Uploaded by 林建佑

SIEMENS 7SJ551 Manual

advertisement
Multi-f unction Protection Relay
for Motors, Transformers, Blow-out Coils, Cables and Overhead Lines
-
Figure 1
-
Order No. G88700-C3527-07-7600
instruction Manual
illustration of the multi-function protection relay MFR 7SJ551
O Siemens Nederland N.V. 1998 Version R03-03
1
,
,
MFR7SJ551
Introduction
Certificate of Conformity
This product is in conformity with the directive of the Council of the European Communities on the
harmonisation of the laws of the Member States relating to electromagnetic compatibility (EMC Council
Directive 89/336/EEC).
Conformity is proved by tests that have been performed according to article 10 of the Council Directive in
accordance with the generic standards EN 50081-2 and EN 50082-2 by Siemens Nederland N.V.
The device is designed and manufactured for application in industrial environment.
The device is designed in accordance with the standards of IEC 255 and VDE 0435 part 303.
MFR 7SJ551
Introduction
contents
1 introduction
.......................................................................................................................8
.............................................................................................................................................
.................................................................................................................................................
1.1 Application
8
..
1.2 Features
8
1.3 Implemented functions .........................................................................................................................
10
2 Design
2.1
2.2
2.3
............................................................................................................................I 1
............................
.
.
..............................................................................................
....................................................................................................................................
.................................................................................................................................
Arrangements
11
.
Dimensions
13
Ordering data
16
2.3.1 Protection unit ................................................................................................................................
16
2.3.2 Interface unit...................................................................................................................................
I6
17
2.3.3 Operation and evaluation software.................................................................................................
17
2.3.4 Spare parts ....................................................... ..............................................................................
2.3.5 Surface mounting bracket ..............................................................................................................
17
2.3.6.0ptical cable...................................................................................................................................17
3 Technical data ...............................................................................................................
18
3.1
...................................................................................................................................
General data
18
3.1 .1 Inputs / outputs ...............................................................................................................................
18
3.1.2 Electrical tests .........................
.
....................................................................................................
22
3.1.3 Mechanical stress test ....................................................................................................................
24
3.1.4 Climatic stress tests .......................................................................................................................
24
3.1.5 Service conditions ..........................................................................................................................25
3.1.6 Interchangeability........................................................................................................................... 25
3.1.7 Design ............................................................................................................................................
25
3.2
Component data ............................................................................................................................26
3.3
Thermal overload protection
26
26
3.3.1 Rotor thermal overload protection ..................................................................................................
3.3.2 Stator thermal overload protection .................................................................................................28
3.3.3 Thermal overload protection of non-rotating objects ......................................................................
29
30
Ambient temperature biasing (optional)
3.4
3.5
Start inhibit
31
3.6
Locked rotor protection
32
32
3.7
Zero speed protection
3.8
Unbalance protection
33
3.9
Undercurrent protection ......................;........................................................................................
34
3.1 0
Overtemperature protection (optional)
35
3.1 1
Low set overcurrent protection
36
3.1 1.1 Definite time overcurrent protection .............................................................................................
36
3.1 1.2 Inverse time overcurrent protection.............................................................................................. 37
3.1 1.3 Custom curve overcurrent protection ...........................................................................................
39
40
High set overcurrent protection
3.12
Curve switch
41
3.1 3
Directional earthfault protection (optional)
42
3.14
Undervoltage protection (optional)
44
3.1 5
3.1 6
Overvoltage protection (optional)
45
3.1 7
Breaker failure trip
46
3.1 8
Block ...............................................................................................................................................
46
3.1 9
External command
47
3.20
Ancillary functions
47
....................................................................................................
.....................................................................................
.....................................................................................................................................
................................................................................................................
...................................................................................................................
....................................................................................................................
.....................................................................................
.................................................................................................
...................................................................................................
................................................................................................................................
................................................................................
.............................................................................................
...............................................................................................
.........................................................................................................................
......................................................................................................................
........................................................................................................................
MFR 7SJ551
Introduction
4 Method of operation
1
........................................................................................................49
................................................................................................
....................................................................................................
