SEL-451 Protection, Automation, and Bay Control System Advanced feeder protection and complete substation bay control in one economical system • Customize distribution protection using multiple instantaneous, time-overcurrent, and directional elements. • Detect high-impedance faults with Arc Sense™ technology (AST). • Implement bay control with complete two-breaker control and high-speed breaker failure detection. • Transform the way you modernize your substation with SEL Time-Domain Link (TiDL®) and Sampled Values (SV) technologies. Functional Overview Bus ANSI Numbers/Acronyms and Functions 25 27 32 (O,U) 50 50BF 51 52PB 59 67 79 81 (O,U) 1 3 SEL-451 Line 25 27 32OU 50 50BF 51 52PB 59 67 79 81OU 85 RIO BRM DFR HIZ HBL HMI LGC LOC MET PMU SER SBM SIP Additional Functions 3 THM 1 4 2 IRIG-B EIA-232 Ethernet1* SEL-451-5 3 Bus 16 SEC 50G 85 RIO BRM DFR HBL HIZ HMI LDE LGC LOC MET PMU SBM SER SIP SV THM TiDL 16 SEC 1 2 Synchronism Check Undervoltage Over- and Underpower RMS Overcurrent Dual Breaker Failure Overcurrent Time-Overcurrent Trip/Close Pushbuttons* Overvoltage Directional Overcurrent Autoreclosing Over-/Underfrequency 2 Ethernet Ethernet Station Bus Process Bus SEL-451-6† Access Security (Serial, Ethernet) Best Choice Ground SEL Mirrored Bits® Communications Breaker Wear Monitor Event Reports Harmonic Blocking High-Impedance Fault Detection AST* Operator Interface Load Encroachment Expanded SELogic® Control Equations Fault Locator High-Accuracy Metering Synchrophasors Station Battery Monitor Sequential Events Recorder Software-Invertible Polarities IEC 61850-9-2 Sampled Values Technology*† IEC 60255-Compliant Thermal Model Time-Domain Link Technology* Copper or fiber-optic *Optional feature 1 SV subscriber relays have no analog input boards and instead receive voltages and current through Ethernet. † Key Features Comprehensive Feeder Protection Customize distribution protection in the SEL-451 Protection, Automation, and Bay Control System with multiple instantaneous, time-overcurrent, and directional elements combined with SELogic control equations. AST detects high-impedance faults, while low-energy analog (LEA) voltage inputs help protect pad-mounted switchgear. Powerful Bay Control and High-Speed Breaker Protection Comprehensive two-breaker control and breaker failure protection complement the versatility of the SEL-451 programmable logic to meet your bay control needs. Easily control motor-operated switches, capacitor banks, and field I/O from the front panel or remotely. Built-In Real-Time Synchrophasor Measurements Help system operators understand the network status with real-time visual displays of system phase angles and frequency. High-accuracy synchronized phasor measurements provide information and control to match the frequency and phase angle for critical activities, such as switching, startup, and power transfer. Monitoring That Maximizes the Capability of Substation Equipment Fully load equipment by monitoring power, including thermal or rolling interval demand as well as peak demand on positive-, negative-, and zero-sequence current. Digital Secondary System Technologies Modernize your substation by applying SEL TiDL technology or SEL SV technology. Both of these digital secondary system solutions replace copper wires with fiber-optic cables to increase safety, reduce costs associated with using copper wires, and limit the impact of electromagnetic interference. TiDL is a simple and secure digital secondary system solution that is easy to implement, with no external time source or network engineering required. Apply the TiDLenabled SEL-451-5 in the control house with the SEL-2240 Axion® TiDL node in the yard, which provides remote I/O, digitizes analog signals, and sends the signals over fiberoptic cables to the relay. SEL SV combines protection in the merging unit with the flexibility of IEC 61850-9-2 to increase power system reliability. Apply the SEL-451-6 with SEL SV technology to receive IEC 61850-9-2 SV data over fiber-optic cables from SEL merging units or other SV-compliant units. Product Overview—SEL-451-5 Relay EIA-232 front serial port is quick and convenient for system setup and local access. Easy-to-use keypad aids simple navigation. Interactive bay display with userconfigurable apparatus labels allows the operator to view the status of breakers and disconnect switches and to control them. Front-panel LEDs indicate custom alarms and provide fast and simple information to assist dispatchers and line crews with rapid power restoration. Programmable operator pushbuttons with user-configurable labels allow