CODE OF 1 P RACTICE Repair And Overhaul Ex Electrical Apparatus Publication No: 300 Revi sion 1 December 1991 BEAMNAEMT CODE OF PRACflCE FOR THE REPAIR AND OVERHAUL OF ELECTRICAL APPARATUS FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES (other than Mining Applications or Explosive Processing and Manufacture) T hi s Code has been prepared by the BEAMA Committee for Electrical Equipment in Flammable Atmospheres (CEEFA) a nd the Association of Electrical and Mechanical Trades (AEMT) with the participation of User Organisations. The HSE have also been consulted and participated in the preparation of this Code. The Department of Energy considers repairs or overhauls which meet the provisions of this Code will be appropriate for offshore installations on the United IGngdom Continental Shelf. This code of practice takes the form of recommendations. Whilst it is intended to cover the majority of situations which will be met in practice it is not possible for the code to cover every contingency. The reader should therefore bear in mind that specific situations may call for add itional precautions which are not specified in thjs code. In particular, compliance with the code does not necessarily confer immunity from any statutory or legal requirement. In case of doubt about any particular apparatus or procedure the reader should refer to the original manufacturer, user or certifying authority in order to satisfy himself as to the steps which need to be taken to deal with the particular circumstances facing him. This publkation shall not be reproduced or repeated, in whole or in part, nor stored in any informat ion storage or retrieval system without the previous written consent of both BEAMA Limited and AEMT Limited. Published jointly by BEAMA Limited and AEMT Limited © 1984 BEAMA/AEMT Reprinted January 1994 (editorial revision). Reprinted August 1998 Price: £35 (Overseas £40) Printed in England: ISBN 0 9509409 1 7 (AEMT) ISBN 0 90 1639 12 5 (BEAMA) The main parts of the code of practice are:- PART ONE PARTTWO PART THREEPART FOUR PARTFIVE PART SIX PARTSEVENPARTElGHT- GENERAL REQUIREMENTS TYPE OF PROTECTION 'd' (FLAMEPROOF) TYPE OF PROTECfiON 'i' (INTRINSIC SAFETY) TYPE OF PROTECTION 'p' (PRESSURIZED) TYPE OF PROTECTION 'e' (INCREASED SAFETY) TYPE OF PROTECTION 'N' or 'n' (NON-SPARKING) TYPE OF PROTECTION's' (SPEClAL PROTECTION) PR0TECJ10N BY ENCLOSURE FOR USE IN THE PRESENCE OF COMBUSTIBLE DUSTS CONTENTS: Page Foreword IV PART ONE -GENERAL REQUIREMENTS Introduction Section One - General Section Two - Guidance for the Manufacturer Section Three - Guidance for the User Section Four- Guidance for the Repairer 1-1 1-2 1-7 1-7 1-8 Appendix 1 -Identification of Repaired Apparatus PART TWO- TYPE OF PROTECTION 'd' (FLAMEPROOF) 2-1 2-1 2-1 Introduction Section One -General Section Two - Repair and Overhaul Section Three - Reclamation Section Four- Modifications 2-6 2-7 PART THREE- TYPE OF PROTECTION 'i' (INTRINSIC SAFETY) 3-1 3-1 3-1 Introduction Section One -General Section Two -Repair and Overhaul Section Three -Reclamation Section Four- Modifications 3-4 3-4 11 PART FOUR -TYPE OF PROTECTION 'p' (PRESSURIZED) Introduction Section One - General Section Two -Repair and Overhaul Section Three -Reclamation Section Four -Modifications Page 4-1 4-1 4-1 4-5 4-6 PART FIVE- TYPE OF PROTECfiON 'e' (INCREASED SAFETY) 5-1 5-1 5-1 5-6 5-7 Introduction Section One - General Section Two -Repair and Overhaul Section Three- Reclamation Section Four - Modifications PART SIX- TYPE OF PROTECTION 'N' or 'n' (NON-SPARKING) 6-1 Introduction Section One - General Section Two - Repair and Overhaul Section Three -Reclamation Section Four- Modifications 6-1 6-1 6-5 6-7 PART SEVEN -TYPE OF PROTECfiON 's' (SPECIAL PROTECTION) 7-1 Introduction Section One - General Section Two -Repair and Overhaul Section Three - Reclamation Section Four -Modifications 7-1 7-1 1-3 7-4 PART EIGHT- PROTECTION BY ENCLOSURE FOR USE IN THE PRESENCE OF COMBUSTIBLE DUSTS Introduction Section One - General Section Two -Repair and Overhaul Section Three- Reclamation Section Four -Modifications 8-1 8-1 8-1 8-5 8-6 w FOREWORD Since 1970 there have been sweeping changes in the field of electrical equipment for potentially explosive atmospheres with the introduction, internationally, of developments in explosion protection concepts, construction and test specifications, codes of practice and safety legislation. Over the same period there have been corresponding increases in the production and use of potentially explosive substances in manufacturing and finishing processes which have widened the application of explosion protected apparatus far beyond the traditional sector represented by the oil refining and distribution industry. Many more manufacturers, users, installers and repairers are now involvedt some for the first time, in this specialized technical field which is more constrained by detailed Standards, codes of practice, application and legislation than other sections ofthe electrical industry. The construction and test Standards are framed to facilitate apparatus having acceptable levels and margins of safety. Overall level of safety depends also upon the strict observance of codes of practice. This code recommends procedures and practices to be followed in connection with repairs and overhauls. lV PART ONE- GENERAL REQUIREMENTS 0. INTRODUCTION This code is divided into separate parts, each concerned with an individual type of protection. In those cases where an apparatus incorporates more than one type of protection, reference should be made to the parts involved. The reader should, however, note that this code excludes types of protection 'o' - oil filling, 'q' - sand filling or quartz filling etc. and also type 'm' which is generally considered to be irreparable. The objective of this code, as well as giving guidance on the practical means of maintaining the electrical safety and performance requirements of repaired apparatus, also recommends procedure:s for maintaining after repair compliance of the apparatus with the provisions of the Certificate of Assurance or Conformity or with the provisions of the appropriate explosion protected Standard where a certificate is not available.* The nature of the explosion protection offered by each type of protection varies according to its unique features:. For example, the nature of explosion protection afforded by Type of Protection 'd' is essentially mechanical, whereas that afforded by Type of Protection 'i' is essentially electrical. Reference should! be made to the appropdate Standard(s) for details. · Users are recommended to utilise the most appropriate repair facilities for any particular item of equipment, whether they be the facilities of the manufacturer or a suitably competent and equipped repairer.** The code recognises the necessity of a required level of competence for the repair of apparatus. Some manufacturers may recommend that the apparatus be repaired only by them. In the case of the repair or overhaul of apparatu1s which has been the subject of third party certification, such as by BASEEFA, it may be necessary to clarify the position of the continued conformity of the apparatus with the certificate. * NOTE: While most apparatus of this kind is certified by a recognised third party test house, such as BASEEFA, some apparatus may be self-certified by manufacturers or other bodies and may not attract a Certificate of Assurance or Conformity. ** NOTE: Whilst some manufacturers recommend that certain equipment be returned to them for repair and some nominate repairers, there are also competent independent repair organisations who have the facilities to carry out this class of work. 1-1 Assuming that repairs and overhauls are carried out using good engineering practices then:1. If manufacturers' specified parts or parts as specified in the certification documentation are used in a repair or overhaul then the a pparatus should remain in conformity with the certificate. 2. If repairs or modifications are carried out on apparatus specifically as detailed in the certification documents then the apparatus should still conform with the certificate. 3. If repair or overhaul is carried out on apparatus in accordance with this code of ·practice and the re levant Standard(s), although not in compliance with 1 & 2 above, then it is unlikely that the apparatus wi11 be unsafe although it may not conform fully with the certificate. 4. If other repair or modification techniques are used then it wiLl be necessary to ascertain, from the manufacturers, and/or the certification authority, the suitability of the apparatus for continued use in a potentiaJly explosive atmosphere. SECTION ONE- GENERAL 1. Scope This code of practice (i) gives guidance, principally of a technical nature, on the repair and overhaul of certified apparatus designed for use in potentially explosive atmospheres (other than mining applications or explosive processing and manufacture). (ii) does not cover maintenance, other than when repair and overhaul cannot be disassociated from maintenance, neither does it give advice on cable entry systems which may require renewa1 when the apparatus is re-installed. Recommendations regarding routine maintenance, and the selection and installation of electrical apparatus for use in potentially explosive atmospheres may be found in BS 5345 and BS 6467 Pt 2. (iii) practices are adopted throughout. assumes that good engineering This Part of the code of practice (i) covers those aspects of repair and overhaul which are common to all explosion protected apparatus and subsequent sections provide guidance relevant to specific types of protection. (ii) also identifies certain specific responsibilities under the Health and Safety at Work etc. Act 1974 as applicable to those who are likely to be concerned with the repair of certified apparatus. 1-2 NOTE Much of the content of this code is concerned with the re pair and overhaul of electrical rotating machines. This is not because they are the most important items of expJosion protected equipment; rather because they are often major items of repairable capital equipment in which, whatever type of protection is involved, sufficient commonality of construction exists as to make possible more detailed guidelines for their repair and overhauL 2. References Standards and other publications relevant to thjs code are listed in AnnexA. 3. D efinition and Explanation of Terms 3.1 Serviceable Condition A condition which permits a replacement or reclaimed component part to be used without prejudice to the performance or explosion protection aspects of the apparatus, with due regard to the certification requirements as applicable, in which such a component part is used. 3.2 Repair* An action to restore a faulty apparatus to its fully serviceable condition and in compliance with the relevant Standard. 3.3 Overhaul* An action to restore to fully serviceable condition an apparatus which bas been in use or in storage for a period of time but which is not .Q.ecessarily faulty. 3.4 Maintenance Routine actions taken in accordance with the recommendations of Section Four of BS 5345 Part 1, to preserve the fully serviceable condition of the installed apparatus. 3.5 Component Part An indivisible item from an assembly of such parts which form an apparatus. * NOTE: The term "repair" a nd/or "overhaul" employed in this code are/is equated with the term "refurbishing.. used in Guidance Notes GS8, relating to the H ealth and Safety at Work etc. Act 1974. 1-3 3.6 Reclamation A means of repair involving, for example, the removal or addition of material to reclaim component parts which have sustained damage., in order to restore such parts to a fully serviceable condition in accordance with the relevant Standard. 3.7 Modification A change, to the design of the apparatus which may affect fit, form or function. 3.8 material~ Manufacturer The maker of the apparatus (who may also be the supplier, the importer or the agent) in whose name usually the certification (where appropriate) of the apparatus was originally registered. 3.9 User The user of the apparatus. 3.10 Repairer The repairer of the apparatus - who may be the manufacturer, the user or a third party (repair agency). 3.11 Certification In the context of this Code, certification, leading to the issue of a Cer.tificate of Assurance or a Certificate of Conformity, refers primarily to assessments of apparatus carried out by any one of the test houses** notified to the European Communities Commission under ArticJe 14 of the Framework EEC Directive 76/117/EEC, as publis'hed in the Official Journal of the European Communities No. L 24/25. This Code may a_lso apply to apparatus certified by other recognised certification authorities, or to apparatus which has been self-certified by manufacturers or users as complying with recognised Standards. **NOTE: BASEEFA (British Approvals Service for Electrical Equipment in Flammable Atmospheres) and SIRA Test and Certification Ltd are now the British National Testing and Certification Authorities recognised as the test houses nominated to the European Commission under the European Directives concerned with apparatus for use in potentially explosive atmospheres in surface industries. 1-4 3.12 Certificate References A certificate reference number may refer to a single design or a range of apparatus of similar design. The suffix ''B" or "X" to the reference number indicates special conditions of use and the certification documents need to be studied before such apparatus is installed, repaired or overhauled. An 'S' suffix indicates that the apparatus is intended for use rn a safe area only, but it may form part of a certified system. The 'S' suffix has been superseded by [EExia] for new equipment. 