What is hydraulic surge or water hammer? How it develops, its impact all these information is covered in this
post as Basics of Hydraulic Surge or Water Hammer.
Introduction
Inertia is the tendency of matter to remain in its existing state of motion, unless acted upon by outside forces.
More energy is required to change steady state motion than to maintain it.
Thus, more energy is expended to increase or decrease flowing velocity in a pipeline than is necessary to
maintain the liquid’s steady state motion. One measure of the energy used to change liquid motion is pressure.
If velocity is changed quickly by the application of much energy in a short period of time, the pressure change
will be more significant than when the same amount of energy is expended over a long time period. Thus, the
energy applied to change pressure by 100 psi in one second is the same amount of energy as that applied for
10 seconds to change pressure by 100psi.
What is hydraulic surge or water hammer?
Any change from steady state conditions creates a temporary variation in pressure or flow called hydraulic /
pressure transients. Or in other words they occur when the flow of fluid in a pipeline is abruptly changed.
Hydraulic transients are commonly called hydraulic surge, hydraulic shock, or water hammer.
Hydraulic Shock Valve Closing Pressure surges are produced by unsteady flow resulting from either
acceleration or deceleration of a liquid. Every flowing fluid accumulates kinetic energy (velocity head), the
strength of which is determined by the weight of the fluid and the speed with which it is moving. If the speed of
this fluid is changed, i.e., suddenly slowed or stopped, the kinetic energy is transformed into pressure energy
and causes the normal system pressure to increase.
This unsteady state phenomenon deals with the change between kinetic energy and pressure energy, which
may be positive or negative. If the pressure induced exceeds the pressure rating of a pipe given by the
manufacturer, the pipe may rupture. Detrimental consequence may result unless a pressure protection device
is installed. The hydraulic engineer, water supply designer and pumping system operator have the responsibility
to ensure the surges due to water hammer are within acceptable limits and can be dampened as quickly as
possible. These conditions can result in piping failure, damage to pumps, fittings, instrumentation and other
system components.
These hydraulic/ pressure transients, or surges, can be created in piping systems due to the following
reasons.
Sudden opening or closing of valves in a pipeline (quick acting valves)
Rapid starting or stopping of the pumps in a pumping system
Sudden increases in the inflow to a river or a sewer due to flash storm runoff
Operating errors or malfunctioning of equipment.
Their magnitude is a function of the
Change in flowing velocity;
Liquid density;
Sound speed in the liquid and piping system.
These hydraulic transients may range in importance from a slight pressure and/or velocity change, to
sufficiently high vacuum or pressure to collapse or burst pipes and fittings or damage pumps.
Surge (often called Water hammer) causes many of the problems experienced in liquid systems: high and low
pressures; severe pipe loads; unwanted trips and shutdowns; pipe movement and vibration; bursting disc
rupture; and equipment damage.
When a fluid is flowing with a constant velocity through a pipe and a downstream valve is closed, the following
sequence of events takes place:
The water adjacent to the valve is stopped; the momentum in the fluid is converted to a pressure head,
which compresses the fluid and expands the pipe walls.
The flow of adjacent particles within the water is successively brought to rest, transforming momentum into
pressure energy.
When the water is compressed due to the sudden stop., the pressure wave travels upstream to the end of
the pipe at wave velocity – “A”. If the pipe length is “L”, then after L÷A seconds the wave will be at the
upstream end. The pressure wave, after reaching the upstream end (i.e. valve, etc.) of the pipe, is reversed
and returns to the downstream valve at 2L÷A seconds after valve closure.
During this time, the fluid pressure and the pipe stress will be greater than normal. If the fluid were ideal,
there would be no resistance to flow and surges would continue to repeat indefinitely. With friction and pipe
elasticity, the pressure amplitudes diminish gradually until original momentum is absorbed.