front-panel customization. Choose from a vertical or horizontal, panel-mount or rack-mount chassis and different size options. Use a maximum of 68 output contacts.1 Communications protocols include FTP, Telnet, synchrophasors, DNP3 LAN/WAN, the Parallel Redundancy Protocol (PRP), the IEEE 1588 Precision Time Protocol Version 2 (PTPv2),** and IEC 61850 Edition 2. Order six current inputs in standard terminal blocks (as shown) or a Connectorized® hardware configuration. Choose six voltage inputs in either standard terminal blocks, a Connectorized hardware configuration, or an LEA hardware configuration. Use one front and three rear EIA-232 ports for Mirrored Bits communications, DNP3, SCADA, and engineering access. Use a maximum of 103 input contacts.1 Choose from power supply options such as 24–48 Vdc; 48–125 Vdc or 110–120 Vac; or 125–250 Vdc or 110–240 Vac. Requires 8U chassis 1 **For PTP implementation, Ports 5A and 5B must be ordered as an option. Applications Protection Complete Overcurrent Protection Pad-Mounted Switchgear Protection Customize distribution protection with multiple instantaneous and time-overcurrent elements combined with SELogic control equations. You can select from four phase, four negative-sequence, and four ground instantaneous overcurrent elements to best fit your application. Best Choice Ground Directional Element® logic optimizes directional element performance and eliminates the need for many directional settings. Protect pad-mounted switchgear using the SEL-451 with LEA voltage inputs. This helps reduce overall system costs by eliminating amplification electronics between the line sensor and the relay. Having fewer devices leads to a simpler system, a reduction in labor costs, and the elimination of a possible point of failure. Electric Voltage Divider High-Impedance Fault Detection Detect high-impedance faults with AST. Highimpedance faults are a common result of a downed conductor on surfaces with poor conductivity. With AST, alarm or trip for faults that produce low fault current and are undetectable with conventional overcurrent relays. C1 Cable SEL-451 Vpri C2 Cc Vsec VY or VZ Terminal Voltage Input (8 Vac LEA input) Bay Control BAYNAME Two-Breaker Bay Control Meet your bay control needs with complete two-breaker control and high-speed breaker failure detection. You can easily control motor-operated switches, capacitor banks, and field I/O from the front panel or remotely. Configurable labels make it easy to customize the relay controls to match your application. Different bus configurations are available, including single- and dual-busbar, transfer bus, tie-breaker, breaker-and-a-half, ring-bus (shown in the figure), double-bus/double-breaker, and source-transfer configurations. BAYLAB1 SW1 BAYLAB2 BK1 BK2 SW2 Flexible I/O Options SW3 Select different combinations of I/O boards to match each application. The SEL-451 supports up to four additional I/O boards for a total of up to 103 inputs and up to 68 outputs depending on configuration. NAVIG 6 ANALOGS I:99999.9 A V:9999.9 KV P:9999.9 MW Q:9999.9 MV F:99.9 HZ ESC Panel Integration Racked Breaker Support Support racked breakers where they are used. Racked breaker mosaics provide visual indication of not only whether the breaker is open or closed but also for which position the breaker is in (racked in, test, or racked out). Disconnect Monitoring and Control Use up to 20 disconnects for bay control applications. All disconnects can be either controlled or in a monitor-only state. A setting for each disconnect allows you to tailor it for each application. Improve efficiency and simplify installation with more target LEDs and operator pushbuttons. The 4U, 5U, and 8U chassis have options for an additional eight target LEDs and four operator control pushbuttons. You can also include arc-suppressed trip/close pushbuttons for an enhanced solution. Display the breaker status and control the breaker position, even if the relay is not powered, with auxiliary breaker trip/close control pushbuttons and indicating lamps. The 24 target LEDs indicate the relay state and various trip conditions and are configurable for specific applications. You can modify the 12 operator pushbuttons to replace traditional panel switches and meet operator control needs. + + Close (manual/local) Remote Close/ Autoreclose Breakerr Open n Breaker Breaker B C losed Closed 43 local 43 4 local 52a To Close Circuit 52b - 52 TC - Trip (manual/local) Remote Trip/ Protection Trips Automation VAR-Supervised Time-Undervoltage Characteristic Custom Automation With SELogic Control Equations Create your own custom applications using powerful SELogic control equations. This allows you to: 15 • Prevent cascading voltage collapse using VAR-supervised time-undervoltage elements. • Create an adaptive inverse-time overcurrent characteristic to adjust pickup based on load conditions. • Protect ungrounded-wye shunt capacitor banks. 