KEYNOTES - BASIC CEILING DETAILS NOTAS - DETALLES BASICOS DE PLAFON 7 6 1 ATTACH WALL ANGLE AT CEILING PERIMETER. FIJAR ANGULO PERIMETRAL AL MURO. 2 WALL ANGLE. ANGULO PERIMETRAL. 3 REMOVE CLIP FROM CROSS TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE SECUNDARIA AL ANGULO PERIMETRAL. 4 CROSS TEE. TEE SECUNDARIA. 5 CEILING PANEL. PANEL DE PLAFON. 6 STEEL HANGER ROD AND CHANNEL CLIP BY OTHERS. VARILLA DE SUSPENSION Y CLIP DE CANAL POR OTROS. 7 ATTACH GRID TO CARRYING CHANNEL WITH USG V-14 FURRING CLIP OR EQUAL. FIJAR SUSPENSION A CARNELTA DE CARGA CON USG V-14 CLIP O IGUAL. 8 FIELD-CUT CROSS TEE AT WALL ANGLE. CORTE DE TEE AL ANGULO PERIMETRAL. 9 FIELD-CUT EDGE TO MATCH PANEL PROFILE. AJUSTE DE PLAFON PARA ENCAJAR EN EL ANGULO. 10 SHADOW MOLDING. ANGULO PERIMETRAL. 11 REMOVE CLIP FROM MAIN TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE PRINCIPAL AL ANGULO PERIMETRAL. 12 MAIN TEE. TEE PRINCIPAL. 14 13 FIELD-CUT MAIN TEE AT WALL ANGLE. CORTE DE TEE PRINCIPAL AL ANGULO PERIMETRAL. 1 14 STEEL CARRYING CHANNEL BY OTHERS. CANAL DE CARGO POR OTROS. 15 SQUARE-CUT PANEL AT PERIMETER (OPTIONAL INSTALLATION). AJUSTE EN PLAFON PERIMETRAL (INSTALACION OPCIONAL). 14 3/8 in [10 mm] 3/8 in [10 mm] 4 4 8 3 1 1 2 5 2 DX/DXL CROSS TEE WITH SLB PANEL 1 5 12 5 DX/DXL GRID ATTACHED TO SUSPENDED STEEL FRAMING - CROSS TEE ELEVATION FULL CEILING PANEL WITH WALL ANGLE Scale: 6" = 1'-0" 2 PANEL AND GRID SECTION CUT THROUGH MAIN TEE DX/DXL CROSS TEE WITH SLB PANEL 3 Scale: 6" = 1'-0" 9 FIELD-CUT GRID AND PANEL AT WALL ANGLE Scale: 6" = 1'-0" 6 7 11 12 14 12 12 1 15 ADDITIONAL NOTES: 10 5 4 5 5 PREFERRED INSTALLATION: PROFILE EDGE OF PANEL TO BE SHOWN AT REVEAL MOLDING. FIELD-CUT AND ROUT EDGE TO MATCH IF NECESSARY. 4 DX/DXL MAIN TEE WITH SLB PANEL DX/DXL GRID ATTACHED TO SUSPENDED STEEL FRAMING - MAIN TEE ELEVATION DX/DXL MAIN TEE WITH SLB PANEL PANEL AND GRID SECTION CUT THROUGH CROSS TEE FIELD-CUT GRID WITH SQUARE-CUT PANEL USG Corporation 550 West Adams Street Chicago, IL 60661 USA WWW.USG.com T. 800-USG4YOU DISCLAIMER: THE USG PRODUCT DETAILS CONTAINED HEREIN ARE INTENDED FOR USE AS PRODUCT REFERENCE MATERIAL BY ARCHITECTS, ENGINEERS, OTHER DESIGN PROFESSIONALS, CONTRACTORS, BUILDING CODE OFFICIALS, OR OTHER COMPETENT CONSTRUCTION INDUSTRY TRADE PROFESSIONALS HAVING AN INTEREST IN THE SELECTION, SPECIFICATION AND USE OF PRODUCTS MANUFACTURED BY THE SUBSIDIARIES OF USG CORPORATION. THE DRAWINGS ARE INTENDED SOLELY AS TECHNICAL SUPPORT INCIDENT TO THE SALE AND USE OF USG PRODUCTS AND NOT INTENDED TO BE A SUBSTITUTE FOR THE DESIGN REVIEW AND APPROVAL OF THE LICENSED DESIGN PROFESSIONALS FOR THE PROJECT. THESE MATERIALS MAY BE PRINTED AND/OR TRANSFERRED ELECTRONICALLY SOLELY AS NEEDED BY THE USER. BECAUSE CAD ELECTRONIC FILES AND BIM (BUILDING INFORMATION MODELING ) FILES CAN BE MODIFIED BY OTHER PARTIES, WITHOUT NOTICE OR INDICATION OF SUCH MODIFICATIONS, MODIFICATION OF USG PRODUCT CAD DRAWINGS IS THE SOLE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. 