Electric Power Systems Research 210 (2022) 108108 Contents lists available at ScienceDirect Electric Power Systems Research journal homepage: www.elsevier.com/locate/epsr Short-circuit calculation method for unbalanced distribution networks with doubly fed induction generators Fan Xiao a, *, Yongjun Xia a, Kanjun Zhang a, Zhe Zhang b, Xianggen Yin b a b Electric Power Research Institute of Hubei Electric Power Co., Ltd., Wuhan 430077, China; State Key Laboratory of Advanced Electromagnetic Engineering and Technology (Huazhong University of Science and Technology), Wuhan 430074, China A R T I C L E I N F O A B S T R A C T Keywords: New energy source Wind turbines Photovoltaic power Unbalanced distribution network Short circuit calculation Phase component In an unbalanced distribution network, transforming three-phase unbalanced components into components with positive, negative, and zero sequences is difficult. Moreover, the fault currents of doubly fed induction generators (DFIGs) exhibit a complex nonlinear relationship. The fault characteristics of DFIGs with an activated crowbar differ from those with a non-activated crowbar. Moreover, distinguishing between these two crowbar conditions based on calculations is difficult. Therefore, the traditional symmetric component method is unsuitable for unbalanced distribution networks with DFIGs owing to its low calculation accuracy. In this work, the equivalent calculation phase component models of DFIGs are analyzed using low-voltage control strategies. In particular, the activation criterion of crowbar protection in the time domain is proposed. A novel fault analysis method for unbalanced distribution networks with DFIGs is also proposed. The action condition of crowbar protection is assessed using the traversal method, and the coupling relationship among DFIGs is determined using an iterative calculation method. Finally, the effectiveness of the proposed fault analysis method is verified by simulation. 1. Introduction In power systems, accurate calculation of short-circuit currents is vital for the selection of electrical equipment, calculation of relay pro­ tection settings, and operation as well as control of grids. Traditional power grid fault analysis methods are primarily employed for symmet­ rical components. However, in unbalanced distribution networks, such methods are incapable of decoupling three-phase asymmetrical com­ ponents into positive-component, negative-component, and zero se­ quences. More specifically, in unbalanced distribution networks, the use of such methods can result in considerable errors between the calculated and actual fault values. Moreover, the fault currents of different types of new energy sources exhibit a complex nonlinear relationship, and it is difficult to calculate the short-circuit currents in power grids. Further­ more, under grid fault conditions, the crowbar of doubly fed induction generators (DFIGs) could either be activated or non-activated; therefore, it is difficult to accurately distinguish fault conditions using traditional fault analysis methods. An incorrect assessment of the crowbar condi­ tion leads to a significant deviation between the calculated and actual results. Therefore, it can be preliminary deduced that the traditional symmetrical component calculation method is unsuitable for computing the fault values of unbalanced distribution networks with DFIGs. Accurate fault calculation models of new energy power sources are the bases of fault analysis in power grids. Accordingly, the fault calcu­ lation model of an inverter-interfaced distributed generator (IIDG) can be considered equivalent to the current source model [1]. Fault calcu­ lation models used for DFIGs vary depending on the status of the crowbar, i.e., whether the crowbar is activated or non-activated. Under activated crowbar protection conditions, the fault calculation model for DFIGs is equivalent to the asynchronous motor model proposed in [2]. Under non-activated crowbar protection conditions, the low-voltage ride-through control strategies (LVRT) of DFIGs under symmetrical or unsymmetrical fault conditions have been implemented to enhance the safety of DFIGs [3–6]. Accordingly, the short-circuit current model of the DFIG under symmetrical fault conditions was developed [7]. Moreover, the transient response of DFIG under unsymmetrical fault conditions was also investigated [8]. Thus far, the short-circuit calcu­ lation model of DFIGs under unsymmetrical fault conditions has not been formulated. In particular, there are considerable differences in the fault currents of DFIGs under activated and non-activated crowbars; however, no assessment method for distinguishing the DFIG fault cur­ rents between the two crowbars has been formulated. For the fault analysis method, several studies have focused on the * Corresponding author. E-mail address: xiao103fan@163.com (F. Xiao). https://doi.org/10.1016/j.epsr.2022.108108 Received 16 March 2021; Received in revised form 8 May 2022; Accepted 15 May 2022 Available online 20 May 2022 0378-7796/© 2022 Elsevier B.V. All rights reserved. F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 A list of symbols DFIG IIDG LVRT RSC IDFIG,1 γDG,1 i+ sd i+ sq δU,1 UDFIGre,1 UDFIGim,1 IDFIG,2 γDG,2 − Isd isq δU,2 UDFIGre,2 UDFIGim,2 ZDFIG,1 ZDFIG,2 Lr σ R ;r Lm Lsσ s i∗rf R ′ double-fed induction generator inverter interfaced distributed generator low voltage ride through control rotor-side converter grid-side converter amplitude of the positive-sequence component in the fault current of the DFIG phase angle of the positive-sequence component in the fault current of the DFIG d-axis components of the stator current in (dq)+ synchronous rotating reference frames q-axis components of the stator current in (dq)+ synchronous rotating reference frames phase angle of positive-sequence component of the stator voltage real parts of the positive-sequence component in the stator voltage imaginary parts of the positive-sequence component in the stator voltage amplitude of the negative-sequence component in the fault current of the DFIG phase angle of the negative-sequence component in the fault current of the DFIG d-axis components of the stator current in (dq)synchronous rotating reference frames d-axis components of the stator current in (dq)synchronous rotating reference frames phase angle of negative-sequence component of the stator voltage real part of the negative-sequence component of the stator voltage imaginary part of the negative-sequence component of the stator voltage positive-sequence equivalent impedance in sequence networks negative-sequence equivalent impedance in sequence networks leakage reactance of the rotor ω1 i∗r udc0 C t0 Pg Pr n ZDFIGi,1 ZDFIGi.2 I˙DFIGi,a I˙DFIGi,b I˙DFIGi,c I˙DFIGi,1 I˙DFIGi,2 Uk Ik UDGm IDGm h Ik,a,sc short-circuit current calculation method of power grids with new energy sources. The IIDG in a power grid can be considered equivalent to a model with variable impedance and constant voltage source in series, PQ node, or PI node [9–11]. For power grids with IIDGs, a calculation method has been proposed for the short-circuit current contribution of current control inverter-based distributed generation sources [12]. Moreover, several improved iterative calculation methods based on symmetrical component calculation have also been proposed [13–15]. However, existing research has not considered unbalanced distribution networks and the activation of the DFIG crowbar. For power grids with DFIGs, the short-circuit calculation model of DFIGs based on the voltage of a grid-connected point is derived according to the LVRT strategy. Moreover, short-circuit calculation methods based on symmetrical component calculation have been proposed [16–17]. However, if the power grid structure is unbalanced, the calculation results obtained via traditional symmetrical component methods are most likely to deviate significantly from the actual results. In [16], the feeder was modified to be balanced in the symmetrical pre-fault state using line section pa­ rameters. In [17], the fault analysis of balanced power grids with distributed generators was based on the symmetrical component method. Existing fault calculation methods cannot satisfy the fault analysis requirements of unbalanced distribution networks. equivalent resistance of the rotor winding mutual inductance between the stator and rotor leakage reactance of the stator slip reference signal of the DFIG rotor current resistance synchronous angular velocity setting value of the rotor current under the condition of activated crowbar rated voltage of the DC bus capacitor of the DC bus time of failure output power of the GSC active power of the RSC number of grid nodes positive-sequence equivalent impedance of DFIG at i − th node under condition of activated crowbar negative-sequence equivalent impedance of DFIG at i − th node under the condition of activated crowbar short-circuit current injected by the DFIG at i − th node into the a-phase circuit short-circuit current injected by the DFIG at i − th node into the b-phase circuit short-circuit current injected by the DFIG at i − th node into the c-phase circuit short-circuit current injected by the DFIG at i − th node in the positive-sequence networks short-circuit current injected by the DFIG at i − th node in the negative-sequence networks three-phase voltage at the fault pointkafter modification of the phase component node admittance matrix three-phase current at the fault pointkafter modification of the phase component node admittance matrix three-phase voltage of the DFIG at the m − th node three-phase injection current of the DFIG at the m − th node h-th iteration ground current at node k Furthermore, a considerable difference exists in the DFIG fault current under activated and non-activated crowbar conditions, leading to a substantial deviation between calculated and actual results. Further­ more, existing fault calculation methods cannot determine whether the crowbar is activated. Hence, the above-mentioned short-circuit calcu­ lation methods cannot satisfy the fault analysis requirements of unbal­ anced distribution networks with DFIGs. In this study, a novel fault analysis method is proposed for unbal­ anced distribution networks with new energy sources. Existing fault analysis methods of power systems are based on the symmetrical component method. Consequently, they are unable to meet the fault analysis requirements of an unbalanced distribution network with new energy sources and cannot determine whether the crowbar of DFIGs is activated. Thus, the use of these methods can result in considerable errors between the calculated and actual fault values in unbalanced distribution networks with DFIGs. This article is organized as follows. Section 2 presents the phase component short-circuit calculation models of DFIGs under nonactivated and activated crowbar conditions. Moreover, the activation criterion of the crowbar protection in the time domain is also discussed. Section 3 elaborates on an improved phase component method for un­ balanced distribution networks with DFIGs. It also presents the 2 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 1. DFIG structure. components in the output current of the DFIG through the coordi­ nated control of RSC and GSC. 2) The LVRT strategy for the DFIG has a balanced stator current. The control target of this strategy involves eliminating components with a negative sequence in the output current of the DFIG. 3) The LVRT strategy for the DFIG has a constant electromagnetic tor­ que. The control target of this strategy involves eliminating doublefrequency components in the electromagnetic torque of the DFIG, thereby reducing the mechanical torsional vibration in the shaft system. calculation results obtained via an iterative method. The action condi­ tion of crowbar protection assessed by the traversal method is eluci­ dated. In Section 4, the results of the proposed method are compared with those of other methods. PSCAD/EMTDC is used to simulate and validate the effectiveness of the proposed fault analysis method. The results are discussed in this section. 2. Short-circuit calculation model of distribution network with DFIGs Each type of new energy source has a unique structure, LVRT strat­ egy, and protection device (such as a crowbar). Therefore, the shortcircuit current of different new energy sources can vary considerably. Therefore, it is necessary to formulate an equivalent short-circuit calculation model for new energy sources. The inverter power supply, such as the photovoltaic (PV) power supply and direct-drive wind tur­ bine, has the same short-circuit characteristics as those of a DFIG without crowbar action. Hence, the DFIG is used as an example for analysis in this work. The crowbar and rotor-side converter (RSC) have a significant in­ fluence on the fault current characteristics of the DFIG. Therefore, the short-circuit calculation models of the DFIG are established under acti­ vated and non-activated crowbar conditions. Fig. 1 Under the three-phase asymmetrical fault condition, the equivalent calculation model of the DFIG is identical to the controlled current source model in [3,4][3,4]. Accordingly, the positive-sequence compo­ nent of short-circuit current in the DFIG can be characterized as follows: ⎧ ⎪ I˙DFIG,1 = IDFIG,1 ∠γDG,1 ⎪ ⎪ ⎪ √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ ⎨ ( + )2 ( + )2 (1) I = isd + isq DFIG,1 ⎪ ⎪ ⎪ ⎪ + ⎩γ DG,1 = θI + δU,1 where IDFIG,1 and γDG,1 denote the amplitude and phase angle of the positive-sequence component in the DFIG fault current, respectively, + + + + and θ+ I = arctan[isq /isd ], where isd and isq represent the d-axis and q-axis components of the stator current in (dq)+ synchronous rotating refer­ ence frames, respectively. Moreover,δU,1 = arctan(UDFIGim,1 /UDFIGre,1 ) indicates the phase angle of the positive-sequence component of stator voltage. Finally, UDFIGre,1 and UDFIGim,1 represent the real and imaginary parts of the positive-sequence component of the stator voltage, respectively. Similarly, the negative-sequence component of the short-circuit current in the DFIG under the non-activated crowbar condition is characterized as follows: ⎧ ⎪ I˙DFIG,2 = IDFIG,2 ∠γDG,2 ⎪ ⎪ ⎪ √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ ⎨ ( − )2 ( − )2 (2) I = isd + isq DFIG,2 ⎪ ⎪ ⎪ ⎪ − ⎩γ DG,2 = θI + δU,2 2.1. Calculation model of DFIG under non-activated crowbar condition Under the non-activated crowbar condition, the fault current char­ acteristics of the DFIG are related to the LVRT strategy of the RSC and grid-side converter (GSC). According to the technical regulations of the wind farm power system reported in [18] and [19], the reactive power of the DFIG must be specified to ensure that the voltage requirement of the power grid is satisfied. Under asymmetric fault conditions, unbal­ anced heating, torque ripple, and output power oscillation could occur in the stator winding of the DFIG [18]. The LVRT strategy of DFIG was studied [5–8] to ensure the safety of the DFIG. The typical LVRT stra­ tegies for DFIGs are as follows. 