INSULATING OIL, FLUID AND GASSES E E T E 2 / 4 6 4 P OWE R SYST E M E LE M E N T T EST IN G AN D M AIN T EN AN CE Introduction Insulating oils, fluids, and gases are used as dielectrics in the electrical equipment and apparatus. The liquids used in the transformers are mineral oil and synthetic fluids, such as askarel, silicone, RTemp, Wecosal, Alpha 1, and GE R113. Power Transformer transformers have their windings immersed Distribution Transformer Mineral oil is also used as a dielectric in circuit breakers, reclosers, interrupters, and the like. Sectionaliser Load break Oil Circuit Breaker The most common insulating gas used in circuit breakers and completely enclosed substations is sulfur hexafluoride (SF6). High Voltage SF6 Circuit Breaker Medium Voltage SF6 Circuit Breaker • The ability of insulating oils, fluids, and gases to serve as effective dielectric and coolant is adversely affected by their deterioration. • The deterioration of insulating oil, fluids, and gases is due to contamination, overheating, electrical stress, and oxidation. • Moisture is the most common contaminant which adversely affects the insulating properties of these liquids and gases. • High temperatures from increased load and/or environmental conditions accelerate the deterioration process. • To assure continuity of service, safety, and maintenance, a condition monitoring program, consisting of electrical and chemical testing, is necessary for these dielectrics. Insulating Oil • To properly maintain the transformer oil free of contaminants, regular inspection of the transformer and purification of the oil is needed. • Hydrocarbon (mineral oil #10) oil is used as an insulating fluid in transformers and circuit breakers because of its high dielectric strength and chemical stability. Deterioration of Insulating Oil I. Effect of Oxygen on Oil Moisture contamination is the most common cause of deterioration in the insulating quality of oil. This contamination can be readily corrected by purification. Atmospheric oxygen and oxygen contained in water are the sources available for the oxidation of insulating oils. The rate of oxidation also depends on the temperature of the oil; the higher the temperature is, the faster the oxidative breakdown. An increase in temperature of 10°C (50°F) generally doubles the rate of oxidation. II. Moisture in Oil Water can be present in oil in a dissolved form, as tiny droplets mixed with the oil (emulsion), or in a free state at the bottom of the container holding the oil. Demulsification occurs when the tiny droplets unite to form larger drops, which sink to the bottom and form a pool of free water. Emulsified water typically requires vacuum dehydration, as the emulsification cannot typically be broken by filtration or by excellerated gravity (centrifuge). A very small amount of emulsified water has a marked influence in reducing dielectric strength of oil. Free moisture in oil usually shows up above 50 to 60ppm depending upon temperature. Accepted levels of water in oil are shown in Table 4.1. Electrical Power Equipment Testing and Maintenance 2nd Ed. By: Paul Gill The amount of moisture that can be dissolved in oil increases rapidly as the oil temperature increases, as shown in Figure 4.1. Electrical Power Equipment Testing and Maintenance 2nd Ed. By: Paul Gill Therefore, an insulating oil purified at too high a temperature may lose a large percentage of its dielectric strength on cooling, because the dissolved moisture is then changed to an emulsion, unless vacuum dehydration is used as the purification process. Vacuum Dehydration Oil Purification System III. Absorption of Moisture by Insulating Materials Solid insulation (paper insulation) in transformers is very porous and thirstily absorbs water. Some of the water that is dissolved in the oil is absorbed from the oil by the cellouse (paper) winding insulation. As more water is dissolved in the oil, more water is absorbed by the insulation of the transformer windings. Once absorbed, it is difficult to remove. The most effective method for drying out the insulation in transformers is with heat and vacuum. Sometimes a vacuum cannot be applied in the field; then the transformer insulation must be dried by circulation of hot, dry oil. This oil should then be cooled and dried. Since the dielectric strength of insulation is reduced by absorption of moisture, it is important that the insulation not be allowed to absorb it in the first place. IV. Absorption of Nitrogen by Oil Special precaution should be taken in operating transformers with nitrogen over the oil to avoid bubbling of the oil due to release of dissolved nitrogen when the pressure drops. Experience has shown that the automatic gas- pressure regulating system should be adjusted to limit the nitrogen pressure range from 1/2 to 3 psi (lb/sq.in.) gauge to avoid formation of these bubbles and subsequent troubles due to corona deterioration. Function of Insulating Oil in an electrical equipment ❖ It serves and provide insulation ❖ Serves as a cooling agent ❖ Helps to extinguish arc caused by switching and fault event ❖ Use as sample for diagnosis of the health of the equipment Insulating Oil Testing ➢ Transformer oil reacts with oxygen to form organic acids, esters, and phenolic compounds which ultimately leads to sludging of the transformer. ➢ The rate of this phenomena increases with an increased exposure to air and temperature. Also