1. MECHANICAL FASTENERS MAY BE REQUIRED. CHECK WITH LOCAL CODE FOR COMPLIANCE. OPTIONAL INSTALLATION: SQUARE-CUT AND ENCAPSULATE EDGE AT PERIMETER. FULL CEILING PANEL WITH SHADOWLINE ANGLE Scale: 6" = 1'-0" 10 5 Scale: 6" = 1'-0" 6 Scale: 6" = 1'-0" USG BASIC GRID DETAILS (NON SEISMIC) DETALLES BASICOS DEL SISTEMA DE SUSPENSION (SIN RESISTENCIA SISMICA) ISSUE RECORD: REV: DATE: 00 14/03/2017 SHEET INFORMATION: USG - BLACK IRON DETAILS DX / DXL GRID SC3199 KEYNOTES - BASIC CEILING DETAILS NOTAS - DETALLES BASICOS DE PLAFON 7 6 14 3/8 in [10 mm] 3/8 in [10 mm] 4 ATTACH WALL ANGLE AT CEILING PERIMETER. FIJAR ANGULO PERIMETRAL AL MURO. 2 WALL ANGLE. ANGULO PERIMETRAL. 3 REMOVE CLIP FROM CROSS TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE SECUNDARIA AL ANGULO PERIMETRAL. 4 CROSS TEE. TEE SECUNDARIA. 4 3 8 1 1 5 CEILING PANEL. PANEL DE PLAFON. 2 6 STEEL HANGER ROD AND CHANNEL CLIP BY OTHERS. VARILLA DE SUSPENSION Y CLIP DE CANAL POR OTROS. 7 ATTACH GRID TO CARRYING CHANNEL WITH USG V-14 FURRING CLIP OR EQUAL. FIJAR SUSPENSION A CARNELTA DE CARGA CON USG V-14 CLIP O IGUAL. 8 FIELD-CUT CROSS TEE AT WALL ANGLE. CORTE DE TEE AL ANGULO PERIMETRAL. 9 FIELD-CUT EDGE TO MATCH PANEL PROFILE. AJUSTE DE PLAFON PARA ENCAJAR EN EL ANGULO. 10 SHADOW MOLDING. ANGULO PERIMETRAL. 11 REMOVE CLIP FROM MAIN TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE PRINCIPAL AL ANGULO PERIMETRAL. 12 MAIN TEE. TEE PRINCIPAL. 13 FIELD-CUT MAIN TEE AT WALL ANGLE. CORTE DE TEE PRINCIPAL AL ANGULO PERIMETRAL. 14 STEEL CARRYING CHANNEL BY OTHERS. CANAL DE CARGO POR OTROS. 15 SQUARE-CUT PANEL AT PERIMETER (OPTIONAL INSTALLATION). AJUSTE EN PLAFON PERIMETRAL (INSTALACION OPCIONAL). 5 2 5 12 DXT/DXLT CROSS TEE WITH FLB PANEL 1 1 5 DXT/DXLT GRID ATTACHED TO SUSPENDED STEEL FRAMING - CROSS TEE ELEVATION FULL CEILING PANEL WITH WALL ANGLE Scale: 6" = 1'-0" 2 PANEL AND GRID SECTION CUT THROUGH MAIN TEE DXT/DXLT CROSS TEE WITH FLB PANEL 3 Scale: 6" = 1'-0" 9 FIELD-CUT GRID AND PANEL AT WALL ANGLE Scale: 6" = 1'-0" 6 7 11 12 14 12 12 1 13 1 15 ADDITIONAL NOTES: 10 5 4 5 5 PREFERRED INSTALLATION: PROFILE EDGE OF PANEL TO BE SHOWN AT REVEAL MOLDING. FIELD-CUT AND ROUT EDGE TO MATCH IF NECESSARY. 4 DXT/DXLT MAIN TEE WITH FLB PANEL DXT/DXLT GRID ATTACHED TO SUSPENDED STEEL FRAMING - MAIN TEE ELEVATION DXT/DXLT MAIN TEE WITH FLB PANEL PANEL AND GRID SECTION CUT THROUGH CROSS TEE FIELD-CUT GRID WITH SQUARE-CUT PANEL USG Corporation 550 West Adams Street Chicago, IL 60661 USA WWW.USG.com T. 800-USG4YOU DISCLAIMER: THE USG PRODUCT DETAILS CONTAINED HEREIN ARE INTENDED FOR USE AS PRODUCT REFERENCE MATERIAL BY ARCHITECTS, ENGINEERS, OTHER DESIGN PROFESSIONALS, CONTRACTORS, BUILDING CODE OFFICIALS, OR OTHER COMPETENT