Sabre Ring Main Unit Sabre catalogue Table of contents Introduction to Lucy Electric Product panorama Introduction to Sabre Installation and operating conditions Safety features Application example Standards The Sabre range Non extensible range Extensible range Mounting style Product characteristics i. Product presentation ii. User interface and interlocking mechanism iii. Ring switch iv. Vacuum circuit breaker v. Circuit breaker protection a. TLF b. Protection relays vi. Protection CTs for TLF and relays vii. Bushings Options and accessories i. Secondary injection ii. Actuators (motors) iii. Cable boxes, glands and accessories iv. Bus bar couplings v. MV sensors vi. Watchdog for relays vii. Operation counter viii. Castell locks ix. Protection trip remote indicator x. Shunt trip coils xi. Earth fault indicators (EFI) Cable terminations Remote terminal unit (RTU) Smart grid ready Technical data sheet Dimensions Models, options and accessories Sabre models and options order form Air metering unit (AMU) i. Characteristics ii. Mounting style iii. Dimensions iv. Options and Accessories Air metering unit (AMU) order form Sabre accessories order form Page 2 3 4 5 6 6 9 9 10 10 12 17 19 19 20 21 21 22 22 24 27 27 28 28 28 29 30 30 30 30 30 30 31 31 32 33 34 35 37 47 53 57 57 57 58 60 66 68 Introduction to Lucy Electric Lucy Electric is a global leader in switching, protection and automation solutions for electrical distribution systems with over 100 years’ industry experience. From its modest beginnings in street lighting, the company today is a specialist in secondary power distribution, engineering highperformance medium voltage switchgear for utility, industrial and commercial applications with a broad product portfolio that includes overhead line equipment and retrofit and automation solutions. the capability to manufacture equipment to suit almost any location, climate or situation, Lucy Electric can also offer maintenance packages and dedicated after sales support throughout the product lifecycle. A specialist UK based research and development facility ensures that Lucy Electric’s products are always at the cutting edge of technology enabling rapid response to evolving technical and market demands of customers. All of our purpose built, state of the art manufacturing facilities espouse the latest international Quality and Environmental standards. The global profile of Lucy Electric is emphasised through manufacturing facilities in the United Arab Emirates, Saudi Arabia and India, offices in Dubai, Malaysia and South Engineering excellence coupled with state of the art technology make Lucy Electric one of the few companies that can offer truly bespoke solutions. With Africa and an established global network of industrial partners and contractors operating in over 50 countries worldwide. Ring main unit range evolution TRIDENT SCIMITAR SABRE AEGIS 1965 1970 1975 1980 1985 1990 1995 2000 2005 2010 2015 Page 3 Product panorama Lucy Electric medium voltage and high voltage range Range name Type Rated voltage (up to) Trident Scimitar Sabre Aegis Rapier GX Ring main unit Rapier AX Rapier DSB Switch disconnector 15.5kV 17.5kV24kV24kV38kV36kV145kV Mode of fault current Fuse Fuse Vacuum Vacuum--interruption Insulation medium Oil SF6 Air Air Rated current 630A 800A 2500A (up to) Mounting Ground / Transformer Ground Installation Pole Indoor / Outdoor Outdoor Operation Local / Remote Page 4 Pole Structure Introduction to Sabre Sabre ring main units are designed for secondary distribution networks up to 24kV. The range is an ideal solution for indoor/outdoor compact substations and is available in non-extensible, extensible and modular formats to suit various application requirements. All of the switching functions are insulated with SF6 gas and sealed in a stainless steel tank with a leakage rate of less than 0.1% per year. The structural tank welding is performed by a robotic welding process ensuring high reliability with a product life expectancy of more than 30 years. The housing is fully treated using zinc coated steel and electrostatically applied oven cured paint to resist degradation from pollution and harsh climatic conditions. The transformer protection is by vacuum circuit breaker. On request, the units can be supplied with integrated automation for remote monitoring and control functions. Characteristics: • Anti-reflex mechanism to prevent load break switch opening under fault conditions • Fully interlocked operation with padlocking facility for maximum operator protection • Freestanding and transformer mounted units • Integrated earth and test facility for easy and safe cable test without removing cable connections Actuators (motorised) for ring switches and circuit breakers • Choice of TLF (time limit fuses) or self/auxiliary powered relay protection Seamless integration with SCADA network for remote operation and control • Maintenance free with 30 years life expectancy • Up to 24kV and 630Amps ratings • Non extensible, extensible and modular range • Switching functions enclosed in a SF6 gas insulated steel tank, sealed for life • Intuitive single line mimic diagram for simple and safe operation • • Page 5 Installation and operating conditions • IP54 outdoor installation (kiosk not necessary) • Ambient temperature for operation: -25°C to 60°C • Average temperature over 24 hours: 40°C • Maximum altitude for operation without derating:1000m • Insulation medium: SF6 Gas • Interruption medium: Vacuum Safety features Operation mechanism The operating mechanism of the ring switches and circuit breaker incorporates mechanical interlocks and padlocking facilities which make it impossible to simultaneously close the ring switch/circuit breaker and the earth switch. Anti-reflex mechanism Anti-reflex mechanisms on ring switches ensure a time delay between switching operations. Internal arc withstand Sabre gas tanks are fully internal arc rated and this feature is also available on the cable boxes (optional) to ensure maximum operator safety in the event of internal faults. The gas tanks are available in AF (front), AFL (front and lateral) and AFLR (front, lateral and rear) ratings. For more details on internal arc classification (IAC) ratings, please refer to the technical data sheet. Page 6 Cable earth and test facility (E&T) E&T feature is used for testing cable insulation and to locate faults in the circuit without the need to remove the main cables from the cable box. Ring switches: E&T is a standard feature located at the bottom of the unit. The cable test access cover is fully interlocked and cannot be opened until the ring switch or circuit breaker switch is in the Earth ON position. The test bushings are earthed with a star bar which has to be removed for cable tests. Vacuum circuit breakers: E&T is an optional feature only on 630A VCB and is located at the top of the unit Cable boxes The cable boxes are located laterally or at the rear of the ring main unit. Factory mounted protection CTs are provided on the circuit breaker cable bushings for ease of installation and to avoid any potential damage to the CT during transit and connection. For additional operator safety, the cable boxes are earthed and can be interlocked to allow access to the operator only if the function is in the Earth ON position. There is an option to supply these cable boxes with internal arc rating as per IEC standards (for further information, please refer to the cable box, gland and accessories section). Page 7 Safety features VPIS VPIS (Voltage Presence Indication System) is an optional feature in the Sabre range. The VPIS receives a voltage signal through the voltage divider built into the cable bushings. They can also be fitted with neon lights and momentary latching push buttons to show voltage presence without needing external testing probes. Two types of voltage presence indication devices are offered: • Pfisterer sockets • Neon indicators with push-to-test buttons and phase comparator sockets Pfisterer sockets Neon indicator with push-to-test buttons Gas pressure indicator • A gas pressure indicator is fitted to the tank which has green and red sectors to indicate the minimum permissible pressure for safe operation • An optional remote gas pressure alarm (1N/O) can be specified to alert the operator in the event of gas pressure falling below the permissible operable limit Page 8 Application examples The key areas of application are • Energy i. Generation: wind power, solar power ii. Distribution: compact substations • Infrastructure: tunnels, airports, ports, underground railway stations • Commercial buildings: hospitals, shopping centres, hotels, office buildings, data centres • Industries: water and waste water, mining, minerals, automotive, iron and steel, paper and pulp, cement and petroleum Standards International Standards IEC 62271-1 IEC 62271-100 IEC 62271-102 IEC 62271-103 IEC 62271-200 ENA TS 41-36 Page 9 The Sabre range Non extensible range Non extensible ring main units are an ideal solution for compact outdoor substations. Along with low voltage distribution cabinets, these units can be easily coupled to the distribution transformer, forming