1) The LVRT strategy for the DFIG has constant active power. The control target of this strategy involves eliminating double-frequency where IDFIG,2 and γDG,2 denote the amplitude and phase angle of the 3 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 is turned off when the rotor current flows through the crowbar. Under this condition, the fault current of the DFIG under the activated crowbar condition significantly differs from that under the non-activated crowbar condition. Accordingly, a novel equivalent short-circuit calcu­ lation model of the DFIG needs to be established. As reported in [20], the steady-state fundamental frequency component of the DFIG can be considered equivalent to an asynchronous motor model. Accordingly, the equivalent impedance of the DFIG in the positive-sequence and negative-sequence networks can be obtained as follows: ( ⎧ ′) ⎪ ⎪ ZDFIG,1 = jω1 Lsσ + jω1 Lrσ + Rr ‖ jω1 Lm ⎪ ⎨ s (3) ( ) ′ ⎪ ⎪ ⎪ ⎩ ZDFIG,2 = jω1 Lsσ + jω1 Lrσ + Rr ‖ jω1 Lm 2− s where ZDFIG,1 and ZDFIG,2 denote the positive-sequence and negativesequence equivalent impedances in sequence networks, ′ respectively.Lrσ symbolizes the rotor leakage reactance, Rr denotes the equivalent resistance of rotor winding, Lm represents the mutual inductance between stator and rotor, Lsσ denotes the stator leakage reactance, andsis the slip. The equivalent DFIG circuit in the sequence networks under an activated crowbar condition is shown in Fig. 3. 2.3. Activation criterion of crowbar protection Considering that the crowbar activation is based on the overcurrent of the RSC or the overvoltage of the direct current (DC) bus, the acti­ vation criteria of the crowbar under the two conditions are investigated. Fig. 2. Equivalent crowbar condition. circuit of the DFIG under the 2.3.1. RSC Over-current According to Mohammadi et al. [3,4], the DFIG rotor current can be ascertained using the following relationships: ⎧ ′ ⎨ i+ (t) = i+∗ + Kd ⋅K+ e− Rs t/L s sin(ω1 t + θ1 ) rd+ rdf + (4) ⎩ i+ (t) = i+∗ + K ⋅K e− Rs t/L′ s cos(ω t + θ ) d + 1 1 rq+ rqf + non-activated negative-sequence component in the DFIG fault current, respectively, and θ−I = arctan[i−sq /i−sd ], where isd and isd represent the d-axis and q-axis components of the stator current in (dq)− synchronous rotating refer­ ence frames, respectively. Moreover,δU,2 = arctan(UDFIGre,2 /UDFIGim,2 ) indicates the phase angle of the negative-sequence component of stator voltage. Finally, UDFIGre,2 and UDFIGim,2 represent the real and imaginary parts of the negative-sequence component of stator voltage, respectively. + − i Under fault conditions, i+ sd , isq , Isd , and Isq are related to the reference rotor current value, which can be calculated according to the LVRT strategy for the DFIG. Therefore, the equivalent DFIG model under asymmetric fault conditions can be derived by substituting the d-axis and q-axis components of the DFIG’s short-circuit current into Eqs. (1) and (2). Under symmetric fault conditions, there is no negative-sequence component in the short-circuit current of the DFIG. In other words, the amplitude of the negative-sequence component in Eq. (2) is zero, and the controlled negative-sequence current source model is disconnected from the negative-sequence equivalent circuit. The equivalent DFIG model in the sequence networks of the power grid is depicted in Fig. 2. The fault current characteristics of the IIDG are the same as those of the DFIG under the non-activated crowbar condition. Therefore, the IIDG can be considered to be equivalent to a controlled current source model. The corresponding equivalent model of short-circuit calculation can be formulated according to the LVRT scheme of the IIDG. ⎧ ⎨ i− (t) = i− ∗ rd− rdf − + Kd ⋅K− e− ⎩ i− (t) = i− ∗ − K ⋅K e− d − rq− rqf − Rs t/L Rs t/L ′ ′ s s sin(ω1 t + θ2 ) cos(ω1 t + θ2 ) (5) where Kd = Lm /(σ Ls Lr ); “∗” indicates the reference signal, i∗rf denotes the reference signal of the DFIG’s rotor current, and R denotes the resis­ tance. Subscripts r and s indicate the rotor and stator, respectively; ω1 symbolizes the synchronous angular velocity;K+ = √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ √̅̅̅̅̅̅̅̅̅̅̅ (9Us+ − 17Usn )2 + 72U2s+ /(17ω1 ); K− = 3Us− /( 17ω1 ); θ1 = √̅̅̅ √̅̅̅ ′ arctan[6 2Us+ /(17Usn − 9Us+ )]; θ2 = arctan (2 2 /3); and Ls = Ls − 2 Lm /Lr . When the rotor current exceeds the activation value of the crowbar, crowbar resistance is activated. Therefore, the crowbar is activated if the following condition is satisfied: +2 − 2 − 2 ∗2 i2r (t) =i+2 rd+ (t)+irq+ (t)+ird− (t)+irq− (t) ≥ ir (6) where i∗r indicates the setting value of the rotor current under the acti­ vated crowbar condition. 2.3.2. DC capacitor of over-voltage According to the RSC circuit, GSC circuit, and capacitor, the voltage equation of the capacitance can be expressed as follows: / ∫t ( ) u2dc (t) = u2dc0 + 2 Pr − Pg dt C (7) 2.2. Calculation model of DFIG under activated crowbar condition Under fault conditions, the switching device of the crowbar is usually turned on, and the crowbar can be maintained in a short-circuited state to ensure the safe operation of the RSC. The switching device of the RSC t0 where udc0 and C are the rated voltage and capacitance of the DC bus, 4 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 3. Equivalent circuit of DFIG considering the influence of crowbar. Fig. 4. Outer voltage control loop of the GSC. respectively, t0 denotes the time of failure, Pg is the GSC output power, and Pr denotes the RSC active power. If Δudc is assumed as the fault component of the DC bus voltage, then udc = udc0 + Δudc exists under fault conditions. Generally, the DC bus voltage does not exceed 1.1 times the rated voltage, therefore, Δu2dc can be neglected. According to Eq. (7), Δudc can be derived as follows. / ∫t ( Pr − Pg )dt Cudc0 Δudc (t) = (8) Thus, we obtain the following. p2 Δudc (t)+ The outer voltage control loop of the GSC is depicted in Fig. 4. The output current of the GSC can fast-track the reference value. Hence, the current value of the GSC can be considered approximately equal to the reference value of the GSC. Accordingly, Δudc can be rewritten as follows: ] [∫ t / ∫t ∫t Δudc (t) = (9) Pr dt − ugd ki Δudc (t)dt)dt + kp Δudc (t) Cudc0 t0 (10) By assuming that the GSC output current is continuous when the failure occurs, i.e., igd (t0− ) = igd (t0+ ), the definite solution of (10) can be obtained as follows: { ( ( Δu)dc (t(0 ) =)/0 (11) pΔudc (t0 ) = Pr − ugd t0+ igd t0+ Cudc0 = Us+ Pr /CUs udc0 t0 t0 kp ugd ki ugd pΔudc (t)+ Δudc (t) = 0 Cudc0 Cudc0 where Us indicates the rated voltage of the DFIG. Eq. (10) is a second-order homogeneous differential equation with constant coefficients; hence, it can have two conjugate complex roots and two mutually different real roots. In this study, both cases are considered. (1) Eq. (10) has two distinct roots. 