CONSTRUCTION INDUSTRY TRADE PROFESSIONALS HAVING AN INTEREST IN THE SELECTION, SPECIFICATION AND USE OF PRODUCTS MANUFACTURED BY THE SUBSIDIARIES OF USG CORPORATION. THE DRAWINGS ARE INTENDED SOLELY AS TECHNICAL SUPPORT INCIDENT TO THE SALE AND USE OF USG PRODUCTS AND NOT INTENDED TO BE A SUBSTITUTE FOR THE DESIGN REVIEW AND APPROVAL OF THE LICENSED DESIGN PROFESSIONALS FOR THE PROJECT. THESE MATERIALS MAY BE PRINTED AND/OR TRANSFERRED ELECTRONICALLY SOLELY AS NEEDED BY THE USER. BECAUSE CAD ELECTRONIC FILES AND BIM (BUILDING INFORMATION MODELING ) FILES CAN BE MODIFIED BY OTHER PARTIES, WITHOUT NOTICE OR INDICATION OF SUCH MODIFICATIONS, MODIFICATION OF USG PRODUCT CAD DRAWINGS IS THE SOLE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. 1. MECHANICAL FASTENERS MAY BE REQUIRED. CHECK WITH LOCAL CODE FOR COMPLIANCE. OPTIONAL INSTALLATION: SQUARE-CUT AND ENCAPSULATE EDGE AT PERIMETER. FULL CEILING PANEL WITH SHADOWLINE ANGLE Scale: 6" = 1'-0" 10 5 Scale: 6" = 1'-0" 6 Scale: 6" = 1'-0" USG BASIC GRID DETAILS (NON SEISMIC) DETALLES BASICOS DEL SISTEMA DE SUSPENSION (SIN RESISTENCIA SISMICA) ISSUE RECORD: REV: DATE: 00 14/03/2017 SHEET INFORMATION: USG - BLACK IRON DETAILS DXT / DXLT GRID SC3199 KEYNOTES - BASIC CEILING DETAILS NOTAS - DETALLES BASICOS DE PLAFON 6 7 1 ATTACH WALL ANGLE AT CEILING PERIMETER. FIJAR ANGULO PERIMETRAL AL MURO. 2 WALL ANGLE. ANGULO PERIMETRAL. 3 REMOVE CLIP FROM CROSS TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE SECUNDARIA AL ANGULO PERIMETRAL. 4 CROSS TEE. TEE SECUNDARIA. 5 CEILING PANEL. PANEL DE PLAFON. 6 STEEL HANGER ROD AND CHANNEL CLIP BY OTHERS. VARILLA DE SUSPENSION Y CLIP DE CANAL POR OTROS. 7 ATTACH GRID TO CARRYING CHANNEL WITH USG V-14 FURRING CLIP OR EQUAL. FIJAR SUSPENSION A CARNELTA DE CARGA CON USG V-14 CLIP O IGUAL. 8 FIELD-CUT CROSS TEE AT WALL ANGLE. CORTE DE TEE AL ANGULO PERIMETRAL. 9 SQUARE-CUT PANEL AT PERIMETER. AJUSTE EN PLAFON PERIMETRAL. 10 SHADOW MOLDING. ANGULO PERIMETRAL. 11 MAIN TEE. TEE PRINCIPAL. 12 REMOVE CLIP FROM MAIN TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE PRINCIPAL AL ANGULO PERIMETRAL. 13 13 FIELD-CUT MAIN TEE AT WALL ANGLE. CORTE DE TEE PRINCIPAL AL ANGULO PERIMETRAL. 1 14 STEEL CARRYING CHANNEL BY OTHERS. CANAL DE CARGO POR OTROS. 14 3/8 in [10 mm] 3/8 in [10 mm] 4 8 4 3 9 1 1 2 5 5 DXI CROSS TEE ELEVATION WITH FLB PANEL 1 FULL CEILING PANEL WITH WALL ANGLE Scale: 6" = 1'-0" 5 11 DXI GRID ATTACHED TO SUSPENDED STEEL FRAMING - CROSS TEE ELEVATION 2 PANEL AND GRID SECTION CUT THROUGH MAIN TEE DXI CROSS TEE ELEVATION WITH FLB PANEL 3 Scale: 6" = 1'-0" 2 FIELD-CUT GRID AND PANEL AT WALL ANGLE Scale: 6" = 1'-0" 6 7 12 14 11 11 11 1 9 ADDITIONAL NOTES: 1. MECHANICAL FASTENERS MAY BE REQUIRED. CHECK WITH LOCAL CODE FOR COMPLIANCE. 