3.13 Marking Explanatory information on the marking of apparatus can be found in BASEEFAEx-Memo No.1. It may be necessary to remove or supplement the label in certain circumstances as follows - 3.14 i) if after repair or overhaul an apparatus is changed such that it no longer conforms with either the Stand~d or certificate, the certification label should be removed but the rating and other details should be preserved. ii) if the ·apparatus is changed during repair or overhaul so that it still complies with the Standard but does not necessarily comply with the certificate, the certification label should be supplemented by the addition of marking referred lo in Part 1 Section 4 Clause 5 (p 1-9). Copy Winding Copy Winding is defined as that process by which a winding is totally or partially replaced by another, the characteristics and properties of which are comparable with the original. • 4. Statutory Requirements The folJowing references on certain specific requirements of the Health and ·Safety at Work etc. Act 1974 are for guidance only and the reader's attention is drawn to the complete requirements of the Act and relevant regulations made from time to time under the Act. 4.1 Manufacturer The manufacturer's responsibj}jties under the Health and Safety at Work etc. Act 1974 are stated in Section 6 of the Act, in particular: 1-5 "Clause 6 (1) (c) to take such steps as are necessary to secure that there will be available in connection with the use of the article at work adequate information* about the use for which it is designed and has been tested, and about any conditions necessary to ensur~~ that, when put to that use, it will be safe and without risks to health." For further clarification reference should be made to the Guidance Notes on the Health & Sa£ety at Work etc. Act 1974, GS8. *NOTE: Adequate Information It is not reasonably practical to assume that adequate information is or can be so widely d 1rculated that it is always available where and when it is needed. Sources of adequate information are users, manufacturers or certifying authorities. 4.2 User Apart from the need to comply with Section 2 of the HeaJth and Safety at Work etc. Act 1974 (regarding safe installation and maintenance duties of the employer), the user is also required to pay due regard to Section 6 of the Act should he wish to undertake the repair or overhaul of the equipment himself. However, the user should also be aware of the following Guidance Note GS8 issued by the Health and Safety Executive. "61. When an article is sent for refurbishing and the ownership passes 1to the refurbisher, then so do the duties under Section 6." The user should also have regard to the following: The Electricity at Work Regulations 1989 and HSE Memorandum of Guidance on tbeEWR. 4.3 Repairer The repairer's responsibility is covered by the following extract from the Guidance Note GS8 issued by the Health and Safety Executive. "61. .... If, however, it is sent for repair or modification and the ownership does not pass to the repairer or modifier, then it would appear that neither do the duties under Section 6. But where the repairer or modifier is involved in the erection or installation of such an article on any premises when it iis to be used by persons at work, then he may have duties lander subsection 6(3). However, in the event of an accident occurring, e.g. as the result of the negligence of the 1repairer or modifier, be may be held liable under Section 36 of the Act." 1-6 SECTION TWO - GUIDANCE FOR THE MANUFACTURER 1. Documents In addition to the certificate, other documents, e.g. the appropriate drawings, specifications, etc., suitable for the repair and/or overhaul, should be available. 1.1 Repair and Overhaul Data The data available for the repair and/or overhaul should generally include, but need not be limited to, details of: - technical specification performance and conditions of use dismantUng and assembly instructions certification limitations, where specified marking (including certification marking) recommended methods of repair/overhaul for the apparatus The information may be subject to manufacturers' amendments including those relative to certification. 1.2 Spare Parts A list of spare parts should be included with the repair and/or overhaul data which should identify those parts that particularly affect the means by which the apparatus complies with the appropriate Standard or certificate. SECTION THREE- GUIDANCE FOR THE USER 1. Certificates and Documents The certificate and other related documents should be obtained as part of the original purchase contract. 2. Records and Work Instructions It will be in the interest of the user that the repairer is notified, wherever possible, of the fault and/or nature of the work to be done. Records of any previous repairs, overhauls or modifications should be kept by the user and made available to the repairer. The user should inform the repairer, for safety and health reason s, as to the nature. of any harmful contaminating dust to which the apparatus sent for repair has been exposed so that appropriate precautions may be taken before work commences. Special requirements stipulated in users' specifications, and which are supplementary to the various Standards, should be brought to the attention of the repairer. 3. Re-instailation of Repaired Apparatus Before repaired apparatus is re-commissioned, cable entry systems should be checked to ensure they are undamaged and are appropriate to the apparatus type of protection. Recommendations may be found in BS 5345. 1-7 SECTION FOUR- GUIDANCE FOR THE REPAIRER 1. Certification and Standards The repairer's attention is directed to the need to be informed of, and to comply with the rel~vant explosion protected Standards and certification requirements applicable to the apparatus to be repaired or overhauled. Ll Tiaining The repairer of the apparatus should ensure that those concerned with the repair and/or overhaul of the certified apparatus are trained and supervised on this type of work. Such training should cover: i) General principles of types of protection and marking ii) Those aspects of equipment design which affect the protection concept iii) Certification and Standards iv) The identification of replacement parts or components authorized by the manufacturer v) The particular techniques to be employed in repairs referred to in other parts of this code. Appropriate refresher training should be given from time to time. 2. Testing Should it prove impracticable to carry out certain tests, e.g. a component of a complete apparatus taken off site for repair, such as a rotor of a rotating machine, it would be necessatry before putting the repaired equipment back into service to ascertain from the user or manufacturer the consequences of omitting such tests. Attention is drawn to Section 40 of the Health amd Safety at Work etc. Act 1974 which states:- 1-8 "In any proceedings for an offence under any of the rel~ant statutory provisions consisting of a failure to cqmply with a duty or requirement to do something so far as is practicable or so far as is reasonably practicable, or to use the best practicable means to do something, it shall be for the accused to prove (as the case may be) that it was not practicable or not reasonably practicable to clio more than was in fact done to satisfy the duty or requiirement, or that there was no better practicable means than was in fact used to satisfy the duty or requirement." 3. Documentation The repairer should seek to obtain all necessary information/d~ta from the manufacturer or user for the repair and/or overhaul of the apparatus. This may include information relating to previous repairs, overhauls or modifications. He should also have availaQ.le, and refer to, the relevant explosion protected Standard. The repairer should ensure that the user receives copies of records of all work carried out on the apparatus. 4. Spare Parts It is preferable to obtain new parts from the manufacturer, and the repairer should ensure that only appropriate spare parts are used :in the repair or overhaul of certified apparatus. Depending on the nature of the apparatus, those spare parts may be identified by the manufacturer, the apparatus Standard or the relevant certification documentation. 4.1 Sealed Parts Parts which are required by the apparatus. specification and certificate documents to be sealed may be replaced only by the particular spare part(s) detailed in the parts list. Note: 5 Devices incorporated in an apparatus to indicate interference by third parties (e.g. security seals) as distinct from those required in the certification documents, are not intended to fa] I within the scope of this sub-clause. Sparking Any evidence of unusual sparking identified by t:he repairer should be referred to the manufacturer. To avoid the incidence of incendive sparking, the only precautions wbieh can be taken at present relate to bonding. Any bonding arrangements should be replaced andl positioned to at least the provisiqns of the original specifi~tion. 1-9 On dismantling rotating machines, if inspection of the rotor indicates signs of sparking, this should be referred to the manufacturer for advice. At present, it is not possible to deal with corona discharges should they occur. 6. Identification of Repaired Apparatus Apparatus should be marked to identify tbe repair or overhaul and the repairer's identity. The preferred marking for repaired apparatus is given in Appendix I (Page,l-14). Records should also be maintained giving full details of the repair work carried out. 7. Quality Assurance Adequate quality control and quaJity assurance procedures should be followed. NOTE: In this context, 'adequate' denotes that the procedures should be documented and supervised by staff who have been trained in such QA and QC procedures. Guidance may be obtained from BS 5750. 8. Reclamations 8.1 Exceptions This clause is only concerned with reclamations which affect explosion protection. Where explosion protection is not affected, reclamation should be affected by good engineering practice. 8.2 Exclusions Some component parts are considered not to be reclaimable and are therefore excluded from the scope of this document: e.g. i) Component parts made from the following materials glass, plastics, or any material that is not dimensionally stable ii) Fasteners iii) Component parts, e.g. some encapsulated assemblies, which have been stated by the manufacturer not to be subjected to .rep~ir. 1-10 8.3 Requirements Any reclamation should be carried out by trained personnel~ skilled in the process to be employed1 using good engineering practices. If any proprietary process is used, the instructions of the originator of such a process should be followed. All reclamations should be properly documented and records retained. Such records should include - i) Identification of the component part ii) Method of reclamation iii) Detrul of any dimensions which diffe r from those in relevant certification documents or the original dimensions of the component part. iv) Date v) Name of the orgi'misation carrying out the reclamation If the reclamation is carried out other than by the user, the user should be provided with a copy of the record. A reclamation procedure which would result in dimensions affecting explosion protection integrity being different from those given in relevant certification documents may be permissible if such changed dimensions still meet the stipulations of the relevant explosion protection Standard. 1n the event of any uncertainty regarding the permissibility, from an explosion protection safety point of view, of an intended reclamation procedure, the advice of the manufacturer or certifying authority should be sought. It may also be necessary to carry out tests to verify that the reclamation procedure is acceptable. 8.4 RecJamation Procedures The following outlines some of the reclamation procedures which MAY be applicable to explosion protected apparatus. IT SHOULD BE RECOGNISED THAT NOT ALL PROCEDURES ARE APPLICABlE TO AlL MEIHODS OF PROTECITON. DETAILED ADVICE IS GIVEN IN TilE APPROPRIATE PARTS OF THIS CODE. It wiJJ be the responsibility of the repairer to satisfy himself, on the completion of reclamation, that the apparatus is in a fully serviceable condition and complies with the Standard(s) for the relevant explosion protection concept. 1-11 8.4.1 Metal Spraying This method should be used only when the extent of the wear or damage, plus the machining necessary to prepare the component part for reclamation, does not weaken tbe part beyond safe limits. A sprayed metal inlay, whilst adding some stiffness, should not be taken into account when strength is considered. Indeed, the machining process prior to the application of metal spray may introduce stress raisers which may further weaken the component. Detailed procedures are_given in BS 4761. Metal spraying is not recommended for some high speed, large diameter applications and is only acceptable where the materials are metallurgically compahble and the parent base metal is free from defects. See also BS 4495 and BS 4950 for other spraying processes. 8.4.2 Electro-plating Electro-plating is an acceptable procedure provided the part is not weakened beyond safe limits. Detailed procedures for Chromium and Nickel plating are given in BS 4641 and 4758 respectively. 8.4.3 Sleeving This method should be used only when the extent of the wear or damage, plus the machining necessary to prepare the part for reclamation, does not weaken the part beyond safe limits. A sleeve, whilst adding some stiffness, should not be taken into account when strength is considered. 8.4.4 Brazing or welding Reclamation by brazing or welding may be considered so long as the technique employed ensures the correct penetration and fusion of braze or weld with parent metal, resulting in adequate reinforcement, the prevention of distortion, the relief of stresses and the absence of It should be recognised that welding raises the blow-holes. temperature of the component to a high level and may cause fatigue cracks to propagate. 8.4.5 Metal Stitching The cold reclamation of a fractured casting by tbe technique of closing the fracture with nickel aHoy stitches and sealing the crack by nickel aiJoy chain studding may be admissible subject to a suitable thickness of casting. 8.4.6 Machining of Stator and Rotor Cores (Rotating Machines) Damaged stator or rotor cores should not be machined (skimmed) without reference to the manufacturer to ascertain the maximum permissible air gap, which should not be exceeded. 1-12 This restriction could affect the viability of fitting a new shaft into an existing core if the core then requires trueing up tq restore concentricity. 