4.1
4.2
Operation of the complete unit
4 9
Thermal overload protection
50
4.2.1 Theoretical background .................................................................................................................
50
4.2.1.1 Single-body thermal overload model ..................................................................................
50
4.2.1.2 Two-body thermal overload model......................................................................................
53
4.2.2 Rotor thermal overload protection .................................................................................................
54
4.2.3 Stator thermal overload protection ................................................................................................
55
4.2.4 Thermal overload protection of transformers, blow-out coils and cables ......................................56
4.3
Ambient temperature biasing (optional)
57
4.4
Start inhibit
58
4.5
Emergency restart
59
4.6
Locked rotor protection
59
4.7
Zero speed protection
60
4.8
Motor start-up protection
60
4.9
Unbalance protection
62
4.9.1 General ..........................................................................................................................................62
4.9.2 Unbalance protection of motors ................................................................................................... 63
4.1 0
Undercurrent protection
63
4.10.1 General ........................................................................................................................................
63
4.1 0.2 Motor undercurrent protection ..................................................................................................... 64
4.1 1
Overtemperature protection (optional)
64
4.12
Low set overcurrent protection
65
4.12.1 Definite time overcurrent protection .............................................................................................
65
4.12.2 Inverse time overcurrent protection .............................................................................................
65
4.12.3 Custom curve overcurrent protection ..........................................................................................
66
4.13
High set overcurrent protection
66
4.1 3.1 Fast busbar protection using the reverse interlock scheme ........................................................ 67
4.14
Curve switch
67
4.15
Directional earth fault protection (optional)
67
4.1 5.1 Cos f determination .....................................................................................................................
68
4.1 5.2 Sin f determination.......................................................................................................................69
4.1 5.3 Sensitivity emprovement by shifting the symmetry axis ..............................................................
69
4.1 5.4 Correcting the angular error of the core balance transformer .....................................................69
4.1 5.5 Earth fault location .......................................................................................................................
70
4.1 6
Undervoltage protection (optional)
70
4.17
Overvoltage protection (optional)
71
71
4.18
Breaker failure trip
4.19
Block
72
4.20
External command
72
4.21
Circuit breaker position
72 .
4.22
Ancillary functions
72
4.22.1 Processing of annunciations........................................................................................................
72
4.22.2 Fault event data storage and transmission (optional)..................................................................73
4.22.3 Operational value measurements ................................................................................................
74
4.22.4 Demand ampere meter ...............................................................................................................
74
74
4.22.5 Test facilities ................................................................................................................................
4.22.6 Hardware monitoring ...................................................................................................................
74
.....................................................................................
....................................................................................................................................
........................................................................................................................
...............................................................................................................
..................................................................................................................
.............................................................................................................
...................................................................................................................
..............................................................................................................
....................................................................................
...................................................................................................
.............................................................................................
...........................................................................................................................
...............................................................................
.............................................................................................
...............................................................................................
........................................................................................................................
........................................................................................................................................
........................................................................................................................
...............................................................................................................
...................................................................................................................
..................................................................................................76
5 installation instructions
5.1
5.2
.........................................................................................................
..................................................................................................................................
Unpacking and repacking
76
Preparations
76
5.2.1 Mounting and connections .............................................................................................................
77
77
5.2.2 Checking the rated data ..............................................................................................................
5.2.3 Checking the (optional)
interface unit transmission link ................................................................ 77
. .
5.2.4 connections .................................................................................................................................... 7 8
5.2.5 Checking the connections .......................................................................................................78
~
1
Introduction
MFR 7SJ551
Operating ia7istrwctiorms
6
......................................................................................80
........................................................................................................................
.................................................................................................................
6.1
6.2
Safety precautions
80
Dialogue with the relay
80
6.2.1 Display panel ..................................................................................................................................
80
6.2.2 Keyboard ........................................................................................................................................80
81
6.2.3 LED indicators ................................................................................................................................
81
6.2.4 Operation with a personal computer ..............................................................................................
6.2.5 Front view of the relay ....................................................................................................................
82
6.3
Parameterizing procedure
83
6.3.1 Menu structure ...............................................................................................................................
83
6.3.2 Initial display ...................................................................................................................................