10 4 5 4 5 5 DXI MAIN TEE ELEVATION WITH FLB PANEL DXI GRID ATTACHED TO SUSPENDED STEEL FRAMING - MAIN TEE ELEVATION DXI MAIN TEE ELEVATION WITH FLB PANEL FULL CEILING PANEL WITH SHADOWLINE ANGLE PANEL AND GRID SECTION CUT THROUGH CROSS TEE FIELD-CUT GRID WITH SQUARE-CUT PANEL Scale: 6" = 1'-0" USG Corporation 550 West Adams Street Chicago, IL 60661 USA WWW.USG.com T. 800-USG4YOU DISCLAIMER: THE USG PRODUCT DETAILS CONTAINED HEREIN ARE INTENDED FOR USE AS PRODUCT REFERENCE MATERIAL BY ARCHITECTS, ENGINEERS, OTHER DESIGN PROFESSIONALS, CONTRACTORS, BUILDING CODE OFFICIALS, OR OTHER COMPETENT CONSTRUCTION INDUSTRY TRADE PROFESSIONALS HAVING AN INTEREST IN THE SELECTION, SPECIFICATION AND USE OF PRODUCTS MANUFACTURED BY THE SUBSIDIARIES OF USG CORPORATION. THE DRAWINGS ARE INTENDED SOLELY AS TECHNICAL SUPPORT INCIDENT TO THE SALE AND USE OF USG PRODUCTS AND NOT INTENDED TO BE A SUBSTITUTE FOR THE DESIGN REVIEW AND APPROVAL OF THE LICENSED DESIGN PROFESSIONALS FOR THE PROJECT. THESE MATERIALS MAY BE PRINTED AND/OR TRANSFERRED ELECTRONICALLY SOLELY AS NEEDED BY THE USER. BECAUSE CAD ELECTRONIC FILES AND BIM (BUILDING INFORMATION MODELING ) FILES CAN BE MODIFIED BY OTHER PARTIES, WITHOUT NOTICE OR INDICATION OF SUCH MODIFICATIONS, MODIFICATION OF USG PRODUCT CAD DRAWINGS IS THE SOLE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. 5 Scale: 6" = 1'-0" 6 10 Scale: 6" = 1'-0" USG BASIC GRID DETAILS (NON SEISMIC) DETALLES BASICOS DEL SISTEMA DE SUSPENSION (SIN RESISTENCIA SISMICA) ISSUE RECORD: REV: DATE: 00 14/03/2017 SHEET INFORMATION: USG - BLACK IRON DETAILS DXI GRID SC3199 KEYNOTES - BASIC CEILING DETAILS NOTAS - DETALLES BASICOS DE PLAFON 7 6 ATTACH WALL ANGLE AT CEILING PERIMETER. FIJAR ANGULO PERIMETRAL AL MURO. 2 WALL ANGLE. ANGULO PERIMETRAL. 3 REMOVE CLIP FROM CROSS TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE SECUNDARIA AL ANGULO PERIMETRAL. 4 CROSS TEE. TEE SECUNDARIA. 5 CEILING PANEL. PANEL DE PLAFON. 6 STEEL HANGER ROD AND CHANNEL CLIP BY OTHERS. VARILLA DE SUSPENSION Y CLIP DE CANAL POR OTROS. 7 ATTACH GRID TO CARRYING CHANNEL WITH USG V-14 FURRING CLIP OR EQUAL. FIJAR SUSPENSION A CARNELTA DE CARGA CON USG V-14 CLIP O IGUAL. 8 FIELD-CUT CROSS TEE AT WALL ANGLE. CORTE DE TEE AL ANGULO PERIMETRAL. 9 SQUARE-CUT PANEL AT PERIMETER. AJUSTE EN PLAFON PERIMETRAL. 10 SHADOW MOLDING. ANGULO PERIMETRAL. 11 MAIN TEE. TEE PRINCIPAL. 12 REMOVE CLIP FROM MAIN TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE PRINCIPAL AL ANGULO PERIMETRAL. 13 13 FIELD-CUT MAIN TEE AT WALL ANGLE. CORTE DE TEE PRINCIPAL AL ANGULO PERIMETRAL. 1 14 STEEL CARRYING CHANNEL BY OTHERS. CANAL DE CARGO POR OTROS. 14 3/8 in [10 mm] 3/8 in [10 mm] 4 8 4 3 9 1 1 2 5 5 DXI CROSS TEE ELEVATION WITH PANZ PANEL 1 1 FULL CEILING PANEL WITH WALL ANGLE Scale: 6" = 1'-0" 5 11 DXI GRID ATTACHED TO SUSPENDED STEEL FRAMING - CROSS TEE ELEVATION 2 PANEL AND GRID SECTION CUT THROUGH MAIN TEE DXI CROSS TEE ELEVATION WITH PANZ PANEL 3 Scale: 6" = 1'-0" 2 FIELD-CUT GRID AND PANEL AT WALL ANGLE Scale: 6" = 1'-0" 6 7 12 14 11 11 11 1 9 ADDITIONAL NOTES: 1. MECHANICAL FASTENERS MAY BE REQUIRED. CHECK WITH LOCAL CODE FOR COMPLIANCE. 