8.4.7 Threaded Holes for Fasteners Threads which have been damaged to beyond an acceptable extent, may be reclaimed, depending upon the type of explosion protection, by the following means - i) ii) iii) iv) v) Oversize drilling and re-tapping Oversize drilling, re-tapping and the fitting of a proprietary thread insert Oversize drilling, plugging, re-drilling and re-tapping Plugging, re-drilling and tapping elsewhere Plug-welding, re-drilling and tapping 8.4.8 Re-Machining Re-machining worn or damaged surfaces may be considered providing the component part is not weakened beyond safe limits, provided that the integrity of the encl0sure is maintained and the required surface finish is achieved. 9. Modifications No modification should be made to certified apparatus unless that modification is permitted in the certificate or is approved in writing by the manufacturer. Subsequent parts of this code of practice give detailed guidance regarding modifications in the context of different types of protection. Particular attention is drawn to the need for care when adding an inverter to an Ex rotating machine in ensuring that this is done only when the intended combination of inverter and rotating machine is specified in the certificate or in the rotating machine manufacturer's documentation. Third Party repairers should use special care to establish that any inverter on which they are asked to work is so specified. Where a modification is proposed which would result in the apparatus not conforming with either the certification documents or the relevant explosion protected Standard, the user should be informed in writing and his written instructions obtained. If the proposal is carried out the certification label would be removed (see Section 1 Clause 3.13 page 1-5). 10. Temporary Repairs A temporary repair intended to achieve continued short term operation of apparatus should only be carried out if retention of explosion Certain temporary repair procedures protection aspects is ensured. may thereby be debarred. Any temporary repair should be brought up to full repair standard as soon as possible. 1-13 11. Removal of damaged Windings The procedure of softening the impregnating varnish of windings with solvents before stripping is acceptable. The alternative procedure, of the application of heat to facilitate the removal of windings, is acceptable provided that the operation is carried out with caution so as not to affect significantly the insulation between the laminations of magnetic parts. Particular caution is necessary and, if in doubt, the advice of the manufacturer sought regarding the construction of the core and the inter-laminar insulation material in respect of apparatus with type of protectjon 'e' and apparatus with any other type of protection having temperature class T6, T5 or T 4. The need for particular caution in those circumstances arises from the fact that an increase in core loss, which could result from degradation of inter-laminar insulation, could significantly affect type 'e' parameters (tE time etc.) or result in the temperature classification being exceedea. It is the repairer's responsibility to satisfy himself, as in all reclamation procedures, that on completion of the reclamation the apparatus is in a fully serviceable condition and complies with the Standard(s) for the releva nt explosion concept (see page 1-11, Clause 7.4 Reclamation Procedures). 1-14 Appendix 1 Identification of repaired apparatus by marking Marking Information Repairs not affecting the int~ ofthe explosion features need not be marked. All other repaired and overhauled apparatus should be marked on the main part in a visible place. 'This marking should be legible and durable taking into account possible chemical corrosion. The marking should include; (i) the relevant symbol (see below); (li) the standard number "IEC 79-19, or national equivalent; (Iii) the name of the repairer or his registered trade mark; (iv) the repairer's reference number relating to the rt1pair;, ( v) the date of the overhaul/ repair. The marking may be on a plate permanently attached to the repaired apparatus. In the event of subsequent repairs, the earlier plate may be removed, a record being made of all the markings on it. Symbols 1. This mark shall be used when the original certificate is available, and the apparatus is repaired in full compliance with the certificate and standard. 2. 1bis mark shall be used when the apparatus has been repaired in compliance with the standard only. 3. The earlier BBAMA AEMT Code of Practice upright triangle, with "R;, mit should no longer be used. 1 - 15. ( 1QQ~ Revision ) PART1WO ·1YPE OF PROTECTION 'd'- FLAMEPROOF 0 lNTRODUCfiON This part of the code of practice is intended to complement BS 5345, Parts 1 and 31 with regard to matters in respect of repair and overhaul of Ex 'd' apparatus. A Hst of relevant constructional and testing Standards which should be referred to when repairing or overhauling Ex 'd' apparatus can be found in Annex A (Page v). This part of the code of practice should be read in conjunction with the General Requirements -Part One of this code. Type of Protection 'd' - A type of protection in which parts which can ignite an explosive atmosphere are placed in an enclosure which can withstand the pressure developed during an internal explosion of an explosive mixture and wbic:h prevents the transmission of the explosion to the explosive atmosphere surrounding the enclosure.. SECTION ONE- GENERAL 1. Scope This part of the code outlines the requirements of the Manufacturer, User and Repairer in connection with the repair and overhaul of electrical apparatus, type of protection 'd', and gives recommendations as to compliance with apparatus certification requirements and relevant certification Standards. SECfiON TWO- REPAIR AND OVERHAUL 1. Enclosures i) It is preferable to obtain new parts from the manufacturer. Damaged parts may be repaired, given that the type of protection as stipulated in the certification documents (if appropriate) is preserved. Particular attention should be paid to the correct assembly of flameproof enc.losures after repair or overhaul, to ensure that the joint(s) complies with the .requirements of the Standard. Where joints are not gasketed, they may be protected by the use of grease, non-setting sealing compound or non-hardening tape, in accordance with BS 5345, Paril3. ii) Where gaskets which are not part of the flamepath are incorporated into the flameproof joints, r_eplacements should be of the same 2-1 materials and dimensions as the original. Any proposed change of material should be referred to the apparatus manufacturer, user or certification authority. 2. ill) The drilling of holes into an enclosure is a modification and should not be carried out without reference to the manufacturer or, in exceptional circumstances, to the certifYing authority. iv) c:;are should be taken when changing surface finish, paint, etc., as this may affect the surface temperature of the enclosure and thus the temperature classification. v) Before a rewound or repaired rotating machine is put back into service, it is essential to ensure that fan cover ventilation holes are not blocked or so damaged as to impair the passage of cooling air over the machine, and that any fan clearances are in compliance with the requirements of the Standard, if appropriate. Should a fan or fan cover be so damaged as to require renewal, the replacement parts must be of the same dimensions and at least the same quality as the original parts and should, where appropriate, take account of the requirements of the Standard to avoid frictional sparking and electrostatic charging, and the chernjcal environment in which the machine is used. Cable and Conduit Entries Entries into flameproof enclosures should conform, after repair or overhau~ to the conditions detailed in the appropriate Standard and/or certification documents where applicable. 3. Terminations Care should be taken when refurbishing terminations to maintain clearance and creepage distances. Any replacement terminals, busrungs, or parts, should conform to the relevant apparatus Standard and/or certification documents, where applicable. 4. Insulation A class of insulation the same as, or superior to, that originally provided may be employed, e.g. a winding insulated with cJass E material may be repaired using class F material. A superior class of insulation compared with that orjginally used does not permit an increase in apparatus rating without ·r eference to the manufacturer. 2-2 5. Internal Connections There are no particular requirements relating to this type of protection but repairs to internal connections should be of a standard at least equivalent to that of the original design. 6. Windings 6.1 General The original winding data should preferably be obtained from the manufacturer; if this is not possible then use may be made of copy winding techniques. The materials used in rewinding should comprise a recognised insulation system. If the system is superior in cJass to the original, advantage should not be taken to jncrease the rating of the winding, without reference to the manufacturer, as the temperature classification of the apparatus could then be adversely affected. 6.2 Repair of Rotating Machine Rotors Faulty die cast aluminium rotor cages should be replaced by new rotors obtained from the manufacturer or his distributor. Bar wound cage rotors may be rewound using similar materials of identical specification. Particular care is necessary to ensure that, when replacing conductors in a cage rotor, such conductors are tight in the slots. The method of ~chieving tightness employed by the manufacturer should be adopted. . 6.3 Testing after Repair of Windings 6.3.1 General Windings, after complete or partial repair, should be subjected, preferably with the apparatus assembled, to the following tests, so far as is reasonably practicable: a) The resistance of each winding sbouJd be measured at room temperature and verified. In the case of three phase windings the resistance of each phase, or between line terminals should be balanced. b) An insulation resistance test should be applied to measure the resistance between the windings and earth, between windings where possible, between windings and auxiliaries, and between auxiliaries and earth. A minimum test voltage of 500 volts d.c. is recommended. Minimum acceptable insulation resistance values are a function of rated voltage, temperature, type of apparatus and whether the rewind is partial or complete. However, for example, the insulation resistance should not be Jess than 20 megohms at 20°C on a completely rewound apparatus intended for use up to 660V. 2-3 6.3.2 c) A high voltage test in accordance with a relevant Standard should be applied between windings and earth, between windings where possible, and between windings and aUXIliaries attached to the windings. d) The apparatus should preferably be energised at rated supply and the supply current/secondary voltage measured. The measured value should be compared with that derived from the manufacturer•s data, where available, and in three-phases systems should be balanced in all phases. e) High voltage (e.g. lOOOV ac/1500V de and above) and other special apparatus may require additional tests which should be agreed with the user or the manufacturer. Rotating Machines Rotating machines, in addition to the above tests, should be subjected to the following tests, so far as is reasonably practicable: 6.4 a) The machine should be run at full speed and the cause of any untoward noise and/or vibration investigated and corrected. b) The stator windings of cage machines should be energised at an appropriate reduced voltage, with the rotor locked, to obtain the full load rated current and to check balance on all phases. (The test, which in some respects is an alternative to a full load test, is 1used to confirm the integrity of the stator winding and its joints and to indicate the presence of rotor defects). c) High voltage (e.g. 1000V ac/1500V de and above) and non-cage machines may require alternative and/or additional tests which should be agreed with the user or n:mnufacturer. Note: Guidance on test voltages and additional tests for rotating machines is given in BS 4999, Part 143. AuxiliaryEquipment a) Temperature sensors If such sensors are included to monitor winding temperatures, it is recommended that they are embedded into the winding before varnishing and curing. b) Flameproof brake units Where a flameproof brake unit attached to a rotating machine is also certified, and is in need of repair, it is recommended that it be returned to the manufacturer, together with the machine. This course is recommended because of the close construction constraints. 2-4 c) Other auxiliary devices Where auxiliary devices are based on different types of protection, then the corresponding parts of this Code should be consulted before any repairs are undertaken. 7. Light Transmitting Parts No attempt should be made to re-cement or repair light transmitting parts, and only compl~te replacement assemblies, as specified by the manufacturer, should be used. Solvents should not be used for cleaning light transmitting parts made from plastics. Household detergents are recommended for this purpose. 8. Encapsulated Parts In general, encapsulated parts are not considered suitable for repair. 9. Batteries Batteries are rarely used in type of protection 'd' apparatus. Where batteries are employed, the manufacturer's advice should be followed. 10. Lamps Lamp types specified by the manufacturer should be used as replacements and the maximum wattage specified should not be exceeded. 11. Lampholders Replacements listed by the manufacturer should be used. 12. Ballasts Chokes or capacitors should be replaced only by manufacturer's listed parts, unless reference is made to the manufacturer to determine if alternatives may be used. 2-5 SECfiON THREE- RECLAMATION Reclamations using the techniques detailed in Part One, Section Four, may be used with type of protection 'd' apparatus subject to the following restricHons. 1. Enclosures Reclaimed component parts of flameproof enclosures may only be used if they pass, when appropriate, the applicable over-pressure test. Damag¢ to components .wbich are not an integral part of the flameproof enclosure, e.g. fixing lugs, may be repaired by welding, or metal stitching but care is required to ensure that the integrity and stability of the apparatus is not impaired. It is particularly important to check that any cracks being repaired do not extend into the flameproof enclosure. The efficacy of reclaiming or repairing by the technique of welding maY' be further compounded by considerations of different base materials, e.g. aluminium, cast iron or steel. It is suggested that if uncertainty exists the repairer seeks advice, preferably from the manufacturer, before this technique is adopted. 