BERITA ACARA TEST COMMISSIONING DAN TRAINING PERTITION AIR CONDITIONER / PAC MMR 1 & 3 PEMBANGUNAN DATA CENTER MMR DAN POI PT. Tiga Kreasi , Elektrikal , Elektronika , Plumbing dan Mekanikal 2023 CM KONSULTAN PROJECT TEST COMMISSIONING MMR 1 & 3 3 UNIT PAC KONTRAKTOR Siswo B.Rahmat Project Manager Hormat kami, Kontraktor Pelaksana Tes simulasi alarm Setting PAC dg LAN system ( 2 running1 stand by bergantian) Tes PAC alarm water system Tes konfigurasi dg FM 9 10 11 12 PAC Posisi Tes Running PAC Posisi Tes Running PAC Posisi Tes Running PAC Posisi Tes Running PAC Posisi Tes Running Service Manifold,Tang Amphere, Termometer Digital, Form Tescom. Catat hasil ukur tekanan freon,amphere electrical,temperatur in-out 8 Kabel LAN Sensor water alarm Dry contact relay FM PAC Posisi Tes Running PAC Posisi Stand by Power. Pac Posisi Off Pac Posisi Off Pac Posisi Off Pac Posisi Off Pac Posisi Off KETERANGAN Service Manifold, Tang Amphere, Termometer Digital Tang Amphere Phasa Meter Service Manifold Service Manifold Service Manifold Service Manifold ALAT KERJA Lakukan posisi semua MCB status on,dan tekan tombol power PAC ON, paralel pengisian freon lewat pentil pengisian area indoor sampai tekanan pipa gas 70-80 psi. Lakukan pembuangan gas N2 di pipa instalasi sampai habis lewat pentil pipa area outdoor. Lakukan vakum pada pipa instalasi sampai tekanan mines 29 atau mines 30 psi (durasi waktu sekitar 3 jam ) Isi pipa instalasi dg freon R 407 c lewat pentil pipa area outdoorsampai tekanan 90 psi. Pengecekan phasa R,S,T power PAC dg benar. Naikan MCB display pada indoor PAC untuk energized compresor selama 9 jam . Pastikan Instalasi pipa PAC dari Indoor to outdoor selesai lulus tess press minnimum 24 jam. URAIAN KERJA 7 6 5 4 3 2 1 No. Pekerjaan : Start Up PAC Stulz Tanggal : 14 Juni 2023 Lokasi : Data Center MMR 1&3 METODE TEST COMMISIONING PAC PT. KARUNIA INTI MANDIRI General Contractor & Suppliyer Jl. Sumur Batu Raya Blok A3 No. 13 Sumur Batu Kemayoran Jakarta Pusat 10640 Telp. 021 – 4241661 Fax. 021 – 4252671 Email : karuniaintimandiri2000@gmail.com Deltamas User Training CRAC 6/14/2023 ditetapkan. dengan parameter yang telah ruangan secara presisi sesuai suhu udara dan kelembapan Untuk mengatur dan menjaga FUNGSI PRESISI AC 2 1 CRAC TYPE : ASD 251 A (Cyber Air 3) Unit Overview Air Cooled Condensor Page 4 1 A/AS-Sytem : Air Cooled / Direct Expansion (DX) System Unit Overview Page 5 1 Nominal Cooling Capacity (kW) D = Downflow U = Upflow Fan Unit position: S = Standard L = Low energy Unit version: Cyber Air 1 = 1 Circuit 2 = 2 Circuits Page 6 Number of refrigerant circuits: A = Air-Cooled G = Water-Cooled GE = Indirect Free Cooling ACW = Dual Fluid Air-Cooled GCW = Dual Fluid Water-Cooled Cooling System: ASD 251 A NOMENCLATURE DX Unit Overview A = Aluminium, hammer finish S= Steel, powdercoated Condenser frame: 38°C ambient, Max. 45°C condensation Nominal Capacity (kW) V = Vertical Airflow direction: S = Standard L = Low noise Noise level: Condenser 1 Fan quantity 1 = R407C, R134a, (R22) 2 = R410A Refrigerant: KSV 037 A 2 1 Unit Overview Page 7 Display View - C7000 Advance Terminal Overview Unit Page 8 C7000 Advance Terminal Overview Unit Page 9 not attainable bus member selected bus member running unit IOC standby unit IOC „myself“ AT „foreign“ AT Bus Overview AT Page 10 C7000 Info Operate Config Menu Structure AT Page 11 Info → info Menu Structure AT Page 12 Control → operate Menu Structure AT Page 13 Service → config Menu Structure AT Page 14 BMS message Zone: 2+1 with an average of temperature and humidity Alarm Sequencing Page 15 In case of a failure Our Zone 1 BMS message Zone: 2+1 with an average of temperature and humidity Our Zone 1 Page 16 In case temperature increases overload function is activated Overload Sequencing BMS message Zone 2+1 with an average of temperature and humidity Time Sequencing Rotation after adjusted time Our Zone 1 Page 17 3. Jasa penggantian part. 3. Pemeriksaan panel elektrikal. 