Relay Test Report 11/20/2021 PAGE 1 Nameplate Data MANUFACTURER: Siemens ASSET ID: B2+RP09 SUBSTATION 500kV New Lahore (South) LZOP: PROTECTION: Differential Prot. Set I MODEL: 7UT63 SERIAL NUMBER: PT RATIO: kV : TEST STATUS: Pass DATASHEET: Counter Clockwise Rotation 0-360 Lead JOB #: PTW # 919 RELAY FIRMWARE: V A Differential Settings Pickup Trip Time Prefault Level Prefault Time Off Delay Through Fault Current 2nd Harmonic Content Fault Duration ICT Correction 0.2 20 50 800 0 100 15 500 525 3,000 pu ms % ms ms % Ib % ms NO Current Tolerance 12 Trip Time Tolerance 10 Simulate Breaker NO Use Reference Voltage NO +50 Slope From X Axis Ibias Equation Unrestrained Pickup 10 pu Slope Ibias(pu) Gradient (%) 1 0 30 2 2.5 60 ms Harmonic Tolerance 15 % Harmonic Ramp Mode Ramp To Operate Nth Harmonic Content 30 % 5th Nominal Current Protected Object kV 750 *A vertical offset is created between slopes when two equivalent restraint values are entered. The Gradient % of the first equivalent point will be the value of the vertical offset in per unit. 231 MVA :1 A kV 2,400 824.786 A 0 :1 A 1,874.51 A YY0 0.275 A Single Phase Pickup Factor Sat Nov 20 10:52:06 2021 % % 0.781 A Interposing CTs 1.50 1.50 Single Phase Pickup Factor Stabilization Test Phase A-N B-N C-A Injected Currents W1 Sat Nov 20 11:03:23 2021 Currents Observed From Relay W2 W1 I (A) ϕ (°) I (A) ϕ (°) 0.275 0 0.781 180 824.78 0 1,874.5 180 0.275 240 0.781 60 824.78 240 1,874.5 60 0.275 120 0.781 300 824.78 120 1,874.5 300 W2 ϕ (°) Idiff I (A) ϕ (°) Ibias I (A) 823.00 0 1,870.0 180 2.02 0 829.00 240 1,870.0 60 1.98 0 823.00 120 1,870.0 300 2.02 0.01 Timing Test TEST EQUIPMENT USED: FREJA546 (SN201906070004) COPYRIGHT © 2002-2021 POWERDB, INC. Sat Nov 20 11:13:09 2021 TESTED BY: www.powerdb.com Form Schema 0 Relay Test Report 11/20/2021 PAGE 2 Phase Tested Fault Current (% Ib) Expected Trip Time (s) Maximum Trip Time (s) Measured Trip Time (s) P/F A-N 100.0 0.020 0.072 0.029 P B-N 100.0 0.020 0.072 0.032 P C-N 100.0 0.020 0.072 0.028 P ABC 100.0 0.020 0.072 0.029 P Pickup Test Sat Nov 20 13:16:25 2021 Winding 1 Phase Winding 2 Pickup Setting (pu) Pickup (pu) Pickup (A) Error (%) P/F Pickup Setting (pu) Pickup (pu) Pickup (A) Error (%) P/F A-N 0.20 0.198 0.082 -1.0 P 0.20 0.192 0.225 -4.0 P B-N 0.20 0.196 0.081 -2.0 P 0.20 0.192 0.225 -4.0 P C-N 0.20 0.192 0.079 -4.0 P 0.20 0.194 0.227 -3.0 P ABC 0.20 0.198 0.054 -1.0 P 0.20 0.194 0.152 -3.0 P # Ibias (pu) Idiff (pu) W1 (A) W2 (A) Error (%) P/F 1 1.30 0.39 0.23 0.36 -1.0 P 2 1.90 0.57 0.34 0.52 -0.0 P 3 2.30 0.69 0.41 0.63 0.0 P 4 3.20 0.96 0.57 0.87 -0.0 P 5 3.70 1.10 0.66 1.02 -1.0 P 6 4.20 1.26 0.75 1.15 -0.3 P 7 0.40 0.19 0.08 0.08 -5.0 P 8 6.50 2.40 1.22 1.60 -0.0 P 9 7.40 2.91 1.42 1.75 -1.0 P COPYRIGHT © 2002-2021 POWERDB, INC. Characteristic Test Sat Nov 20 12:20:24 2021 Characteristic Shot Test Sat Nov 20 12:23:47 2021 www.powerdb.com Form Schema 0 Relay Test Report 11/20/2021 PAGE 3 # Ibias (pu) Idiff (pu) W1 (A) W2 (A) P/F 1 3.10 1.30 0.60 0.70 P ... 2 4.40 1.20 0.77 1.25 P ... 3 5.90 2.40 1.14 1.37 P ... 4 6.20 2.00 1.13 1.64 P ... 5 6.90 3.10 1.37 1.48 P ... 6 7.50 2.80 1.42 1.84 P ... 7 2.20 0.50 0.37 0.66 P ... 8 1.50 0.70 0.30 0.31 P ... Winding 1 Winding 2 Phase 2nd Harmonic Pickup = 0.150A , Tolerance = 15%Block Test Funda2nd 2nd mental Harmonic Harmonic I (A) I (A) I (%) Error (%) P/F Sat Nov 20 12:37:23 2021 Pickup = 0.150A , Tolerance = 15% Funda2nd 2nd P/F Error mental Harmonic Harmonic (%) I (A) I (A) I (%) A-N 1.00 0.132 13.250 -11.7 P 1.00 0.140 14.050 -6.3 P B-N 1.00 0.133 13.350 -11.0 P 1.00 0.139 13.950 -7.0 P C-N 1.00 0.133 13.350 -11.0 P 1.00 0.141 14.150 -5.7 P ABC 1.00 0.131 13.150 -12.3 P 1.00 0.132 13.250 -11.7 P Nth Harmonic Shot Test Phase Winding 1 Winding 2 Fundamental Current = 1.000A Fundamental Current = 1.000A 5th 5th Harmonic Harmonic Operate I (A) I (%) 5th 5th No Harmonic Harmonic Operate I (A) I (%) 5th 5th Harmonic Harmonic Operate I (A) I (%) 5th 5th No Harmonic Harmonic Operate I (A) I (%) A-N 0.250 25.00 P 0.350 35.00 P 0.250 25.00 P 0.350 35.00 P B-N 0.250 25.00 P 0.350 35.00 P 0.250 25.00 P 0.350 35.00 P C-N 0.250 25.00 P 0.350 35.00 P 0.250 25.00 P 0.350 35.00 P ABC 0.250 25.00 P 0.350 35.00 P 0.250 25.00 P 0.350 35.00 P Harmonic Content for No Operation: COPYRIGHT © 2002-2021 POWERDB, INC. 35 % www.powerdb.com Harmonic Content for Operation: 25 % Form Schema 0