The explanation of water hammer in the previous paragraphs assumes instantaneous closure. But valves
require a finite time to close. If closure takes place in a time less than 2L÷A, then it is termed “critical” (TC)
and the incremental pressure rise is shown in the table. The table shows the increase in water pressure of a
system for each one foot per second flow rate and each 100 feet of PVC pipe. For other “Run” lengths and
“Velocities” multiply “Peak Pressure Surge” accordingly.
V
= Velocity Change, (Feet/Second) =
1
L
= Pipe Run Length, Ft.
=
100
W =
Fluid Density, #/Ft.3
=
62.4 (Water)
K
Modulus Of Fluid, Psi.
=
300,000 (Water)
Dr =
Dimension Ratio (In./In.)
=
Pipe O.D.÷ Wall Thickness
Tc =
Critical Valve Close Time (Sec.) =
(2 X L)÷A
P
=
Pressure Change (Psi) (Peak)
=
(W X A X V)÷4,636.6, (Adds To Flow Press.)
A
=
Wave Velocity (Feet/Second)
=
4,660÷[1+{K X (-2+Dr)÷E}]½
E
=
Modulus Of Material Psi.
=
400,000 ( Pvc)
=
Dimension
(DR)
Rated Pressure
(A) Wave Velocity
Ratio
(Tc) Critical
(P) Peak
Close Time
Surge
Pressure
All Sizes
13.5
315
1,502
0.13
20.21
All Sizes
17
250
1,331
0.15
17.92
All Sizes
21
200
1,193
0.17
16.06
All Sizes
26
160
1,069
0.19
14.39
All Sizes
32.5
125
954
0.21
12.84
½
7.7
600
2,029
0.10
27.31
¾
9.3
480
1,831
0.11
24.65
1
9.9
450
1,771
0.11
23.83
1¼
11.9
370
1,605
0.12
21.61
1½
13.1
330
1,526
0.13
20.54
2
15.4
280
1,402
0.14
18.87
2½
14.2
300
1,463
0.14
19.69
3
16.2
260
1,365
0.15
18.37
4
19
220
1,257
0.16
16.91
5
21.6
190
1,176
0.17
15.83
6
23.7
180
1,121
0.18
15.09
8
26.8
160
1,053
0.19
14.17
½
5.7
850
2,398
0.08
32.28
¾
6.8
690
2,173
0.09
29.24
1
7.4
630
2,074
0.10
27.91
1¼
8.7
520
1,898
0.11
25.55
1½
9.5
470
1,810
0.11
24.37
2
10.9
400
1,682
0.12
22.64
2½
10.4
420
1,725
0.12
23.21
3
11.7
370
1,620
0.12
21.8
4
13.4
320
1,508
0.13
20.29
5
14.8
290
1,431
0.14
19.26
6
15.3
280
1,407
0.14
18.93
8
17.3
250
1,319
0.15
17.76
Schedule 40 pipe
Schedule 80 pipe
Peak surge pressure (P) is directly proportional to the velocity changes (V). P tabled above is per foot/sec.
Velocity change.
Critical valve close time (TC) is directly proportional to the pipe run length (L). TC tabled above is per 100 ft.
Of run length.
If actual valve close time (TA) is less than the critical time (TC), then the peak surge is as shown, but if TA is
greater than TC, then the approximate pressure surge is (PA) = (0.027 x L x V)÷TA (psi).
Air slugs in a system can create surge velocities far in excess of the system design flow rate. Abrupt flow
changes and high flow rates can compound to create very high hydraulic pressure shocks.
Study of Hydraulic Transients
The study of hydraulic transient began with the investigation of sound wave propagation in air, followed by
theories derived by Joukowski (1900; a Russian scientist) and Allievi (1903; a French researcher). In 1897,
Joukowski conducted extensive experiments in Moscow on pipes with diameters ranging from 50mm to
150mm and lengths from 350m to 7620m. He developed a formula for the surge wave velocity, the rise of
pressure and velocity reduction. He also discussed the effect of various closing rates (gradual or
instantaneous) of a valve.
