Currently, IEC 61850 requires the use of engineering
tools to configure the devices in offline mode, and it would not be convenient within a Smart
Home context. More work can be done on the plug-and-play features of IEC 61850, such as
[18].
IEC 61850 defines the mapping between ACSI services and underlying protocols such as
Ethernet, MMS, etc. The next step is to investigate how communication technologies, such as
ZigBee, 802.11, 3G, LTE, etc., can support the use of IEC 61850 for different applications
from different domains, e.g. metering, control and automation.
70
References
[1]
IEC 61850-1 TR Ed.2, "Communication networks and systems for power utility
automation – Part 1: Introduction and Overview", 2012.
[2]
IEC 61850-5, "Communication networks and systems for power utility automation –
Part 5: Communication requirements for functions and device models", 2012.
[3]
IEC 61850-7-1 Ed.2, "Communication networks and systems for power utility
automation – Part 7-1: Basic communication structure – Principles and models", 2008.
[4]
IEC 61850-7-2 Ed.2, "Communication networks and systems for power utility
automation – Part 7-2: Basic information and communication structure – Abstract
communication service interface (ACSI)", 2008.
[5]
IEC 61850-7-3 Ed.2, "Communication networks and systems for power utility
automation – Part 7-1: Basic communication structure – Common data classes", 2008.
[6]
IEC 61850-7-4, "Communication networks and systems for power utility automation
– Part 7-4: Basic communication structure – Compatible Logical Node classes and
data classes", 2008.
[7]
IEC 61850-7-420 Final Draft International Standard (FDIS), "Communication
networks and systems for power utility automation – Part 7-420: Basic
communication structure – Distributed energy resources Logical Nodes", 2008.
[8]
IEC 61850-8-1 Ed.2, "Communication networks and systems for power utility
automation – Part 8-1: Specific Communication Service Mapping (SCSM) – Mapping
to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3", 2009.
[9]
IEC 61850-90-7 Ed.1 Draft Technical Report, "Communication networks and systems
for power utility automation – Part 90-7: IEC 61850 object models for photovoltaic,
storage, and other DER inverters", 2012.
[10]
IEC TR 61850-90-8 Draft, "Communication networks and systems for power utility
automation – Part 90-8: IEC 61850 object models for electric mobility", 2012.
[11]
SMB Smart Grid Strategic Group (SG3), "IEC Smart Grid Standardization Roadmap"
[12]
Frans Campfens, "the Role of the DNO in Smart Grid Cyber Security", European
Smart Grid Cyber Security and Privacy, Amsterdam November, 2011.
[13]
SMB Smart Grid Strategic Group (SG3), "IEC Smart Grid Standardization Roadmap",
Edition 1.0, June 2010.
71
[14]
United Nations Office for the Coordination of Humanitarian Affairs and the Internal
Displacement Monitoring Centre, "Monitoring disaster displacement in the context of
climate change", 2008
[15]
http://smartgridsherpa.com/blog/defining-microgrids-the-enabler-for-localdistributed-energy-infrastructure-development
[16]
Hassan Farhangi, "The path of the Smart Grid", IEEE power & energy magazine,
2010
[17]
IEC 61850-90-4 TR Ed.1: Communication networks and systems for power utility
automation – Part 90-4: Network engineering guidelines for substations, Draft
Technical Report, 2012.
[18]
Juergen Carstens, " A Plug & Play Concept for IEC 61850 in a Smart Grid",
SIEMENS AG 2011
[19]
EPRI's IntelliGridSM initiative, [Online]. Available: http://intelligrid.epri.com
[20]
GridWise Architecture Council, [Online]. Available: http://www.gridwiseac.org
[21]
Ericsson, "Smart-grid communications: enabling next-generation energy networks",
EBR #1, 2012
[22]
Javier Juárez, Carlos Rodríguez-Morcillo, José Antonio Rodríguez-Mondéjar,
“Simulation of IEC 61850-based substations under OMNeT++”, Proceedings of the
5th International ICST Conference on Simulation Tools and Techniques, 2012
[23]
IEC 61850-90-1 Ed 1.0, “Communication Networks and Systems in Substations –
Part 9-1: Specific Communication Service Mapping (SCSM) – Serial Unidirectional
Multidrop Point to Point Link”, 2001
[24]
IEC 61850-9-2 Ed.2, “Communication networks and systems for power utility
automation – Part 9-2: Specific Communication Service Mapping (SCSM) – Sampled
values over ISO/IEC 8802-3”, 2009
72
Download