Where: Q aproximately account for the losses caused for typical fittings in a duct run and multiply by 0.1 in. wg/100 ft (0.8 Pa/m) and compare with the available external static pressure of the HVAC unit. = Heat flow (watts) Lńs = Airflow (liters per second) Dt Example 5−10 (I−P) = Temperature difference (°C) A heating unit has an airflow rating of 4000 cfm and an output of 150,000 Btuh. Find the final discharge temperature with 75 degree F inlet air. Using Equation 5−10: AF Example 5−10 (SI) A heating unit has airflow of 1000 L/s and an output of 50 kW. Find the final discharge temperature with 24 degree C inlet air. 1.23 Dt = 20.3°C Q lńs An air handling unit has an external static pressure of 125 to 375 Pa depending on the fan rpm and motor power (kW). Estimate if an 80 m duct run with many fittings would be feasible. 80 m × 4 (1 + 3) = 320 m equivalent length Q + 1.23 DT + 0.1 in.wg = 0.9 in. wg 100 ft The estimated system loss falls about half way within the HVAC unit pressure capacity. Final temperature = 75° + 34.7° = 109.7°F Using Equation 5−10: 225 ft × 4 (1 + 3) = 900 ft equivalent length 900 ft Q + 1.08 cfm Dt Q 150, 000 Dt + + 1.08 cfm 1.08 4000 Dt = 34.7°F Example 5−9 (SI) An air handling unit has an external static pressure range of 0.50 to 1.50 in. wg depending on the fan rpm and motor horsepower. Estimate if a 225 ft duct run with many fittings would be feasible. T Example 5−9 (I−P) + lńs Dt 320 m × 0.8 Pa/m = 256 Pa 50kW 1000WńkW 1.23 2000lńs The estimated system loss falls about halfway within the HVAC unit pressure capacity. 5.9.3 Friction Loss Chart Final temperature = 24° + 20.3°= 44.3°C HVAC Unit/Duct Relationship DR 5.9.2 The selection of HVAC units is important to the design of the connected duct systems. A lower airflow will result in higher temperature rises. The air velocity and length of the duct system also affects the temperature losses through the duct walls as well as the straight duct and fitting pressure losses. Once the HVAC air handling unit has been selected, the individual space loads are proportioned from the total airflow and the airflow for each section is marked on the duct layout. The range of the HVAC unit external static pressure may limit the velocities and pressure drops that may be used in the individual duct sections. For lower pressure systems, a pressure drop of 0.1 in. wg per 100 in. (0.8 Pa/m) is a good place to start. Measure the longest duct run (an assumption is made that it has the highest pressure drop). For a rough estimate, double or triple the duct run length this will 5.14 Figures 5−8 and 5−9 are part charts from Figures A−1 and A−1M. If data for any two conditions of the duct are known, the other two unknowns may be obtained from the charts. The shaded area indicates the recommended design range. Example 5−11 (I−P) Using Figure A−1 find the duct diameter and airflow velocity for 700 cfm at 0.1 in. wg/100 ft duct friction loss. The plotted solution can be found in Figure A−1. The duct velocity = 900 fpm and the duct size = 12 in. diameter. Example 5−11 (SI) Using Figure A−1M, find the duct diameter and airflow velocity for 200 L/s at 0.9 Pa/m duct friction loss. The plotted solution can be found in Figure A−1M. The duct velocity = 4.2 m/s and the diameter = 250 mm. HVAC Systems Duct Design • Fourth Edition