0 5 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 5. Flowchart of short-circuit current calculation method for unbalanced distribution network with DFIGs. Under this condition, Δudc can be derived by combining Eqs. (10) and (11). Δudc (t) = N1 e− λ1 t − N1 e − λ2 t Under this condition, Δudc can be obtained according to Eqs. (10) and (11). (12) Δudc (t) = N2 e− αt sin(βt) (13) √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ where N2 = 2Us+ Pr /CUs udc0 4ki σ − k2p σ2 ; α = kp σ /2; and β = √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ 4ki σ − k2p σ 2 /2. √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ where λ1 = (kp σ − k2p σ 2 − 4ki σ ) /2; σ = ugd /Cudc0 ; λ2 = (kp σ + √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ k2p σ2 − 4ki σ) /2; and N1 = 2Us+ Pr /CUs udc0 k2p σ 2 − 4ki σ. According to the conservation principle of power, the sum of the output active powers of RSCPr and statorPs is equal to the output wind (2) Eq. (10) also has two conjugate complex roots. 6 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 6. Single-line diagram of IEEE 13 node feeder with DFIGs. TABLE 1 Branch currents when a three-phase fault occurs at f. Branch 650-632 632-633 633-634 632-645 645-646 632-671 671-680 671-692 692-675 671-684 684-652 684-611 DG1 DG2 Measured values Phase A Mag. Ang. (kA) (◦ ) 4.42 -66 0.076 -35 0.66 -35 / / / / 4.49 -65 4.6 -68.5 0.28 69 0.068 -23 0.013 -36 0.013 -35.8 / / 1.2 -55 1.54 -126 Phase B Mag. (kA) 4.38 0.059 0.51 0.117 0.039 4.36 4.5 0.25 0.012 / / / 1.2 1.52 Ang. (◦ ) 161 -158 -158 -145.5 -120 162 161 -30 -167 / / / -175 114 Phase C Mag. (kA) 4.38 0.059 0.51 / / 3.74 3.85 0.24 0.052 0.02 / 0.02 1.2 1.53 Ang. (◦ ) 49 82 83 / / 50 47 -176 82 118 / 118 65 -5.8 Calculated values Phase A Mag. Ang. (kA) (◦ ) 4.31 -65 0.076 -36.5 0.65 -36 / / / / 4.4 -64 4.5 -67.5 0.28 64 0.07 -28 0.01 -41 0.01 -41 / / 1.19 -57 1.53 -126 Phase B Mag. (kA) 4.29 0.06 0.5 0.116 0.04 4.3 4.4 0.24 0.01 / / / 1.19 1.53 Ang. (◦ ) 163.5 -160 -160 -146.5 -120.5 163.5 162 -36 -172 / / / -177 114 Phase C Mag. (kA) 4.29 0.06 0.5 / / 3.67 3.76 0.24 0.05 0.02 / 0.02 1.19 1.53 Ang. (◦ ) 50.5 81 81 / / 51.5 48 -177.5 78.5 114 / 114.5 63 -6 Calculated values Phase A Mag. Ang. (kV) (◦ ) 2.4 0 1.48 -0.7 1.48 -0.6 0.165 -1.6 / / / / 0.5 -7.5 0 / 0.5 -7.3 0.5 -7.6 0.5 -7.2 0.5 -7.2 / / Phase B Mag. (kV) 2.4 1.47 1.485 0.166 1.45 1.45 0.53 0 0.53 0.53 / / / Ang. (◦ ) -120 -120.7 -121.6 -121.6 -120 -120 -129.5 / -129.5 -130 / / / Phase C Mag. (kV) 2.4 1.47 1.485 0.166 1.48 1.48 0.53 0 0.54 0.54 0.535 / 0.53 Ang. (◦ ) 120 119.3 118.4 118.4 120 120 114.5 / 114.4 114.5 114.3 / 114.2 TABLE 2 Node voltages when a three-phase fault occurs at f. Node 650 632 633 634 645 646 671 680 692 675 684 652 611 Measured values Phase A Mag. Ang. (kV) (◦ ) 2.4 0 1.45 2.3 1.497 0.3 0.166 -0.7 / / / / 0.49 -2 0 / 0.48 -2 0.48 -2.3 0.48 -2 0.485 -1.95 / / Phase B Mag. (kV) 2.4 1.44 1.497 0.167 1.46 1.465 0.52 0 0.52 0.52 / / / Ang. (◦ ) -120 -119 -120 -121 -121 -121 -125 / -125 -125.5 / / / Phase C Mag. (kV) 2.4 1.44 1.497 0.167 1.5 1.5 0.52 0 0.53 0.53 0.53 / 0.52 Ang. (◦ ) 120 119 120 119 120 120 118 / 118.5 118.6 118.5 / 118 turbine active powerP0 . Thus, the output active power of RSC can be expressed as follows: / / Ls − Lm i−rdf∗ − Us− Ls Pr = P0 − Ps = P0 − Lm i+∗ (14) rdf + Us+ where u∗dc denotes the threshold value of voltage in the DC bus when the crowbar is activated. The crowbar is activated if the following condition is satisfied. 7 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 7. Deviation between the simulated and calculated values of branch currents (under three-phase fault conditions). udc0 + Δudc t ≥ u∗dc should be developed for unbalanced distribution networks with DFIGs. In the present study, an improved short-circuit calculation method based on the traditional phase component calculation is proposed for unbalanced distribution networks with DFIGs. The principle steps of the traditional phase component calculation method are as follows. First, the phase component node admittance matrix is established according to the power system network under normal conditions and then modi­ fied according to the various types of grid faults. Second, the phase component node voltage equation is established such that the threephase node voltage and three-phase current of each branch can be solved analytically. However, the short-circuit current characteristics of DFIGs are more complex than those of the traditional synchronous generators. In particular, the LVRT strategy has a significant impact on the short-circuit current when the crowbar is activated. A non-linear relationship between output current and stator voltage exists. There­ fore, the traditional phase component short-circuit calculation method cannot satisfy the requirements for the analysis of unbalanced distri­ bution networks with DFIGs. (15) 3. Short-circuit calculation method for unbalanced distribution networks with DFIGs For unbalanced power grids with DFIGs, the improved short-circuit calculation method based on symmetrical component calculation can satisfy the short-circuit calculation requirement of the power system. For an asymmetrical power grid with DFIGs, the distribution network may exhibit unbalanced phase load, unbalanced line impedance and admittance, and possible asymmetrical structures of some transformers in. A complex coupling relationship may also exist among the networks with positive, negative, and zero sequences. Consequently, it is difficult to accurately decouple the three-phase power components into positivesequence, negative-sequence, and zero-sequence coordinates of the power grid. A considerable deviation between the calculated and actual values is expected if an improved calculation method based on the traditional symmetrical component analysis is employed to compute the short-circuit current of the unbalanced distribution network with DFIGs. It has a substantial impact on the protection setting, grid operation, and equipment selection. Therefore, a new short-circuit calculation method 8 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 8. Deviation between the simulated and calculated values of node voltages (under three-phase fault conditions). TABLE 3 Branch currents under the condition that two-phase fault occurs at f. Branch 650-632 632-633 633-634 632-645 645-646 632-671 671-680 671-692 692-675 671-684 684-652 684-611 DG1 DG2 Measured values Phase A Mag. Ang. (kA) (◦ ) 0.308 -31.5 0.086 -34.8 0.72 -34 / / / / 0.39 -16.2 0 / 0.115 24.2 0.22 -21 0.06 -33 0.06 -33 / / 1.3 -34 1.17 -53 Phase B Mag. (kA) 3.38 0.067 0.6 0.125 0.038 3.33 3.42 0.2 0.03 / / / 1.3 1.17 Ang. (◦ ) -167 -170 -169 -155 -119 -165 -163 31 159 / / / -154 -173 Phase C Mag. (kA) 3.38 0.067 0.6 / / 3.17 3.42 0.16 0.12 0.04 / 0.045 1.3 1.17 Ang. (◦ ) 17.7 95 96 / / 18.88 17 -147 122 159 / 158.8 86 67 3.1. Phase component node admittance matrix under normal condition According to the phase component model of each power component, the phase component node admittance matrix under normal conditions can be established as follows: 9 Calculated values Phase A Mag. Ang. (kA) (◦ ) 0.3 -29.5 0.085 -35 0.73 -35 / / / / 0.395 -16 0 / 0.12 24.5 0.23 -21 0.06 -33 0.06 -33 / / 1.285 -36 1.14 -55 Phase B Mag. (kA) 3.3 0.07 0.595 0.127 0.038 3.25 3.34 0.2 0.03 / / / 1.285 1.14 Ang. (◦ ) -165.7 -170 -170 -156 -120 -163 -161 30 159 / / / -156 -175 Phase C Mag. (kA) 3.17 0.07 0.595 / / 3.1 3.34 0.165 0.115 0.04 / 0.04 1.285 1.14 Ang. (◦ ) 19.5 95 95 59.5 / 21 19 -148 121 157 / 157 84 65 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 TABLE 4 Node voltages under the condition that two-phase fault occurs at f. Node 650 632 633 634 645 646 671 680 692 675 684 652 611 Measured values Phase A Mag. Ang. (kV) (◦ ) 2.4 0 2.394 0.819 2.396 1.044 0.2696 0.342 / / / / 2.316 0.66 2.3 1.86 2.316 0.65 2.3 0.42 2.31 0.65 2.29 0.76 / / Phase B Mag. (kV) 2.4 1.74 1.748 0.1968 1.722 1.72 1.26 1.18 1.26 1.268 / / / Ang. (◦ ) -120 -132.8 -132.1 -132.9 -133 -133.1 -159.2 179.8 -159 -159 / / / Phase C Mag. (kV) 2.4 1.74 1.748 0.1968 1.758 1.755 1.26 1.15 1.24 1.24 1.24 / 1.236 Ang. (◦ ) 120 133.1 133.5 132.8 133 133.2 159 179.6 159 159 158 / 158 Calculated values Phase A Mag. Ang. (kV) (◦ ) 2.4 0 2.36 0.7 2.36 0.9 0.266 0.19 / / / / 2.28 0.4 2.26 1.6 2.28 0.4 2.26 0.2 2.27 0.5 2.26 0.65 / / Phase B Mag. (kV) 2.4 1.73 1.74 0.196 1.68 1.68 1.29 1.14 1.3 1.3 / / / Ang. (◦ ) -120 -133 -133 -133 -133 -133 -159 179 -159 -159.5 / / / Fig. 9. Deviation between the simulated and calculated values of branch currents (under phase-to-phase fault conditions). 10 Phase C Mag. (kV) 2.4 1.74 1.74 0.196 1.72 1.72 1.18 1.14 1.18 1.18 1.18 / 1.18 Ang. (◦ ) 120 132 133 133 133 133 157 179 157 157 157 / 157 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 10. Deviation between the simulated and calculated values of node voltages (under phase-to-phase fault conditions). ⎧ ⎪ ⎪ ⎡ ⎪ ⎪ Y11 Y12 ⎪ ⎪ ⎪ ⎪ ⎢Y ⎪ ⎪ Y22 21 ⎢ ⎪ ⎪ Y=⎢ ⎪ ⎪ ⎣ ... ... ⎪ ⎪ ⎪ ⎪ ⎨ Yn1 Yn2 ⎡ ⎪ ⎪ ij ij ⎪ ⎪ ⎪ ⎢ Yaa Yab ⎪ ⎪ ⎢ ij ij ⎪ ⎪ Y Ybb ⎪ Yij = ⎢ ⎪ ⎣ ba ⎪ ij ij ⎪ ⎪ Yca Ycb ⎪ ⎪ ⎪ ⎪ ⎩ Y1n ... Y2n ⎥ ⎥ ⎥ ... ⎦ ... ... ij Yac ij Ybc ij Ycc at the ith node; ZDFIGi,1 and ZDFIGi.2 represent the positive and negativesequence equivalent impedances of DFIG at the ith node under the activated crowbar condition, respectively. Under the non-activated crowbar condition, the short-circuit current of DFIG is related to the LVRT strategy. Combining Eqs. (1) and (2), the phase component short-circuit calculation model of the DFIG becomes equivalent to the controlled current source phase component model, which is expressed as follows. ⎡ ⎤ ⎤ ⎡ I˙DFIGi,a I˙DFIGi,1 − 1 ⎣ I˙DFIGi,b ⎦ = S ⎣ I˙DFIGi,2 ⎦ (18) I˙DFIGi,c 0 ⎤ ... Ynn ⎤ (16) ⎥ ⎥ ⎥ ⎦ where n denotes the number of grid nodes, and i and j are node indices. where I˙DFIGi,a , I˙DFIGi,b , and I˙DFIGi,c represent the three-phase short-circuit currents injected by the DFIG at the ith node into the circuits of Phases A, B, and C, respectively. I˙DFIGi,1 and I˙DFIG,2 represent the short-circuit current injected by the DFIG at the ith node in the positive-sequence and negative-sequence networks, respectively. If the LVRT strategy for a DFIG is adopted to eliminate the negativesequence components in the fault current, then the components in the DFIG fault current can be reduced to zero. The short-circuit calculation model for the phase components of the DFIG can be expressed as IDFIGi,120 = [ I˙DFIGi,1 0 0 ]T . 3.2. Phase component model of DFIG Under the activated crowbar condition, the equivalent DFIG model in the power system can be considered equivalent to an asynchronous motor model. The phase component short-circuit calculation model of the DFIG can be expressed as follows: ⎡ ⎤ ⎡ ⎤ ZDFIGi,a ZDFIGi,1 ⎣ ZDFIGi,b ⎦ = S− 1 ⎣ ZDFIGi,2 ⎦ (17) ZDFIGi,c 0 ⎡ ⎤ 1 1 1 ∘ ∘ 2 ⎣ where S = a a 1 ⎦, a = ej120 , and a2 = ej240 ; ZDFIGi,a , ZDFIGi,b , 2 a a 1 and ZDFIGi,c represent the three-phase equivalent impedances of the DFIG 3.3. Node voltage equation based on fault types − 1 Under the non-activated crowbar condition, the short-circuit current of other branches increases when the short-circuit current of DFIG is 11 F. Xiao et al. TABLE 5 Branch currents when the two-phase grounding fault occurs at f. Branch 12 Phase A Mag. (kA) 1.6 Ang. (◦ ) -145 Phase B Mag. (kA) 1.79 Ang. (◦ ) 100 Phase C Mag. (kA) 1.1 Ang. (◦ ) -29 Proposed method Considering the activation of crowbar (The crowbar of DFIG 2 is activated) Phase A Phase B Mag. Ang. Mag. Ang. (kA) (◦ ) (kA) (◦ ) 1.6 -145 1.78 100 0.162 162 0.178 42 0.159 -78 0.162 162 0.178 42 0.16 -78 0.149 160 0.169 38.3 0.159 -80.7 0.062 164 0.065 44 0.081 -72 0.064 164 0.066 44 0.082 -72 0.083 -74 0.066 166.6 0.065 45.5 / / 0.135 136.7 / / / / 0.136 136.8 / / / / 0.135 136.4 / / / / 0.063 132 / / / / 0.065 133 / / / / 0.063 132.3 / / 0.129 -127 0.102 109 0.146 -8.44 0.131 -128 0.106 108 0.148 -8.2 0.387 -125.7 0.375 109 0.327 -3 0.515 -148 0.574 127 0.01 32 0.512 -146 0.58 128 0.01 33 0.742 -177 0.887 109 0.015 8.5 0.213 -10.3 0.241 -22 0.33 -10.6 0.213 -10 0.242 -21 0.33 -10.8 0.586 -24.7 0.465 -71.9 0.295 -4.76 0.0005 -156 0.00015 -164 0.02 60 0.0005 -156 0.0001 -164 0.02 60 0.0005 0 0.00025 171 0.0294 31.3 0.11 -132 / / 0.047 25 0.11 -132 / / 0.046 24 0.0027 -174 / / 0.0161 -174 / / / / 0.049 -149 / / / / 0.048 -150 0.0161 -173.6 / / / / / / / / 0.01 26.3 / / / / 0.01 26.2 / / / / 0.0155 0.57 0.213 0.207 170 -39 0.24 0.208 158 -153 0.291 0.204 159 83 0.214 0.207 170 -38 0.24 0.207 158 -158 0.29 0.207 158 82 0.207 0.207 156 -36 0.207 0.207 36 -156 0.207 0.207 -84 84 Without considering the activation of crowbar (Balanced stator current strategy of DFIGs) Phase C Mag. (kA) 1.1 Ang. (◦ ) -29 Phase A Mag. (kA) 0.46 Ang. (◦ ) -143 Phase B Mag. (kA) 0.56 Ang. (◦ ) 89.5 Phase C Mag. (kA) 0.397 Ang. (◦ ) 25.2 Electric Power Systems Research 210 (2022) 108108 650632 632633 633634 632645 645646 632671 671680 671692 692675 671684 684652 684611 DG1 DG2 Measured values F. Xiao et al. added to the grid. Under the activated crowbar condition, the DFIG is equivalent to an asynchronous motor model, and the short-circuit cur­ rent of other branches decreases. Therefore, the phase component node admittance matrix is established based on the non-activated crowbar condition. Note that the crowbar condition has to be determined. If the crowbar is activated, then the phase component node admittance matrix must be modified according to Eq. (3). If the crowbar is not activated, then the phase component node admittance matrix under normal con­ ditions can be used directly. The phase component nodal admittance matrixY is established ac­ cording to the fault types of the unbalanced distribution network. The voltage equation of the phase component node under fault conditions is expressed as follows: ⎡ ⎤ ⎡ ⎤ U1 I1 ⎢ U 2 ⎥ ⎢ I2 ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ... ⎥ ⎢ ... ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ′ U k ⎥ ⎢ Ik ⎥ ⎥ = (19) Y⎢ ⎢ ... ⎥ ⎢ ... ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ UDGm ⎥ ⎢ IDGm ⎥ ⎢ ⎥ ⎢ ⎥ ⎣ ... ⎦ ⎣ ... ⎦ UN IN Ang. (◦ ) -90 -63.9 -59.3 -60.3 / / -173 -174 -173 -173 -93.7 -96 / Phase B Mag. (kV) 2.85 2.69 2.47 0.293 1.87 2.97 0.008 0.0088 0.009 0.009 / / / Ang. (◦ ) 150 177 -176 -177 176 0 109 108 109 106 / / / Phase C Mag. (kV) 2.85 2.75 2.59 0.292 2.8 1.36 0.61 0.62 0.67 0.608 0.49 / 0.503 Ang. (◦ ) 29 58.4 2.55 62.4 59 58 42 39 42 34 23.7 / 26.1 ′ Phase A Mag. (kV) 2.85 2.72 2.45 0.288 / / 0.007 0.0067 0.007 0.007 0.018 0.019 / ]T ]T [ [ where Ui = U̇i,a U̇i,b U̇i,c and Ii = I˙i,a I˙i,b I˙i,c ; Uk and Ik represent the three-phase voltage and current at the fault pointk after modifying the phase component node admittance matrix, respectively. UDGm and IDGm represent the three-phase voltage and injection current of the DFIG at the mth node, respectively. Due to the nonlinear relationship between the DFIG short-circuit current and stator voltage, the traditional phase component method cannot be used to solve the problem of an unbalanced distribution network with DFIGs. Accordingly, an improved phase component shortcircuit calculation method for unbalanced distribution networks with DFIGs is proposed. The calculation flowchart of the improved method is shown in Fig. 5. The key steps of the proposed method are as follows. Step 1) The phase component node admittance matrix and phase component node voltage equation are established according to the actual structure and parameters of the distribution network. Step 2) The DFIG crowbar is not activated and the output current of the DFIG under normal conditions is considered as the first iteration value of its equivalent current source model. Step 3) The phase component node admittance matrix and the cor­ responding phase component node voltage equation are modified ac­ cording to the different fault types; here, a modification method is proposed. Proposed method Consider the activation of crowbar (The crowbar of DFIG 2 is activated) Phase A Phase B Mag. Ang. Mag. Ang. (kV) (◦ ) (kV) (◦ ) 2.85 -90 2.85 150 2.72 -60 2.70 178 2.52 -38.5 2.53 -156 0.28 -30.8 0.291 -156.8 / / 1.86 -156.8 / / 1.36 9.6 0.0052 -148 0.0052 128 0.0052 -148 0.0054 128 0.0052 -148 0.0052 128 0.0052 -148 0.0053 128 0.011 -68.4 / / 0.011 -68.4 / / / / / / Phase C Mag. (kV) 2.85 2.74 2.55 0.293 2.6 2.68 0.4 0.4 0.4 0.4 0.33 / 0.33 Ang. (◦ ) 30 60 84 83.3 59 56.7 63 62.5 62.5 62.5 52 / 52 Without consider the activation of crowbar (Balanced stator current strategy of DFIGs) Electric Power Systems Research 210 (2022) 108108 Phase B Mag. (kV) 2.85 2.69 2.55 0.293 1.87 1.37 0.005 0.0051 0.0057 0.0057 / / / Ang. (◦ ) 150 179 -156 -156.8 -156.8 9.73 128 128 128 128 / / / Phase C Mag. (kV) 2.85 2.73 2.53 0.291 2.598 2.67 0.4 0.405 0.405 0.405 0.33 / 0.33 If an A-phase grounding fault occurs at node k, then the A-phase potential of node k is zero, U̇k,a = 0. Ik,a,sc is the ground current at node k. Accordingly, the current source connected to other nodes is related to the system or node potential. Moreover, the output value of corre­ sponding current sources can be obtained according to the potential of ′ ′ ′ the access node. Then, I = Ii ; IDGm = IDGm ; Ik = Ik + Ika,sc ; and U̇k,a = 0. The phase component node voltage equation can be rewritten as follows: Phase A Mag. (kV) 2.85 2.72 2.52 0.286 / / 0.005 0.0055 0.0057 0.0051 0.012 0.012 / 650 632 633 634 645 646 671 680 692 675 684 652 611 Ang. (◦ ) -90 -60 -38.3 -30.6 / / -148 -148 -148.7 -148 -68.7 -68.7 / Measured values Node TABLE 6 Node voltages when the two-phase grounding fault occurs at f. Ang. (◦ ) 29.9 59.9 84.2 83.5 59.3 58.3 63 62.7 62.8 63 51.6 / 51.6 (1) Single-phase grounding fault 13 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 11. Amplitude error among calculated values of branch currents under Phase B-to-Phase C grounding fault condition (crowbar activation considered or neglected). Fig. 12. Phase angle error among calculated values of branch currents under Phase B-to-Phase C grounding fault condition (crowbar activation considered or neglected). ⎡ ⎤ ⎡ ⎤ ] ′ ′ T Ik,b Ik,c . In Eq. (20), the injection current source includes the in­ jection current source before and after the fault as well as the injection current source affected by the terminal voltage. The voltage value of each phase at each node can be solved iteratively by substituting the output current of the DFIG under normal conditions into Eq. (20). [ ⎢ U′ ⎥ ⎢ I ′ ⎥ ⎢ 1 ⎥ ⎢ 1 ⎥ ⎢ ′ ⎥ ⎢ ′ ⎥ ⎢ U 2 ⎥ ⎢ I2 ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ... ⎥ ⎢ ... ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ′ ⎥ ⎢ ′ ⎥ ⎢ ⎥ ⎢ Ik ⎥ ′′ ⎢ Uk ⎥ ⎢ ⎥ Y ⎢ ⎥=⎢ ⎥ ⎢ ... ⎥ ⎢ ... ⎥ ⎢ ′ ⎥ ⎢ ′ ⎥ ⎢U ⎥ ⎢I ⎥ ⎢ DGm ⎥ ⎢ DGm ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ... ⎥ ⎢ ... ⎥ ⎢ ′ ⎥ ⎢ ′ ⎥ ⎣ U ⎦ ⎣ I ⎦ N N (20) (1) Phase-to-phase fault By assuming that an interphase short-circuit fault occurs at Phases B and C of node k, these phases can be injected with the short-circuit ′ ′ currents, I˙sc and I˙ = I˙k,b + I˙sc , I˙ = I˙k,c − I˙sc . The voltages of Phases k,b [ where U k = 0 ′ Uk,b ′ Uk,c ′ ]T and I k = ′ [ Ik,a + Ik,a,sc ′ Ik,b ′ Ik,c ′ ]T k,c ′ ′ ′ B and C at node k are U̇k,b = U̇k,c = U̇k . The Phase B element at the kth node is replaced with the sum of the Phase B and Phase C elements to eliminate I˙sc . Accordingly, the rows and columns of Phase C at the kth node in the pre-fault phase component node admittance matrix are . When Uk,a = 0, the rows and columns of Phase A of this node are deleted ′ without affecting the calculation of Eq. (20). Subsequently, Ik,a,sc is ] [ ′ ′ ′ ′ ′ T eliminated. Therefore, Y becomes Y ; U k = Uk,b Uk,c ; and I k = 14 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Fig. 13. Amplitude error among calculated values of node voltages under Phase B-to-Phase C grounding fault condition (crowbar activation considered or neglected). Fig. 14. Phase angle error among calculated values of node voltages under Phase B-to-Phase C grounding fault condition (crowbar activation considered or neglected). ′ ]T [ ′ ′ ′ ′ ′ deleted; thus, Y becomes Y . Moreover, Uk = Uk,a Uk,b + Uk,c and Ik ]T [ ′ ′ ′ = Ik,a Ik,b + Ik,c , and one equation is removed from the expression where I˙k,ba = − I˙k,ab , I˙k,ac = − I˙k,ca , and I˙k,cb = − I˙k,bc . The phase voltage at node k is U̇k,a = U̇k,b = U̇k,c = U̇k . Therefore, the simplified method under the three-phase fault condition is equivalent to the simplified method under the phase-to-phase fault condition. Rows a, b, and c of the kth node are added, and I˙k,ba , I˙k,ac , and I˙k,cb are eliminated. Accordingly, the fault currents of the unbalanced distribution networks with DFIGs can be solved iteratively. Step 4) According to the node voltage equation under the fault condition and based on the phase component calculation model of the DFIG ((1) and (2)), the current along each branch and the voltage on each node are solved iteratively. Step 5) If the new energy source is a DFIG, then the crowbar con­ dition is evaluated according to Criterion 1. If the crowbar is activated, then the phase component node admittance matrix and phase compo­ nent node voltage equation should be modified according to the equivalent asynchronous motor model of the DFIG under the activated crowbar condition. Then, return to Step 3); if the crowbar is not acti­ vated, then proceed to Step 6). in (20). Under this condition, the injection current source only includes such sources before and after the fault as well as the injection current source affected by the terminal voltage. Accordingly, the fault currents of unbalanced distribution networks with DFIGs can be solved iteratively. (1) Three-phase fault Assuming that a three-phase fault occurs at node k, the injected current of each phase at node k can be expressed as follows: ⎡ ⎤ ⎡ ⎤ I˙k,a + I˙k,ba + I˙k,ca ⎢ ′ ⎥ ⎢ I˙ ⎥ = ⎣ I˙k,b + I˙k,ab + I˙k,cb ⎦ ⎣ k,b ⎦ ′ I˙k,c + I˙k,ac + I˙k,bc I˙k,c ′ I˙k,a (21) 15 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 Eqs. (6) and (15) indicate that the relationship between the rotor current ir (t) and DC bus voltage udc (t), which are time-varying functions. The amplitudes of the rotor current and DC bus voltage are affected by the terminal voltage