10 4 5 4 5 5 DXI MAIN TEE ELEVATION WITH PANZ PANEL DXI GRID ATTACHED TO SUSPENDED STEEL FRAMING - MAIN TEE ELEVATION DXI MAIN TEE ELEVATION WITH PANZ PANEL FULL CEILING PANEL WITH SHADOWLINE ANGLE PANEL AND GRID SECTION CUT THROUGH CROSS TEE FIELD-CUT GRID WITH SQUARE-CUT PANEL Scale: 6" = 1'-0" USG Corporation 550 West Adams Street Chicago, IL 60661 USA WWW.USG.com T. 800-USG4YOU DISCLAIMER: THE USG PRODUCT DETAILS CONTAINED HEREIN ARE INTENDED FOR USE AS PRODUCT REFERENCE MATERIAL BY ARCHITECTS, ENGINEERS, OTHER DESIGN PROFESSIONALS, CONTRACTORS, BUILDING CODE OFFICIALS, OR OTHER COMPETENT CONSTRUCTION INDUSTRY TRADE PROFESSIONALS HAVING AN INTEREST IN THE SELECTION, SPECIFICATION AND USE OF PRODUCTS MANUFACTURED BY THE SUBSIDIARIES OF USG CORPORATION. THE DRAWINGS ARE INTENDED SOLELY AS TECHNICAL SUPPORT INCIDENT TO THE SALE AND USE OF USG PRODUCTS AND NOT INTENDED TO BE A SUBSTITUTE FOR THE DESIGN REVIEW AND APPROVAL OF THE LICENSED DESIGN PROFESSIONALS FOR THE PROJECT. THESE MATERIALS MAY BE PRINTED AND/OR TRANSFERRED ELECTRONICALLY SOLELY AS NEEDED BY THE USER. BECAUSE CAD ELECTRONIC FILES AND BIM (BUILDING INFORMATION MODELING ) FILES CAN BE MODIFIED BY OTHER PARTIES, WITHOUT NOTICE OR INDICATION OF SUCH MODIFICATIONS, MODIFICATION OF USG PRODUCT CAD DRAWINGS IS THE SOLE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. 5 Scale: 6" = 1'-0" 6 10 Scale: 6" = 1'-0" USG BASIC GRID DETAILS (NON SEISMIC) DETALLES BASICOS DEL SISTEMA DE SUSPENSION (SIN RESISTENCIA SISMICA) ISSUE RECORD: REV: DATE: 00 14/03/2017 SHEET INFORMATION: USG - BLACK IRON DETAILS DXI GRID, PANZ PANEL SC3199 KEYNOTES - BASIC CEILING DETAILS NOTAS - DETALLES BASICOS DE PLAFON 7 6 1 ATTACH WALL ANGLE AT CEILING PERIMETER. FIJAR ANGULO PERIMETRAL AL MURO. 2 WALL ANGLE. ANGULO PERIMETRAL. 3 REMOVE CLIP FROM CROSS TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE SECUNDARIA AL ANGULO PERIMETRAL. 4 CROSS TEE. TEE SECUNDARIA. 5 CEILING PANEL. PANEL DE PLAFON. 6 STEEL HANGER ROD AND CHANNEL CLIP BY OTHERS. VARILLA DE SUSPENSION Y CLIP DE CANAL POR OTROS. 7 ATTACH GRID TO CARRYING CHANNEL WITH USG V-14 FURRING CLIP OR EQUAL. FIJAR SUSPENSION A CARNELTA DE CARGA CON USG V-14 CLIP O IGUAL. 8 FIELD-CUT CROSS TEE AT WALL ANGLE. CORTE DE TEE AL ANGULO PERIMETRAL. 9 SQUARE-CUT PANEL AT PERIMETER. AJUSTE EN PLAFON PERIMETRAL. 10 SHADOW MOLDING. ANGULO PERIMETRAL. 11 MAIN TEE. TEE PRINCIPAL. 12 REMOVE CLIP FROM MAIN TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE PRINCIPAL AL ANGULO PERIMETRAL. 13 FIELD-CUT MAIN TEE AT WALL ANGLE. CORTE DE TEE PRINCIPAL AL ANGULO PERIMETRAL. 14 STEEL CARRYING CHANNEL BY OTHERS. CANAL DE CARGO POR OTROS. 