a compact outdoor package substation. Modular non-extensible ring switches are an ideal solution for making a switching point in the network. • Ring main units VRN2a 12/15.5kV, 2 ring switches 630A + 1 VCB 250A VRN6a: 12/15.5kV, 2 ring switches 630A + 1 VCB 250/630A Page 10 VRNFS 17.5KV, 2 ring switches 630A + 1VCB 400A VRN24 24kV, 2 ring switches 630A + 1 VCB 400A Page 11 The Sabre range • Modular ring switch DSN6a 12/15.5kV, 2 ring switches 630A Extensible range The extensible range is used to add another function on the left, right or both sides of switchgear installed in secondary networks. This is an ideal solution to allow future upgrades to systems when extra capacity is required. The units can be easily extended in any combination on site without specific tooling or floor preparation and without the need to transfer SF6 gas. The extensible range is designed to be mounted outdoors without needing a kiosk. Page 12 The units are extended as shown in the diagram below: All the extensible units are available in the following configurations: • Left hand • Right hand • Both sides • Ring main units VRE2a 12/15.5kV, 2 ring switches 630A + 1 VCB 250A VRE6a 12/15.5kV, 2 ring switches 630A + 1 VCB 250/630A Page 13 The Sabre range • Modular ring switch SSE6a 12/15.5kV, 1 ring switch 630A DSE6a 12/15.5kV, 2 ring switches 630A Page 14 • Modular circuit breakers VCE2a 12/15.5kV, 1 VCB 250A VCE6a 12/15.5kV, 1 VCB 630A Page 15 • Modular circuit breakers VCE24 24kV, 1 VCB 400A Page 16 Mounting style • Freestanding units Outdoor free standing with bottom entry cable box Page 17 Indoor free standing with top entry cable box • Transformer mounted unit The Sabre ring main unit along with the low voltage distribution cabinet is mounted on the distribution transformer to form a low cost outdoor package substation to be used in distribution networks. Page 18 Product characteristics i. Product presentation VRE6a RMU parts labeled. For other products please refer to their respective IOM. 1 Fascia / front panel 2 Optional ‘pull to trip’ knob & ‘tripped on fault’ indicator blanks 3 Circuit breaker/Tee-off operation slot 4 Circuit breaker/Tee-off indicator 5 Circuit breaker/Tee-off selector 6 Disconnector operation slot 7 Disconnector indicator (service/earth) 8 Disconnector padlock flap 9 Ring switch 2 indicator 10 Ring switch 2 selector 11 Ring switch 2 motor pack 12 Ring switch cable test access cover 13 Ring switch 1 selector 14 Door 15 Ring switch 1 indicator 16 Ring switch 1 operating aperture 17 Circuit label - customer customization 18 Optional VPIS plates for LH/RH Ring switches & CB/Tee-off 19 SF6 top up valve - Hansen coupling 20 Pressure indicator 21 TLF Page 19 1 2 21 3 4 5 8 6 20 7 19 18 17 14 16 15 9 11 13 12 10 ii. User interface and interlocking mechanism Safety interlocking Ring switch and circuit breaker mechanisms are fitted with safety interlocks to protect the operator and equipment from unintentional operation Position Interlock status Ring switch Selector Cable box (optional) Earth & test interlock ON Main ON Locked OFF Main ON Locked OFF Earth ON Locked Earth ON Earth OFF Unlocked Ring switch mechanism Position Interlock status Circuit breaker Selector Cable compartment interlock (optional) Earth & test interlock (optional) ON Main Locked Locked OFF (Tripped) Main Locked Locked OFF (Reset) Earth Locked Locked Earth ON Earth Unlocked Unlocked Earth ON Earth Locked Locked OFF (Tripped) Earth Locked Locked Circuit breaker mechanism Page 20 iii. Ring switch Standard features • Three function ON, OFF & Earth spring loaded mechanism, independent manual operation • Single mechanism with rotary moving shaft for switching ON/OFF/Earth positions • Interlocked selector with padlocking facility for selecting Mains or Earth ON position • Single line intuitive mimic diagram with clear indication of switch status (ON, OFF or Earth position) • Fully interlocked cable earth and test (E&T) facility • • • • • • • Gas pressure indicator shafts, one for circuit breaker ON/OFF position and another for selecting disconnector in Mains or Earth (isolation) Interlocked disconnector selector, locked from operation when circuit breaker is in ON position Trip coil for receiving tripping signal from relay or TLF devices Protection function TLF or relay (customer specific) Single line intuitive mimic diagram with clear indication of switch status (ON, OFF or Earth position) Gas pressure indicator Horizontal cable terminations at the rear of the unit with parallel bushings (except for VRNFS and VRN24 which have DIN 400 type C bushings as standard) Protection CTs (current transformers) mounted on cable bushings (customer specific ratios) Padlock facility (8mm diameter hole) for all the operating positions • Lateral cable terminations with DIN 400 type C bushings • • Padlock facility (8mm diameter hole) for all the operating positions • Optional features, factory fitted Optional features, factory fitted • Remote low gas pressure alarm,1N/O • VPIS - voltage presence indication system • Remote switch position indicator (1N/O,1N/C and 2N/O, 2NC) • Short circuit and earth fault current indicators (EFI) • Actuator (motor) wiring • Castell locks Optional features also available as retrofit • Actuator (motor) for ring switch (only if unit is pre wired for motorisation) • Internal arc rated cable box • Wide range of cable glands and accessories to accommodate 1 and 3 core cables (refer to cable box section for further information) iv. Vacuum circuit breaker • 250A rated vacuum circuit breaker for transformer protection • 400A rated vacuum circuit breaker for transformer/downstream network protection • 630A rated vacuum circuit breaker for transformer/downstream network protection Standard features • Three functions (ON, OFF & Earth), two position spring loaded mechanism, independent manual operation • Single mechanism with two independent operating Page 21 • Remote low gas pressure alarm,1N/O • Mechanical (manual) pull-to-trip button for local operation • VPIS (voltage presence indication system - refer to VPIS section for more details) • Remote circuit breaker position indicator (1N/O,1N/C and 2N/O, 2NC) • Fully interlocked cable earth and test facility (only on 630A VCB) • Self-powered relay for protection (customer specific) • TLF (time limit fuses) for alternative protection • Wide range of CTs for TLF and relay protection • Remote protection trip output status signal (for TLF or relay trip status) 1N/O • Shunt trip coils for external tripping • Tripped on fault indication • Watchdog for relays (only available with selective relays) • Circuit breaker actuator enabled indication • Actuators (motor) wiring Optional features also available as retrofit • Actuator (motor) for CB (only if unit is pre wired for motorisation) • Internal arc rated cable box • Wide range of cable glands and accessories to accommodate 1 and 3 core cables (refer to cable box section for further information) v. Circuit breaker protection Two types of protection devices are offered to protect the circuit breaker • TLF : Time limit fuses • Protection relays a. TLF When utilised in conjunction with circuit breaker type ring main units, time limit fuses (TLF) are a cost effective method of providing fault protection for overcurrent and earth faults (optional) to a transformer of 2MVA or less. It is a recognised method of protection and was developed to comply with EA 41-26 (now superseded by ENA TS 4136) with fuse links in accordance with ENA TS 12-6. It should be noted that the TLF protection system is not a device for limiting overload levels of individual transformers. It should be used for fault protection only. The TLF system provides protection for overcurrent and earth faults between the MV circuit breaker and the LV protection device. The selected TLF rating should be such that it allows for discrimination between the MV & LV devices. This will ensure that the circuit breaker does not open for faults beyond the LV distributor protection device. When fitted with TLF, the Lucy RMU can also be configured to enable tripping of the circuit breaker from remote devices (Bukholtz, LV CB etc). Fuse dimensions: Length 57mm x Diameter 13mm Lucy Electric customers in Europe, the Middle East, Africa and Asia are currently using TLF protection system within their distribution networks. Page 22 Recommended TLF settings Transformer ratings (kVA) 200 315 500 Rated voltage (kV) ct ratio 50/5 Earth fault setting = 25A (instantaneous trip) Earth fault setting = 30A (instantaneous trip) 1000 3.3 10A 6.6 5A 10A 15A 11 3A 5A 10A 15A 13.8 3A 5A 10A 15A 3A 5A 7.5A 24 ct ratio 100/5 800 3.3 6.6 1250 1600 2000 TFL fuse rating (A) 5A 10A 15A 5A 7.5A 12.5A 15A 11 5A 7.5A 10A 12.5A 15A 13.8 5A 7.5A 10A 12.5A 15A 5A 5A 24 7.5A Advantage of vacuum circuit breaker with TLF compared to HV fuses Feature VCB with TLF Overall cost of units Fuse switch Similar Approximate fuse replacement cost Maximum rating of transformer, can be protected $5 $50 2MVA* 1MVA Maximum rated normal current 630A 200A Physical size of fuses Small Large Possibility of some pollution while changing fuses causing PD and flashover