and time (t) after failure. Therefore, the resulting amplitudes of the rotor current and DC bus voltage are ergodic. In other words, the aforementioned amplitudes can be calculated at every time point. Let ihm,r = {ihm,r (t), t > 0} and uhm,dc = {uhm,dc (t), t ≥ 0} denote the rotor fundamentally ignored. Therefore, the transient DFIG process for the relay protection setting and equipment selection in power systems can be ignored. In this study, the voltage level of the test system is 4.16 kV, and the system frequency is 60 Hz. Parameters T1 and T2 are the same. The rated capacity is 1.6 MVA, the turns ratio is 0.69 kV/4.16 kV, the winding type is Y/D, and the leakage reactance is 0.0622 pu. The parameters of the IEEE 13 Node Test Feeder are described in [21]. The rated capacities of the two DFIGs are 1.5 MW, Usn = 690 V, Lm = 2.1767 pu, and Ls = Lr =0.1245 pu; the rated rotor speed is 1.2 pu. The faults of node f are assumed to be a three-phase balanced fault and a Phase B-to-Phase C fault. The calculated and measured values of the phase fault current and phase node voltage when a three-phase fault occurs at node f are summarized in Tables 5 and 6, respectively. Tables 7 and 8 list the calculated and measured values of the phase fault current and phase node voltage of the Phase B-to-Phase C fault occurrence at node f, respectively. current and DC bus voltage, respectively. Let the DFIG values at the mth node be in the finite set S = {0,1,2,...,Z}, where 0, 1, 2,..., Z indicates the state at different times after failure, and Z = 100 000. Accordingly, the following is derived: ⎧ √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ ⎪ ⎨ ih (t) = i+h2 (t) + i+h2 (t) + i− h2 (t) + i− h2 (t) m,r m,rd+ m,rq+ m,rd− m,rq− (22) ⎪ ⎩ uhm,dc (t) = um,dc0 + Δuhm,dc (t) where h indicates the h-th iteration. The corresponding amplitude vectors of rotor current and DC bus voltage are defined as follows: [ ] ⎧ ⎨ Ihm,r = ihm,r0 (t), ihm,r1 (t),ihm,r2 (t),..., ihm,rZ (t) [ ] (23) ⎩ Uh = uh (t), uh (t),uh (t),..., uh (t) 1 1 Z m,dc m,dc m,dc m,dc 2 4.1. Three-phase fault Three-phase short-circuit faults are simulated at different nodes of the IEEE 13 node model to verify the effectiveness of the proposed method. In this study, a balanced three-phase fault occurs at node f. The calculated and measured values of the phase fault current and phase node voltage are summarized in Tables 1 and 2, respectively. The de­ viation between the simulated and calculated values of the branch current is illustrated in Fig. 7. Moreover, the deviation between the simulated and calculated values of the node voltage is shown in Fig. 8. Table 2 and Fig. 8 indicate that the maximum deviation between the calculated and measured values of node voltage is 4.16%, while the maximum angle error between the calculated and measured values is 5.5◦ . As indicated in Table 1 and Fig. 7, the Phase A load connected to node 652 is minimal; thus, the load current is also considerably small. Therefore, a certain deviation exists between the calculated and measured values of the branch currents in nodes 671–684 and 684–652. The maximum deviation between the calculated and measured values of currents of the other branches is 2.5%, and the angular error is 5◦ . In other words, the proposed phase component short-circuit current calculation method satisfies the requirements of short-circuit calculation for unbalanced distribution networks with DFIGs. m,dc where ihm,r0 (t) =ihm,r0 (0) and ihm,rZ (t) = ihm,rZ− 1 (t + 10− 6 ). Moreover, uhm,dc 0 (t) = uhm,dc 0 (0) and uhm,dc Z (t) = uhm,dc Z− 1 (t + 10− 6 ). Therefore, the activation criterion of the crowbar protection of the DFIG at the m-th node in the h-th iteration can be obtained as follows. Criterion 1 : h h Im,r > i∗m,r or Um,dc > u∗m,dc (24) Step 6) If Criterion 2 is satisfied, then the iterative process is completed; proceed to Step 7). If Criterion 2 is not satisfied, then the last iteration value of the node voltage can be substituted into the equivalent phase component calculation model of the DFIG (i.e., Eqs. (1) and (2)) as the initial value of the DFIG’s injection current in the next iteration; return to Step 5). Criterion 2 is given as follows: ⃒ ⃒ ⃒ ⃒ ⃒) (⃒ h h− 1 ⃒ ⃒ h h− 1 ⃒ ⃒ h h− 1 ⃒ ⃒ Criterion 2 : max ⃒V̇ i,a − V̇ i,a ⃒, ⃒V̇ i,b − V̇ i,b ⃒, ⃒V̇ i,c − V̇ i,c ⃒ ≤ ε (25) 4.2. Asymmetric fault The simulation results and theoretical values are comparatively analyzed by considering the Phase B-to-Phase C fault at node f as an example. The calculated and measured values of the branch currents and node voltages are summarized in Tables 3 and 4, respectively, and their deviations are shown in Figs. 9 and 10, respectively. Table 3 and Fig. 9 indicate that the maximum deviations between the calculated and measured values of the branch current and angular error are 4.5% and 2◦ , respectively. From Table 4 and Fig. 10, it is evident that the maximum deviation values between the calculated and measured values of node voltage and angular error are 6.7% and 2%, respectively. For an unbalanced distribution network, regardless of the symmetry or asymmetry of fault conditions, the maximum magnitude and angle errors between the calculated and measured values of the branch current and node voltage are extremely small. In other words, the proposed fault calculation method satisfies the requirements of short-circuit calculation for unbalanced distribution networks with DFIGs. where h represents the h-th iteration, irepresents the ith node, andε in­ dicates the threshold value, which is typically 0.02 pu. Step 7) Based on the impedance relationship of the phases of each branch, the current in the branch is calculated according to the last iterative voltage value of the corresponding node. Step 8) End. 4. Simulation A simulation model of IEEE 13 Node Test Feeder with DFIGs was formulated to verify the effectiveness of the proposed short-circuit current calculation method for unbalanced distribution networks with DFIGs, as shown in Fig. 6. Many LVRT strategies can be used for DFIGs. For instance, the balanced stator current strategy is applied to DFIG1 and DFIG2. The phase component short-circuit current calculation method was tested under various fault conditions. In this study, two DFIGs that are connected to nodes 633 and 692 are considered as ex­ amples. The effectiveness of the proposed method was verified. Ac­ cording to Mohammadi et al. [3] and [4], the DFIG short-circuit current undergoes a slight change during the power grid fault, which can be 4.3. Comparison of methods Generally, crowbar activation is not considered in the traditional fault analysis method. In this study, crowbar activation can be assessed using the proposed method whose calculation results were found to be more accurate. The fault at node f is assumed to be a Phase B-to-Phase C 16 F. Xiao et al. Electric Power Systems Research 210 (2022) 108108 grounding fault. Under this fault condition, the crowbar of DFIG2 shown in Fig. 6 is activated. Tables 5 and 6 summarize the results of the pro­ posed method with or without the activation of the crowbar. The calculation results in the second column of these tables are based on the activated condition of the crowbar of DFIG2, whereas those in the third column are based on the balanced stator current strategy of DFIG2. The amplitude and phase angle errors of the