14 3/8 in [10 mm] 3/8 in [10 mm] 4 4 3 8 1 1 9 2 5 5 DXF/DXLF CROSS TEE ELEVATION WITH FLB PANEL 1 FULL CEILING PANEL WITH WALL ANGLE Scale: 6" = 1'-0" 5 11 DXF/DXLF GRID ATTACHED TO SUSPENDED STEEL FRAMING - CROSS TEE ELEVATION 2 PANEL AND GRID SECTION CUT THROUGH MAIN TEE Scale: 6" = 1'-0" 2 DXF/DXLF CROSS TEE ELEVATION WITH FLB PANEL 3 FIELD-CUT GRID AND PANEL AT WALL ANGLE Scale: 6" = 1'-0" 6 7 11 12 11 14 11 1 13 1 9 ADDITIONAL NOTES: 10 5 5 4 5 1. MECHANICAL FASTENERS MAY BE REQUIRED. CHECK WITH LOCAL CODE FOR COMPLIANCE. 10 PREFERRED INSTALLATION: PROFILE EDGE OF PANEL TO BE SHOWN AT REVEAL MOLDING. FIELD-CUT AND ROUT EDGE TO MATCH IF NECESSARY. 4 DXF/DXLF MAIN TEE ELEVATION WITH FLB PANEL DXF/DXLF GRID ATTACHED TO SUSPENDED STEEL FRAMING - MAIN TEE ELEVATION DXF/DXLF MAIN TEE ELEVATION WITH FLB PANEL FULL CEILING PANEL WITH SHADOWLINE ANGLE PANEL AND GRID SECTION CUT THROUGH CROSS TEE FIELD-CUT GRID WITH SQUARE-CUT PANEL Scale: 6" = 1'-0" USG Corporation 550 West Adams Street Chicago, IL 60661 USA WWW.USG.com T. 800-USG4YOU DISCLAIMER: THE USG PRODUCT DETAILS CONTAINED HEREIN ARE INTENDED FOR USE AS PRODUCT REFERENCE MATERIAL BY ARCHITECTS, ENGINEERS, OTHER DESIGN PROFESSIONALS, CONTRACTORS, BUILDING CODE OFFICIALS, OR OTHER COMPETENT CONSTRUCTION INDUSTRY TRADE PROFESSIONALS HAVING AN INTEREST IN THE SELECTION, SPECIFICATION AND USE OF PRODUCTS MANUFACTURED BY THE SUBSIDIARIES OF USG CORPORATION. THE DRAWINGS ARE INTENDED SOLELY AS TECHNICAL SUPPORT INCIDENT TO THE SALE AND USE OF USG PRODUCTS AND NOT INTENDED TO BE A SUBSTITUTE FOR THE DESIGN REVIEW AND APPROVAL OF THE LICENSED DESIGN PROFESSIONALS FOR THE PROJECT. THESE MATERIALS MAY BE PRINTED AND/OR TRANSFERRED ELECTRONICALLY SOLELY AS NEEDED BY THE USER. BECAUSE CAD ELECTRONIC FILES AND BIM (BUILDING INFORMATION MODELING ) FILES CAN BE MODIFIED BY OTHER PARTIES, WITHOUT NOTICE OR INDICATION OF SUCH MODIFICATIONS, MODIFICATION OF USG PRODUCT CAD DRAWINGS IS THE SOLE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. 5 Scale: 6" = 1'-0" 6 Scale: 6" = 1'-0" USG BASIC GRID DETAILS (NON SEISMIC) DETALLES BASICOS DEL SISTEMA DE SUSPENSION (SIN RESISTENCIA SISMICA) ISSUE RECORD: REV: DATE: 00 14/03/2017 SHEET INFORMATION: USG - BLACK IRON DETAILS DXF / DXLF GRID SC3199 KEYNOTES - BASIC CEILING DETAILS NOTAS - DETALLES BASICOS DE PLAFON 7 6 1 ATTACH WALL ANGLE AT CEILING PERIMETER. FIJAR ANGULO PERIMETRAL AL MURO. 2 WALL ANGLE. ANGULO PERIMETRAL. 3 REMOVE CLIP FROM CROSS TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE SECUNDARIA AL ANGULO PERIMETRAL. 4 CROSS TEE. TEE SECUNDARIA. 5 CEILING PANEL. PANEL DE PLAFON. 6 STEEL HANGER ROD AND CHANNEL CLIP BY OTHERS. VARILLA DE SUSPENSION Y CLIP DE CANAL POR OTROS. 7 ATTACH GRID TO CARRYING CHANNEL WITH USG V-14 FURRING CLIP OR EQUAL. FIJAR SUSPENSION A CARNELTA DE CARGA CON USG V-14 CLIP O IGUAL. 