3.4.1 Timer settings input pre-set Sequence name Sequence number Timer pre-set Timer adjustable range Batch Verified Yes Mixer initiation 1 30s 30s-2mins Coagulant 2 10min 10-15mins PH adjustment 3 10mins 10-15mins Flocculation 4 15mins - Mixer stopping 5 15s 15s-1min Settlement 6 30mins 30-1hour Discharge 7 5mins 3-5mins Sludge transfer 8 6mins 5-6mins Aeration 1 16hours - Settlement 2 90mins >2hours Discharge 3 5mins 3-5mins Sludge transfer 4 - - SBR No 3.4.2 Pump testing Pump name Direction of pump Clockwise Filter Feed pump Backwash Pump SBR Pump Break pump EQ pump Screen pump Mixer Air Blower Sludge Pump Filter press feed pump Counterclockwise Leakages Verified Yes Yes No No Remarks if any 3.4.3 Manual / auto Valve and Pump testing Control valve and pump Valve and pump operations Control panel On Off Screen pump EQ pump Sludge pump Filter press pump Break pump Filter Feed pump Backwash pump Air Blower Mixer Coagulant Acid Flocculant MV1 MV2 Air Blower SV Nutrient SBR MV1 SBR MV2 Actual condition On Off Indicator light Green Red Verified Yes No Remarks 3.4.4 High and low levels of Tanks Tank Type Screen tank HIGH / LOW HIGH EQ tank HIGH LOW Batch tank HIGH LOW Break tank HIGH SBR tank HIGH LOW Filter feed tank HIGH Indicator Remarks 3.4.5 PH control settings Relay 1 OPEN/ CLOSE Close Open Value 6.5 6.0 Nature Acid 2 Close Open 5.0 5.5 Alkaline Verified 3.4.6 incoming power voltage test No Phase to Phase Voltage (v) 1 R-Y 415 418.0 2 Y-B 414 418.0 3 R-B 415 421.6 4 R-N 236 242.4 5 B-N 237 242.8 6 Y-N 236 240.0 Verified Yes Remarks No