issues No Yes LV side HV side Very small with multi ratio CT Large Fuse location inside the unit Range of fuses required for different rated transformers (* No issues with transfer current switching to IEC 62271-105, which minimizes the MVA rating) Advantage of vacuum circuit breaker with TLF compared to protection relays Feature TLF Protection relay Installation cost of function Low High Not required As required Auxiliary power source for operation Delay in activation of trip function due to capacitor charging time lag No delay Delay Employee training on setting tripping curves Not required Required Additional training on different manufacturer setting up procedure Not required Required Maintenance and repair cost Low High Operating temperature limitations None Up to 70 °C Upstream and downstream discrimination protection of circuit Yes Yes Overcurrent and Earth fault protection Yes Yes Page 23 b. Protection relays Woodward WIP 1 Manufacturer Woodward Range WIP1 Functions The Sabre range can be fitted with self-powered relays for protecting the transformer or downstream network from fault currents by tripping the circuit breaker. These relays incorporate many advanced features and have a variety of settings to provide discrimination protection in networks. The self-powered feature eliminates reliance on external power sources and increases the performance and reliability of the protection function. Below are the technical characteristics of Woodward WIP1 and Fanox SIAC range. Other manufacturers’ relays can also be incorporated into the units on request. Phase overcurrent • Short circuit protection • Number of overcurrent elements 2 Earth overcurrent • Number of earth overcurrent elements 2 Characteristics Display (measuring values and parameters) • Setting via buttons • Standard CT (1A/5A) 1A LED pickup • LED trip indicator • Flag indication output • Fault memory • Clock • Password protection • Electro impulse and relay contact output • Number of output relays 3 C/O Input remote tripping • Interface O RS 485 interface with pro open data protocol O RS-485 interface with Modbus protocol O Additional power supply Key • Standard O O Option Page 24 Fanox Manufacturer Range Fanox Fanox Fanox SIAC*********D SIAC*********B SIAC*********FA • • • Functions Phase overcurrent Short circuit protection Number of overcurrent elements Earth overcurrent Number of earth overcurrent elements Pickup level Startup time (Trip time after fault. Single phase) • • • 2 50P: Tap:0.1…30xIn Time:0,02…300 s 51P: Tap:0.1…7xIn 2 50P: Tap:0.1…30xIn Time:0,02…300 s 51P: Tap:0.1…7xIn 3 (2) 50P: Tap:0.1…30xIn Time:0,02…300 s 51P: Tap:0.1…7xIn • • • 2 50N: Tap:0.1…30xIn Time:0,02…300 s 51N: Tap:0.1…7xIn 2 50N: Tap:0.1…30xIn Time:0,02…300 s 51N: Tap:0.1…7xIn 3 (2) 50N: Tap:0.1…30xIn Time:0,02…300 s 51N: Tap:0.1…7xIn 0,2xIn(single phase) 0,1xIn (three phase) 0,2xIn(single phase) 0,1xIn (three phase) 0,2xIn(single phase) 0,1xIn (three phase) 130 ms 130 ms 70 ms • (Display 20x2) • (Display 20x2) • (Display 20x2) • • • • The test menu can be used to check the operation of the signaling components (LEDs and magnetic indicators), along with the trip output and the signaling outputs • The test menu can be used to check the operation of the signaling components (LEDs and magnetic indicators), along with the trip output and the signaling outputs • The test menu can be used to check the operation of the signaling components (LEDs and magnetic indicators), along with the trip output and the signaling outputs Characteristics Display (measuring values and parameters) Setting via buttons Test menu Settings groups 1 1 3 1A or 5A (depending on model) 1A or 5A (depending on model) 1A or 5A (depending on model) LED pickup The pickup message is shown at the display. Besides, the SIA-C front panel has three LED pilot lights to show the type of power being used: self-power, battery or auxiliary power The pickup message is shown at the display. Besides, the SIA-C front panel has three LED pilot lights to show the type of power being used: self-power, battery or auxiliary power The pickup message is shown at the display. Besides, the SIA-C front panel has two LED pilot lights to show the type of power being used: self-power or battery LED trip indicator To signal the trip, the front panel is equipped with 1 bistable magnetic indicator which indicates a trip has occurred To signal the trip, the front panel is equipped with 1 bistable magnetic indicator which indicates a trip has occurred To signal the trip, the front panel is equipped with 2 bistable magnetic indicators which indicates a trip has occurred Standard CT (1A/5A) Page 25 Manufacturer Fanox Fanox Fanox SIAC*********D SIAC*********B SIAC*********FA Flag indication output Flags are included in the relay, no need of external modules Flags are included in the relay, no need of external modules Flags are included in the relay, no need of external modules Fault memory 20 fault reports (64 events each) 20 fault reports (64 events each) 20 fault reports (64 events each) 500 events in non-volatile RAM memory 500 events in non-volatile RAM memory 500 events in non-volatile RAM memory Clock • • • Password protection • • • • Trip contact for striker or coil • Trip contact for striker or coil • Trip contact for striker or coil 2 NO/NC 2 NO/NC 3 NO Watchdog contact - - - Input remote tripping • • • Interface Range Events Characteristics Electro impulse and relay contact output Number of output relays O O O RS 485 interface with pro open data protocol - - - RS-485 interface with Modbus protocol O Option included in the relay, no need for an external module MODBUS O Option included in the relay, no need for an external module MODBUS O Option included in the relay, no need for an external module MODBUS O Option included in the relay, no need for an external module O Option included in the relay, no need for an external module O Option included in the relay, no need for an external module No need for an internal battery to keep events and faults due to FRAM memory No need for an internal battery to keep events and faults due to FRAM memory No need for an internal battery to keep events and faults due to FRAM memory Additional power supply Battery Other manufacturers’ relays are also available on request, please contact our local Sales Office for more information. Page 26 vi. Protection CTs for TLF and relays The protection CT is used in conjunction with relays or TLF protection to protect a wide range of distribution transformers. These CTs are mounted on the circuit breaker tee-off bushings inside the cable box to guard them from damage in transportation, installation and adverse weather conditions. A comprehensive range of CTs* is available to suit varied application requirements Dual ratio CT 100/50/Dual ratio CT 200:100/Triple ratio CT 150:100:50/*Please contact our local Sales Office for more information vii. Bushings DIN 400 type C i. Cable bushings a. Ring switch: DIN 400 type C (125mm phase centre distance) b. Vacuum circuit breaker tee-off: • Parallel bushings (105mm phase centre distance) Optional adaptor for converting parallel bushings connection to DIN 400 type C (125mm phase centre distance) • DIN 400 type C (125mm phase centre distance) Parallel bushings c. Metering unit: DIN 400 type C (125mm phase centre distance) ii. Bus bar extension bushings: (Obround 125mm phase centre distance) iii. Test bushings Obround bushings Test bushings Page 27 Options and accessories i. Secondary injection Secondary injection is used to test the relays or TLF operation without switching on the high voltage supply to the unit. A low voltage is applied to the secondary side of the CT connection (located in terminal box) to test the operation of the protection devices at the time of commissioning and routine tests. Marshalling box ii. Actuators (motors) Sabre units are fitted with 24V DC motors, which can be powered from the Gemini remote terminal unit (RTU) 24V DC battery in the event of mains AC supply failure. Ring switch actuator Vaccum circuit breaker actuator Page 28 iii. Cable boxes, glands and accessories Cable box Cable boxes are available for the following: o Ring switches cable bushings o Circuit breakers tee-off bushings o Metering units bushings o Extensible bus bar bushings • Safety interlocks: The cable boxes can be interlocked with a ring switch or circuit breaker mechanism. Interlocked cable boxes can only be removed when the circuit is in the ‘Earth ON’ position • Internal arc rating o Non internal arc rated cable box as standard o Internal arc rated cable boxes 12.5kA 1sec and 20kA 1 sec as optional • Cable box lengths o 450mm o 610mm • Cable entry o Top entry with • IP50 standard (indoor only) o Bottom entry with IP54 as standard • Straight • Angled Bottom entry Cable gland and gland plates • Cable gland and gland plates o 1 x 3 core cable • X size • Gland plates o X size gland plate with earth stud • Glands o X tube glands o X brass wiping gland • Y size • Gland plates o Y size gland with earth stud • Glands o Y tube glands o Y brass wiping gland o 3 x 1 core cable • Gland plates • 3 hole split steel with earth stud • 3 hole