84
6.4
Main menu (OFF LINE)
84
6.5
SETTINGS menu
85
6.6
Settings for DEVICE DATA
86
6.6.1 Non-rotating device ........................................................................................................................
87
6.6.2 Rotating device...............................................................................................................................
87
6.7
Settings for CHANNELS
89
6.8
Settings for PROTECTIONS
93
6.8.1 THERMAL OVERLOAD protection ................................................................................................ 94
6.8.1.1 Thermal overload protection for rotating objects .................................................................
94
6.8.1.2 Thermal overload protection for non-rotating objects ..........................................................
97
6.8.2 AMBIENT TEMPERATURE BIASING (optional) ...........................................................................99
6.8.3 START INHIBIT ............................................................................................................................ 100
102
6.8.4 EMERGENCY RESTART ...........................................................................................................
6.8.5 OVERTEMPERATURE protection (optional) ...............................................................................
103
6.8.6 UNDERCURRENT protection ......................................................................................................
104
6.8.7 LOW SET OVERCURRENT protection .......................................................................................
105
6.8.7.1 Definite time phase fault overcurrent protection ................................................................
106
6.8.7.2 Definite time earth fault overcurrent protection .................................................................
108
6.8.7.3 Inverse time phase fault overcurrent protection ................................................................ 109
6.8.7.4 Inverse time.earth fault overcurrent protection ..................................................................110
6.8.7.5 Custom curve overcurrent protection ................................................................................111
6.8.8 HIGH SET OVERCURRENT protection.......................................................................................113
114
6.8.9 UNBALANCE protection .............................................................................................................
6.8.1 0 DIRECTIONAL EARTHFAULT protection (optional) ..................................................................
115
6.8.1 1 LOCKED ROTOR protection.............:........................................................................................
118
6.8.12 ZERO SPEED protection ............................................................................................................
118
6.8.1 3 UNDERVOLTAGE protection (optional) .....................................................................................
119
6.8.1 4 OVERVOLTAGE protection (optional) ...................................................................................I19
6.8.1 5 BREAKER FAILURE TRIP .........................................................................................................
120
6.8.16 CURVE SWITCH .......................................................................................................................122
6.8.17 BLOCK .......................................................................................................................................
123
6.8.1 8 EXTERNAL COMMAND ............................................................................................................
125
125
6.8.1 9 CIRCUIT BREAKER POSITION ................................................................................................
6.9
Settings for TRANSIENT DATA
127
6.10
Settings for the REAL TIME CLOCK
127
6.11
MARSHALLING of binary inputs, binary outputs and LED indicators
128
6.1 1 1 General .......................................................................................................................................
128
6.1 1.2 Marshalling of the BINARY INPUTS ..........................................................................................129
6.1 1.3 Marshalling of the OUTPUT RELAYS ........................................................................................
132
6.1 1.4 Marshalling of the LED INDICATORS (optional) ........................................................................
136
6.12
Settings for SERIAL COMMUNICATION (optional)
137
6.13
Putting the relay into operative mode (ON LINE)
139
6.14
Annunciations
140
6.14.1 Introduction.................................................................................................................................
140
6.14.2 MEASURED VALUES ................................................................................................................ 141
6.14.3 COUNTERS ...............................................................................................................................4 3
6.14.4ALARM /TRIP DATA .................................................................................................................143
6.1 4.5 DEMAND AMPERE METER ....................................................................................................
146
6.14.6 RUNNING HOURS ....................................................................................................................147
............................................................................................................
..................................................................................................................
............................................................................................................................
...........................................................................................................
................................................................................................................
.........................................................................................................
.
..................................................................................................
..........................................................................................
...................................
..................................................................
....................................................................
..............................................................................................................................
I
...
Introduction
MFR 7SJ551
I
6.1 4.7 MANUFACTURER DATA ..........................................................................................................
148
Resetting all settings t o factory settings
149
6.15
Testing and commissioning
151
6.16
6.16.1 General .......................................................................................................................................
151
6.1 6.2 Testing the measurement of operational values .......................................................................
152
6.1,6.3 Testing the motor status ............................................................................................................
153
153
6.1 6.4 Testing the rotor thermal overload protection ............................................................................
