DC Load Flow Prof Dr. Ashik Ahmed Islamic University of Technology Department of EEE Introduction • Load flow analysis helps in finding the steady state operating point of a large power system under normal operating condition having many generators, transformers, transmission lines, shunt elements, and loads. • Normal operating condition implies that, Vi ,min Vi Vi ,max Pgi ,min Pgi Pgi ,max Sij ,line Sij ,line ,max • The steady state operating point implies, the knowledge of Pg , slack , Qg , slack , Qg , PV , PV , VPQ , PQ Ploss , Pline , Qloss , Qline Introduction • AC Load flow analysis is accurate but requires the solution of nonlinear set of equations. • No analytical solution is possible, requiring adoption of iterative algorithms: Gauss-Siedel, Newton-Raphson, Fast-decoupled, Backwardforward sweep, etc. • Being iterative, the time required for AC load flow solution is comparatively larger. • When quick and approximate information regarding the network variables (voltage, current, power flow, power loss) are of interest, DC load flow is the best way to adopt. AC Load Flow: Revisit Power Injected at bus i: Pi Pgi Pdi Qi Qgi Qdi Current Injected at bus i in terms of complex power: I i Pi jQi Pi jQi e j i * Vi Injected current and bus voltage relation: I bus n bus x1 Vi Ybus n Vbus n bus x nbus bus x1 nbus nbus j 1 j 1 Current Injected at bus i in terms of bus admittance: I i YijV j Yij ij V j j Yij Gij2 Bij2 * Complex power injected at bus i: nbus nbus * Si Vi I i Vi Yij ij V j j Vi i Yij ij V j j j 1 j 1 nbus Vi V j Yij (i j ij ) j 1 AC Load Flow: Revisit nbus Real power injected at bus i: Pi real ( Si ) Vi V j Yij cos(i j ij ) Pgi Pdi j 1 nbus Reactive power injected at bus i: Qi imag ( Si ) Vi V j Yij sin(i j ij ) Qgi Qdi j 1 • The above two equations are nonlinear in nature • Analytical solution is not possible • Numerical techniques are adopted to solve the unknowns AC Load Flow: Revisit Line Power Flow expressions: Sij Vi I ij* V V j Vi i jx ij * Vi i V j j Vi i jx ij Vi 2 Vi V j (i j ) j xij Vi 2 Vi V j cos(i j ) j Vi V j sin(i j ) Pij jQij j xij Pij Vi V j sin(i j ) xij Vi Vi V j cos(i j ) 2 ; Qij xij Assumption for DC load flow • Line resistances are small compared to the line reactances zij rij jxij jxij ; ij 900 • Bus voltage magnitudes are approximated to 1.0 p.u. Vi 1.0 p.u • Deviation of bus voltage angles between the connected buses are very small i j is very small. cos i j 1 ; sin i j i j • Shunt admittances are neglected • Transformer tap settings are neglected DC load flow Expressions nbus • Simplified Pi expression: Pi Bij (i j ) j 1 nbus j 1, j i Bij (i j ) (1) nbus • Simplified Qi expression: Qi Bij (2) j 1 • Simplified Pij expression: Pij (i j ) xij • Simplified Qij expression: Qij 0 (3) (4) So, the unknowns for DC load flow problem are the bus voltage angles. There are no reactive power flowing through the lines. DC load flow: Observations • For an Nbus system, the bus voltage angle of the swing bus is known beforehand. • Thus, the no. of unknowns for the DC load flow becomes Nbus – 1. • Once the remaining bus voltage angles are known, real power injections at the buses and real power flows through the lines can be calculated using equations Eq. (1) and Eq. (3), respectively. • As the line resistances are neglected, there will be no line losses in a DC load flow solution. • Eq. (1) and Eq. (3) depicts the linear nature of DC load flow. DC load flow: 3-bus system • For a 3-bus system, Eq. (1) can be expressed as: P1 B12 1 2 B13 1 3 B12 B13 1 B12 2 B133 P2 B21 2 1 B23 2 3 Ybus B21 B23 2 B211 B233 B 11 B 12 j[ B] j B 21 B 22 B 31 B 32 P3 B31 3 1 B32 3 2 B31 B32 3 B311 B32 2 • In Matrix form: P1 B12 B13 P B 21 2 P3 B31 B12 B21 B23 B32 B13 1 B23 2 B31 B32 3 (5) B 13 B 23 B 33 DC load flow: 3-bus system • Considering bus 1 as the swing bus, 𝜃1 = 0. • So, for a 3-bus system, the only unknowns are 𝜃2 and 𝜃3 . • Hence, writing Eq. (5) in terms of unknown angles: • So, P2 B21 B23 P B 32 3 2 B21 B23 B 32 3 B23 2 B31 B32 3 1 B23 P2 B31 B32 P3 P ( N bus / B 1) X 1 ( N 1) X 1 B / bus ( N bus 1) X ( N bus 1) 1 ( Nbus 1) X ( Nbus 1) ( N bus 1) X 1 P ( N bus 1) X 1 • It is to be noted that, P1 is still unknown, but can be obtained once P12 and P13 are calculated. (1 3 ) (1 2 ) P12 ; P13 x12 x13 P1 P12 P13 DC load flow: 3-bus system • The line flows can be expressed in Matrix form as: 0 0 1 1 0 1 P12 1/ x12 P 0 0 1 1 1/ x 0 23 23 2 P13 0 0 1/ x13 1 0 1 3 Pline bline A p.u. Pline MVAbase bline A MW 2 1 3 DC load flow: 3-bus system Example • Bus data Bus No. Bus Type PD (MW) QD (MVAr) PG (MW) 1 Slack 0 0 Unknown 2 PV 10 5 63 3 PQ 90 30 0 2 1 • Line Data 3 Line No. From Bus To Bus X (p.u.) Rating (MVA) 1 1 2 0.0576 250 2 2 3 0.092 250 3 1 3 0.17 150 Base Apparent Power = 100 MVA DC load flow: 3-bus system Example • Bus Admittance Matrix Entries (all in p.u.) Y11 y12 y13 1 1 j17.3611 j 5.8824 j 23.2435 jx12 jx13 Y12 Y21 y12 j17.3611 Y13 Y31 y13 j 5.8824 Y22 y21 y23 1 1 j17.3611 j10.8696 j 28.2307 jx21 jx23 Y23 Y32 y23 j10.8696 Y33 y31 y32 1 1 j 5.8824 j10.8696 j16.7520 jx31 jx32 DC load flow: 3-bus system Example Ybus j 5.8824 j 23.2435 j17.3611 j17.3611 j 28.2307 j10.8696 j 5.8824 j10.8696 j16.7520 B12 B21 17.3611; B13 B31 5.8824; B23 B32 10.8696; 28.2307 10.8696 B / 10.8696 16.7520 1 2 28.2307 10.8696 (63 10) /100 0.0025 10.8696 16.7520 (0 90) /100 0.0554 rad 3 DC load flow: 3-bus system Example 0 0 1 1 0 0 4.3403 P12 17.3611 P 100 0 0 1 1 0.0025 57.5002 MW 10.8696 0 23 P13 0 0 5.8824 1 0 1 0.0554 32.5885 Pg1 P12 P13 4.3403 32.5885 36.9288 MW Total Generation Pg1 Pg 2 63 36.9288 99.9288 MW Total demand Pd 2 Pd 3 10 90 100 MW