proposed method with or without the activation of the crowbar are presented in Figs. 11–14, where CB denotes the crowbar. In these figures, “considered CB” means that crowbar activation can be considered, whereas “not considered CB” indicates that this activation is neglected. For DFIG2, the action condi­ tion of the crowbar is assessed using the proposed method. Additionally, the fault calculation model of DFIG2 is consistently based on the balanced stator current control strategy. As shown in Figs. 11 and 12, when crowbar activation is neglected, the maximum amplitude and angular errors among the calculated values of branch currents are 267% and 157◦ , respectively. However, when crowbar activation is considered, these errors are only 3.23% and 5◦ , respectively. As shown in Figs. 13 and 14, when crowbar activation is neglected, the maximum amplitude and angular errors among the calculated node voltages are 116.8% and − 81◦ , respectively. However, when crowbar activation is considered, these errors decrease to 2.1% and − 1.6◦ , respectively. The result indicates that the effect of crowbar activation must be considered in the short-circuit calculation method for unbal­ anced distribution networks with DFIGs. Therefore, the difference between the measured values and calcu­ lation results when crowbar activation is neglected is considerable. However, when crowbar activation is considered, the measured and calculated values are essentially the same. Therefore, under activated crowbar conditions, the DFIG cannot be considered equivalent to a current source model based on the previously developed LVRT strategy, and crowbar activation must be correctly evaluated using the failure analysis method. The proposed method is also applicable to unbalanced distribution networks with IIDGs, such as photovoltaic power systems and direct drive wind turbines. Xianggen Yin: Investigation, Conceptualization. Jinyu Wen:Conceptualization, Methodology, Declaration of Competing Interest The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper. Acknowledgments The research is supported by the State Grid Headquarters Science and Technology Project (No. 5400-202122573A-0-5-SF). References [1] G. Carpinelli, A. Bracale, P. Caramia, A.R. Di Fazio, Three-phase photovoltaic generators modeling in unbalanced short-circuit operating conditions, Electr. Power Energy Syst. 113 (2019) 941–951. [2] J. Morren, Short-circuit current of wind turbines with doubly-fed induction generator, IEEE Trans. Energy Convers. 22 (2007) 174–180. [3] J. Mohammadi, S. Afsharnia, S. Vaez-Zadeh, Efficient fault-ride-through control strategy of DFIG-based wind turbines during the grid faults, Energy Convers. Manag. 78 (2014) 88–95. Fault ride-through capability of DFIG wind turbines. Renewable Energy, 2007; 32(9): 1594-1610. [4] Jun Yao, Jinxin Pei, Depeng Xu, Ruikuo Liu, Xuewei Wang, Caisheng Wang, Coordinated control of a hybrid wind farm with DFIG-based and PMSG-based wind power generation systems under asymmetrical grid faults, Renew. Energy 127 (2018) 613–629. [5] S Z Chen, N C Cheung, K C Wong, Integral sliding-mode direct torque control of doubly-fed induction generators under unbalanced grid voltage, IEEE Trans. Energy Convers. 25 (2016) 356–368. [6] T. Ghennam, K. Aliouane, F. Akel, B. Francois, E.M. Berkouk, Advanced control system of DFIG based wind generators for reactive power production and integration in a wind farm dispatching, Energy Convers. Manag. 105 (2015) 240–250. [7] Kong Xiangping, Zhang Zhe, Yin Xianggen, Wen Minghao, Study of fault current characteristics of the DFIG considering dynamic response of the RSC, IEEE Trans. Energy Convers. 29 (2014) 278–287. [8] F Xiao, Z Zhang, X Yin, Fault current characteristics of the DFIG under asymmetrical fault conditions, Energies 8 (10) (2015) 10971–10992. [9] Weixing Li, Pupu Chao, Xiaodong Liang, Yong Sun, Jinling Qi. Modeling of complete fault ride-through processes for DFIG-Based wind turbines, Renew. Energy 118 (2018) 1001–1014. [10] M.E. Baran, I. El-Markaby, Fault analysis on distribution feeders with distributed generators, IEEE Trans. Power Syst. 20 (2005) 1757–1764. [11] I. Zubia, J.X. Ostolaza, A. Susperregui, J.J. Ugartemendia, Multi-machine transient modelling of wind farms: an essential approach to the study of fault conditions in the distribution network, Appl. Energy 89 (1) (2012) 421–429. [12] Insu Kim, A calculation method for the short-circuit current contribution of current control inverter-based distributed generation sources at balanced conditions, Electr. Power Syst. Res. 190 (2021), 106839, https://doi.org/10.1016/j. epsr.2020.106839. [13] H Hooshyar, M E Baran, Fault analysis on distribution feeders with high penetration of PV systems, IEEE Trans. Power Syst. 28 (2013) 2890–2896. [14] Q Wang, N Zhou, L. Ye, Fault analysis for distribution networks with currentcontrolled three-phase inverter-interfaced distributed generators, IEEE Trans. Power Deliv. 30 (2015) 1532–1542. [15] R.M. Furlaneto, I. Kocar, A. Grilo-Pavani, Short circuit network equivalents of systems with inverter-based resources, 199, Electric Power Systems Research, 2021, 107314. [16] Luka Strezoski, Marija Prica, Generalized Δ-circuit concept for integration of distributed generators in online short circuit calculations, IEEE Trans. Power Syst. (2022), https://doi.org/10.1109/TPWRS.2016.2617158. [17] T. Kauffmann, U. Karaagac, Short-circuit model for type-IV wind turbine generators with decoupled sequence control, IEEE Trans. Power Deliv. (2022), https://doi.org/10.1109/TPWRD.2019.2908686. [18] State Grid. GB/T 19963-2011 Technical rule for connecting wind farm to power system[S]. 2011.(in Chinese). [19] M Tsili, S. Papathanassiou, A review of grid code technical requirements for wind farms, IET Renew. Power Gener. 3 (2009) 308–332. [20] Kong Xiangping, Study on fault current characteristics of doubly-fed wind turbines considering impact of crowbar protection, Trans. China Electrotech. Soc. 30 (2015) 99–110. [21] IEEE Distrib, System Analysis Sub, in: IEEE 13 Node Test Feeder [Online], 2022. Available: http://ewh.ieee.org/soc/pes/dsacom/testfeeders/. 5. Conclusions The symmetrical component method cannot satisfy the requirements of short-circuit calculation for unbalanced distribution networks with DFIGs. Therefore, a novel short-circuit calculation method was proposed in this study. The short-circuit calculation equivalent models based on the phase components of DFIGs were established based on the LVRT strategy. In particular, the activation criteria of crowbar protection were proposed. Subsequently, an improved fault analysis method for unbal­ anced distribution networks with DFIGs was proposed based on traversal and iteration. Finally, the efficacy of the proposed short-circuit calculation method was verified by simulations. The simulation results indicate that the proposed short-circuit calculation method is highly accurate. This study has considerable significance for short-circuit calculation, operation control, and protection setting of unbalanced distribution networks with DFIGs. Credit author statement Fan Xiao: Conceptualization, Methodology, Validation, WritingOriginal draft preparation. Yongjun Xia: Data curation, Validation. Kanjun Zhang: Validation, Writing-Original draft preparation. Zhe Zhang: Investigation, Conceptualization, Writing-Reviewing and Editing. 17