6.1 6.5 Testing the stator thermal overload protection ........................................................................156
6.1 6.6 Testing the thermal overload protection of non-rotating objects ............................................... 159
161
6.1 6.7 Testing the ambient temperature biasing ..................................................................................
162
6.1 6.8 Testing the start inhibit .........;....................................................................................................
163
6.1 6.9. Testing the emergency restart ..................................................................................................
163
6.1 6.10 Testing the overtemperature protection ...................................................................................
163
6.1 6.1 1 Testing the undercurrent protection.........................................................................................
6.1 6.1 2 Testing the low set overcurrent protection...............................................................................
164
6.16.1 2.1 Testing the definite time overcurrent protection............................................................
164
165
6.1 6.12.2 Testing the inverse time overcurrent protection............................................................
6.1 6.1 2.3 Testing the custom curve overcurrent protection ........................................................
165
166
6.1 6.1 3 Testing the high set overcurrent protection .............................................................................
166
6.16.1 4 Testing the unbalance protection ............................................................................................
167
6.1 6.1 5 Testing the locked rotor protection ..........................................................................................
168
6.1 6.1 6 Testing the zero speed protection ...........................................................................................
6.1 6.1 7 Testing the directional earthfault protection........................................................................ 168
169
6.16.1 8 Testing the undervoltage protection .....................................................................................
;.............169
6.1 6.1 9 Testing the overvoltage protection ............................................................................
6.1 6.20 Testing the breaker failure trip ............................................................................................ 170
6.1 6.21 Testing the curve switch ....................................................................................................... 170
172
6.1 6.22 Testing the block function ........................................................................................................
173
6.1 6.23 Testing the external command ............................................................................................
173
6.1 6.24 Testing the circuit breaker position ..........................................................................................
6.17
Commissioning using primary tests
174
6.1 7.1 Current circuit checks .................................................................................................................
174
6.17.2 Checking the reverse interlock scheme (if used) ...................................................................... 174
175
6.17.3 Testing the switching of binary inputs and outputs ....................................................................
176
6.17.4 Tripping test including circuit breaker ........................................................................................
6.1 7.5 Putting the relay into operation ..................................................................................................176
.................................................................................
....................................................................................................
..
.......................................................................................
1
Maintenance and trouble shooting
7
I
7.1
7.2
7.3
7.4
7.5
7.6
................................................................177
.........................................................................................................................................177
Self test ........................................................................................................................................177
Replacing the real time clock module ................................................................................... 178
Power failure test ........................................................................................................................179
General
Routine checks .................................................................................................................. 1 7 7
Trouble shooting ........................................................................................... .........................176
7.6.1 Replacing the mini-fuse ............................................................................................................... 180
Repairs .............................................................................................................182
Storage .............................................................................................................183
~
I
Appendix
.
.
.
.
A
B
C
D
E.
................................................................................................................................ 184I
............................... ...........................................................................
.............................................................................................................
....................................................................................................
.............................................................................................................................
General diagrams
185
Typical wiring diagrams
190
Motor application example
192
Default values
199
Setting tables .......................................................................................................................
204
I
"
'
MFR 7SJ551
F.
Introduction
Advice of return 7SJ55 ................................................................................................................
224
NOTE:
This instruction manual does not intend to cover ail
details in equipment, nor to provide for every
possible contingency occurring in connection with
installation, operation or maintenance.
a
-
Should further information be desired or should
particular problems arise which are not covered
sufficiently for the purchaser's purpose, the matter
should be referred to the local Siemens sales
office.
The contents of this instruction manual shall not
become part nor modify any prior or existing
agreement, commitment or relationship. The sales
contract contains the entire obligations of Siemens.
The warranty contained in the contract between the
parties is the sole warranty of Siemens. Any
statements contained herein do not create new
warranties nor modify the existing warranty.
1
1
" ,
Introduction
MFR 7SJ551
I
Introduction
1.I
Application
The relay MFR 7SJ551 is a modern protection unit
for low, medium and high voltage electricity
network components like motors, transformers,
blow-out coils, cables, overhead lines and capacitor
banks. The treatment of the electricity network star
point is oi no concern. The main applications of
MFR 7SJ551 are:
- protection against too high temperature
- protection against short circuit situations.