1.1. Flameproof Joints Damaged or corroded flameproof joint faces may be machined after consultation with the manufacturer wherever possible, providing any resultant joint gap and flange dimensions are not affected in such a way that they contravene the construction standard. It is particularly important that tbe quality of surface finishes is not reduced below that allowed for in the Standard, where applicable. a) b) c) Flanged Joints Welding, electroplating and re-machining flanged joint faces may be permissible, having due regard to the limitations of the technique (Part One). However, metal spraying by the unfused method is not generally recommended. Spigoted/CyJindrical Joints Machining the male part will require addition of metal to, and machining of, the female part (or vice versa), thus ensuring that tbe flamepath dimensions comply with the Standard. If only one part is damaged, that part may be restored to its original dimensions by the addition of metal and re-machining. The addition of metal may be by electro-plating, sleeving or welding, but metal spraying by· the unfused method is not generally recommended. Threaded Joints (i) Cable and conduit entries. It is not recommended that damaged male threaded parts be reclaimed; new components should be used. Damaged female threads may be repaired after consultation with the manufacturer. (ii) Screwed covers. Reclamation of the threaded parts of screwed covers and of the associated housings may be impracticable and is not recommended. 2:-6 1.2 Threaded Holes for Fasteners R~clamation of damaged threaded boles may only be achieved using the techniques described in Part One, provided that there is due consultation with the manufacturer and the Standard is not contravened. 2. Shafts and Housings Shafts and bearing housings, including flameproof joints, may be reclaimed, e.g. by the use of metal spraying or sleeving techniques, any subsequent machining sl1all be to the flamepath dimensions as specified in the Standard. Welding may be appropriate having due regard to the limitations of this technique. (See relevant Section of Part 1). 3. Journals Journals may be built up by electro-plating or metal spraying. 4. Rotors and Stators Rotors and stators may be lightly skimmed to remove eccentricities and surface damage providing that the resultant increased air gap between rotor and stator does not result in, for example, change of pressure piling characteristics or in higher external surface temperatures that .infringe the temperature class of the machine. It is suggested that if uncertainty exists with regard to possible detrimental effects the repairer seeks advice, preferably from the manufacturer, before this procedure is adopted. Skimmed or damaged stator cores should be submitted to a "flux test" to ensure that there are no remaining hot spots which could infringe the temperature classification or cause subsequent damage to the stator windings. SECTION FOUR- MODIFICATIONS 1. Enclosures No modification affecting the explosion protection should be carried out to parts of a flameproof enclosure without reference to the manufacturer or, in exceptional circumstances, with the certifying authority. 2. Cable or Conduit Entries - Additional entries should not be made without reference to the manufacturer. 2-7 Indirect entry, where the external conductors are connected by means of a plug and socket, or within a terminal box, should not be changed to direct entry, i.e. where the external conductors and cables are connected within the main enclosure. 3. Terminations Termination assemblies contammg a flameproof joint should not be modified, e.g. terminals with bushings between indirect entry terminal box and main encl0sure. · Termination assemblies not containing a flameproof joint may be replaced by alternatives of adequate design and construction in terms of number, current carrying capacity, creepage and clearance distances, and quality. 4. 5. Windings i) lt is permissible to rewind apparatus for another voltage, after reference to the manufacturer, provided that, for example, the magnetic loading, current densities, and losses are not increased, appropriate new creepage and clearance distances are observed and the new voltage is within the limits of the certification documents. The rating plate should be changed to show the new parameters. ii) Rewinding a rotating machine for a different speed is not permissible without reference to the manufacturer, since the electrical and thermal characteristics of the machine could be significantly altered so as to take it outside the limits imposed by the assigned temperature class (T-rating). Auxiliary Equipment In cases where additional auxiliary equipment is requested, e.g. anti-condensation beaters or temperature sensors, the manufacturer should be consulted to establish the feasibility of, and procedure for, the proposed addition. 2-8 PART THREE- TYPE OF PROTECTION 'i'- INTRINSIC SAFE'IY 0. INTRODUCTION This code of practice is intended to complement BS 5345 Parts 1 and 4 with regard to matters in respect of repair and overhaul of Ex 'i' apparatus. A Jist of relevant constructional and testing Standards, which should be referred to when a repair or overhaul of Ex 'i' apparatus is to be carried out, can be found j.n Annex A (Page v). This code of practice should be read in conjunction with the General Requirements Part One of this code. Type of protection 'i' - A circuit ·in which no spark or any thermal effect pmduced in the test conditions prescribed in the relevant Standard(s) (which include normal operation and specific fault condition) is capable of causing ignition of a given explosive atmosphere. SECfiON ONE - GENERAL 1. Scope This Part of the code outlines the requirements of Manufacturer, User and Repairer in connection with the repair and overhaul of electrical apparatus type of protection 'i' and gives recommendations as to compliance with current apparatus certification requirements, and relevant certification Standards. Note; IntrinsicaUy safe equipment may have one of two categories of approval, Exia and Exib -(for Zone 0 areas only Exia is accepted). However, the _recommendations for repair and overhaul apply to both categories and are irrespective of what hazardous area (i.e. Zone 0, Zone 1 or Zone 2), the equipment is installed. Furthermore, the safety of intrinsically safe systems depends upon all pieces of apparatus which form it and upon the interconnecting wiring. The same consideration should be given to those parts of the system which are installed in the non-hazardous area as for those parts installed in the hazardous area. SECfiON TWO -REPAIR AND OVERHAUL 1. Enclosures The enclosures of intrinsically safe apparatus are intended to provide a minimum degree of protection of JP 20 for indoor applications, or a minimum of IP 54 if the apparatus is used in outdoor applications. Any repairs should not result in reduction in the degree of protection. A more stringent degree of protection than that specified in the Standard may have been provided to cater for environmental conditions, in which case any repair should not jeopardize such higher degree of protection. 3-1 2. Cable Entries Special entries are used to maintain the required degree of protec6on of the enclosure. Any repairs should not result in reduction in the degree of protection. 3. Terminations Care should be taken when refurbishing terminal compartments to maintain terminal clearances and creepages in accordance with the Standard. 4. Fuses The replacement of fuses should be carried out with care. Replaceable fuses are normally used to protect transformers and it is important that the replacement is rated as specified and has the same characteristics and rupturing capacity. 5. Relays H a relay is found to be faulty, the replacement should be obtained from the equipment manufacturer. 6. Shunt Diode Safe!)' Barriers These devices are totally encapsulated and no repair is possible. It is not necessary to replace a faulty device with one of exactly the same type number and manufacture but the replacement should have the same certification marking and electrical rating. The replacement should not degrade the safety of the installation, e.g. by reducing creepage-clearance distances below those specified in the appropriate Standard. 7. Printed Circuit Boards These parts or the equipment often have critical distances between conducting tracks (creepage distances) which !;hould not be reduced. Therefore, when components are replaced care should be taken in positioning them on the board. Where boards .need to be varnished after rep~ir, at least two coats of insulating varnish of the type prescribed by the manufacturer should be paplied in the approved manner, i.e. brush, dip, coating, etc. 3-2 8. Optocouplers Only components of the same or directly equivalent type and certification should be used as replacements. 9. Electrical Components Some component(s), e.g. Zener diodes, of particular type(s) may have been specialJy selected and only these types may be used as replacements. Normally these will be obtained only from the equipment manufacturer. · 10. Batteries Only those types specified in the equipment manufacturer's instructions should be used as replacements. Where batteries are encapsulated tbe whole assembly should be.replaced. 11. Internal Wiring Certain distances between conductors, and their segregation, are critical. Therefore, if disturbed, jnternal wiring should be re-located in its original position. 12. Transformers If a transformer is found to be faulty, the replacement should be obtained from the equipment manufacturer. No attempt should be made to repair or replace any embedded (encapsulated) thermal trip device. 13. Encapsulated Components Encapsulated components, e.g. batteries with internal current limiting resistors or fuse-Zener diode assemblies, are non-repairable and should be replaced only with approved assemblies from the equipment manufacturer. 14. Non-Electrical Parts Where apparatus has non-electrical pans, e.g. fittings or windows, that do not affect the electrical circuit, or creepage or cJearance distances and, hence, the intrinsic safety, then these parts may be replaced by new parts of equivalent type. 3-3 SECTION THREE- RECLAMATION No attempt should be made to reclaim components on which intrinsic safety depends. SECfiON FOUR- MODIFICATIONS Modifications which may affect the intrinsic safety of the apparatus should not be carried out without reference to the manufacturer and/or the certification authority. Note: After modification, apparatus should be assessed to ensure that it complies with the intrinsically safe system documentation before it is reinstaJJed. It is recommended that this assessment is carried out by a person other than the one who carried out the modification. 3-4 PART FOUR- TYPE PROTECITON tp'- PRESSURIZED 0. INTRODUCTION This part of the code of practice is intended to compliment BS 5345, Parts 1 and 5, with regard to matters in respect of repair and overhaul of Ex 'p' apparatus. A list of relevant constructional and testing Standards, which should be referred to when a repair or overhaul of Ex 'p' apparatus is to be carried out, can be faun~ in Annex A (Page v). This part of the code of practice should be read in conjunction with the General Requirements - Part One of this code. Type of protection tp• - A type of protection by which the entry of a surrounding atmosphere into the enclosure of the electrical apparatus is prevented by maintaining, inside the said enclosure, a protective gas at a higher pressure than that of the surrounding atmosphere. The overpressure is maintained either with or without a continuous flow of the protective gas. · SECfiON ONE- GENERAL 1. Scope This part of the code outlines the requirements of the Manufacturer, User and Repairer in connection with the repair and overhaul of electrical apparatus, type of protection 'p', and gives recommendations as to the compliance with current apparatus certification requirements and relevant Standards. SECTION TWO -REPAIR AND OVERHAUL 1. Enclosures l.l While it is preferable to obtain new parts from the manufacturer, in principle, a damaged part may be repaired or replaced with another given that, when compared with the original, it: i) is of at least equivalent strength; ii) does not result in a greater leakage rate of protective gas; iii) does not restrict the flow of protective gas jnto or through the enclosure; 4-1 iv) is not shaped or fitted so as to permit the potentially explosive atmosphere to enter the enclosure; v) is not of a construction which would result in stagnant volumes of atmosphere inside the enclosure; vi) does not reduce the rate of heat dissipation from the enclosure or its contents. 1.2 Gaskets or other sealing devices should be replaced with others of the same materiaL However a different gasket material may be used provided that it is suitable for its purpose and is compatible with the environment. 2. Cable and Conduit Entries Entries should preserve the degree of protection originally provided, and should not allow increased leakage of protective gas. 3. Terminations There are no specific requirements but the preservation of creepage and clearance distances as originally provided should be ensured. 4. Insulation Any replacement insulation used in the course of repair or overhaul should be at least of the quality and class of that originally employed. 5. Internal Connections There are no particular requirements but internal connections should not be electrically, thermally or mechanically inferior to those originally fitted and should be of a standard at least equivalent to that of the original design. 6. Windings 6.1 General The original winding data should preferably be obtained from the manufacturer; if this is not possible then use may be made of copy winding techniques. The materials used in rewinding should comprise a If superior in class to the original, recognised insulation system. advantage should not be taken to increase the rating of the winding as the temperature classification of the apparatus could then be adversely affected. 