Joukowski’s Law: water hammer head H at instantaneous valve closure in a rigid pipe
Maximum
(1)
where
vo = flow velocity before valve closure
c = wave celerity or velocity of sound in liquid
If the pressure in a closed conduit drops below the vapour pressure of a liquid, then cavities (where the water
column is separated by an air space) are formed. This phenomenon is called water column separation.. This is
the worst condition for water hammer, and may result in the pipeline not being able to withstand the external
forces and hence collapse. This can be a problem for large diameter thin walled pipes and plastic pipes with
low pressure rating or carrying hot liquids. The rejoining of separated water columns can produced high
pressures putting the pipeline at risk. The frequent expansion and contraction may cause failure of cement
lining in metal pipes.
For acceleration and deceleration of an incompressible liquid in a pipe, a head loss term due to unsteady
motion of changing velocity “dv” in time “dt”
(2)
is included in the Bernoulli equation
(3)
Pressure Waves Due To Instantaneous Velocity
Change
Wave propagation and reflection in a single rigid pipe
In Physics we learned that the frequency (f) of a sound wave in an pipe with one end closed is f = l/c = 4L/c,
where L is the length of the pipe, l is wavelength, and c is the velocity of sound wave in a liquid. If the closure
time t <= 2L/c, it is called sudden or instantaneous closure; and gradual closure if t 4L/c.
Let’s now consider the fluctuations of the excess pressures caused by an instantaneous closure of a valve
located at the downstream end of a pipe. If the frictional loss along the pipe is neglected, the sudden change in
fluid velocity from v = vo to v = 0 at the valve generates a surge wave propagating upstream, accompanying by
a positive excess pressure head D H. The surge wave eventually reflects from the reservoir and advancing
downstream. On reaching at the closed valve, it then propagates upstream with a negative surge wave, and so
on. The fluctuations in pressure head D H throughout the first cycle are depicted in the following sketches. In
reality, the magnitude of the excess pressure dampens due to friction.
The increase in water head is
(4)
and celerity of water hammer waves in a compressible fluid in a rigid pipe is given by
where the bulk modulus of elasticity K is defined as
(5)
Celerity of transient in a non-rigid pipe
In addition to the bulk modulus of elasticity K of the fluid, the velocity of water hammer waves depends also on
the elastic properties of the conduit and external restraints.
Neglecting the presence of free gases, Halliwell (1963) provided a general expression:
(6)
where
E = Young’s modulus of elasticity of the conduit walls
y = a non-dimensional parameter depends on the elastic properties of the conduit
which is a function of (e, wall thickness; D, conduit diameter and Poisson ratio n)
Rigid conduits y = 0 (7)
Thin-walled elastic conduits
1. conduit anchored against longitudinal movement throughout its length
2. conduit anchored against longitudinal movement at the upper end
(8.a)
(8.b)
3. conduit with frequent expansion joints (8.c)
Polyvinyl Chloride (PVC) and reinforced plastic pipe
Equation (6) can be used provided proper values of K and E are used.
Thick-walled elastic conduits
Non-circular conduits
Tunnels through solid rock
Some common values of E, n, K:
Material
E (GPa)
Poisson’s v
K (GPa)
Density (kg/m3)
Brass
78-110
0.36
Mild steel
200-212
0.27
– Perspex
6.0
0.33
– Polyethylene
0.8
0.46
– PVC rigid
2.4-2.75
Water, fresh
2.19
999 (20C)
Water, sea
2.27
1025 (15C)
Plastic
Partial valve closure
If the response of water hammer is linearly elastic, when a valve is partially closed which reduces the velocity
by “dv” from vo, then from equation (4)
(9)
and it can be shown that
(10)
where
Ho = pressure head at valve with the valve fully open
Ao = normal valve orifice area when fully open
A = valve orifice area after partial closure
If partial closure is sudden or instantaneous, Delta H in equation (10) is given by equation (9); if gradual, Delta
H is given by equation (2), ie. Delta H = (L/g) (dv/dt).