Too high temperatures in electric components
cause isolation ageing, which leads to lifetime
shortening of the component. Temperature
protection is accompanied with relatively low
currents and long time settings. Excessive
temperature rising can appear because of:
- overload
- asymmetrical load or phase loss
- underload (fans and pumps)
- stalled rotor
- multiple starting and tripping
- starting too long.
Short-circuits in electric components are
characterised by very high currents. These currents
1.2
Besides phase and earth short-circuit protection
MFR 7SJ551 is used as earth fault direction
protection for isolated, compensated and highohmic earthed networks.
Furthermore MFR 7SJ551 can be put on as backup protection for differential protection (for
generators, motors, transformers, lines or bus
bars) and distance protection.
MFR 7SJ551 provides a complete statistical record
of the protected electric component. The number of
alarms and trips is recorded in a memory. All
relevant alarm and trip data such as origin, day and
time, duration and trip levels can be read off on the
display. During an alarm or trip event the
magnitudes of the instantaneous values are stored
for a period of 3 seconds. This information can be
visualized with a PC connected to either the RS485 or the fibre optic interface. Furthermore, the
serial interfaces can be used for incorporating MFR
7SJ551 in a substation management system. For
data transmission an standardized protocol is used
in accordance with IEC 870-5.
Features
- Controller system with powerful microcontroller;
-
are acceptable only for short periods of time
because of the acting short-circuit strengths.
completely digitally measured value processing
and control from data acquisition and digitizing
of the measured values up to the trip and close
decision for the circuit breaker;
-
complete scope of functions required for the
protection of motors, transformers and cables;
- separate setting tables for the protection of
rotating and non-rotating network components;
- all current and voltage protection functions
(except thermal overload protection which is
based on True RMS measurement) based on
the values of the nominal frequency (digital
Fourier filtering); the direct current component
and the higher harmonic components are
suppressed and do not disturb the protection
functions;
- complete galvanic and reliable separation of the
internal processing circuits from the
measurement, control and supply circuits of the
system, with screened analogue input
transducers, binary input and output modules
and DC converter;
- thermal overload protection of rotating devices:
separate thermal replica for stator and rotor
based on True RMS current measurement
up to 2 heating time constants for the stator
thermal replica
separate cooling time constants for stator
and rotor thermal replica
ambient temperature biasing of thermal
replica
incorporation of additional heating effects of
asymmetrical currents;
"
I
MFR 7SJ551
- thermal overload protection of non-rotating
devices:
up to 2 heating time constants with extremely
wide setting ranges for optimal thermal
protection of cables and transformers
s externally adjustable time constant
ambient temperature biasing of thermal
replica;
Introduction
-
curve switch and blocking functions offering an
adaptive feature to change the relay
characteristics according to prevailing system
conditions (like motor status 'start' or 'running');
-
equipped with highly sophisticated protection
algorithms which offer optimal flexibility in
grading with other protection relays and with the
thermal limit curves of primary components;
-
software matrix for signalling and tripping relays;
-
real time clock: last 3 events are stored with real
time stamps of alarm and trip data;
-
continuous monitoring of the measured values
and the hardware and software of the relay;
-
storage of fault data, storage of instantaneous
values during a fault for fault recording;
-
communication with a PC or a substation
management system through an RS485
interface or a fibre optic interface (optional)
using an IEC 870-5-103 protocol.
- connection of up to 8 temperature sensors
(optional);
- multi-curve overcurrent and earth fault
protection:
e
insensitive for transients and DC
components
e
separate two-stage tripping characteristics
for phase and earth elements
four selectable internationally standardized
(BS 142, IEC 255-4) tripping characteristics
for phase elements: normally inverse, very
inverse, extremely inverse and definite time
e two additional tripping characteristics for the
earth element: long time earth fauit and
residual dependent time;
custom curves instead of standard curves
can be programmed to offer optimal flexibility
for both phase and earth elements;
"
6
MFR 7SJ551
1.3
Introduction
Implemented functions
MFR 7SJ551 contains the following functions.