4-2 6.2 Repair of Rotating Machine Rotors Faulty die cast aluminium rotor cages should be replaced by new rotors obtained from the manufacturer or his distributor. Bar wound cage rotors may be rewound using similar materials of identical sp~cification. Particular care is necessary to ensure that, when replacing conductors in a cage rotor, such conductors are tight in the slots. The method of achie:vi:ng tightness employed by the manufacturer should be adopted. 6.3 Testing after Repair of Windlings 6.3.1 General Windings, after complete or partial repair, should be subjected, preferably with the apparatus assembled, to the following tests, so far as is reasonably practicable: a) The resistance of each winding should be measured at room temperature and verified. In the cas~ of three phase windings the re1sistance of each phase, or between Une terminals should be balanced. b) An insulation resistance test should be applied to measure the resistance between the windings and earth, between windings where possible, between windings and ~uxiliaries, and between amdiliaries and earth. A minimum test voltage of 500 volts d.c. is recommended. Minimum acceptable insulation resistance values are a function of rated voltage, temperature, type of apparatus and whether the rewind is partial or complete. _ However, for example, the ins-ulation resistance should not be less than 20 megohms at 20°C on a completely rewound apparatus· intended for use up to 660V. c) A high voltage t'est, jn accordance with a relevant Standard, should be applied between wjndings and earth, between windings where possible, and between windings and ·auxiliaries attached to the windings. d) The apparatus should preferably be energised at rated supp'ly and the supply current/secondary voltage measured. The measured value slhould be compared with that derived from the manufacturer's data, where available, and in three-phase systems should be balanced in :au phases. e) High voltage (e.~~· 1000V ac/1500V de and above), and otller special apparatus may require additional tests wrucb should be agreed with the user or manufacturer. 4-3 6.3.2 Rotating Machines Rotating machines, in addition to the above tests, should be subjected to the following tests, so far ~ts is reasonably practicable: a) The machine shnuld be run at full speed and the cause of any· untoward noise amd/or mechanical V'ibration investigated and corrected. b) The stator windings of cage machines should be energised at an appropriate ~reduced voltage, with the rotor locked, to obtain the fuU load rated current and to ensure balance on all phases. (The test, which in some respects is an alternative to a full load test, is used to confirm the integrity of the~ stator winding and its joints and to indicate the presence of rotor defects). c) High voltage (e.g.. lOOOV ac/1500V de and above) and non-cage machines may 1require alternative and/or additional tests which should be agreed with the user or manufacturer. Guidance on tes:t voltages and additional tests for rotating machines is given in BS 4999, Part 143. 7. Light Transmitting Parts Solvents should not be used for cleaning light transmitting parts made from plastics. Household detergents are recommended for this purpose. 8. Encapsulated Parts In general, encapsulated parts are not considered suitable for repair. 9. Batteries Batteries are rarely, if ever, used in type of protection 'p' apparatus. Where batter.ies are employed, the manufacturer's advice should be sought. 10. Lamps Lamp types specified by the~ manufacturer should be used as replacements and the maximum wattage specified should not be exceeded~ 11. Lampholders Replacements listed by the manufacturer should be used. 4-4 12. Ballasts Chokes or capacitors should be replaced only by manufacturer's listed parts, unless reference is made to the manufacturer to de termine if alternatives may be used. SECfiON THREE- RECLAMATION Reclamation using the techniques detailed in Part One, Section Four, may be used with type of protection 'p' equipment subject to the following restrictions: 1. Enclosures Damage to enclosures, terminal boxes and covers may be repaired by welding or metal stitching but care is necessary to ensure that the integrity of the apparatus is not significantly impaired as to degrade the type of protection, in particular, that it remains capable of withstanding the impact test and the appropriate level of overpressure. 1.1 Joints Damaged or corroded ·joint faces may be machined provided that the mechanical strength and operation of the component is not impaired and the degree of protection is not affected. Spigoted joints are normally provided to achieve close tolerance location. Thus, machining the male part will require addition of metal to, and the machining of, the female part (or vice versa) to retain the location p roperties of the joint. If only one part is damaged, that part may be restored to its original dimensions by the addition of metal and re-machining. The addition of metal may be by electro-plating, sleeving, or welding, but metal spraying by the unfused method is not generally recommended. 1.2 Threaded Holes Reclamation of damaged threaded holes may be achieved using the techniques descnbed in Part One of this code. 2. Shafts and Housings Shafts and bearing housings may be reclaimed, preferably by use of metal spraying or sl~eving techniques. Welding may be appropriate having due regard to the limitations of this technique, see Part One of this code. 4-5 3. Journals Journals may be built up by electro-plating or metal spraying. 4. Rotors and Stators Rotors and stators may be lightly skimmed to remove eccentricities and surface damage, after consultation with the manufacturer, providing that the resultant increased air gap between rotor and stator does not result in higher external surface temperatures that infringe the temperature class of the .machine. Skimmed or damaged stator cores should be subjected to a "flux test" to ensure that there are no remaining hot spots which could infringe the temperature classification or cause subsequent damage to the stator windings. SECfiON FOUR- MODIFICATIONS 1. 2. Enclosures i) Enclosures not containing a source of release of flammable gas may be modified. Any modified part should meet the conditions given in Section Two: Clause 1.1. ii) Enclosures with an internal source of release of flammable gas such as analysers, chromatographs, etc. should not be modified in any way whatsoever without reference to the manufacturer. iii) The point(s) at which the level of overpressure and the rate of flow of purging gas is (are) monitored should not be altered nor should the setting of any timer or other monitoring devices be changed. Cable and Conduit Entries Special care to be taken that if alteration is made to entries the specified type and degree of protection are maintained. 3. Terminations Modification of terminations may be made using good engineering practices. 4-6 4. 5. Windings i) It ii) Re·winding a rotating machine for a different speed is not permissible without reference to the manufacturer, since the electrical and thermal characteristics of tbe machine could be signiificantly altered so as to take it outsjde the limits imposed by the assigned temperature class (T-rating), if appropriate, and the efficacy of the pressurizing system could be jeopardized. iis permissible to rewind apparatus for another voltage, after reference to the manufacturer, provided that, for example, the magnetic loading, current densities and losses are :not increased, appropriate new creepage and clea1rance distances are observed and the new voltage is within the limits of the certi~fication documents. The rating plate should be changed to show the new parameters. Auxiliary Equipment In cases where additional auxiliary equipment is requested, e.g. anti-condensation beaters or temperature sensors, the manufacturer should be consulted to establish the feasibility of, and procedure for, the proposed addition. 4-7 PART FIVE -1YPE OF PROTECTION 'e'- INCREASED SAFE1Y 0. INTRODUCfiON This part of the code of practice is intended to compliment BS 5345, Parts 1 and 6, with regard to matters in respect of repair and overhaul of Ex 'e' apparatus. A list of relevant constructional and testing Standards, which should be referred to when a repair or overhaul of Ex 'e' apparatus is to be carried out, can be found.in AnnexA (Page v). This part of the code of practice should be read in conjunction with the General Requirements - Part One of this code. Type of Protection 'e' - A type of protection by which measures are applied so as to prevent, with a higher degree of security, the possibility of excessive temperatures and of the occurrence of arcs or sparks in the interior and on the external parts of electrical apparatus which does not produce them in normal service. SECfiON ONE- GENERAL t. Scope This part of the Code outlines the requirements of Manufacturer, User and Repairer in connection with the repair and overhaul of Electrical Apparatus type of protection 'e' and gives recommendations as to compliance with apparatus certification requirements, and relevant certification Standards. SECTION TWO - REPAIR AND OVERHAUL 1. Enclosures 1.1 While it is preferable to obtain new parts from the manufacturer, in principle, damaged parts may be repaired or replaced with others, given that the degree of protection and temperature classification as stipulated on the certification label are preserved. 1.2 A more stringent degree of protection than that specified in the Standard may have been provided to cater for environmental conditions, in which case any ,epair should not jeopardize such higher degree of protection. 1.3 Particular attention is drawn to impact test requirements of all parts of the enclosure, and also the degree of protection to be provided for air inlet and outlet openings, as given in the apparatus Standard. 1.4 Adequate clearance should be maintained between stationary and rotating parts in accordance with the Standard. 5-1 1.5 Attention is drawn to the effects of surface finishes, paint, etc. on the temperature classification of enclosures. Only finishes specified by the manufacturer should be applied. 1.6 Before a rewound or repaired rotating machine is put back into service, it is essential to ensure that any fan cover ventilation holes are not blocked or so damaged as to impair the passage of cooling air over the machine, and that fan clearances are in compliance with the certification requirements. Should a fan or fan cover be so damaged as to require renewal, the replacement parts should be of the same dimensions as the original and at least of the same quality of the original parts, and s~ould where appropriate take . account of the requirement of the Standard to avoid frictional sparking . and electrostatic charging, and the chemical environment in which the machine is used. 2. Cable or Conduit Entries Entries should preserve IP54 minimum . degree of protection or such higher degree of protection as may have been provided - see cJause 1.2, page 5-1. 3. 4. Terminations i) The design of terminations in terms of the materials used, the creepage and clearance distances and the comparative tracking indices of termination insulation, will normally be fully specified in the certification documents. Replacement parts should preferably be obtained from the manufacturer or his advice sought regarding acceptable alternatives. ii) Where terminations are loose leads the methods of termination, including insulation, should be in accordance with the certification documents. Insulation Comprehensive details of the insulation system of windings, including. the type of impregnation varnish, are normally incJuded in the certification documents. Full information should be sought from the manufacturer. 5. Internal Connections Internal connections may be renewed, given that any insulation on such connections is not electrically, thermally or mechanically inferior to that originally supplied. The _cross-sectional area of any replacement connection should not be: less than that originally fitted. 5-2 The permitted methods of connecting conductors are given in the relevant Standards. 6. Windings 6.1 General The electrical construction of a type of protection 'e' apparatus decisively influences the explosion safety and the repairer should be in full possession of the necessary information and equipment Unless the repairer c·a n meet all the requirements it should be recognised that the rewinding should be carried out by the original manufacturer as intimated in BS 5345 Part 1. Before the repair, the original winding data should lbe obtained, i.e. Type of Winding- e.g. single layer, double layer, etc. Winding diagram Number of conductors/slot, parallel path:s per phase Interphase connections Conductor size Insulation system, including varnish specification Resistance/phase or between terminals The winding data should generally be available from the manufacturer. It is necessary to restore the windings to the ~original condition, this applies to the whole of the winding. It is not recommended to have a partial winding replacement, except on larger apparatus where this may be practicable, unless reference bas been made to the manufacturer or certifying authority. 6.2 Repair of Rotating Machine Rotors Rotors with faulty die cast aluminium cages s.h ould be replaced by completely new rotors obtained from the manufacturer or his distnlmtor. Bar wound cage rotors may be rewound using materials of identical specifications. Particular care is necessary to ensure that if replacing conductors in a cage rotor, such conductors are tight in the slots. The method of achieving tightness employ1ed by the manufacturer should be adopted. 