SYMMETRICAL COMPONENTS In 1918 one of the most powerful tools for dealing with unbalanced polyphase circuit was discussed by C.L. Fortescue at a meeting of the America Institute of Electrical Engineers. Since the time the method of symmetrical components has become of great importance and has been the subject of many articles and experimental investigations. Unsymmetrical faults on transmission systems, which may consist of short circuits, impedance between lines, impedance from one or two lines to ground, or open conductors, are studied by the method of symmetrical components. SYNTHESIS OF UNSYMMETRICAL PHASORS FROM THEIR SYMMETRICAL COMPONENTS Fortescue’s work proves that an unbalanced system of n related phasors can be resolved into n systems of balanced phasors called the symmetrical components of the original phasors. The n phasors of each set of components are equal in length, and the angles between adjacent phasors of the set are equal. Although the method is applicable to any unbalanced polyphase system, we shall confine our discussion to three-phase systems. SYNTHESIS OF UNSYMMETRICAL PHASORS FROM THEIR SYMMETRICAL COMPONENTS It is customary, when solving a problem by symmetrical components, to designate the three phases of the system as A, B, and C in such a manner that the phase sequence of the voltages and currents in the system is ABC. Thus the phase sequence of the positivesequence components of the unbalanced phasors is ABC, and the phase sequence of the negative-sequence components is ACB. If the original phasors are voltages, they may be designated ππ , ππ & ππ . The three sets of symmetrical components are designated by the additional subscript 1 for the positive-sequence components, 2 for the negative-sequence components, and 0 for the zero-sequence components. SYNTHESIS OF UNSYMMETRICAL PHASORS FROM THEIR SYMMETRICAL COMPONENTS The positive-sequence components of ππ , ππ & ππ πππ ππ1 , ππ1 & ππ1 . Similarly, the negative-sequence components ππ2 , ππ2 & ππ2 , and the zero-sequence components are ππ0 , ππ0 & ππ0 . Figure 1 shows three such sets of symmetrical components. Phasor representing currents will be designated by I with subscripts as for voltages. SYNTHESIS OF UNSYMMETRICAL PHASORS FROM THEIR SYMMETRICAL COMPONENTS Since each of the original unbalanced phasors is the sum of its components, the original phasors expressed interms of their components are ππ = ππ1 + ππ2 + ππ0 ππ = ππ1 + ππ2 + ππ0 ππ = ππ1 + ππ2 + ππ0 SYNTHESIS OF UNSYMMETRICAL PHASORS FROM THEIR SYMMETRICAL COMPONENTS Figure 1 Three sets of balanced phasors which are the symmetrical components of three unbalanced phasors. SYNTHESIS OF UNSYMMETRICAL PHASORS FROM THEIR SYMMETRICAL COMPONENTS • Figure 2 Graphical addition of the components shown in Fig. 1 to obtain three unbalanced phasors. OPERATORS Because of the phase displacement of symmetrical components of the voltages and currents in the three phase system, it is convenient to have a shorthand method of indicating the rotation of a phasor through 120 degree. The result of the multiplication of two complex numbers is the product of their magnitudes and the sum of their angles. If the complex number expressing a phasor is multiplied by a complex number of unit magnitude and angle π , the resulting complex number represents a phasor equal to the original phasor displaced by the angle π. OPERATORS The letter a is commonly used to designated the operator that causes a rotation of 120 degree in the counterclockwise direction. Such an operator is a complex number of unit magnitude with an angle 120 degree and is defined by π = 1∠120° = 1π π2π/3 = −0.5 + π0.866 OPERATORS Figure 3 Phasor diagram of the various power of the operator a. OPERATORS If the operator a is applied to a phasor twice is succession, the phasor is rotated through 240 degree. Three successive application of a rotate the phasor through 360 degree. Thus, π2 = 1∠240° = −0.5 − π0.866 and π3 = 1∠360° = 1∠0° = 1 THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS We have seen (Fig. 2) the synthesis of three unsymmetrical phasors from three sets of symmetrical phasors. The synthesis was made in accordance with the following equations: ππ = ππ1 + ππ2 + ππ0 ππ = ππ1 + ππ2 + ππ0 ππ = ππ1 + ππ2 + ππ0 THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Now let us examine these same equations to determine how to resolve three unsymmetrical phasors into their symmetrical components. First, we note that the number of unknown quantities can be reduced by expressing each component of ππ and ππ as the product of some function of the operator a and a component of ππ . Reference to Fig. 11.1 verifies the following relations: ππ1 = π2 ππ1 ππ2 = πππ2 ππ0 = ππ0 ππ1 = πππ1 ππ2 = π2 ππ2 ππ0 = ππ0 THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS ππ = ππ1 + ππ2 + ππ0 ππ = π2 ππ1 + πππ2 + ππ0 ππ = πππ1 + π2 ππ2 + ππ0 In Matrix form ππ 1 1 ππ = 1 π2 ππ 1 π 1 π π2 ππ0 ππ1 ππ2 THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS ππ Let ππ= ππ ππ 1 1 1 π΄ = 1 π2 π 1 π π2 ππ0 ππ = ππ1 ππ2 The matric equation will become ππ = π΄ππ THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Inverse of A=A-1 −1 π΄ = 1 3 1 1 1 π 1 π2 1 π2 π THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Pre-multiplying the inverse in the matric equation to yields π΄−1 ππ = π΄−1 π΄ππ ππ0 1 1 ππ1 = 1 3 ππ2 1 1 π π2 1 π2 π ππ0 ππ1 ππ2 THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS 1 ππ0 = ππ + ππ + ππ 3 1 ππ1 = ππ + πππ + π2 ππ 3 1 ππ2 = ππ + π2 ππ + πππ 3 THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS The preceding equations could have been written for any set of related phasors, and we might have written them for currents instead of for voltages. They may be solved either analytically or graphically. Because some of the preceding equations are so fundamental, they are summarized for currents: πΌπ = πΌπ1 + πΌπ2 + πΌπ0 πΌπ = π2 πΌπ1 + ππΌπ2 + πΌπ0 πΌπ = ππΌπ1 + π2 πΌπ2 + πΌπ0 1 πΌπ0 = 3 πΌπ + πΌπ + πΌπ 1 πΌπ1 = 3 πΌπ + ππΌπ + π2 πΌπ 1 πΌπ2 = 3 πΌπ + π2 πΌπ + ππΌπ In a three-phase Y-connected system, the neutral current In is the sum of the line currents: πΌπ = πΌπ + πΌπ + πΌπ THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Problem: Calculate the sequence components of the following balanced line-to-neutral voltages with ABC sequence: πππ 277∠0π ππ = πππ = 277∠ −120π π£πππ‘π πππ 277∠120π THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Solution: π0 = 1 3 277∠0π + 277∠ −120π +277∠120π = 0 π1 = 1 3 277∠0π + π277∠ −120π +π2277∠120π = 277∠0 π£πππ‘π = πππ π2 = 1 3 277∠0π + π2277∠ −120π +π277∠120π = 0 This example illustrates the fact that balanced three-phase systems with ABC sequence (or positive sequence) have no zero-sequence or negative-sequence components. For this example, the positive-sequence voltage V1 equals Van, and the zero-sequence and negative-sequence voltages are both zero. THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Problem: A wye-connected load has balanced currents with ACB sequence given by πΌπ 10∠0π πΌπ = πΌπ = 10∠120π π΄πππππ πΌπ 10∠ − 120π Calculate the sequence currents. THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Solution: 1 πΌ0 = 10∠0π + 10∠120π + 10∠ − 120π = 0 3 1 πΌ1 = 10∠0π + π10∠120π + π210∠ − 120π 3 =0 1 3 10∠0π + π210∠120π + π10∠ − 120π = 10∠0 = πΌπ This example illustrates the fact that balanced threephase systems with ACB sequence (or negative sequence) have no zero-sequence or positive-sequence components. For this example the negative-sequence current I2 equals Ia, and the zero-sequence and positive-sequence currents are both zero. πΌ2 = THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Problem: A three-phase line feeding a balanced-Y load has one of its phases (phase B) open. The load neutral is grounded, and the unbalanced line currents are πΌπ 10∠0π πΌπ = πΌπ = π΄πππππ 0 πΌπ 10∠120π Calculate the sequence currents and the neutral current. THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS THE SYMMETRICAL COMPONENTS OF UNSYMMETRICAL PHASORS Solution: πΌ0 = 1 3 10∠0π + 0 + 10∠120π = 3.333∠60 1 πΌ1 = 10∠0π + 0 + π210∠120π = 6.667∠0 3 1 πΌ2 = 10∠0π + 0 + π10∠120π = 3.333∠60 3 πΌπ = 10∠0π + 0 + 10∠120π = 10 ∠60A=3πΌ0 This example illustrates the fact that unbalanced threephase systems may have nonzero values for all sequence components. Also, the neutral current equals three times the zero-sequence current. Definition of Sequence Networks Definition of Sequence Networks Definition of Sequence Networks Sequence Network Models of Power System Components Sequence Network Models of Power System Components Sequence Network Models of Power System Components Sequence Network Models of Power System Components Sequence Network Models of Power System Components Sequence Network Models of Power System Components Sequence Network Models of Power System Components Sequence Network Models of Power System Components Simplified Derivation of Transformer ZeroSequence Circuit Modeling Simplified Derivation of Transformer ZeroSequence Circuit Modeling Simplified Derivation of Transformer ZeroSequence Circuit Modeling Simplified Derivation of Transformer ZeroSequence Circuit Modeling Simplified Derivation of Transformer ZeroSequence Circuit Modeling Transformers (Zero-Sequence Circuit Model) Transformers (Zero-Sequence Circuit Model) Transformers (Zero-Sequence Circuit Model) Transformers (Zero-Sequence Circuit Model) Transmission Lines (Positive Sequence Network) Transmission Lines (Negative Sequence Network) The same model as the positive-sequence network is used for transmission lines in as much as the positive-sequence and negativesequence impedances of transmission lines are the same Transmission Lines (Zero Sequence Network) The zero-sequence network model for a transmission line is the same as that of the positive- and negative-sequence networks. The sequence impedance of the