split steel with earth bar • 3 hole solid brass with earth stud • 3 hole solid brass with earth bar • Glands • Single core compression gland • Single core heat shrink glands Top entry cable box Angled cable box For further information refer to the accessories table. Page 29 iv. Bus bar couplings Bus bar couplings are used to connect two extensible units. Bus bar coupling lengths • 453mm • 500mm • 750mm Bus bar insulation types • Heat shrink (manufactured by SPS) • Heat shrink (manufactured by Raychem) • Heat shrink (manufactured by REPL) • Cold fit rubber boot (manufactured by Pirelli) v. MV sensors MV sensors are used to detect the medium voltage in the cable and send a signal to the remote control device for auto changeover. vi. Watchdog for relays They are used to check the healthy operation of relays. vii. Operation counter They are used to count the number of mechanical operations of the ring switch and circuit breaker mechanisms. viii. Castell locks Ring switch: Castell locks are used to prevent closing of the open point in the ring network. Circuit breaker: Key free Earth ON: They are typically used for preventing transformer cubicle access until the circuit breaker is in the Earth ON position. ix. Protection trip remote indicator They are used to send a signal to a remote terminal unit if a protection device relay or TLF has tripped (operated). Castell lock Page 30 x. Shunt trip coils Shunt trips are magnetic coils that are used to trip circuit breakers through local push buttons, RTUs or additional transformer protection devices. Shunt trips are available in the following voltages: • • • DC voltage: 12V, 24V, 48V and 110V AC voltages: 110V, 240V Multiple voltage range: 24VAC/DC – 240VAC/DC. Shunt trip xi. Earth Fault Indicators (EFI) Earth fault indicators (EFI) are used for rapid location and isolation of faults on medium voltage networks in open loop ring main networks. When the unit detects asymmetrical currents in the 3 phase cable, an earth fault is indicated by means of a flashing LED or mechanical flag. Below is the list of EFIs available for the Sabre range Manufacturer Model: BLZ-50 BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50 Suparule Sensorform Features 3.6V lithium ½ AA 850mAH battery Power source 110-240V a.c. Voltage range 1 – 38kV Trip current 50A Primary indication LED Flashing duration >1000 hrs Mech-flag (RED) - - Minimum fault duration LED Mech-flag LED 10 hrs - 10 hrs 2.5 cycles Manual reset Push button Automatic timer reset 4 or 8 hrs selectable 10 secs after mains restore Manual trip test Push button Operating temperature -40°C to +80°C Operating humidity 0-100% RH Ingress protection Current sensor diameter: CT on current carrying phase IP65 CT100: 100mm • • • • • • CT150: 150mm O O O O O O CT300: 300mm O O O O O O Remote flashing LED indicator O O O O O O Auxiliary relay, 1N/O latching O O O O O O Key • Standard O Option Other manufacturers’ EFIs are also available on request, please contact our local sales office for more information. Page 31 Cable terminations The bushings are accessible by removing the cable box covers at the lateral and rear of the unit. The maximum cable sizes that can be used are: • 300mm² 3 - core • 500mm² single - core. The following types of terminations can be used with the Sabre range: Insulating bushing boot Heat shrink insulating bushing boot Profile “C” bolted separable DIN type C bushings (cable boxes) • Insulating bushing boot • Heat shrink insulating bushing boot • Profile “C” bolted separable Obround bushings (bus bar extension) The following cable connections could be used if direct cable connection is required on the bus bar bushings • Insulating bushing boot • Heat shrink insulating bushing boot Parallel bushings (tee-off ) The following connectors could be used if cable tee-off direct cable connection is required • Insulating bushing boot • Heat shrink insulating bushing boot Page 32 Remote terminal unit (RTU) The Sabre range can be configured with the next- generation Gemini 3 RTU. This is an all new, highly flexible, general-purpose Remote Terminal Unit designed to remotely monitor and control medium and high voltage switchgear. The Gemini 3 has a modular design such that it can be configured from a simple monitoring only device to a fully functional automated switch controller. It has the ability to transition from a basic to an advanced RTU by plugging in additional modules. These modules are rugged, making the device field serviceable and future proof. The Gemini 3 modules available are: Characteristics • Fault detection (Earth and Phase) • LED status indicators • Real time clock (SCADA synchronised) • Dual isolated Ethernet and RS232 ports • Isolated RS485 port • Supervisory selection and indication • Event memory – 7000 events in non-volatile memory • Communication protocol - DNP 3.0 TCP/IP or Serial Master Control Module (MCM) – This contains the main processor and supervises all modules. The MCM handles the protocol communications. - IEC 60870-5-101 - IEC 60870-5-104 - Modbus TCP or RTU Single Switch Module (SSM) – This provides the inputs and outputs to perform secure interlocked control of a single gas enclosed switch. Dual Switch Module (DSM) – This provides the inputs and outputs to perform secure interlocked control of two MV ring switches. Power Supply Module (PSM) – This module works with the switch control modules to provide secure switching operations. The PSM generates regulated power to all other modules and external communication equipment. The PSM also provides the intelligent battery charging function to maintain a secure supply. Input Output Module (IOM) – This is a general purpose module that covers digital and analogue inputs and relay outputs. Fault Passage Module (FPM) – This is a dual fault passage indicator module which detects and alarms for Overcurrent and Earth Faults. Human to Machine Interface (HMI) – This is an optional module that allows local control and monitoring without the need for a Computer. It allows local controls to be issued by an authorised Engineer (security enabled) or just provide data to be viewed locally. Page 33 • Maintenance free Smart-grid ready Gemini 3 RTU integration Key features of Gemini 3 Benefits of Automation • Embedded auto change over and auto sectionalising functions • • Real time network condition monitoring of voltage, current, power, power factor and frequency Reduced time in diagnosing system anomalies as well as locating and isolating faulty sections of the network • Faster response time and quick network reconfiguration • Flexible communication through radio, RS232, RS485, packet data network, GSM, GPRS, PSTN, ethernet TCP / IP and optical fibre. • Optimisation of asset management through the implementation of customised automation schemes • Advanced battery pack to operate under mains AC input failure • • Fully tested to ENATS (Energy Network Association Technical Standards), EMC and environmental standards Reduced operational cost associated with routine network switching • Increased operator safety Automatic transfer scheme Sabre units coupled with Gemini 3 offers full Automatic Transfer Scheme support. This provides the rapid and reliable transfer of the system from one power source to another, in the event of normal source failure. The result is an added layer of reliability in the power supply. Load break switch 1 (S1) Motor Motor M M VDS Load break switch 2 (S2) Motors for load switch operation. VDS for detecting voltage in the line In the event voltage loss, a relay is activated which sends a signal to the RTU control unit. VDS Line 1 Line 2 EFI / FPI EFI / FPI Gemini 3 RTU If a line fault is detected, the EFI sends a signal to the RTU to avoid closing the incoming line onto a fault. RTU detects the signal coming from the VDS and EFI and deploys changeover schemes by opening / closing the load break switches S1 and S2. Page 34 Technical Data Sheet Ring main unit Modular circuit breaker Non Extensible Models VRN2a VRN6a VRNFS Description 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 12 (15.5) 12 (15.5) 17.5 Modular ring switch Non Extensible Extensible VRN24 VRE2a VRE6a VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 2 RSW+ 2 RSW+ 1VCB 1VCB 2 RSW+ 1VCB 1 VCB 1 VCB 1VB 1 RSW 2 RSW 2 RSW General Rated voltage kV Rated frequency Hz 24 12 (15.5) 12 (15.5) 12 (15.5) 12 (15.5) 50/60 24 12 (15.5) 12 (15.5) 50 50/60 12 (15.5) Rated lightning impulse withstand voltage Directly earthed kV 75 (95) 95 125 75 (95) 125 75 (95) Across disconnector kV 85 (110) 110 145 85 (110) 145 85 (110) Rated power frequency withstand voltage Directly earthed kV 28 (38) 38 50 28 (38) 50 28 (38) Across disconnector kV 38 (45) 45 60 38 (45) 60 38 (45) Protection Overall unit IP IP54 Tank with HV parts IP IP67 IP54 LV control box IP Front face + mechanism IP IP2x Cable box IP IP54 Mechanical impact protection IK IK07 (2J) Indoor, IK08 (5J) Outdoor Internal arc protection Unit kA 1 sec 20 21 16 20 16 20 cable box (optional) kA 1 sec 12.5/20 21 12.5 12.5/20 12.5 12.5/20 - Optional Gas tank internal arc ratings AF Standard AFL Optional AFLR - Optional - - Optional SF6 gas Filled