10 Time (s) • Monitor VAR loading, and trip only the feeders with high VAR demand to prevent voltage collapse. 5 Trip Time • Create your own custom curves. 0 0.5 1.0 Voltage Per Unit Harmonic Analysis 120 Harmonic Monitoring 110 Harmonics % of Fundamental Apply the second-, fourth-, and fifth-harmonic elements with individual threshold settings to detect transformer energization and overexcitation conditions. You can use the output from these harmonic detection elements for a variety of functions. For example, modifying the relay settings can improve security, and event reporting makes the identification of transformer energization events fast and simple. 100 90 80 70 60 50 40 30 20 10 60 120 180 240 300 360 420 Frequency Breaker Wear Monitoring Excess Breaker Contact Wear Compare the breaker manufacturer’s published data to the actual interrupted current and number of operations for two breakers, and create alarms accordingly. By monitoring the mechanical and electrical interruption time per pole, you can compare average and last trip times for maintenance scheduling. Excess Mechanical Operating Time Excess Electrical Operating Time Excess Pole Scatter or Pole Discrepancy Phase Currents Auxiliary Contact Inputs Station Battery Voltages Relay Circuit Breaker Monitor Excess Breaker Inactivity Time Excess Motor Running Time Excess kA Interrupted Deviations in Station Battery Voltages Enhanced Event Analysis Software Synchrophasors Use the SEL-451 as a multichannel (six voltages, six currents) digital fault recorder. With SEL-5601-2 ® synchroWAVe Event Software, you can view COMTRADE files from the SEL-451 and other digital fault recorders. Event resolutions from 1 to 8 kHz and event report lengths from 0.25 to 24.00 seconds (1 kHz resolution) are possible. You can perform harmonic analysis of any voltage or current and select the prefault, fault, or postfault portion of the event report to examine. Significantly improve your system’s performance with SEL’s complete synchrophasor solutions, including hardware, communications, viewing and analysis software, data collection, and data archiving. The SEL-451 provides real-time system state measurement with time-synchronized voltages and currents in the IEEE C37.118 standard format. In addition, SEL-5078-2 synchroWAVe Central Software or third-party software allow you to view and analyze system phase angles, load oscillations, voltage profiles, and other critical system information. TiDL Technology In a TiDL solution, Axion TiDL nodes are placed in the yard close to the primary equipment to digitize discrete I/O signals and analog data and then transport them over a fiber-optic cable to the TiDL-enabled SEL-451 in the control house. This innovative technology uses point-to-point connections and a nonroutable protocol, providing a simple and secure solution. Because it does not require an external time source or Ethernet switches, it is easy to implement with no network engineering required. TiDL combines the proven protection of the SEL-400 series relays with the modularity of the Axion, reducing training requirements and providing a scalable and flexible solution. It also provides built-in time synchronization and synchronous sampling, ensuring protection is available in the relay regardless of whether or not an external time signal is available. Substation Yard IAW, IBW, ICW VAY, VBY, VCY VAY, VBY, VCY SEL-2240 Axion SEL-2240 Axion IAW, IBW, ICW SEL-2240 Axion Feeder 1 SEL-2240 Axion Feeder 2 VAZ (sync. check) Fiber-Optic Cable SEL-2240 Axion SEL-451 Control House SEL-451 SEL-451-5 With TiDL Technology 4U chassis with mounting options (vertical or horizontal; panel or rack) accommodates your application needs. Commission button usage prompts the relay to communicate with the Axion TiDL nodes. LEDs indicate the connection status to a remote Axion TiDL node on a per-port basis. Eight 100 Mbps fiber-optic ports allow the TiDL-enabled relay to connect with eight remote Axion TiDL nodes and to receive remote analog and digital data. LEDs indicate a valid configuration and successful commissioning. SEL SV Technology In an SEL SV solution, the SEL-451-6 Relay (subscriber) in the control house receives digitized analog signals from an SV merging unit (publisher) in the yard via a fiberbased