SS-701~1

advertisement
500 Series
560 Surge Protective Device
Submittal Specification
General Specifications
Maximum Continuous Operating Voltage
Short Circuit Current Rating (SCCR)
Operating Frequency Range
EMI/RFI Noise Rejection
Location Type
Nominal Discharge Current (In)
Standard Status Indication
120VAC 125%, all others 115%
200kAIC
47-63Hz
63dB Max
Type 1 / Type 2
20kA
LEDs, Relay Alarm Contacts, Built-in-Test
ANSI/UL 1449 Third Edition
UL 1283, cUL (Type 2 locations)
NEMA 4
10 Years Parts, 5 Years Labor
Certifications
Standard Enclosure
Warranty
Life Cycle Surge Testing (10kA, 20kV, IEEE Cat. C3)
Surge Rating
08-12
16-25
37
Per Mode
15,000
30,000
45,000
Per Phase
30,000
60,000
90,000
Model Number Configurator
UL 1449 Third Edition, Type 1 VPRs
Source
Configuration
YA
YC
DF
_5 _6 _0 _ _ _ _ _A _ _ _G _1 _S
SA
Configuration & Voltage
Single Split
120/240 VAC
Phase, 3W+G
120/208 VAC
YA
YC
Three Phase
WYE, 4W+G
Three Phase
WYE, 4W+G
DB
DF
Three Phase
Delta, 3W+G
Three Phase
Delta, 3W+G
Surge Rating
120/208 VAC
127/220VAC
277/480 VAC
254/440 VAC
240 VAC
480 VAC
Connection Type
N
Available on 80kA-200kA (“08”-“20”)
R
Available on 80kA-375kA (“08”-“37”)
08
80kA Per Mode
160kA Per Phase
12
125kA Per Mode
250kA Per Phase
16
160kA Per Mode
320kA Per Phase
20
200kA Per Mode
400kA Per Phase
25
250kA Per Mode
500kA Per Phase
37
Wire Compression Lugs
375kA Per Mode
750kA Per Phase
Rotary Disconnect Switch
Wire Lug
(N)
08-12
Disconnect
(R)
Wire Lug
(N)
16-25
Disconnect
(R)
Wire Lug
(N)
37
Disconnect
(R)
AxB
D
S
Standard
X
Consult Factory for additional
source configurations, Surge
Ratings, Monitoring Options,
Enclosure Ratings, Etc.
Monitoring Option
Available on 80kA-160kA (“08”-“16”)
A
Red & Green LED’s, Audible Alarm, Alarm
Enable & Disable feature, 2 sets of Relay
Alarm Contacts, Built-in-Test
C
Available on 80kA-160kA (“08”-“16”)
D
Available on 200kA-375kA (“20”-“37”)
T
C
L-G
L-L
N-G
700
1200
1800
1000
1800
1800
700
1000
Remote Monitoring Panel Option
constructed with the monitoring system on a
remote panel - Perfect for custom installations.
Additional Accessories
“A” option plus Surge Counter
“A” option plus Dual Surge Counter
Harness Length
Model Accessory
6 Feet
“X27”
10 Feet
“X57”
20 Feet
“X59”
Example Model #: 560YC20ARTG1X59
CUL Approvals
For all applications requiring CUL approvals,
change the SPD model number from a UL
Type 1 (560xxxxxxxx1x) to a UL Type 2
(560xxxxxxxx2x)
Available Option for ALL units
Advanced Transient Detection System
See publication SL-70109, TS-70109
0.44”
0.44”
[11.1]
Dimensional Information
Surge Connection
Rating
Type
L-N
700
1000
Advanced Transient
Detection System
A Web-Based Power Quality Monitor
Integrated within a Surge Protection Device
Wt




Real-Time Measurements
Event Logging with Time/Date Stamp
Embedded Web Page
Ethernet, MODBUS, RS-485
Communications
 SPD Health Status - % Protection remaining
 LCD Display
16” x 12” 17.25” 9.5” 35 lb.
(406 x 305) (438) (241) (15.9 kg)
16” x 16” 17.25” 10”
45 lb.
(406 x 406) (438) (254) (20.4 kg)
AC
C
A
20” x 16” 21.25” 10”
55 lb.
(508 x 406) (540) (254) (24.9 kg)
20” x 20” 21.25” 14”
85 lb.
(508 x 508) (540) (356) (38.6 kg)
100 Emerson Parkway
Binghamton, NY 13905
P (607) 721 8840
P (800) 288 6169
F (607) 722 8713
E contactsurge@emerson.com
D
D
B
B
*9.0”
9.0”
[229]
(229)
* Enclosure depth changes to 10.0” [254] when the “Advanced
Transient Detection System” monitoring option is selected.
SS-70101 Rev 2 1-15
Download