model is of course the zero-sequence impedance of the line. This is normally higher than the positive- and negativesequence impedances because of the influence of the earth’s resistivity and the ground wire/s. Classification of Power System Short Circuits Shunt Faults Single line-to-ground faults Double line-to-ground faults Line-to-line faults Three-phase faults Classification of Power System Short Circuits Combination of Shunt and Series Faults Single line-to-ground and one-line open Double line-to-ground and one-line open faults Line-to-line and one-line open faults Three-phase and one-line open faults Classification of Power System Short Circuits Combination of Shunt and Series Faults Single line-to-ground and two-line open faults Double line-to-ground and two-line open faults Line-to-line and two-line open faults Three-phase and two-line open faults Balanced Faults (Symmetrical or Three-Phase Faults) Balanced Faults (Symmetrical or Three-Phase Faults) Unbalanced Faults (Single Line-to-Ground Faults) Unbalanced Faults (Single Line-to-Ground Faults) Unbalanced Faults (Line-to-Line Faults) Unbalanced Faults (Line-to-Line Faults) Unbalanced Faults (Line-to-Line Faults) Unbalanced Faults (Double-to-line Ground Fault) Unbalanced Faults (Double-to-line Ground Fault) Unbalanced Faults (Double-to-line Ground Fault) Unbalanced Faults (Double-to-line Ground Fault) Unbalanced Faults (Double-to-line Ground Fault) Assumptions Made to Simplify Fault Calculations 1. Pre-fault load currents are neglected. 2. Pre-fault voltages are assumed equal to 1.0 per unit. 3. Resistances are neglected (only for 115kV & up). 4. Mutual impedances, when not appreciable are neglected. 5. Off-nominal transformer taps are equal to 1.0 per unit. 6. Positive- and negative-sequence impedances are equal. Outline of Procedures for Short Circuit Calculations 1. Setup the network impedances expressed in per unit on a common MVA base in the form of a single-line diagram 2. Determine the single equivalent (Thevenin’s) impedance of each sequence network. 3. Determine the distribution factor giving the current in the individual branches for unit total sequence current. Outline of Procedures for Short Circuit Calculations 4. Interconnect the three sequence networks for the type of fault under considerations and calculate the sequence currents at the fault point. 5. Determine the sequence current distribution by the application of the distribution factors to the sequence currents at the fault point. 6 Synthesize the phase currents from the sequence currents. Outline of Procedures for Short Circuit Calculations 7. Determine the sequence voltages throughout the networks from the sequence current distribution and branch impedances. 8. Synthesize the phase voltages from the sequence voltage components. 9. Convert the pre unit currents and voltages to actual physical units. FAULT CALCULATIONS Problem: A 50 MVA, 11 kV, synchronous generator has a substransient reactance of 20 %. The generator supplies two motors over a transmission line with transformers at both ends as shown in the figure. The motors have rated inputs of 30 and 15 MVA, both 10 kV, with 25% subtransient reactance. The three-phase transformers are both rated 60 MVA, 10.6/121 kV, with leakage reactance of 10% each. Assume zero-sequence reactances for the generator and motors of 6 % each. Current limiting reactors of 2.5 ohms each are connected in the neutral of the generator and motor No. 2. The zero sequence reactance of the transmission line is 300 ohms. The series reactance of the lines is 100 ohms. Draw the positive, negative and zero sequence networks. FAULT CALCULATIONS Problem: Assume that the negative sequence reactance of each machine is equal to its subtransient reactance FAULT CALCULATIONS Solution: Assume base power=50 MVA, Base voltage 11 kV FAULT CALCULATIONS FAULT CALCULATIONS Positive sequence network FAULT CALCULATIONS Negative sequence network FAULT CALCULATIONS Zero sequence network FAULT CALCULATIONS Assignment: (To be passed next meeting) 1.The phase voltages across a certain load are given as: ππ = 176 − π132 π£πππ‘π ππ = −128 − π96 π£πππ‘π ππ = −160 + π100 π£πππ‘π Compute positive, negative and zero sequence component of voltage. FAULT CALCULATIONS Assignment: (To be passed next meeting) 2. A balance delta-connected load is connected to a three-phase system and supplied to it’s a current 0f 15 ∠0 amperes. If the fuse in one of the lines melts, compute the symmetrical components of the line currents. FAULT CALCULATIONS Assignment: (To be passed next meeting) FAULT CALCULATIONS Assignment: (To be passed next meeting) 3. Draw the positive, negative and zero sequence networks of the power system shown below. FAULT CALCULATIONS Assignment: (To be passed next meeting) 4. Figure shown below is a sample power system network. Draw the zero sequence network. Data is given below. FAULT CALCULATIONS Assignment: (To be passed next meeting)