6.3 Testing After Repair of Windings 6.3.1 General Windings, after complete repair, should be su~jected, preferably with the apparatus assembled, to the following tests so far as is reasonably practicable: 5-3 6.3.2 a) The resistance of each winding should be measured at room temperature and verified. In the case of three phase windings the resistance of each phase, or between line terminals should be balanced. b) An insulation resistance test should be applied to measure the resistance between the windings and earth, between windings where possible, between windings and auxiliaries, and between auxiliaries and earth. The minimum test voltage of 500 volts de is recommended. Minimum acceptable insulation resistance values are a function of rated voltage, temperature and type of apparatus. However, for example, the insulation resistance should not be less than 20 megohms at 20°C on a completely rewound apparatus intended for use up to 660V. c) A high voltage test, in accordance with a relevant Standard, should be applied between windings and earth, between windings where possible, and between windings and auxiliaries attached to the windings. d) The apparatus should preferably be energised at rated supply and the supply current/secondary voltage measured. The measured value should be compared with that derived from the manufacturer's data, where available, and in three-phase systems should be balanced in an phases. e) Hig~ voltage (e.g. lOOOV ac/1500V de and above) and other special apparatus may require additional tests which should be agreed with the user or manufacturer. Rotating Machines Rotating machines, in addition to the above tests, should be subjected to the following tests so far as is reasonably practicable: a) The machine should be run at full speed and the cause of any untoward noise and/or mechanical vibration investigated and corrected. b) The stator windings of cage machines should be energised at an appropriate reduced voltage, with the rotor locked, to obtain the full load rated current and to ensure balance on all phases. (The test, which in some respects is an alternative to a full load test, is used to confirm the integrity of the stator winding and its joints and to indicate the presence of rotor defects). c) High Voltage (e.g. 1OOOV ac/1500V de and above) and non-cage machines may require alternative and/or additional tests which should be agreed with the user or manufacturer. Note: Guidance on test voltages and additional tests for rotating machines is given in BS 4999, Part 143. 5-4 6.4 Auxiliary Equipment If temperature sensors are incJuded to monitor winding temperatures, it is recommended that they are embedded into the winding before varnishing and curing. 7. Light Transmitting Parts No attempt should be made to repair light transmitting parts and only replacement components provided by the manufacturer should be used. Solvents should not be used for cleaning light transmitting or other parts made of plastic. Household detergents may be used. 8. Encapsulated Parts In general, encapsulated parts are not considered suitable for repair or reclamation. 9. Batteries Where type of protection 'e' apparatus contains batteries of any kind, reference should be made to the manufacturer~s instructions before carrying out any·repair or replacement. 10. Lamps Lamp types specified by the manufacturer should be used as replacements and the maximum wattage specified should not be exceeded. Special care should be taken with the special single pin tubular fluorescent tube employed for type of protection 'e' luminaires. The single pin, when inserted in the Jampholder, forms a flameproof enclosure and distortion or misalignment may affect the designed explosion protection. 11. Lampholders Lampholders for type of protection 'e' luminaires are invariably of specific types, either single pin for tubular fluorescent lamps or screw for other types. Only replacements specified by the manufacturer should be used. In those cases where the wiring to the lampholder is factory made (crimps etc.) rewiring should not be undertaken unless the repairer has the' equipment to make up the wiring to the same standard. 12. Ballasts Defective chokes and capacitors should only be replaced with manufacturer's listed parts. SECTION THREE-RECLAMATION Reclamations using the techniques detailed in Part One, Section Four, may be used with type of protection 'e' equipment subject to the following restrictions: 1. Enclosures Minor damage to enclosures, terminal boxes and covers can be repaired by welding or metal stitching but care is necessary to ensure that the integrity of the apparatus is not significantly impaired as to degrade the type of protection, in particular, that it remains capable of withstanding the impact test and maintains the degree of protection. 1.1 Joints Damaged or corroded joint faces may be machined providing that the mechanical strength and operation of the component is not impaired and the degree of protection is not affected. Spigoted joints are normally provided to achieve close tolerance location. Thus, machining the male part will require addition of metal to, and machining of, the female part (o.r vice versa) to retain the location properties of the joint. If only one part is damaged, that part may be restored to its original dimensions by the addition of metal and re-machining. The addition of metal may be by electro-plating, sleeving, or welding, but metal spraying by the unfused method is not generally recommended. 12 Threaded Holes Reclamation of damaged threaded holes may be achieved using the techniques described in Part One of this code. 2. Shafts and Housings Shafts and bearing housings may be reclaimed, preferably by use of metal spraying or sleeving techniques. Welding may be appropriate having due regard to the limitations of this technique, see Part One of this code. 3. Journals Journals may be built up by electro-plating or metal spraying. 5-6 4. Rotors an Stators Rotors and stators may be lightly skimmed to remove eccentricities ~nd surface damage, after consultation with the manufacturer, providing that the resultant increased air gap between rotor and stator qoes not result in- i) higher internal and/or external surface temperatures that infringe the temperature class of the machine, or ii) changes in electrical/mechanical performance whicb prevents the electrical/thermal protective devices providing the tripping characteristics required to confonn to the Standard. Skimmed or damaged stator cores should be subjected to a "flux test" to ensure that there are no remailling hot spots whjcb could infrin,g e the temperature classification or cause subsequent damage to the stator windings. SECTION FOUR- MODIFICATIONS 1. Enclosures Enclosures may be modified provided that the specified temperature classification, degree of protection, and impact test requirements are met. 2. Cable and Conduit Entries Special care to be taken that if alteration is made to entries the specified type and degree of protection is maintained. 3. Terminations No modification of terminations should be made without reference to the manufacturer. • 4. Windings i) .. It is permissible to rewind apparatus for another voltage, after reference to the manufacturer, provided that, for example, the magnetic loading, current densities and losses are not increased, new appropriate creepage and clearance distances are observed, and the new voltage, tE time and I AIIN ratio are within the limits of the certification documents. The rating plate should be changed to show the new parameters. 5-7 4. Rotors an Stators Rotors and stators may be lightly skimmed to remove eccentricities and surface damage, after consultation with the manufacturer, providing that the resultant increased air gap between rotor and stator does not result in- i) higher internal and/or external surface temperatures that infringe the temperature class of the machine7 or ii) changes in electrical/mechanical performance which prevents the e}ectricalf.thermal protective devices providing the tripping characteristics required to conform to the Standard. Skimmed or damaged stator cores should be subjected to a "flux test" to ensure that there are no remaining hot spots which could infringe the temperature cJassification or cause subsequent damage to the stator windings. SECTION FOUR- MODIFICATIONS 1. EnClosures Enclosures may be modified provided that the specified temperature classification, degree of protection, and impact test requirements are met. 2. Cable and Conduit Entries Special care to be taken that if alteration is made to entries the specified type and degree of protection is maintained. 3. Terminations No modification of terminations should be made without reference to the manufacturer. 4. Windings i) It is permissible to rewind apparatus for another voltage, after reference to the manufacturer, provided that, for example, the magnetic loading, current densities and losses are not increased, new appropriate creepage and clearance distances are obse.r;ved, and the new v~lt~ge, tE ti_!ll: and I A/IN rat~o ~re Withm the linuts of the certification documents. The tating plate should be changed to show the new parameters. 5-7 li) 5. Rewinding a rotating machine for a different speed is not permissible without reference to the manufacturer, since the electrical and tbermal characteristics of the machine could be significantly altered so as to take it outside the limits of the certificatiom documents. Auxilia!Y Equipment In cases where additional auxiliary equipment is requested, e.g. anti-condensation heat~rs or temperature sensors, the manufacturer should be consulted to establish the feasibility of, and procedure for, the proposed modification. 5-8 PART SIX- TYPE OF PROTECI'ION 'N~ OR 'n'- NON SPARKING 0. INTRODUCTION This part of the code of practice is intended to complement BS 5345, Parts 1 and 7, with regard to matters in respect of repair and overhaul of Ex 'N' apparatus. A list of relevant constructional and testing Standards, which should be referred to when a repair or overhaul of Ex 'N' apparatus is to be carried out, can be found in Annex A (Page v). This part of the code of practice should be read in conjunction with the General Requirements -Part One of this code. Type of Protection 'N' or <n• - A type of protection applied to electrical apparatus such that, in normal operation, it is not capable of igniting the surrounding explosive atmosphere, and a fault capable of causing ignition is not likely to occur. SECTION ONE - GENERAL 1. Scope This part of the code outlines the requirements of the Manufacturer, User and Repairer in connection with the repair and overhaul of electrical apparatus type of protection 'N' or 'n' and gives recommendations as to compliance with apparatus certification requirements and relevant certification Standards. SECTION TWO -REPAIR AND OVERHAUL 1. Enclosures 1.1 Whilst is is preferable to obtain new parts from the manufacturer, in principle, damaged parts may be repaired or replaced with others, given that the degree of protection and temperature classification as stipulated on the certification label is preserved. 1.2 A more stringent degree of protection than that specified in the Standard may have been provided to cater for environmental conditions, in which case any repair should not jeopardise such higher degree of protection. 1.3 Particular attention is drawn to the impact test requirements of all parts of the enclosure, as given in the apparatus Standard. 1.4 Adequate c1earance should be maintained between stationary and rotating parts in accordance with the Standard. '6-1 1.5 Restricted breathing enclosures depend for their explosion protection on gaskets and other means of sealing. Particular attention should be paid to the condition of the sealing arrangements to preserve the type of protection. 1.6 Attention is drawn to the effect of surface finish, paint, etc-. on the temperature classification of enc1osures. 1.7 Before a rewound or repaired rotating machine is put back into service, it is essential to ensure that any fan cover ventilation holes are not blocked or so damaged as to impair the passage of cooling air over the machine and that fa.n clearances are in compliance with the certification requirements. Should a fan or fan cover be so damaged as to require renewal, the replacement parts should be of the same dimensions as the original and at least the same quality of the original parts, and should, where appropriate, take account of the requirement of the Standard to avoid frjctional sparking or electrostatic charging and the chemical environment in which the machine is used. 2. Cable and Conduit Entries Entries should preserve the specified degree of protection. 3. 4. Terminations i) Care should be taken when refurbishing terminal compartments to maintain clearances and creepages in accordance with the Standard. Where non-metallic screws are used for fixing then only replacement screws of similar materials may be used. ii) Where terminations are loose leads the method of termination, including insulation~ should be in accordance with the certification documents. Insulation A class of insulation the same as, or superior to, that originally provided should be employed. If superior in class to the original, advantage should not be taken to increase the rating of the winding as the temperature classification of the apparatus could then be adversely affected. 5. Internal Connections Internal connections may be renewed, given that any insulation on such connections is not electrically, thermally or mechanically inferior to that originally supplied. 6-2 The cross-sectional area of any replacement connection should not be less than that originally fitted. 6. Windings 6.1 General Where rewinding is carried out, it is essential that the original winding data are determined and that the new winding conforms to the original. The original winding data should preferably be obtained from the manufacturer; if this is not possible then use may be made of copy winding techniques. It is not recommended to have a partial winding replacement, except on larger apparatus where this may be practicable, unless reference has been made to the manufacturer or certifying authority. 6.2 Repair of Rotating Machine Rotors A faulty die cast aluminium rotor should be replaced by a complete new rotor obtained from the manufacturer or his distributor. Bar wound cage rotors may be rewound using materials of equivalent specification. Particular care is necessary to ensure that, if replacing conductors in a cage rotor, such conductors are tight in the slots. The method of acrueving tightness employed by the manufacturer should be adopted. 