8 FIELD-CUT CROSS TEE AT WALL ANGLE. CORTE DE TEE AL ANGULO PERIMETRAL. 9 SQUARE-CUT PANEL AT PERIMETER. AJUSTE EN PLAFON PERIMETRAL. 10 SHADOW MOLDING. ANGULO PERIMETRAL. 11 MAIN TEE. TEE PRINCIPAL. 12 REMOVE CLIP FROM MAIN TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE PRINCIPAL AL ANGULO PERIMETRAL. 13 FIELD-CUT MAIN TEE AT WALL ANGLE. CORTE DE TEE PRINCIPAL AL ANGULO PERIMETRAL. 14 STEEL CARRYING CHANNEL BY OTHERS. CANAL DE CARGO POR OTROS. 14 3/8 in [10 mm] 3/8 in [10 mm] 4 4 3 8 1 1 9 2 5 5 DXFF CROSS TEE ELEVATION WITH FLB PANEL 1 FULL CEILING PANEL WITH WALL ANGLE Scale: 6" = 1'-0" 5 11 DXFF GRID ATTACHED TO SUSPENDED STEEL FRAMING - CROSS TEE ELEVATION 2 PANEL AND GRID SECTION CUT THROUGH MAIN TEE Scale: 6" = 1'-0" 2 DXFF CROSS TEE ELEVATION WITH FLB PANEL 3 FIELD-CUT GRID AND PANEL AT WALL ANGLE Scale: 6" = 1'-0" 6 7 11 12 14 11 11 11 1 13 1 9 ADDITIONAL NOTES: 10 4 5 5 4 5 DXFF MAIN TEE ELEVATION WITH FLB PANEL DXFF GRID ATTACHED TO SUSPENDED STEEL FRAMING - MAIN TEE ELEVATION DXFF MAIN TEE ELEVATION WITH FLB PANEL FULL CEILING PANEL WITH SHADOWLINE ANGLE PANEL AND GRID SECTION CUT THROUGH CROSS TEE FIELD-CUT GRID WITH SQUARE-CUT PANEL Scale: 6" = 1'-0" USG Corporation 550 West Adams Street Chicago, IL 60661 USA WWW.USG.com T. 800-USG4YOU DISCLAIMER: THE USG PRODUCT DETAILS CONTAINED HEREIN ARE INTENDED FOR USE AS PRODUCT REFERENCE MATERIAL BY ARCHITECTS, ENGINEERS, OTHER DESIGN PROFESSIONALS, CONTRACTORS, BUILDING CODE OFFICIALS, OR OTHER COMPETENT CONSTRUCTION INDUSTRY TRADE PROFESSIONALS HAVING AN INTEREST IN THE SELECTION, SPECIFICATION AND USE OF PRODUCTS MANUFACTURED BY THE SUBSIDIARIES OF USG CORPORATION. THE DRAWINGS ARE INTENDED SOLELY AS TECHNICAL SUPPORT INCIDENT TO THE SALE AND USE OF USG PRODUCTS AND NOT INTENDED TO BE A SUBSTITUTE FOR THE DESIGN REVIEW AND APPROVAL OF THE LICENSED DESIGN PROFESSIONALS FOR THE PROJECT. THESE MATERIALS MAY BE PRINTED AND/OR TRANSFERRED ELECTRONICALLY SOLELY AS NEEDED BY THE USER. BECAUSE CAD ELECTRONIC FILES AND BIM (BUILDING INFORMATION MODELING ) FILES CAN BE MODIFIED BY OTHER PARTIES, WITHOUT NOTICE OR INDICATION OF SUCH MODIFICATIONS, MODIFICATION OF USG PRODUCT CAD DRAWINGS IS THE SOLE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. 5 Scale: 6" = 1'-0" 6 1. MECHANICAL FASTENERS MAY BE REQUIRED. CHECK WITH LOCAL CODE FOR COMPLIANCE. 10 Scale: 6" = 1'-0" USG BASIC GRID DETAILS (NON SEISMIC) DETALLES BASICOS DEL SISTEMA DE SUSPENSION (SIN RESISTENCIA SISMICA) ISSUE RECORD: REV: DATE: 00 14/03/2017 SHEET INFORMATION: USG - BLACK IRON DETAILS DXFF GRID SC3199 KEYNOTES - BASIC CEILING DETAILS NOTAS - DETALLES BASICOS DE PLAFON 7 6 2 WALL ANGLE. ANGULO PERIMETRAL. 3 REMOVE CLIP FROM CROSS TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE SECUNDARIA AL ANGULO PERIMETRAL. 4 CROSS TEE. TEE SECUNDARIA. 5 CEILING PANEL. PANEL DE PLAFON. 