Protection of motors
ANSI Protection of transformers
blow-out coils
cables
overhead lines
capacitor banks
Rotor thermal overload protection
Stator thermal overload protection
Ambient temperature biasing (optional)
Start inhibit
Emergency restart
Locked rotor protection (failure to accelerate)
Zero speed protection
Unbalance protection
Undercurrent protection
Overtemperature protection (optional)
Definite time overcurrent protection
49R
49
Inverse time overcurrent protection
Custom curve overcurrent protection
High set overcurrent protection
Curve switch
Directional earth fault protection (optional)
Undervoltage protection (optional)
Overvoltage protection (optional)
Breaker failure trip
Block
External command
Circuit breaker position
Self-monitoring
Real time clock
Event recording
Fault recording
Motor statistical data
LED indication
Operational values measurement
Running hours counter
PC programming possibility (optional)
Substation management system connection
(optional)
ANSI
Thermal overload protection
Ambient temperature biasing (optional)
49
Unbalance protection
Undercurrent protection
Overtemperature protection (optional)
Definite time overcurrent protection
46
37
86
48
14
46
37
51
51G
51 N
51
51 G
51 N
50
50G
67N
27
59
For a detailed description please refer to chapter 4.
Inverse time overcurrent protection
Custom curve overcurrent protection
High set overcurrent protection
Curve switch
Directional earth fault protection (optional)
Undervoltage protection (optional)
Overvoltage protection (optional)
Breaker failure trip
Block
External command
Circuit breaker position
Self-monitoring
Real time clock
Event recording
Fault recording
Component statistical data
LED indication
Operational values measurement
PC programming possibility (optional)
Substation management system connection
(optional)
51
51 G
51 N
51
51G
51N
50
50G
67N
27
59
MFR 7SJ551
1)
2
Design
2.1
Arrangements
The complete relay is fitted in a draw-out module of
Double Europe Format. This module is installed in
a housing 7XP20.
The optional interface unit (see figure 2.1)
provides:
- 8 x 3 screw terminals for up to 8 temperature
sensors;
- 9 pole female connector for the RS-485;
- a transceiver and a transmitter fibre optic
interface.
Two types of housings can be delivered:
- 7SJ551*-*A***- in horizontal housing 7XP20 for
-
panel flush mounting or cubicle installation.
7SJ5.51*-*B***- in vertical housing 7XP20 for
panel flush mounting or cubicle installation.
The housing has full sheet-metal covers as well as
a removable front cover with transparent plastic
window for panel mounting.
Guide rails are built in for the support of the plug-in
module. On the top and bottom plates of the
housing, contact areas which are electrically
connected to the housing are installed to mate with
the earthing springs of the module. Connection to
earth is made before the plugs make contact. An
Design
earth screw has been provided on the back of the
housing.
The heavy-duty current plug connectors provide
automatic shorting of the current transformer
circuits whenever the module is withdrawn.
All external signals are connected to combined
screw snap-on terminals on the backside of the
housing. For field wiring, the use of the screwed
terminals is recommended; snap-in connection
requires special tools. See figure 2.2.
The plug modules are labelled according to their
mounting position by means of a grid system (e.g.
XE-IV.2). The individual connections within a
module are numbered consecutively from left to
right (when viewed from the back).
The degree of protection for the housing is IP51,
for the terminals IP21.
For dimensions please refer to figure 2.3.
For surface mounting, surface mounting brackets
are deliverable in two sizes. The short one (depth
271 mm) is used for protection units without
mounted interface module. The long one (depth
288 mm) is used with mounted interface module.
MFR 7SJ551
Figure 2.1
Design
Interface unit
I
Figure 2 . % U N m h M B n ~ ~ r c ! & i M f S w ~ i ~ w )
1
1
MFR 7SJ551
$
2.2
Design
Dimensions
Figure 2.3 shows the dimensions of the housing.
7SJ551 housing for panel flush mounting or cubicle installation 7XP20
interface unit (optional)
recess hole (4 x)
1,
86.4
mounting hole (4
interface unit (optional)
Heavy-current connectors:
Screwed terminal for maximum 4 mm2.
Twin spring crimp connector in parallel for maximum 2.5 mm2.