it should be noted that oxygen is more soluble in oil than found in air. Not only will the sludge adversely affect the dielectric properties of the oil, but it will also interfere with dissipation of heat within the transformer. ASTM International, formerly known as American Society for Testing and Materials, is an international standards organization that develops and publishes voluntary consensus technical standards for a wide range of materials, products, systems, and services. ASTM has over 30,000 volunteer members from more than 140 countries around the world who are producers, users, consumers and general interest parties. These members write ASTM standards through their service on one or more of our 140-plus technical committees. The routine tests and sampling procedures that are conducted on insulating oil are shown in Table 4.2 Dielectric Breakdown Voltage Test (Cup Tests) ➢ This is an AC overvoltage test applied to the insulating liquids to detect their breakdown strength. ➢ The dielectric test simply consists of placing a liquid sample from the transformer or (circuit breaker) in a cup containing two electrodes of specified gap. ➢ The test is repeated for a least five different samples to determine the average dielectric strength. Dielectric Breakdown Voltage Test Acidity Test ❖ The acidity test measures the content of acids formed by oxidation. The acids are directly responsible for sludge formation. These acids precipitate out, as their concentration increases, and become sludge. They also react with metals to form another form of sludge in the transformer. ❖The ASTM D974 and D664 are laboratory tests whereas D1534 is a field test which determines the approximate total acid value of the oil. Acid Number Interfacial Tension (IFT) ➢ The IFT test is employed as an indication of the sludging characteristics of power transformer insulating liquid. It is a test of IFT of water against liquid, which is different from surface tension in that the surface of the water is in contact with liquid instead of air. ➢ The attraction between the water molecules at the interface is influenced by the presence of polar molecules in the liquid in such a way that the presence of more polar compounds causes lower IFT. The polar compounds are sludge particles or their predecessors. Color Test ➢ This test consists of transmitting light through oil samples and comparing the color observed with a standard color chart. The color chart ranges from 0.5 to 8, with the color number 1 used for new oil. Visual Examination Power Factor Test • The power factor of an insulating liquid is the cosine of the phase angle between applied sinusoidal voltage and resulting current. The power factor indicates the dielectric loss of the liquid and thus its dielectric heating. The power factor test is widely used as an acceptance and preventive maintenance test for insulating liquid. • Power factor tests on oil and transformer liquids are commonly made with ASTM D-924 test cell. ➢ Oil having a power factor of less than 0.5% at 20°C is usually considered satisfactory for service. ➢ Oil having a power factor between 0.5% and 2% at 20°C should be considered as being in doubtful condition and at least some type of investigation should be made. ➢ Oil having a power factor of over 2% at 20°C should be investigated and should be reconditioned or replaced. The question of what decision to make regarding disposition of the oil depends on what is causing the high power factor. Dielectric strength tests should be made to determine the presence of moisture. Specific Gravity ➢ Specific gravity of oil is defined as the ratio of the mass of a given volume of oil to the mass of an equal volume of oil of water at a specified temperature. This test is conducted by floating a hydrometer in oil and taking the reading at the meniscus. For oil free of contaminants, such as water, askarel, or silicone, the reading should be less than 0.84. Water Content Test (Karl Fisher Method) ➢ This test is based on the reduction of iodine according to the traditional Karl Fisher reaction. Three methods are used to conduct this test. Methods A and C utilize iodine present in a titration solution while Method B electrically generates the iodine in the equipment. Moisture content of 69kV and higher voltage transformers should be measured regularly and lower voltage transformers on indication of flow dielectric strength of the oil. Electrical Power Equipment Testing and Maintenance 2nd Ed. By: Paul Gill Insulating Fluids Mineral Oil Silicon Oil Synthetic Ester Oil Natural Ester Oil Properties Applications Combustible Gas Analysis of Insulating Oil An oil-filled transformer insulation system consists of insulating oil and cellulose (paper) materials. Under normal use, transformer insulation deteriorates and generates certain combustible and noncombustible gases. This effect becomes more pronounced when the transformer insulation is exposed to higher temperatures. When cellulose insulation (i.e., winding insulation) is overheated to temperatures as low as 140°C, carbon monoxide (CO), carbon dioxide (CO2), and some hydrogen (H) or methane (CH4) are liberated. The rate at which these gases are liberated depends exponentially on the temperature and directly on the volume of the insulation at that temperature. When insulating oil is overheated to temperatures up to 500°C, ethylene (C2H4), ethane (C2H6), and methane (CH4) are liberated. When oil is heated to extreme temperatures, such as an electrical arc, hydrogen (H) and acetylene (C2H4) are liberated in addition to the above mentioned gases. The main cause of gas formation in a transformer is due to the heating of paper and oil insulation and electrical problems inside the transformer tank. There are two methods for detecting these gases: (1) total combustible gas analysis (TCGA), and (2) dissolved gas analysis (DGA) TCGA The method is applicable to power transformers with a nitrogen blanket or conservator system. The equipment used for measuring TCG is basically a Wheatstone bridge circuit. A combination of air and combustible gas sample is passed over a resistor where catalytic burning takes place on the resistor, which causes a proportional change in resistance. Based on the change in resistance of the resistor, the TCG is measured in percent. Assessing the Transformer Condition Using the TCGA in the Gas Space A new transformer should be tested within a week after energization. If it is not gassing and does not start gassing, subsequent tests should be made progressively increasing intervals until the 12-month normal interval is reached. When sudden increases in the combustible gas quantities or generating rates in the gas space of an operating transfer occur and internal fault is suspected, IEEE Standard C57.104-1991 recommends the procedure to be used as shown in Table 4.5. Electrical Power Equipment Testing and Maintenance 2nd Ed. By: Paul Gill DGA • The oil sample is subjected to a vacuum to remove the combustible gases. These gases are then passed through a gas chromatograph and each gas is then extracted and analyzed for type and quantity. The quantity of each gas is given in part per million (ppm) or percent of the total gas present. The analysis of each gas present provides a useful tool in determining the condition of the transformer. The interpretation of the analysis has not yet been perfected to an exact science and is therefore subject to interpretation. Insulating Gases ❖ Insulating gases, such as SF6, N2, fluorocarbons (freons), H2, and CO2 are used in varying degrees as insulating medium in electrical equipment and apparatus. Since SF6 is used as the principal insulation in high- and mediumvoltage circuit breakers, information is provided on this gas in this section. ❖ SF6 in its normal state is odorless, tasteless, nontoxic, noncorrosive, nonflammable, and inert. ❖ Its dielectric strength is 2–3 times that of air, has high thermal stability, and good arc extinguishing properties. ❖ In circuit breakers, its self-healing properties enable it to regenerate itself following an AC interruption. ❖ The SF6 liquefies at a temperature of below 50°F at a pressure of 220 psig, and on the lower end of the vapor pressure curve the gas becomes a liquid at −20°C at a pressure of 50 psig. Maintenance of SF6 ❖ One maintenance item of concern is to monitor the leakage of SF6 gas from the electrical apparatus. ❖ This can be easily accomplished by using a refrigerator-type freon detector. This is a flameless detector that can detect leaks as small as one ounce per year. ❖ The other concern is the contamination of the gas. There are five types of contaminants in the SF6 gas that must be identified which will require corrective actions. ❖ These contaminants are conducting particles, moisture, oil contamination, gaseous contamination, and arc- decomposition products. Conducting Particles ❖Particles of metallic or carbonaceous matter may be found in the gas, especially in the gas-insulated bus. ❖ At normal operating voltages these particles may cause local ionization of the gas. Under normal circumstances no internal flashover results from this ionization because the SF6 gas will absorb the free electrons as rapidly as they are generated. ❖ However, if the voltage gradient gets high enough, ionization proceeds faster than the ions can be absorbed by the gas molecules, and ion avalanche leads to an internal flashover. Moisture ❖ The SF6 gas shipped from the factory has very low moisture content, less than 40 ppm by volume. Moisture is usually introduced into the gas during installation by inadequate evacuation of the equipment before filling. Water molecules adhering to the solid surfaces inside the equipment will diffuse into the gas after filling. Oil Contamination ❖ Oil and oil vapor containing free carbon molecules can cause flashover of the SF6 gas. Operating experience has shown that clean oil and oil vapor free of carbon does not degrade the performance of the gasinsulated equipment in any way. Gaseous Contamination ❖ The gaseous contamination in the SF6 gas may result from three different sources. The first source of contamination is from the factory where it may have been introduced into the gas. The second source of contamination is in filling or operation of the gas-insulated equipment due to improper handling and procedures. The third source is due to arc decomposition products. Arc Products ❖ The SF6 gas is referred to as a self-healing gas. This is because the gas absorbs the free electrons generated by the arc which causes the gas to ionize. These ions recombine to reform the SF6 gas. Not all of the ions and free atoms recombine properly and some permanent breakdown products can form. Therefore, all arced SF6 gas should be regarded as containing toxic byproducts. THANK YOU FOR LISTENING