6.3 Testing After Repair of Windings 6.3.1 General Windings, after complete or partial repair, should be subjeCted, preferably with apparatus assembled, to the fol1owing tests so far as is reasonably practicable: a) The resistance of each winding should be measured at room temperature and verified. In the case of three phase windings the resistance of each phase, or between line terminals should be balanced. b) An insulation resistance test should be applied to measure the resistance between the windings and earth, between windings where possible, between windings and auxiliaries, and between auxi1iaries and earth. A minimum test voltage of 500 volts de is recommended. Minimum acceptable insulation resistance values are a function of rated voltage, temperature, type of apparatus and whether the rewind is partial or complete. However the insulation resistance should not be less than 20 megohms, at 20°C, on a completely rewound apparatus intended for use at up to 650 volts. 6-3 6.3.2 c) A high voltage test in accordance with a relevant Standard should be applied between windings and earth, between windings where possible, and between windings and auxiliaries attached to the windings. d) The apparatus should preferably be energised· at rated supply and supply current/secondary voltage measured. The measured value should be compared with that derived from the manufacturer's data, where available, and in three-phase systems should be balanced in all phases. e) High voltage .(e.g. lOOOV ac/1500V de and above) and other special apparatus may require additional tests which should be agreed with the user or manufacturer. Rotating Machines Rotating machines, in addition to the above tests, should be subjected to the following tests so far as is reasonably practicable: a) The machine should be run at full speed and the cause of any untoward noise and/Or mechanical VIbration investigated and corrected. b) The stator windings of cage machines should be energised at an appropriate reduced voltage, with the rotor locked, to obtain the full load rated current and to ensl:lre balance on all phases. (The . test, which in some respects is an alternative to a full load test, is used to confirm the integrity of the stator winding and its joints and to indicate the presence of rotor defects). c) High voltage (e.g. 1000V ac/1500V de and above) and non-cage machines may require alternative and/or additional tests which should be agreed with the user or manufacturer. Guidance on test voltage and additional tests for rotating machines is given in BS 4999, Part 143. 6.4 Auxiliary Equipment H temperature sensors are included to monitor winding temperatures, it is recommended that they are embedded into the winding before varnishing and curing. 6-4 1. Light Transmitting Parts Solvents should not be used for cleaning light transmtttmg or other parts made of plastic. HousehoJd detergents may be used. 8. Encapsulated Parts In general, encapsulated parts are not considered suitable for repair. 9. Batteries Where type of protection 'N' or 'n' apparatus contains batteries of any kind, reference should be made to the manufacturer's instructions before carrying out any repair or replacement. 10. Lamps Lamp types specified by the manufacturer should be used as replacements and the maximum wattage specified should not be exceeded. 11. Lampholders Replacements listed by the manufacturer should be used. 12. Ballasts Chokes or capacitors should only be replaced with manufacturers listed If these are of proprietary manufacture reference should be parts. made to the original manufacturer to determine if alternatives may be used. 13. Enclosed Break Devices In general enclosed break devices are not considered to be suitable for repair. Replacement parts listed by the manufacturer should be used. SECTION THREE- RECLAMATION Reclamations using the techni9,ues detailed in Part One of the code may be used with type of protection 'N or 'n' equipment subject to the foUowing restrictions: 6-5 1. Enclosures Minor damage to enclosures, terminal boxes and covers may be repaired by welding or metal stitching but care is necessary to ensure that the integrity of the apparatus is not impaired, in particular, that it remains capable of withstanding the impact test and maintains the degree of protection. 2. Joints Damaged or corroded joint faces may be machined providing that the mechanical strength and operation of the component is not impaired and the degree of protection is not affected. Spigoted joints are normally provided to achieve close tolerance location. Thus, machining the male .part wilJ require addition of metal to, and machining of, the female part (or vice versa) to retain If only one part is damaged, the location properties of the joint. that rart may be restored to its original dimensions by the addition of meta and re-machining. The addition of metal may be by electroplating, sleeving, or welding, but metal spraying by the unfused method is not generally recommended. 3. Threaded Holes Reclamation of damaged threaded holes may be achieved using the techniques described in Part One of the code. 4. Rotating Machines i) Shafts and Housings Shafts and bearing housings may be reclaimed, preferably by use of metal spraying or sleeving techniques. Welding may be appropriate having due regard to the limitations of this technique -Part One of this code. ii) Journals Journals may be built up by electroplating or metal spraying. iii) Rotors and Stators Rotors and stators may be lightly skimmed to remove eccentricities and surface damage, providing that the resultant increased air gap between rotor and stator does not result in higher internal or external surface temperatures that infringe the temperature class of the machine. 6-6 Skimmed or damaged stator cores should be subjected to a "flux test" to ensure that there are no remaining hot spots which could infringe the temperature classification or cause subsequent damage to the stator windings. SECTION FOUR- MODIFICATIONS 1. Enclosures Enclosures may be modified provided that the specified temperature classification, degree of protection and impact test requirements are met. 2. Cable and Conduit Entries Care should be taken to ensure that the specified type and degree of protection is maintained. 3. Terminations May be modified provided that compliance with the Standard is maintained. 4. 5. Windings i) It is permissible to rewind apparatus for another voltage, after reference to the manufacturer, provided that, for example, the magnetic loading, current densities and losses are not increased, appropriate new clearances and creepage distances are observed, and the new is within .the limits of the voltage certificate. The rating plate should be changed to show the new parameters. ii) Rewinding a rotating machine for a different speed is not permissible without reference to the manufacturer since the electrical and thermal characteristics of the machine could be significantly altered so as to take it outside the limits of the certification documents. Amoliary Equipment In cases where additional auxiliary equipment is requested, e.g. anti-condensation beaters or temperature sensors, the manufacturer should be consulted to establish the feasibility of, and procedure for, the proposed modification. 6-7 PART SEVEN -'IYPE OF PROTECI'ION 's' - SPECIAL PROTECfiON 0. INTRODUCTION This code of practice is intended to complement BS 5345, Parts 1 and 8, wi!h regard to the matters in respect of repair and overhaul of Ex 's' apparatus. A list of relevant constructional and testing Standards containing specific requirements can be found in Annex A (Page v). This code of practice should be read in conjunction with the General Requirements - Part One of this code. Type of protection 's' - Electrical equipment which is considered safe due to design features other than the formal concepts covered by National Standards, may be certified as specially protected. SECTION ONE- GENERAL 1. Scope This part of the code outlines the requirements of Manufacture rs, Users and R epairers in connection with the repair and/or overhaul of electrical apparatus having type of protection 's', particularly withregard to its compliance with the relevant Standards. Type 1s' is an exceptional case having regard to the fact that it covers a wide variety of applications. Repair or overhaul should be contemplated with caution and reference should be made to the manufacturer in the first instance. Some equipment is only capable of repair or overhaul by the manufacturer. SECTION TWO - REPATR AND OVERHAUL 1. Enclosures Where apparatus of type of protection 's' is enclosed by another type of protection, the repair or overhaul of the enclosure shouJd conform with the appropriate Part of this code. Where the enclosure is of type of protection 's', there are no general rules for repair or overhaul and references shouJd be made to the manufacturer for advice. 7-1 2. Cable and Conduit Entries Entries complying with other types of protection should be repaired/overhauled in compliance with the appropriate Part of this Code. There are no general rules for the repair or overhaul of entries to type of protection 's' and reference should be made to the manufacturer for advice. 3. Terminations Terminations complying with other types of protection should be repaired/overhauled in compliance with the appropriate Part of this code. There are no general rules for the repair or overhaul of terminations to type of protection 's' and reference should be made to the manufacturer for advice. 4. Encapsulated Apparatus In many cases it is not possible to repair or overhaul apparatus which has been encapsulated. Indeed, it is unwise even to attempt to replace or repair the encapsulation itself, except where spedfically recommended by the manufacturer. However, apparatus in which part is type of protection 's', the encapsulation may be repairable or amenable to overhaul if it is the form of a complete, detachable sub-assembly. In such cases it is necessary to ensure that the encapsulated part is free from defects (electrical or mechanical) such as: cracks in the encapsulation, overheated parts, Jack of adhesion of encapsulation from associated parts such as printed circuit boards, chemical attack, etc., and if not, to replace the whole encapsulated part. 5. Flame Arrestors Flame arrestors should be inspected for physical damage, such as cracks, and for contamination/blockage by dirt, corrosion or paint, and be replaced by a new part, if necessary, obtained only from the manufacturer or his authorised suppUers. 6. Batteries Apparatus containing primary or secondary ceUs may be repaired or overhauled only where the cells are intended to be replaced. No attempt should be made to replace encapsulated cells or batteries except where the complete encapsulated assembly may be replaced. 7-2 7. Lamps Factory-sealed handlamps should be returned to the manufacturer for repair or replacement as appropriate. Where lamps are enclosed by avparatus .of other types of protection combined with type of protection 's , reference should be made to .other parts of this code (as appropriate) and to the manufacturers' instructions. 8. Lampholders Where lampholders are covered by other types of protection combined wjth type of protection ·•s•, reference should be made to other Parts of this code (as appropriate) and to the manufacturers' instructions. 9. Ballasts Where ballasts are covered by other types of protection combined with type of protection 's', reference should be made to other Parts of this code (as appropriate) and to the manufacturers' instructions. 10. Light Transmitting Parts Where light transmitting parts are incorporated in apparatus of type of protection 's', they may only be replaced by parts specified by the manufacturer or, where possible, repaired, in accordance with the manufacturers' instructions. SECfiON THREE- RECLAMATION In general, few parts of apparatus to type of protection 's' may be reclaimed except where combined with other types of protection. 1. EncJosures Where enclosures of other types of protection combined with type of protection 's' may be subject to redamation, reference should be made to the relevant Part(s) of this code. Where the enclosure is only type of protection 's', reference should be made to the manufacturer for advice. No attempt should be made to reclaim (or repair) factory sealed assemblies. 2. Cable and Conduit Entries Where entries of other types of protection combined with type of protection 's' may be subject to reclamation, reference should be made to the relevant Part(s) of this code. Where the terminations are only type of protection 's', reference should be made to the manufacturer for advice. 7-3 3. Flame Arrestors In some cases flame arrestors may be reclaimed by special cleaning processes specified by the manufacturer. However, after cleaning, the flameproof or sealed joint between the flame arrestor and its housing should still comply with the requirements of the certificate. SECTION FOUR- MODIFICATION Few parts of type of protection 's' apparatus are amenable to modifications except when combined with other types of protection. 1. Enclosures 2. Entries 3. Terminations Where other types of protection are combined with type of protection 's', reference should be made to the relevant Part(s) of this code for instructions Where type of relatmg to modifications. protection 's' only is involved, refer to the manufacturer. 