6/14/2023 13. Emergency Call & onsite support 12. Pencatatan laporan hasil pemeliharaan. 11. Simulasi fungsi alarm (Jika diperlukan) 10. Pengecekan koneksi kabel power & kontrol 9. Pemeriksaan titik-titik bocor disambungan 8. Pemeriksaan setting parameter pada controller. 7. Pembersihan saluran piping drainase 6. Pemeriksaan fungsi komponen. 5. Pemeriksaan pressure refrigerant 18 2. Penggantian part & material 2. Pemeriksaan fisik dan jalur drainase. 4. Pemeriksaan voltage & arus komponen 1. Scope of Work Preventive Maintenance Point 1-13 Comprehensive Maintenance 1. Pembersihan air filter dan unit outdoor. Preventive Maintenance Pemeliharaan PAC STULZ Tanda ada alarm Compressor 2 non aktif Compressor 1 non aktif Compressor 2 non aktif Semua komponen non aktif Semua komponen non aktif Semua komponen non aktif LOW PRESSURE 2 COMP 1 FAILURE/HP COMP 2 FAILURE/HP AIRFLOW FAILURE WATER ALARM FIRE ALARM 6/14/2023 Compressor 1 non aktif LOW PRESSURE 1 Alarm Efek Tanda bahwa unit dalam kondisi non aktif Kelembapan ruangan aktual Suhu ruangan aktual Penanganan Alarm 19 6/14/2023 4. Lakukan tindakan penanganan sesuai penyebab. 3. Konsultasi Alarm CRAC ke Engineer Stulz 2. Lakukan Dokumentasi Alarm CRAC 1. Periksa informasi pada layar controller unit. Tindakan Awal 20 6/14/2023 Kondensor Kotor • Bersihkan kondensor dengan menggunakan air bertekanan Tindakan Penanganan – High Pressure Alarm 21 6/14/2023 Tindakan Penanganan – Low Pressure Alarm 22 6/14/2023 Sensor Error/Rusak Air 23 • Periksa koneksi kabel pada relay sampai dengan sensor, pastikan tidak ada kabel yang putus atau korsleting • Ganti kabel bila terdapat kerusakan pada kabel • Lakukan penggantian suku cadang Bersihkan air di area pemasangan sensor hingga bersih dan kering Water Alarm : Deteksi adanya air yang menggenang dibawah unit PAC. Tindakan Penanganan – Water Alarm 6/14/2023 AirFlow Failure/Filter Failure Alarm : Deteksi penurunan kecepatan aliran udara yang masuk kembali ke evaporator. 24 6/14/2023 Loss Air Flow/Fan Failure Alarm : Deteksi fungsi kerja dari Blower Fan Indoor, bila alarm ini timbul akan membuat unit PAC Shutdown Tindakan Penanganan – Loss Air Flow / Fan Failure Alarm 25 6/14/2023 Asap atau Api • Pastikan bahwa fire alarm bukan alarm palsu (false alarm). • Hubungi pihak penanggung jawab fire suppression system. Fire Alarm : Deteksi adanya asap atau kebakaran dari sistem pemadam kebakaran (fire suppression) di area data center yang otomatis menonaktifkan unit PAC. Tindakan Penanganan – Fire Alarm 26 6/14/2023 5. Lakukan tindakan penanganan sesuai penyebab. refrigerant dengan manifold gauge 27 4. Untuk alarm yang berhubungan dengan Kompressor, periksa tekanan keseluruhan untuk sementara. 3. Non-aktifkan komponen yang bermasalah atau unit PAC STULZ secara 2. Tekan tombol “RESET” dua kali. 1. Setelah Konsultasi Engineer Stulz Tindakan Akhir 6/14/2023 : 081295000890 : 081398933958 : 089527517642 Hotline Service Stulz Engineer Stulz Dedi Sobari Engineer Stulz M. Sarip Help Desk Stulz 28 Thanks you for your Attention ! Finish Page 29