pressure Bar (G) 0.4 0.5 0.4 0.5 0.4 Minimum operating presure Bar (G) 0 0.3 0 0.3 0 ≤0.1% per annum Annual leakage rate Weight Kg 1.46 1.56 1.78 1.05 1.56 0.78 0.98 Installation conditions Ambient air temperature ˚C 40 / 50 Maximum altitude (without derating)* M 1000 Relative humidity (max) - over period of 24hrs (IEC 62271-1, sub-clause 2.1) 100% Ring main unit Modular circuit breaker Non Extensible Modular ring switch Non Extensible Extensible Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a Description 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 1 VCB 1 VCB 1 VB 1 RSW 2 RSW 2 RSW Bus bars Rated normal current A Rated short time withstand current Rated peak withstand current kA 630 400/630 20 kA 3s 21kA 1s 16kA 3s 20kA 3s 630 16kA 3s 20kA 3s 50 54.6 40 50 40 50 * for higher altitude applications please contact our local Lucy Electric sales office Page 35 Ring main unit Modular circuit breaker Non Extensible Modular ring switch Non Extensible Extensible Models VRN2a VRN6a VRNFS VRN24 Description 2 RSW+ 2 RSW+ 1VCB 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 2 RSW+ 1VCB 1VCB VRE2a VRE6a VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1 VCB 1 VCB 1 VCB 1 RSW 2 RSW 2 RSW Ring switch Rated normal current A 630 400/630 630 630 630 Rated active load breaking current A 630 400/630 630 630 630 Ring switch kA 50 54.6 40 50 50 Earth switch kA 50 54.6 40 50 Rated short circuit making current Rated cable charging breaking current A 50 25 25 Rated short time withstand current Ring switch 20 kA 3s 21kA 1s 16kA 3s 20kA 3s 20kA 3s Earth switch 20 kA 3s 21kA 1s 16kA 3s 20kA 3s 20kA 3s Mechanical endurance class Ring switch M2 (5000) M2 (5000) Earth switch M1 (1000) M1 (1000) Electrical endurance class short circuit making Ring switch E3 (5 times) E1 (2 times) E3 (5 times) E3 (5 times) Earth switch E2 (3 times) E1 (2 times) E2 (3 times) E2 (3 times) Operating mechanism Local: close/open Remote: close/open Handle Handle Actuator (Motor) Actuator (Motor) Ring main unit Modular circuit breaker Non Extensible Modular ring switch Non Extensible Extensible Models VRN2a VRN6a VRNFS VRN24 VRE2a VRE6a VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a Description 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 2 RSW+ 1VCB 1 VCB 1 VCB 1 VCB 1 RSW 2 RSW 2 RSW Vacuum circuit breaker Rated normal current A 250 630 400 400 250 630 250 630 400 Rated active load breaking current A 250 630 400 400 250 630 250 630 400 Rated short circuit breaking current kA 21 16 20 20 16 Rated short circuit making current Circuit breaker kA Earth switch kA 50 7.9 50 54.6 40 54.6 40 50 7.9 Rated cable charging breaking current A 50 40 50 50 25 40 25 Rated short time withstand current Main electrical circuit 20 kA 3s Earthing circuit 3.15kA 20kA 3s 21kA 1s 16kA 3s 21kA 1s 16kA 3s 20kA 3s 3.15kA 3s 20kA 3s 3.15kA 3s 16kA 3s 20kA 3s 16kA 3s Mechanical endurance class Circuit breaker M1 (2000) Earth switch M1 (1000) Electrical endurance class Circuit breaker E2 Earth switch E2 Operating mechanism Tripping time Operating sequence for mechanism Local: close/open Remote: close/open ms <80ms 0-3min-CO-3min-CO Handle Actuator (Motor) Page 36 Dimensions Dimensions & floor: VRN2A Dim A (450mmTaillength cable box in mm) (570mmTaillength cable box in mm) Dim B Dim C Dim D (mm) (mm) (Tee-offbushing height in mm) 1052 600 480 1715 817 1402 970 518 398 1633 735 1320 750 298 178 1413 515 1100 Page 37 Dim B Dim E (Ringbushing heightinmm) Dimensions & floor: VRN6A Dim A Dim B Dim C Dim D (mm) (mm) (mm) 1052 2163 1773 970 2081 750 1861 (Ringbushing heightinmm) Dim E Dim F 817 1402 600 480 1691 735 1320 518 398 1471 515 1100 298 178 (Tee-offbushing (450mmTaillength height in mm) cable box in mm) Dim F (570mmTaillength cable box in mm) NOTE: All dimensions are in mm Page 38 Dimensions Dimensions & floor: VRNFS Page 39 continued Dimensions & floor: VRN24 NOTE: All dimensions are in mm Page 40 Dimensions Dimensions & floor: DSN6A Page 41 continued Dimensions & floor: VRE2A / VRE6A NOTE: All dimensions are in mm Page 42 Dimensions Dimensions & floor: SSE6A Page 43 continued Dimensions & floor: DSE6A NOTE: All dimensions are in mm Page 44 Dimensions & floor: VCE2A / VCE6A Page 45 Dimensions & floor: VCE24 Page 46 Sabre models and options Modular units Range Ring main units Extensibility Non extensible VRN2a Description 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1VCB VRNFS VRN24 VRE2a VRE6a 2 RSW+ 2 RSW+ 1VCB 1VCB Modular ring switches Extensible Non extensible VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1VCB 1VCB 2 RSW Extensible Models VRN6a Modular circuit breaker 1VCB 1 RSW 2 RSW General Extensibility Non extensible LH extensible RH extensible Both sides extensible Impulse withstand voltage (BIL) kVP (choose one from below) • - • - • - • - o o o o o o o o o o o o o - o o o o o o • - 12kV at 75KVP BIL 15.5kV at 95KVP BIL 17.5kV at 95KVP BIL 24kV at 125kVP BIL 24kV at 145kVP BIL Low gas pressure alarm auxiliary contact 1NO Pressure indicator gauge with Hanson coupling Mounting style Transformer mounted unit (fitted with ESI flange) Freestanding unit No ESI flange (with cable box)1 ESI Transformer flange fitted (with/without cable box)1 Height of tee-off bushing from floor (applicable to freestanding units) o o o • o o o • o o • o o o • o o o • o o o • o o o • o o o • o o o • o o o • o o o • o o o • o o o o • o o • o o • o o • o o • o o o o o o • o o • • o • - • - • - 1100mm 1320mm 1348mm 1402mm Height of extension bushings from floor (applicable to free standing units) o o o o o • - o o o - - - - - - - - 1072 mm Any other (available on request) Internal arc protection for gas chamber (tank) AF AFL AFLR Tank exhaust at top Tank exhaust at rear Extensible bus bar bushings: Obround (Hysol) - - - - • o • o • o • o • o • o • o • o • o o • - • o o • - • o • - • o o • - • o o • • • o o • • • o o • • • o o • • • o - • o o • • • o o • • • o o • - • - • o • o • - • - • o • - • o • - - - - Vacuum circuit breaker Short circuit breaking current 16kA RMS 20kA RMS 21kA RMS 25KA RMS 2 NOTE: All dimensions are in mm Page 47 Sabre models and options Extensibility Non extensible VRN2a Description Vacuum circuit breaker 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1VCB Bushings type Parallel bushings Adaptor to convert parallel bushings to DIN 400 type C bushing DIN 400 type C Rated normal current 250A 400A 630A Earth & test facility Circuit breaker protection TLF Relay (choose one from below) WIP1 relay Fanox relay Any other* Protection (CT) current transformers Dual (Primary) ratio CT 100/50/Dual (Primary) ratio CT 200/100/Triple (Primary) ratio CT 150/100/50/Dual (Primary) ratio CT 400/200/Dual (Primary) ratio CT 150/100/Dual (Primary) ratio CT 600/200/Manual "Pull to trip" Remote shunt trip 12V DC 24V DC 48V DC 110V DC 110V AC 240V AC Multi voltage (24V AC/DC- 240V AC/DC) Indication / auxiliary switches Remote protection trip output signal (for TLF or relay trip status) 1N/O Watchdog for relays (only available with selective relays) Tripped on fault indication Circuit breaker actuator enabled indication Circuit breaker service indication 1NO, 1NC 2NO, 2NC Circuit breaker earth indication 1NO, 1NC 2NO, 2NC Key • Standard o Optional - Not applicable Page 48 VRNFS Extensible Non extensible VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1VCB 1VCB 1VCB 1 RSW 2 RSW 2 RSW Extensible Models VRN6a continued VRN24 VRE2a VRE6a 2 RSW+ 2 RSW+ 1VCB 1VCB • o • o - - • o • o • o • o - - - - - - • • - - - - • - - - • - o • o • o - • - • - o • o • - • o • o - - - o o - o o o o o o - - - o o o o o o o o o o o o o o o o o o o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o • o o o o o • o o o o o o o o o o o o o o o o o o o o o o o o o o o o o • - - - o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o - - - o o o o o o o o o - - - o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o - - - 1: Refer to cable box, cable gland and gland plate table for more information 2: Available soon Extensibility Non extensible Models VRN2a Description 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1VCB VRN6a VRNFS Extensible Non extensible VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1VCB 1VCB 1VCB 1 RSW 2 RSW 2 RSW Extensible VRN24 VRE2a VRE6a 2 RSW+ 2 RSW+ 1VCB 1VCB Vacuum circuit breaker VPIS Neon indication push button Neon indication pfisterer socket Operation counter Castell locks Key free earth on Key trapped disconnector service CB ON Actuators (motors) Actuators wiring only Actuators (24V DC motor) for remote control o o o o o o o o o o o - o o o o o o o o o o o o • o - - - - o o o o o o o o o o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o - - - • • • • • o • • • • • • • - - - • • • • • • • o • o • o • - • o • o - - - • o • o • o o o o o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o o o o - - - o o o o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o - - - o o o o o o o o o o o o o o o o o o o o o • • • • • o • • • • • • • - - - - • • • • • o • o • o • - • o • o - - - - • o • o Ring switch 1 (Left hand side) Rated current 400A 630A Earth & test facility Bushings type DIN 400 type C Operation counter Actuators (motors) Actuators wiring only Actuators (24V DC motor) for remote control VPIS Neon indication push button Neon indication pfisterer socket MV sensor Auxiliary switches 1NO, 1NC 2NO, 2NC Castell locks Key free in off position Earth fault indication BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50 BLZ-50 Any other(*) Ring switch 2 (Right hand side) Rated current 400A 630A Earth & test facility Bushings type DIN 400 type C Operation counter Page 49 Extensibility Non extensible Models VRN2a Description 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1VCB VRN6a VRNFS Extensible Non extensible VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1VCB 1VCB 2 RSW Extensible VRN24 VRE2a VRE6a 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1 RSW 2 RSW Ring switch 2 (Right hand side) Actuators (motors) Actuators wiring only Actuators (24V DC motor) for remote control VPIS Neon indication push button Neon indication pfisterer socket MV sensor Auxiliary switches 1NO, 1NC 2NO, 2NC Castell locks Key free in off position Earth fault indication BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50 BLZ-50 Any other(*) Key • Standard o Optional - Not applicable Page 50 o o o o o o o o o o o o - - - - o o o o o o o o o o o o o o o o o o o o o o - - - - o o o o o o o o o o o o o o o o o o - - - - o o o o o o o o o o - - - - o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o - - - - o o o o o o o o o o o o o o 1: Refer to cable box, cable gland and gland plate table for more information 2: Available soon Accessories Cable box, cable gland and gland plate selection table Ring switch 1 Interlocked cable box Cable box internal arc rated (AFL) Top entry IP50 (standard) IP54 (optional) 450mm bushings to gland height,12.5KA IAC 610 mm bushings to gland height,12.5KA IAC Bottom entry (IP54) 450mm bushings to gland height, 12.5 kA IAC 610mm bushings to gland height, 12.5 kA IAC 450mm bushings to gland height, 20KA IAC 610mm bushings to gland height, 20KA IAC Bottom entry angled, 12.5KA IAC Bottom entry deep, 12.5KA IAC Cable box non IAC rated Top entry IP50 (standard) IP54 (optional) 450mm bushings to gland height 610mm bushings to gland height Bottom entry (IP54) 450mm bushings to gland height 610mm bushings to gland height Bottom entry angled Bottom entry deep 1 X 3C cable gland and gland plates X size Gland plates X size gland plate with earth stud Glands X tube glands X brass wiping gland Y size Gland plates Y size gland with earth stud Glands Y tube glands Y brass wiping gland Ring switch 2 Circuit breaker tee-off Extensible bus bars (Not to be used with VRE and DSE) o o o - • o o o • o o o • o o o • o o o o o o o o o o o o o o o o o o o o o o o o o o o • o o o • o o o • o o o • o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o Page 51 Cable box, cable gland and gland plate selection table Ring Ring Circuit Switch 1 Switch 2 breaker tee-off Extensible bus bars (Not to be used with VRE and DSE) 3 x 1C cable gland and gland plates Gland plates 3 hole split steel with earth stud 3 hole split steel with earth bar 3 hole solid brass with earth stud 3 hole solid brass with earth bar o o o o o o o o o o o o o o o o o o o o o o o o 241 378 453 o o • - • o o • - Glands Single core compression gland Single core heat shrink glands Bus bar coupling selection table Bus bar coupling kits (length mm) Insulation for bus bar coupling Heat shrink manufactured by SPS Heat shrink manufactured by Raychem Heat shrink manufactured by REPL Cold fit rubber boot manufactured by Pirelli Quantity Other accessories Padlocks TLF fuses (specify quantity and Amp rating) Foundation bolts (not required for transformer mounting) Adaptor for converting parallel bushings to DIN 400 type C connection Key • Standard Page 52 o Optional - Not applicable Sabre models and options order form To use this form, please photocopy and return the completed form to your nearest Lucy Electric office Tick the boxes with your required order (addresses can be found on the back cover) Name: Company: Address: Tel No: Email: Order number: Order quantity / number of units (please fill separate form for each type) Modular units Range Ring main units Extensibility Non extensible VRN2a Description 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1VCB VRNFS VRN24 VRE2a VRE6a 2 RSW+ 2 RSW+ 1VCB 1VCB Modular ring switches Extensible Non extensible VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1VCB 1VCB 2 RSW - - Extensible Models VRN6a Modular circuit breaker 1VCB 1 RSW 2 RSW General Extensibility Non extensible LH extensible RH extensible Both sides extensible • - • - • - • - - - - - - - - • - - - - - Impulse withstand voltage (BIL) kVP (choose one from below) 12kV at 75KVP BIL 15.5kV at 95KVP BIL 17.5kV at 95KVP BIL 24kV at 125kVP BIL 24kV at 145kVP BIL Low gas pressure alarm auxillary contact 1NO Pressure indicator gauge with Hanson coupling - - - • • • • Mounting style Transformer mounted unit (fitted with ESI flange) Freestanding unit No ESI flange (with cable box) ESI transformer flange fitted (with/without cable box) - - - - - • • • • • • • • • - - - - - - - - - • • • • • • • - • - • - • - - - - - - - - - Height of tee-off bushing from floor (applicable to freestanding units) 1100mm 1320mm 1348mm 1402mm - - • - - Height of extension bushings from floor (applicable to free standing units) 1072 mm Any other (available on request) Internal arc protection for gas chamber (tank) AF AFL AFLR Tank exhaust at top Tank exhaust at rear Extensible bus bar bushings: Obround (Hysol) - - - - • • • • • • • • • • • • • • • • • • • • • - • - • - • - • • • • • • • • - • • • • • Page 53 Sabre models and options order form Extensibility Non extensible VRN2a Description 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1VCB VRN6a VRNFS Extensible Non extensible VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1VCB 1VCB 2 RSW Extensible Models VRN24 VRE2a VRE6a 2 RSW+ 2 RSW+ 1VCB 1VCB continued 1VCB 1 RSW 2 RSW Vacuum circuit breaker Short circuit breaking current • - • - • • - • - • - • - • - • - - - - • • - - • • • • - - - - - - • • - - - - • - - - • - • • • - • - • • - • • - - - - - - - - - - - - - - - - - Remote protection trip output signal (for TLF or relay trip status) 1N/O Watchdog for relays (only available with selective relays) - - - - - - Tripped on fault indication - - - - - - 16kA RMS 20kA RMS 21kA RMS 25KA RMS Bushings type Parallel bushings Adaptor to convert parallel bushings to DIN 400 type C bushing DIN 400 type C Rated normal current 250A 400A 630A Earth & test facility - Circuit breaker protection - TLF Relay (choose one from below) WIP1 relay Fanox realy Any other* Protection (CT) current transformers Dual (Primary) ratio CT 100/50/Dual (Primary) ratio CT 200/100/Triple (Primary) ratio CT 150/100/50/Dual (Primary) ratio CT 400/200/- - - - - - Dual (Primary) ratio CT 150/100/Dual (Primary) ratio CT 600/200/Manual "Pull to trip" • • • Remote shunt trip 12V DC 24V DC 48V DC 110V DC 110V AC 240V AC Multi voltage (24V AC/DC- 240V AC/DC) Indication/ Auxilliary switches Circuit breaker actuator enabled indication Circuit breaker service indication 1NO, 1NC 2NO, 2NC Page 54 Extensibility Non extensible Models VRN2a Description 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1VCB VRN6a VRNFS Circuit breaker earth indication 1NO, 1NC 2NO, 2NC Secondary injection terminals VPIS Neon indication push button Neon indication pfisterer socket Operation counter Castell locks Key free earth on Key trapped disconnector service CB ON Actuators (motors) Actuators wiring only Actuators (24V DC motor) for remote control Ring switch 1 (Left hand side) Rated current 400A 630A Earth & test facility Bushings type DIN 400 type C Operation counter Actuators (motors) Actuators wiring only Actuators (24V DC motor) for remote control VPIS Neon indication push button Neon indication pfisterer socket MV sensor Auxilliary switches 1NO, 1NC 2NO, 2NC Castell locks Key free in off position Earth fault indication BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50 BLZ-50 Any other(*) Ring switch 2 (Right hand side) Rated current 400A 630A Extensible Non extensible VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1VCB 1VCB 1 RSW 2 RSW 2 RSW - - - - - - - - - - - - Extensible VRN24 VRE2a VRE6a 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB • • - • • • • • • • • • • • • • • • • • • - - - • • • • • • • - • • - - - • • • - - - - - - - - - - - - - - - - - - - • • • • • Page 55 Sabre models and options order form Extensibility Non extensible VRN2a Description 2 RSW+ 2 RSW+ 2 RSW+ 2 RSW+ 1VCB 1VCB 1VCB 1VCB VRN6a VRNFS Extensible Non extensible VCE2a VCE6a VCE24 SSE6a DSE6a DSN6a 1VCB 1VCB 2 RSW Extensible Models VRN24 VRE2a VRE6a 2 RSW+ 2 RSW+ 1VCB 1VCB continued 1VCB 1 RSW 2 RSW Ring switch 2 (Right hand side) Earth & test facility Bushings type DIN 400 type C Operation counter Actuators (motors) Actuators wiring only Actuators (24V DC motor) for remote control VPIS Neon indication push button Neon indication pfisterer socket MV sensor Auxilliary switches 1NO, 1NC 2NO, 2NC Castell locks Key free in off position Earth fault indication BFZ-50 MFZ-50 MLZ-50 CFZ-50 CLZ-50 