7-4 PART EIGHT· PROTECI10N BY ENCLOSURE FOR USE IN THE PRESENCE OF COMBUSTIBLE DUSTS 0. INTRODUCfiON This part of the code of practice is intended to complement BS 6467 Part 2 with regard to matters in respect of the repair and overhaul of apparatus for use in the presence of combustible dusts. A ]jst of relevant constructional and testing standards containing spedfic requirements can be found in Annex A (Page v). This Code of Practice should be read in conjunction with the General requirement - Part One of this code. The foundations for safety for this concept are based on: Protection against ingress of dust Surface temperatures limitation Safety factors for the ignitions temperature of both dust clouds and/or dust layers. SECfiON ONE· GENERAL 1. Scope Thls part of the Code outlines the requirements of the manufacturer, user and repairer in connection with the repair and overhaul of electrical apparatus, with protection by enclosure for use in the presence of combustible dusts. SpeCial care is to be exercised in the repair and overhaul due to the nature of the combustible dust and the variety of dusts encountered. See General Requirements, Page 1·7, Guidance to the User. SECTION TWO- REP AIR AND OVERHAUL 1. Enclosure i) Whilst it is preferred to obtain new parts from the manufacturer, in principle damaged parts may be repaired or replaced with others providing the enclosure protection is maintained to IP65 or IP55 whichever is applicable. Particular attention should be paid to the sealing of the joints. Where gaskets are not fitted sealing compound, suitable for the temperature range of the enclosure, may be used. 8-1 2. ii) Where gaskets are fitted to a joint they must be free from damage otherwise replacements should be of the same materials and dimensions as the origiinal. Any proposed change of material should be referred to the apparatus manufacturer or certification authority. iii) The· drilling of holes into an enclosure is a modification and should not be carried out without reference to the Standard (BS 6467 Pt 1) or the manufacturer. iv) Before a rewound or repaired rotating machine. is put back into service, it is essential to ensure that fan cover ventilation holes are not blocked or so damaged as to impair the passage of coolling air over the machine, and that there are adequate fan clearances in compliance with the req11irements of the Standard, if appropriate. Should a fan or fan cover be so damaged as to require renewal, the replacement parts must be of 1the same dimension and at least the same quality as the original parts, and should where appropriate, take account of the requirements of the Standard to avoid frictional sparking and elec;trostatic charging, and the chemical env1ironment jn which the machine is used. v) If drain holes are evident ensure that screwed plugs are fitted and locked in position. Cable and Conduit Entries Entries into the enclosure should conform after repair and overhaul, to the conditions detailed in the appropriate Standard and/or certification documents where applicable, preserving the 1P65 or IP55 minimum protection as appropriate. 3. Shaft/Motor Entry Sealing Shaft seals have limited life and should be replaced at intervals recommended by the manufacturer (this interval will depend on environmental conditions).. When bearings are replaced, new shaft seals should be fitted, care being taken during re-assembly, by protecting against sharp edges. Thls is not applicable to Labyrinth seals. 4. Tenninations i) Care should be taken when refurbishing terminal compartments to maintain clearances and creepages in accordance with the Standard or ma1nufacturers practices. 'Where non-metallic screws are used for fixing then only replacement screws of similar materials may be used. 8-2 ii) 5. Where terminations are loose leads the method of termination, including insulation, should be in acc{)rdance with the Standards or manufacturers recommendations. Jnsulation A class of insulation the same as or superior to that originally provided should be employed. H superior in class to the original, advantage should not be taken to increase the rating of the winding, as the temperature c1assification of the apparatus could then be adversely affected. 6. Internal Connections Jntem_al connections may be renewed, given that any in-sulation on such connections is not electrically, thermally, or mechanically jnferior to that originally supplied. The cross-sectional area of any replacement connection should not be less than that originally fitted. 7. Windings 7.1 General Where rewinding is carried out, it is essential that the original winding data are determined and that the new winding conforms to the original. The original winding data should preferably be obtained from the manufacturer; if this is not possible then use may be made of copy winding techniques. It is not recommended to have a partial winding replacement, except on larger apparatus where this may be practicable, unless reference has been made to the manufacturer or certifying authority. 7.2 Repair of Rotating Machine Rotors A faulty die cast aluminium rotor should be replaced by a complete new rotor obtained from the manufacturer or his distributor. Bar wound cage rotors may be rewound using materials of equivalent Particular care is necessary to ensure that, if specification. replacing conductors in a cage rotor, such- conductors are tight in the slots. The method of achieving tightness employed by the manufacturer should be adopted. 7.3 Testing After Repair of Windings 7.3.1 General Windings, after complete or partial repair should be subjected, preferably with apparatus assembled, to the following tests so far as is reasonably practicable: 8-3 a) The resistance of each winding should be measured at room temperature and verified. In the case of three phase windings the rt!sistance of each phase, or between line terminals should be balanced. b) An insulation test should be applied to measure the resistance betwe1en the windings and earth, between windings where possible, and between auxiliaries and earth. A minimum test voltage of 500 volts de is recommended. Minimum acceptable insulation resistance values are a function of r~tedl voltage, temperature, type of apparatus and whether the rewind is partial or complete. However the insulation resistamce should not be less than 20 megohms, at 20°C, on a completely rewound apparatus intended for use at up to 650 volts. 7.3.2 c) A high voltage test in accordance with a relevant Standard should be applied between windings and earth, between windings where possible, and between windings and auxiliaries attached to the windings. d) The apparatus should preferably be energised at rated supply and supply current/secondary voltage measured. The measured value should be compared with that derived from the manufacturer's data, where available, and in three-phase systems should be balanced in all phases. e) High voltage (eg lOOOV ac/1500V de and above) and other special apparatus may require additional tests which should be agreed with the user or manufacturer. Rotating Machines Rotating machines, in addition to the above tests, should be subjected to the following tests so far as is reasonably practicable: a) The machine should be run at full speed and the cause of any untoward noise :and/or mechanical Vlbration investigated and corrected. b) The stator windi:ngs of cage machines should be energised at an appropriate reduced voltage, with the rotor locked, to obtain the full load rated current and to ensure balance on all phases. (The test, which in some respects is an alternative to a fuJI load test, is used to confirm the integrity of the~ stator winding and its joints and to indicate the prese:nce of rotor defects). c) High voltage (e.g. lOOOV ac/1500V de and above) and non cage machines may require alternative and/or additional tests which should be agreed with the user or manufacturer. Guidance on test voltages and additional tests for rotating machines is given in BS 4999, Part 143. 7.4 Auxiliary Equipment If the temperature sensors are included to limit external surface temperatures, it is recommended that they are embedded into the winding 'b efore varnishing and curing.. The Standard BS 6467 Part 1 suggests that under adverse electrical conditions temperature semsors should be fitted. In rewinding an electrical rotating machine: temperature sensors should be fitted if incorporated in the original winding. Advice regarding the operating temperature of the sensor .should be obtained from the manufacturer where possible. SECITON THREE- RECLAMATION Reclamation using the techniques detailed in Part One of the code may be used. 1. Enclosures Minor damage to enclosures, terminal boxes and covers may be repaired by welding or metal stitching but care is necessary to ensure that the integrity of the apparatus is not impaired, in particular, that it remains capable of withstanding the impact test and maintains the degree of protection. 2. Joints Damaged or corroded joint faces may be machined providing that the mechankal strength and operation of the component is not impaired and the degree of protection is not affected. Spigoted joints are normally provided to achieve close tolerance location. Thus, matching the male part wilJ require addition of metal to, and machining of the female part (or vice versa) to retain the location properties of the joint. If only one part is damaged, that part may be restored to its original dimensions by the addition of metal and re-machining. The addition of metal may be by electroplating, sleeving, or welding, but metal spraying by the unfused method is not generally recommended. 3. Threaded Holes Reclamation of damaged threaded holes may be achieved using the techniques described in Part. One of the code. 4. Rotating Machines i) Shaits and Housings ShaJfts and bearing housings may be reclaimed, preferably by use of metaJ spraying or s]eeving techniques. Welding may be appropriate having due regard to the limitations of this technique -Part One of this code. 8-5 ii) Journals Journals may be built up by electroplating or metal spraying. Rotors and Stators Rotors and stators may be lightly skimmed to remove eccentricities and surface damage, providing that the resultant increased · air gap between rotor and stator does not result in 4igher internal or external surface temperatures that infringe the temperature class of the machine. Skimmed or damaged stator cores should be subjected to a "flux test" to ensure that there are no remaining bot spots which could infringe the temperature classification or cause subsequent damage to the stator windings. SECTION FOUR- MODIFICATIONS 1. Enclosures Enclosures may be modified provided that the specified temperature classification, degree of protection and impact test requirements are met. 2. Cable and Conduit Entries Care should be taken to ensure that the specified type and degree of protection is maintained. 3. Terminations May be modified providing that compJiance with the Standard maintained. 4. lS Windings i) It is permissible to rewind apparatus for another voltage, after reference to the manufacturer, provided that, for example, the magnetic loading, current densities and 1osses are not increased, appropriate new clearances and creepage distances are observed, and the new voltage is within the limits of the certificate. The rating plate should be changed to show the new parameters. ii) Rewinding a rotating machine for a different speed is not permissible without reference to the manufacturer since the electrical and thermal characteristics of the machine could be significantly altered so as to take it outside the limits of the certification documents. 8-6 5. Auxiliary Equipment In cases where additional auxiliary equipment is requested, e.g. anticondensation heaters or temperature sensors, the manufacturer should be consulted to establish the feasibility of, and the procedure for, the proposed modification. See Clause 7.4 of Section Two for notes on temperature sensors. 8-7 BSI Handbook 22- Quality Assurance- contains the following British Standards: BS.6467 BS.6467 BS.6467 E lectrical apparatus with protection by enclosure for use: in the presence of combustible dustsSpecification for apparatus. Guide to selection, installation and maintenance. Glossary of Terms used in Quality Assurance. A Guide to Quality Assurance. Glossary of Terms used in Metrology. Quality Systems. Reliability of Systems, Equipments and Components. Measurement and Calibration Systems. Guide to the Determination and Use of Quality Related Costs. Pt.l Pt.2 BS.4778 BS.4891 BS.5233 BS.5750 BS.5760 BS.5781 BS.6143 BASEEFA SFA3009: BASEEFA SFA.3012: BASE~FAEx-MEMO No.1- Type of Pro.tection Ex 's'. Type of Protection Ex 'i'. Explanatory Mem.orandum on marking and labelling of certified apparatus and components as used in the UK. Note: Additional relevant Standards are listed in BS.5345 : Part 1 vi Contract requirements: This Code of Practice does not purport to include all the necessary provisions of a contract. Users of this Code of Practice are responsible for its correct application. Revisions: This Code of Practice will be revised when necessary, by the issue either of amendments or of revised eclitions. It is important that users of the Code of Practice ascertain that they are in possession of the latest amendments or edition. PARTICIPATING ORGANISATIONS ENGINEERING EQUIPMENT MATERIALS USERS' ASSOCIATION INSTITUTE OF PETROLEUM AMENDMENTS: Revision 1 incorporates Amendments 1, 2 & 3 AMENDMENT NUMBER DATE OF ISSUE 4 (Correction of typographical error) TEXT AFFECTED 7.3.1 b). Para 2. 200 megohms to read 20 megohms. ~~ Further copjes are available from: BEAMA Limited, Westminster Tower, 3 Albert Embankment, London SEJ 7SL Telephone: 0171-793 3000 Telefax: 0171 -793 3003 Association of Electrical and Mechanical Trades, --- - AEMTLtd St Saviours House St Saviours Place YORK Y017PJ Tel: 01904 674899 Fax: 01904 674896 Vll BEAMA LIMITED BEAMA js the Federation of British Electrotechnjcal and Allied Manufacturers• Associations. Eighteen federated Associations represent between them some 570 com~anies. A wide range of electrical products is covered including:Turbo-generating equipment, transformers and switchgear; metering equipment, rotating electrical machines, installation equipment including circuit-breakers, conduit, plugs, sockets, wiring accessories, switches and controls; and power supplies. Laboratory, medical and nucleonic instruments; diagnostic instrumentation and reagents; electronic test and measurement equipment; measurement, control and systems; volumetric liquid meters; control valves; programmable controllers; sensors and transducers; high and low voltage controJgear components and systems; and power electronics. Electrical and electronic insulation material; welding equipment; interactive and mains signalling equipment; membrane type switches; cable connectors; emergency lighting; industrial heating and industrial cleaning machines. Advanced and traditional electric road vehicles; vehicles, electric mobility vehicles and components. industrial electric THE ASSOCIATION OF ELECTRICAL AND MECHANICAL TRADES The AEMT is :recognised as the Association in UK which represents the electrical repair and merchanting industry. It has more than 150 member companies engaged in the repair, reconditioning and merchanting of industrial electrical equipment including motors, control gear, transformers and a wide range of allied apparatus. It also has some 40 Associate Members, being companies which supply materials, equipment and services to those engaged in the repair of electrical apparatus.