Further connectors:
Screwed terminal for maximum 1.5 mm2.
Twin spring crimp connector in parallel for maximum 1.5 mm2.
Dimensions in mm
Figure 2.3
Dimensions for housing 7XP20 for panel flush mounting or cubicle installation
cl
MFR 7SJ551
Figure 2.4 shows the surface mounting bracket.
Figure 2.4
Dimensions for suriace mounting bracket for panel surface mounting
~esign'
"
I
MFR 7SJ551
I)
MFR 7SJ.551 can be mounted in standard 19 inch double height racks. Figure 2.5 shows the relevant
dimensions.
Figure 2.5
Mounting of MFR 7SJ.551 in standard 19"racks
Design
1
MFR7SJ551
2.3
Ordering data
2.3.1
Protection unit
[ Multi-Function Protection Relay
Rated current: rated freoluencv
Auxiilarv voltaae
Construction
I in horizontal housing 7XP20 for panel flush mounting or
cubicle mounting
in vertical housing 7XP20 for panel flush mounting or
cubicle mountina
Operating language
English
German
Connections
1 standard version
Desian
1
7SJ551 1
7
8
j
9
[a1
11
-
0
1
14
10 1
extended input / output: 3 extra inputs, 2 extra outputs,
4 extra LED indicators
extended input Ioutput: 3 extra inputs, 2 extra outputs,
4 extra LED indicators + voltage functions (single
phase)
2
extended input loutput: 3 extra inputs, 2 extra outputs,
4 extra LED indicators + voltage functions (single
phase) earth fault direction
(only in combination with e,,,,,iv, 1 A)
3
Interface module
15
1 without
RS485 + optical FSMA-interface
RS485 + optical FSMA-interface + connection for 2 RTD
elements ,
RS485 + optical FSMA-interface + connection for 8 RTD
elements
B
C
D
MFR 7SJ551
2.3.2
Design
interface unit
The interface unit can be ordered separately with the following ordering numbers. It is always possible to equip
the protection unit with the interface unit later on.
RS-485 + optical FSMA-interface ...................................................
RS-485 + optical FSMA-interface + connection for 2 RTD elements ..
RS-485 + optical FSMA-interface + connection for 8 RTD elements ..
2.3.3
Operation and evaluation software
Operation and evaluation software 7SJ551 Communication Utility
English ........................................................................................
German ....................................................... i....................... .......
@
2.3.4
G88700-C3526-L130
G88700-C3526-L131
G88700-C3526-L132
688700-M3587-R100
G88700-H3587-R200
Spare pans
Complete housing for panel flush mounting or cubicle installation .......
Front cap .....................................................................................
Enbedded software English 1) .........................................................
Enbedded software German 1) ........................................................
G88700-63526-b153
G88080-W-350-b110
G88080-C3526-L9X1
688080-C3526-L9XO
1) By ordering software please give the serienumber of the relay
2.3.5
Surface mounting bracket
Surface mounting bracket long (depth 288 mm) ...............................
Surface mounting bracket short (depth 271 mm) ..............................
2.3.6
Optical cable
Optical cable complete (5 meter).....................................................
Notebook connector ....................................................................
G88700-C3526-L154
G88080-X504-Lf 10
MFR 7SJ551
Technical data
I)
Technical data
3.1.1
laputs / outputs
Setting ranges
Full scale phase current
Full scale regular earth current
Full scale sensitive earth current
Irn,~
,,I
I, ,
,
Current transformer ratio
?