6 STEEL HANGER ROD AND CHANNEL CLIP BY OTHERS. VARILLA DE SUSPENSION Y CLIP DE CANAL POR OTROS. 7 ATTACH GRID TO CARRYING CHANNEL WITH USG V-14 FURRING CLIP OR EQUAL. FIJAR SUSPENSION A CARNELTA DE CARGA CON USG V-14 CLIP O IGUAL. 8 FIELD-CUT CROSS TEE AT WALL ANGLE. CORTE DE TEE AL ANGULO PERIMETRAL. 9 SQUARE-CUT PANEL AT PERIMETER. AJUSTE EN PLAFON PERIMETRAL. 10 SHADOW MOLDING. ANGULO PERIMETRAL. 11 MAIN TEE. TEE PRINCIPAL. 12 REMOVE CLIP FROM MAIN TEE AT WALL ANGLE. ELIMINAR EL CLIP DE LA TEE PRINCIPAL AL ANGULO PERIMETRAL. 13 FIELD-CUT MAIN TEE AT WALL ANGLE. CORTE DE TEE PRINCIPAL AL ANGULO PERIMETRAL. 14 STEEL CARRYING CHANNEL BY OTHERS. CANAL DE CARGO POR OTROS. 3/8 in [10 mm] 4 4 8 3 9 1 1 5 5 DXFF CROSS TEE ELEVATION WITH PANZ PANEL 1 ATTACH WALL ANGLE AT CEILING PERIMETER. FIJAR ANGULO PERIMETRAL AL MURO. 14 3/8 in [10 mm] 2 1 FULL CEILING PANEL WITH WALL ANGLE Scale: 6" = 1'-0" 5 11 DXFF GRID ATTACHED TO SUSPENDED STEEL FRAMING - CROSS TEE ELEVATION 2 PANEL AND GRID SECTION CUT THROUGH MAIN TEE Scale: 6" = 1'-0" 2 DXFF CROSS TEE ELEVATION WITH PANZ PANEL 3 FIELD-CUT GRID AND PANEL AT WALL ANGLE Scale: 6" = 1'-0" 6 7 11 12 14 11 11 11 1 13 1 9 ADDITIONAL NOTES: 10 4 5 5 4 5 DXFF MAIN TEE ELEVATION WITH PANZ PANEL DXFF GRID ATTACHED TO SUSPENDED STEEL FRAMING - MAIN TEE ELEVATION DXFF MAIN TEE ELEVATION WITH PANZ PANEL FULL CEILING PANEL WITH SHADOWLINE ANGLE PANEL AND GRID SECTION CUT THROUGH CROSS TEE FIELD-CUT GRID WITH SQUARE-CUT PANEL Scale: 6" = 1'-0" USG Corporation 550 West Adams Street Chicago, IL 60661 USA WWW.USG.com T. 800-USG4YOU DISCLAIMER: THE USG PRODUCT DETAILS CONTAINED HEREIN ARE INTENDED FOR USE AS PRODUCT REFERENCE MATERIAL BY ARCHITECTS, ENGINEERS, OTHER DESIGN PROFESSIONALS, CONTRACTORS, BUILDING CODE OFFICIALS, OR OTHER COMPETENT CONSTRUCTION INDUSTRY TRADE PROFESSIONALS HAVING AN INTEREST IN THE SELECTION, SPECIFICATION AND USE OF PRODUCTS MANUFACTURED BY THE SUBSIDIARIES OF USG CORPORATION. THE DRAWINGS ARE INTENDED SOLELY AS TECHNICAL SUPPORT INCIDENT TO THE SALE AND USE OF USG PRODUCTS AND NOT INTENDED TO BE A SUBSTITUTE FOR THE DESIGN REVIEW AND APPROVAL OF THE LICENSED DESIGN PROFESSIONALS FOR THE PROJECT. THESE MATERIALS MAY BE PRINTED AND/OR TRANSFERRED ELECTRONICALLY SOLELY AS NEEDED BY THE USER. BECAUSE CAD ELECTRONIC FILES AND BIM (BUILDING INFORMATION MODELING ) FILES CAN BE MODIFIED BY OTHER PARTIES, WITHOUT NOTICE OR INDICATION OF SUCH MODIFICATIONS, MODIFICATION OF USG PRODUCT CAD DRAWINGS IS THE SOLE RESPONSIBILITY OF THE DESIGN PROFESSIONAL. 5 Scale: 6" = 1'-0" 6 1. MECHANICAL FASTENERS MAY BE REQUIRED. CHECK WITH LOCAL CODE FOR COMPLIANCE. 10 Scale: 6" = 1'-0" USG BASIC GRID DETAILS (NON SEISMIC) DETALLES BASICOS DEL SISTEMA DE SUSPENSION (SIN RESISTENCIA SISMICA) ISSUE RECORD: REV: DATE: 00 14/03/2017 SHEET INFORMATION: USG - BLACK IRON DETAILS DXFF GRID, PANZ PANEL SC3199