BLZ-50 Any other(*) • • • • • • - - - - • • • • • • - • • - - - - • • - - - - - - - - - - - - - - - - - - - - * Please fill the details in comments section below. Comments Page 56 Key • Standard Option select - Not applicable Air metering unit (AMU) i. Characteristics • • • • • Up to 15.5kV and 630A rating Freestanding and RMU mounted version Voltage transformer (VT) isolation for HV testing Bus bar metering and tee-off metering options Trip lock out relay for RMU/AMU combinations for emergency tripping • Wide range of CT and VT options to suit various application needs • IP54 for outdoor installation without needing a kiosk Tee-off metering RMU mounted ii. Mounting style a. Tee-off metering b. BC: Bus bar connected c. FS: Free standing metering Free standing metering unit Tee-off metering Bus bars connected metering Free standing metering Page 57 iii.Dimensions Dimensions & floor: AMU Free standing Page 58 Dimensions: Tee-off AMU (RMU mounted) NOTE: All dimensions are in mm Page 59 iv.Options and Accessories Metering units General Impulse withstand voltage (BIL) kVP (choose one from below) 12kV at 75KVP BIL 15.5kV at 95KVP BIL Rated current 250A 630A Mounting style FS: Freestanding BC: Bus bar connected TC: Ring main unit (tee-off ) mounted Bushings type FS: Freestanding Incoming DIN type C Outgoing DIN type C BC: Bus bar connected Incoming DIN type C Outgoing DIN type C TC: Ring main unit (tee-off ) mounted Incoming direct connection to RMU Outgoing DIN type C o o o o o o o • • • • • • VT - Voltage transformer VT primary fused protection Unfused primary VT with tool free bus bar isolation for VT testing (only for 630A) Fused primary VT VT type Dual ratio (Primary) 3 Phase - 3 limb 11000/6600/110V, class 1, 50VA/PH Single ratio (Primary) 3 Phase - 3 limb 11000/110V, class 1, 50VA/PH Single ratio (Primary) 3 Phase - 3 limb 6600/110V, class 1, 50VA/PH Single ratio (Primary) 1 Phase - 1 limb 13800/110V, class 0.5, 50VA/PH Dual ratio (Primary) 1 Phase - 1 limb 11000/6600/110V, class 0.2, 50VA/PH o o Number of VT 1 1 1 2 3 2 3 Dual ratio (Primary) 3 Phase - 5 limb, Ratio: 11000/6600/110v, Class 0.5, 50VA/PH 1 Dual ratio (Primary) 3 Phase - 5 Limb, Ratio: 11000/6600/110v, Class 0.5, 20VA/PH 1 Single ratio (Primary) 3 Phase - 5 Limb, Ratio: 11000/110v, Class 0.5, 50VA/PH 1 Dual ratio (Primary) 3 Phase - 5 Limb, Ratio: 11000/6600/110v, Class 0.5, 50VA/PH 1 Page 60 o o o o o o o o o o o CT - Current Transformer Reference Number Number of CT’s Single ratio (Primary), 30/5A, 7.5VA, Class 0.5, STC 20.1kA/1sec SR1B2C4S13 2/3 Single ratio (Primary), 50/5A, 7.5VA, Class 1.0, STC 18.4kA/1sec SR2B2C7S9 2/3 Single ratio (Primary), 100/1A, 15VA, Class 0.2s, STC 18.4kA/1sec SR4B3C1S10 2/3 Single ratio (Primary), 100/5A, 10VA, Class 0.2, STC 18.4kA/3sec SR5B4C2S10 2/3 Single ratio (Primary), 200/5A, 15VA, Class 0.2s, STC 18.4kA/3sec SR5B4C4S10 2/3 Single ratio (Primary), 200/5A, 15VA, Class 0.5, STC 18.4kA/3sec SR5B4C5S10 2/3 CT Type Single ratio (Primary), 200/5A, 15VA, Class 0.5s, STC 18.4kA/3sec SR6B1C5S9 2/3 Single ratio (Primary), 300/5A, 5VA, Class 0.5s, STC 18.4kA/1sec SR6B4C1S10 2/3 Single ratio (Primary), 300/5A, 15VA, Class 0.2, STC 18.4kA/3sec SR7B4C5S10 2/3 Single ratio (Primary), 400/5A, 15VA, Class 0.5s, STC 18.4kA/3sec SR8B4C4S9 2/3 Single ratio (Primary), 500/5A, 15VA, Class 0.5, STC 18.4kA/1sec SR9B3C4S12 2/3 Single ratio (Primary), 630/5A, 10VA, Class 0.5, STC 20kA/3sec SR9B3C5S11 2/3 Single ratio (Primary), 630/5A, 10VA, Class 0.5s, STC 20kA/1sec DR10B2C5S11 2/3 Dual ratio (Primary), 50/25/5A, 7.5VA, Class 0.5s, STC 20kA/1sec DR10B3C5S6 2/3 Dual ratio (Primary), 50/25/5A, 10VA, Class 0.5s, STC 16kA/1sec DR10B3C5S6 2/3 Dual ratio (Primary), 50/25/5A, 10VA, Class 0.5s, STC 16kA/1sec DR10B3C5S6 2/3 Dual ratio (Primary), 50/25/5A, 10VA, Class 0.5s, STC 8kA/0.5sec DR10B3C5S2 2/3 Dual ratio (Primary), 100/50/5A, 7.5VA, Class 0.5, STC 13.1kA/0.5sec DR12B2C4S4 2/3 Dual ratio (Primary), 100/50/5A, 7.5VA, Class 1.0s, STC 18.4kA/1sec DR12B2C8S9 2/3 Dual ratio (Primary), 100/50/5A, 7.5VA, Class 1.0s, STC 18.4kA/1sec DR12B2C8S9 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5s, STC 12.5kA/1sec DR12B3C5S3 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5s, STC 16kA/1sec DR12B3C5S6 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5s, STC 8kA/0.5sec DR12B3C5S2 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5,16kA/1sec DR12B3C4S6 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5s, STC 12.5kA/1sec DR12B3C5S3 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5s, STC 16kA/1sec DR12B3C5S6 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5s, STC 16kA/3sec DR12B3C5S7 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5s, STC 16kA/3sec DR12B3C5S7 2/3 Dual ratio (Primary), 100/50/5A, 10VA, Class 0.5s, STC 20kA/1sec DR12B3C5S11 2/3 Dual ratio (Primary), 100/50/5A, 15VA, Class 0.5, STC 18.4kA/3sec DR12B4C4S10 2/3 Dual ratio (Primary), 100/50/5A, 15VA, Class 0.5, STC 16kA/1sec DR12B4C4S6 2/3 Dual ratio (Primary), 100/50/5A, 15VA, Class 0.5, STC 20kA/1sec DR12B4C4S11 2/3 Dual ratio (Primary), 100/50/5A, 15VA, Class 1.0, STC 13.1kA/1sec DR12B4C7S5 2/3 Dual ratio (Primary), 120/60/5A, 15VA, Class 0.5, STC 18.4kA/1sec DR13B4C4S9 2/3 Dual ratio (Primary), 120/60/5A, 15VA, Class 0.5s, STC 16kA/3sec DR13B4C5S7 2/3 Dual ratio (Primary), 150/75/5A, 10VA, Class 0.5s, STC 20kA/3sec DR14B3C5S12 2/3 Dual ratio (Primary), 150/75/5A, 10VA, Class 0.5s, STC 20kA/3sec Dual ratio (Primary), 200/100/1A, 10VA, Class 0.2, STC 18.4kA/3sec DR14B3C5S12 2/3 DR15B3C1S10 2/3 Dual ratio (Primary), 200/100/5A, 5VA, Class 0.5s, STC 18.4kA/1sec DR16B1C5S9 2/3 Dual ratio (Primary), 200/100/5A, 5VA, Class 0.5, STC 18.4kA/1sec DR16B1C4S9 2/3 o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o Page 61 CT - Current Transformer Reference Number Number of CT’s Dual ratio (Primary), 200/100/5A, 7.5VA, Class 1.0, STC 18.4kA/1sec DR16B2C7S9 2/3 Dual ratio (Primary), 200/100/5A, 7.5VA, Class 1.0s, STC 18.4kA/1sec DR16B2C8S9 2/3 Dual ratio (Primary), 200/100/5A, 10VA, Class 0.5s, STC 16kA/3sec DR16B3C5S7 2/3 Dual ratio (Primary), 200/100/5A, 10VA, Class 0.5s, STC 16kA/3sec DR16B3C5S7 2/3 Dual ratio (Primary), 200/100/5A, 10VA, Class 0.5, STC 12.5kA/1sec DR16B3C4S3 2/3 Dual ratio (Primary), 200/100/5A, 10VA, Class 0.5, STC 16kA/1sec DR16B3C4S6 2/3 Dual ratio (Primary), 200/100/5A, 10VA, Class 0.5s, STC 12.5kA/1sec DR16B3C5S3 2/3 Dual ratio (Primary), 200/100/5A, 10VA, Class 0.5s, STC 16kA/3sec DR16B3C5S7 2/3 Dual ratio (Primary), 200/100/5A, 10VA, Class 0.5s, STC 16kA/3sec DR16B3C5S7 2/3 Dual ratio (Primary), 200/100/5A, 10VA, Class 0.5s, STC 20kA/1sec DR16B3C5S11 2/3 Dual ratio (Primary), 200/100/5A, 15VA, Class 0.5s, STC 18.4kA/3sec CT Type DR16B4C5S10 2/3 Dual ratio (Primary), 300/50/5A, 15VA, Class 0.5, STC 16kA/1sec DR17B4C4S6 2/3 Dual ratio (Primary), 300/150/5A, 10VA, Class 0.5s, STC 20kA/3sec DR18B3C5S12 2/3 Dual ratio (Primary), 300/150/5A, 15VA, Class 1.0s, STC 16kA/1sec DR18B4C8S6 2/3 Dual ratio (Primary), 400/200/5A, 10VA, Class 0.5, STC 12.5kA/1sec DR19B3C4S3 2/3 Dual ratio (Primary), 400/200/5A, 10VA, Class 0.5s, STC 12.5kA/1sec DR19B3C5S3 2/3 Dual ratio (Primary), 400/200/5A, 10VA, Class 0.5s, STC 16kA/3sec DR19B3C5S7 2/3 Dual ratio (Primary), 400/200/5A, 10VA, Class 1.0, STC 20kA/3sec DR19B3C7S12 2/3 Dual ratio (Primary), 400/200/5A, 15VA, Class 0.5, STC 18.4kA/1sec DR19B4C4S9 2/3 Dual ratio (Primary), 400/200/5A, 15VA, Class 0.5s, STC 18.4kA/1sec DR19B4C5S9 2/3 Dual ratio (Primary), 400/200/5A, 15VA, Class 0.5s, STC 20kA/1sec DR19B4C5S11 2/3 Dual ratio (Primary), 400/200/5A, 20VA, Class 0.25s, STC 18.4kA/3sec DR19B5C3S10 2/3 Dual ratio (Primary), 400/300/5A, 15VA, Class 0.2s, STC 16kA/1sec DR20B4C2S6 2/3 Dual ratio (Primary), 600/200/5A, 10VA, Class 0.5s, STC 16kA/3sec DR21B3C5S7 2/3 Dual ratio (Primary), 600/300/5A, 7.5VA, Class 1.0, STC 18.4kA/1sec DR22B2C7S9 2/3 Dual ratio (Primary), 600/300/5A, 10VA, Class 0.5s, STC 18.4kA/1sec DR22B3C5S9 2/3 Dual ratio (Primary), 600/400/1A, 10VA, Class 0.5s, STC 16kA/3sec DR23B3C5S7 2/3 Dual ratio (Primary), 600/400/5A, 10VA, Class 0.5s, STC 16kA/3sec DR24B3C5S7 2/3 Dual ratio (Primary), 600/400/15A, 15VA, Class 0.5, STC 18kA/3sec DR25B4C4S8 2/3 Triple ratio (Primary), 30/20/10/5A, 10VA, Class 0.5, STC 6.7kA/1sec TR26B3C4S1 2/3 Triple ratio (Primary), 50/25/10/5A, 15VA, Class 0.5s, STC 6.7kA/1sec TR27B4C5S1 2/3 Triple ratio (Primary), 200/100/50/5A, 10VA, Class 0.5s, STC 16kA/3sec TR28B3C5S7 2/3 Triple ratio (Primary), 200/100/50/5A, 10VA, Class 0.5s, STC 16kA/1sec TR28B3C5S6 2/3 Triple ratio (Primary), 200/100/50/5A, 10VA, Class 0.5s, STC 16kA/3sec TR28B3C5S7 2/3 Triple ratio (Primary), 200/100/50/5A, 10VA, Class 0.5s, STC 18.4kA/1sec TR28B3C5S9 2/3 Triple ratio (Primary), 200/100/50/5A, 15VA, Class 0.5s, STC 18.4kA/1sec TR28B4C5S9 2/3 Triple ratio (Primary), 200/100/50/5A, 15VA, Class 0.5s, STC 18.4kA/1sec TR28B4C5S9 2/3 Triple ratio (Primary), 400/200/100/5A, 10VA, Class 0.5s, STC 16kA/3sec TR29B3C5S7 2/3 Triple ratio(Primary), 600/300/150/5A, 15VA, Class 0.5m, STC 32kA/1sec TR30B4C6S14 2/3 Page 62 o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o o Accessories Shunt trip supply (110VAC