Ethernet network. The system uses precise time synchronization via IRIG-B or PTP. The SEL-451-6 offers the traditional protection available in the SEL-451-5 and can also receive SV data. Because all SEL SV devices are compliant with IEC 61850-9-2 and the UCA 61850-9-2LE guideline, they can be used with primary equipment that generates similar SV streams, with other manufacturers’ SV-compliant units, or with SEL merging units that offer built-in protection (such as the SEL-401 Merging Unit and the SEL-421-7 Protection, Automation, and Control Merging Unit). SEL SV technology allows you to create a flexible Ethernet-based point-to-multipoint network using tools such as software-defined networks or VLANs to fit your application needs. You can use the SEL-2740S SoftwareDefined Network Switch to provide centralized traffic engineering and improve Ethernet performance. The switch acts as a transparent PTP clock that supports the IEEE C37.238 power system profile, ensuring submicrosecond time synchronization of the end devices. Substation Yard VAY, VBY, VCY IAW, IBW, ICW IAW, IBW, ICW SEL-401 SEL-401 Feeder 1 Control House Feeder 2 Fiber-Optic Cable GPS Clock Ethernet Switch SEL-2740S SEL-451 SEL-2488 SEL-451 SEL-451-6 With SV Technology The 4U chassis has various mounting options to accommodate hardware needs. Select fiber-optic, copper, or mixed Ethernet with separate ports for SV data and engineering access. Choose from power supply options such as 24–48 Vdc; 48–125 Vdc or 110–120 Vac; or 125–250 Vdc or 110–240 Vac. Accessibility and Communications Built-In Web Server Access basic SEL-451 information on a standard Ethernet network with the built-in web server. From there you can view the relay status, Sequential Events Recorder (SER) data, metering information, and settings with easy access within a local network. For increased security, web server access requires a relay password and the information is limited to a read-only view. Mirrored Bits Communications This field-proven technology provides simple and powerful bidirectional digital communications between devices. Mirrored Bits communications can transmit/receive information between upstream relays and downstream recloser controls to enhance coordination and generate faster tripping for downstream faults. Ethernet-Based Communications An Ethernet card option provides two copper, fiber, or mixed ports for failover redundancy. Simplify the Ethernet network topology and reduce external equipment with dual Ethernet ports that offer a switched mode for looped Ethernet networks. Available Ethernet communications protocols include FTP, Telnet, DNP3 LAN/WAN, IEEE 1588 PTPv2, IEC 61850 Edition 2, IEEE C37.118 synchrophasors, and PRP. 52 52 SEL-421 SEL-451 SEL-421 MIRRORED BITS Communications Digital, Analog, or Virtual Terminal ® Engineering Access SEL-451 Wide-Area Network SEL-2488 GPS Clock Ethernet Switch SEL-451 SEL-2740S SEL-487B SEL-421 SEL-3530 SEL-451 SEL-451 Specifications General AC Current Inputs (6 total) 5 A nominal AC Voltage Inputs (6 total) 300 VL-N continuous, 600 Vac for 10 seconds LEA Voltage Inputs 0–8 VL-N continuous, 300 Vac for 10 seconds Serial 1 front-panel and 3 rear-panel EIA-232 serial ports 1 A nominal 300–57,600 bps Ethernet Communications protocols include FTP, Telnet, synchrophasors, DNP3 LAN/WAN, PRP, PTPv2, and IEC 61850 Edition 2 (optional). Choose from the following port options: Two 100BASE-FX fiber-optic network ports Two 10/100BASE-T twisted-pair network ports One 10/100BASE-T twisted-pair network port and one 100BASE-FX fiber-optic network port TiDL Ports Fiber-optic ports: 8 Range: ~2 km Data rate: 100 Mbps SV Ports Choose from the following communications port options: Four 10/100BASE-T twisted-pair network ports Four 100BASE-FX fiber-optic network ports Two 10/100BASE-T twisted-pair network ports and two 100BASE-FX fiber-optic network ports Subscriber: As many as 7 SV data streams Data rate: 80 samples per cycle Precise-Time Input Demodulated IRIG-B time input and PTPv2 Synchrophasors IEEE C37.118 standard Up to 60 messages per second Processing AC voltage and current inputs: 8,000 samples per second Protection and control processing: 8 times per power system cycle Power Supply 24–48 Vdc 48–125 Vdc or 110–120 Vac 125–250 Vdc or 110–240 Vac Operating Temperature –40° to +85°C (–40° to +185°F) Note: LCD contrast is impaired for temperatures below –20°C (–4°F) and above +70°C (+158°F). Making Electric Power Safer, More Reliable, and More Economical +1.509.332.1890 | info@selinc.com | selinc.com © 2019 by Schweitzer Engineering Laboratories, Inc. PF00074 · 20190729