When the valve is closed stepwise in time T and the rate of valve closure dA/dt is uniform, then A/Ao = 1 – dt/T
(11)
From equations (10) and (11),
(12)
In equation (12), “dt” is the time in which the pipe velocity is reduced by “dv” and “dt/T” may be taken as a
conveniently small fraction (Smith 1960).
Example of partial valve closure
<Q A valve at the end of a pipeline of length L = 750 m is closed in 10 equal steps each of 2L/c seconds where
c = 1200 m/s. The initial head at the valve is 120 m and initial flow velocity is 3.5 m/s. Determine the pressure
head at the valve after 1.25 and 2.5 seconds and compare with the result for a sudden closure.
<A From equations (9) for Delta H and (12), Delta v can be calculated,
where each step Delta t = 2L/c = 2 x 750/1200 = 1.25 sec; Ho = 120 m, vo = 3.5 m/s
1) after t = 1 Delta t = 1.25 s
Therefore Delta v = 0.137 m/s
and H (at t = 1.25 s) = Ho + Delta H = 120 + (1200/9.81) x 0.137 = 136.76 m
2) after t = 2 Delta t = 2.5 s
new vo = 3.5 – 0.137 = 3.363 m/s, new Ho = 136.76 m; entering equation
(15)
Therefore Delta v = 0.316 m/s
and H (at t = 2.5 s) = Ho + Delta H = 136.6 + (1200/9.81) x 0.316 = 175.4 m
and so on with new t = 3Delta t, … 10Delta t
However, if the valve is closed suddenly, then Delta H = (c/g) vo = 428 m theoretically.
 Tagged
Basics of hydraulic surge
Basics of water hammer
Basics of hydraulic surge or water hammer
hydraulic surge
 Introduction to Pipi…
hydraulic surge or water hammer
Water hammer
Surge Arrestors 
RELATED POSTS
Dual Plate Check Valve
 November 3, 2019
 Admin
Hydrostatic Testing Of Piping Or Pipelines
 January 2, 2020
 Admin
Introduction To Plot Plan
 December 31, 2019
 Admin
Search …
RECENT POSTS
 Common Welding Defects
 Topographical Survey
 NPSH (Net Positive Suction Head)
 Oil Production – Oil and Gas Facilities
Search
 Material Basics – Monel
 Introduction to Intrinsically Safe Systems
 Corrosion Problems Associated with Stainless Steel
 Material Basics – Stainless Steel
 Zeron 100 – Alternative Material for Severe Conditions
 Surge Arrestors
JOBS

JOB Dashboard

Job Submission

Job Listing
CATEGORIES
Select Category
RECENT QUESTIONS
Will there be a totally free app for dinner planning? 0 Answers | 0 Votes
What is IBR and which lines need IBR review? 1 Answer | 0 Votes
Why Drip Leg is required in Steam Line? 1 Answer | 0 Votes
What is the objective of stress analysis ? 1 Answer | 0 Votes
What do you mean by Stress Intensity Factor (SIF)? 1 Answer | 0 Votes
ARCHIVES
Select Month
RECENT COMMENTS
 Admin on What are FBE coating limitations?
 Admin on What is FBE coating thickness?
 Raj on What is SPE and DPE and its Directions?
 Sachin Patil on Design and Engineering
 Dinesh on Design and Engineering
SUBSCRIBE TO BLOG VIA EMAIL
Enter your email address to subscribe to this blog and receive notifications of new posts by email.
Email Address
Subscribe
Join 185 other subscribers
CATEGORIES
Select Category
SUBSCRIBE VIA EMAIL
Email Address
Subscribe
JOBS

JOB Dashboard

Job Submission

Job Listing
PRIVACY POLICY
© COPYRIGHT :
© This Page is copyrighted. Do not copy paste. Unauthorized use and/or duplication of this material without
express and written permission from this site’s author and/or owner is strictly prohibited. Excerpts and links
may be used, provided that full and clear credit is given to the ©designandengg.com
© designandengg.com 2020 | Theme: HamroClass by Themecentury.
Home
About
Questions
Ask a question
Job Submission
JOB Dashboard
Contact
Download