to power shunt trip on RMU) Trip lock out relay Secondary wiring protection MCB Fuses o o o o Power meters Wiring for single meter Metering wiring Wiring for 2 meters Circutor Actaris Meter type Any other (*) 1 Number of meters 2 Meter mounting style Door mounted DIN mounted (window on the door) • o o o o o o o o Marshalling box gland plates Blank gland plate Gland plate with 1 hole (hole size) 20mm 25mm 20mm and 25mm Gland plate with 2 holes (hole sizes) 16mm and 25mm 20mm and 20mm 25mm and 25mm Any other hole sizes / combination(*) Key • Standard o o o o o o o o o Options Page 63 iv.Options and Accessories - continued Cable box, cable gland and gland plate selection table Metering unit Cable box internal arc rated (AFL) Top entry IP50 (standard) IP54 (optional) 450mm bushings to gland height,12.5KA IAC 610 mm bushings to gland height,12.5KA IAC Bottom entry (IP54) 450mm bushings to gland height, 12.5 kA IAC 610mm bushings to gland height, 12.5 kA IAC 450mm bushings to gland height, 20KA IAC 610mm bushings to gland height, 20KA IAC Cable box non IAC rated Top entry IP50 (standard) IP54 (optional) 450mm bushings to gland height 610mm bushings to gland height Bottom entry (IP54) 450mm bushings to gland height 610mm bushings to gland height 1 X 3C cable gland and gland plates X size Gland plates X size gland plate with earth stud Glands X tube glands X brass wiping gland Y size Gland plates Y size gland with earth stud Glands Y tube glands Y brass wiping gland Page 64 Incoming side (for FS only) Outgoing side (for FS and TC only) • o o o • o o o o o o o o o o o • o o o • o o o o o o o o o o o o o o o o o o o Cable box, cable gland and gland plat selection table Metering unit 3 x 1C cable gland and gland plates Gland plates 3 hole split steel with earth stud 3 hole solid brass with earth bar Incoming side (For FS only) Outgoing side (for FS and TC only) o o o o o o o o Glands Single core compression gland Single core heat shrink glands Bus bar coupling selection table Metering unit Incoming side (for FS only) Bus bar coupling kits (length mm) Insulation for bus bar coupling Heat shrink manufactured by SPS Heat shrink manufactured by Raychem Heat shrink manufactured by REPL Outgoing side (for FS and TC only) 500 750 o o • o o • Page 65 Air metering unit (AMU) order form To use this form, please photocopy and return the completed form to your nearest Lucy Electric office Tick the boxes with your required order (addresses can be found on the back cover) Name: Company: Address: Tel No: Fax No: Email: Order number: Order quantity / number of units (please fill separate form for each type) Metering units General Impulse withstand voltage (BIL) kVP (choose one from below) 12kV at 75KVP BIL 15.5kV at 95KVP BIL Rated current 250A 630A Mounting style FS: Freestanding BC: Bus bar connected TC: Ring main unit (tee-off ) mounted Bushings type FS: Freestanding Incoming DIN type C • Outgoing DIN type C • BC: Bus bar connected Incoming DIN type C • Outgoing DIN type C • TC: Ring main unit (tee-off ) mounted Incoming direct coonection to RMU • Outgoing DIN type C • VT - Voltage transformer VT Primary fused protection Unfused primary VT with tool-free bus bar isolation for VT testing (only for 630A) Fused primary VT VT Type Number of VT Dual ratio (Primary) 3 Phase - 3 limb 11000/6600/110V, class 1, 50VA/PH 1 Single ratio (Primary) 3 Phase - 3 limb 11000/110V, class 1, 50VA/PH 1 Single ratio (Primary) 3 Phase - 3 limb 6600/110V, class 1, 50VA/PH 1 Page 66 2 Single ratio (Primary) 1 Phase - 1 limb 13800/110V, class 0.5, 50VA/PH 3 2 Dual ratio (Primary) 1 Phase - 1 limb 11000/6600/110V, class 0.2, 50VA/PH 3 Single ratio (Primary) 3 Phase - 5 Limb, Ratio: 11000/110v, Class 0.5, 50VA/PH 1 Dual ratio (Primary) 3 Phase - 5 limb, Ratio: 11000/6600/110v, Class 0.5, 50VA/PH 1 Dual ratio (Primary) 3 Phase - 5 Limb, Ratio: 11000/6600/110v, Class 0.5, 20VA/PH 1 Dual ratio (Primary) 3 Phase - 5 Limb, Ratio: 11000/6600/110v, Class 0.5, 50VA/PH 1 CT - Current transformer CT Ratio change over link CT Type Number of CT Reference Number (*) Please insert the selected CT Reference Number Accessories Shunt trip supply (110VAC to power shunt trip on RMU) Trip lock out relay Secondary wiring protection MCB Fuses Power meters Wiring for single meter Metering wiring • Wiring for 2 meters Circutor Meter type Actaris Any other (#) 1 Number of meters 2 Meter mounting style Door mounted Din mounted (window on the door) Marshalling box gland plates Blank gland plate Gland plate with 1 hole (hole size) 20mm 25mm 20mm and 25mm Gland plate with 2 holes (hole sizes) 16mm and 25mm 20mm and 20mm 25mm and 25mm Any other hole sizes/ combination(#) # Please fill the details in comments section below. Comments Key • Standard Option select *For CT Reference Numbers check pages 59-60 Page 67 Sabre accessories order form To use this form, please photocopy and return the completed form to your nearest Lucy Electric office Tick the boxes with your required order (addresses can be found on the back cover) Name: Company: Address: Tel No: Fax No: Email: Order number: Order quantity / number of units (please fill separate form for each type) Cable box, cable gland and gland plate selection table Ring switch 1 Ring switch 2 Circuit breaker tee-off Interlocked cable box Extensible bus bars Metering unit (Not to be used with VRE and DSE) Incoming side (for FS only) Outgoing side (for FS and TC only) - - - • • • - - • • - - Cable box internal arc rated (AFL) Top entry IP50 (standard) • • • IP54 (optional) 450mm bushings to gland height,12.5KA IAC 610 mm bushings to gland height,12.5KA IAC Bottom entry (IP54) 450mm bushings to gland height, 12.5 kA IAC 610mm bushings to gland height, 12.5 kA IAC 450mm bushings to gland height, 20KA IAC 610mm bushings to gland height, 20KA IAC Bottom entry angled, 12.5KA IAC Bottom entry deep, 12.5KA IAC Cable box non IAC rated Top entry IP50 (standard) • • • • IP54 (optional) 450mm bushings to gland height 610mm bushings to gland height Bottom entry (IP54) 450mm bushings to gland height 610mm bushings to gland height Bottom entry angled Bottom entry deep 1 X 3C cable gland and gland plates X size Gland plates X size gland plate with earth stud Page 68 Cable box, cable gland and gland plate selection table Circuit Ring Ring Extensible breaker switch 1 switch 2 bus bars tee-off (Not to be used with VRE and DSE) Metering unit Incoming side (for FS only) Outgoing side (for FS and TC only) 1 X 3C cable gland and gland plates Glands X tube glands X brass wiping gland Y size Gland plates Y size gland with earth stud Glands Y tube glands Y brass wiping gland 3 x 1C cable gland and gland plates Gland plates 3 hole split steel with earth stud 3 hole split steel with earth bar 3 hole solid brass with earth stud 3 hole solid brass with earth bar Glands Single core compression gland Single core heat shrink glands Bus bar coupling selection table Bus bar coupling kits (length mm) 453 500 750 • - • - • - Insulation for bus bar coupling Heat shrink manufactured by SPS Heat shrink manufactured by Raychem Heat shrink manufactured by REPL Cold fit rubber boot manufactured by Pirelli Quantity Other accessories Padlocks TLF fuses (specify quantity and amp rating) Foundation bolts (not required for transformer mounting) Adaptor for converting parallel bushings to DIN400 type C connection Key • Standard Option select - Not applicable Page 69 Disclaimer Lucy Electric has a policy of continuous research and development and accordingly reserves the right to change the design and specification of its products without prior notice or liability. Lucy Electric worldwide offices Lucy Electric UK Ltd Howland Road, Thame, Oxfordshire, OX9 3UJ, United Kingdom Tel: +44 1844 267 267 General Tel: +44 1844 267 222 Sales Fax: +44 1844 267 223 Email: salesuk@lucyelectric.com Lucy Switchgear Arabia Co. Ltd Novotel Business Centre, P.O. Box 35340, Dammam 31488, Saudi Arabia Tel: +966 138 147 910 Fax: +966 138 147 914 Email: salessa@lucyelectric.com Lucy Middle East FZE PO Box 17335, Jebel Ali, Dubai, United Arab Emirates Tel: +971 48 129 999 Fax: +971 48 129 900 Email: salesme@lucyelectric.com Lucy Electric South Africa Pty. Ltd Unit 12 & 13, Block C, Honeydew Business Park, 1503 Street, Laser Park, Honeydew, 2170, South Africa Tel: +27 11 025 7490 Fax: +27 11 794 3277 Email: salesza@lucyelectric.com Lucy Electric (Thailand) Ltd 388 Exchange Tower, 37th Flr Unit 3702, Sukhumvit Road, Klongtoey Sub district, Klongtoey District, Bangkok, 10110, Thailand Tel: +66 (02) 663 4290 Fax: +66 (02) 663 4293 Email: salesth@lucyelectric.com Lucy Asia Pacific Sdn Bhd Unit 17-05-06, Level 17, PJX-HM Shah Tower, No.16 Persiaran Barat, 46050 Petaling Jaya, Selangor, Malaysia Tel: +603 74910700 Fax: +603 79316923 Email: salesmy@lucyelectric.com Lucy Equipamentos Elétricos Ltda. Av. das Araucárias 2558 Thomaz Coelho, CEP 83707-067, Araucária Paraná State, Brazil Tel: +55 (41) 2106 2801 Email: salesbrazil@lucyelectric.com Postal Address: P.O. Box 1078, Honeydew, 2040 Lucy Electric India Private Ltd H21, MIDC Ambad, Nasik 422010, India Tel: +91 253 2381603 Fax: +91 253 2381247 Email: salesIndia@lucyelectric.com LESA0920