.age transformer ratio
Measuring circuits
Rated current I,
(3 x Iph+1 x 1),
Rated current I, ,,,itive
1A
Rated voltage U,
(1 x U)
100 V o r 110V
Rated frequency f ,
50 Hz or 60 Hz (selectable)
Burden at I, I U,
- 1 A current inputs
- 5 A current inputs
- 1 A sensitive earth current input
voltage input
capability phase current and regular earth
current path
- thermal (RMS)
10.05
VA
100
x I,
XI,
x I,
x I,
for 1 s
for10s
continuous
one half cycle
x I,
x I,
x I,
x I,
for 1 s
for 10 s
continuous
one half cycle
30
6
-
dynamic (pulse current)
Overload capability sensitive earth current path
thermal (RMS)
-
dynamic (pulse current)
250
75
20
4
200
''
MFR 7SJ551
i
Technical data
0
Accuracy
Phase currents and regular earth currents
for full scale current
,,I =
7
x ,I
0
0.05
to 0.5
X In
0
0.5
to 7
X ,1
- for full scale current
,,I =
14
x I,
0
0.1
to
1
X In
0
1
to 14
X In
- for full scale current, , I =
28
x In
0.2
to 2
X In
0
2
to 28
X 1,
-
Sensitive earth current
- for full scale current I,
,
,
= 0.35
0.003
to0.025
x I,
0
0.025
t00.35
X in
- for full scale current
,,,I
= 0.7
0.005
t00.05
X In
0
0.05
to 0.7
X In
- for full scale current I, ,
,= 1.4
* 0.01
x In
to 0.1
* 0.1
to 1.4
X In
X
50.025
I5
X
In
% of setting value
10.05
I 5
o/'
In
of setting value
50.1
I 5
X
In
10.00125
5 5
x I,
% of setting value
10.0025
I5
X
10.005
5 5
X
S0.0005
I 5
X
X
% of setting value
In
0
X
X
In
In
% of setting value
In
In
% of setting value
Voltage
0.005
0.01
t00.01
to 1.2
X
Un
x
un
Un
% of setting value
Auxiliary supply voltage
Power supply via integrated AC/DC or DCIDC
converter
Rated auxiliary voltage Uh
Permissible variations
-60VDC
24
19.2 - 7 2 V D C
Superimposed AC voltage,
peak to peak
I 12
6
%
%
at rated voltage
at limits of admissible voltage
Power consumption
quiescent
energized
picked up
-
Bridging time during failure or short circuit of auxiliary
voltage
20 ms at
500 ms at
40msat
500 rns at
40rnsat
500 rns at
I
110-250VDC
110-230VAC
8 8 - 3 0 0 ( ~ ~8 8~- 2 5 6 V A C
24 V DC
60 V DC
110VDC
250 V DC
110VAC
230 V AC
Technical data
MFR 7SJ551
vy duty command and signal contacts
Command (trip) and signal relays
basic version
e number
-
contacts per relay
- version with extended 1/0
number
contacts per relay
Switching capacity
MAKE
BREAK
DC
AC
4 command or signal relays
1 monitor relay
output 1 - 4 : 1 NO
monitor
: 1 NC
6 command or signal relays
1 monitor relay
: 2N0
output 1
output 2 - 5 : 1 NO
monitor
: 1 NC
1000 W N A
30 W150 VA
300 V
250 V
5 A continuous
30 A for 0.5 sec
Binary control inputs, number
-
basic version
- version with extended I/O
2 (can be marshalled)
5 (can be marshalled)
Current consumption
24 - 250 V DC
110- 230VAC
approx. 3 mA, independent of the operating voltage
Minimum signal time
2
5 ms
Detection time
5
10ms
Operating voltage
Interface module
0
RS485 serial interface
Floating interface for data communication
with PC or substation management system
Protocol standards
o
Transmission speed
Hamming distance
Connection
Transmission distance
Test voltage
isolated by opto-couplers
IEC 870-5 with VDEWIZVEI recommendation or
protocol DIN 19244
2400 Baud
4800 Baud
9600 Baud
19200 Baud
38400 Baud
d=4
9 pole female D connector
I 1000 m
500 V DC, 2 kV with rated frequency for 1 min.
I
MFR 7SJ551
Technical data
Fibre optic serial interface
e Floating interface for data communication with a isolated according IEC 874-2
control centre
IEC 870-5 with VDEWRVEI recommendation or
e Protocol standards
protocol DIN 19244
2400 Baud
Transmission speed
4800 Baud
9600 Baud
19200 Baud
38400 Baud
d=4
Hamming distance
integrated F-SMA connector for direct optical fibre
Connection
connection e.g. glass fibre 62.5/125 ym
820 nm
0
Optical wave length
ma%.8 dB
o Permissible line attenuation
2 km
8
Transmission distance
factory setting 'light off' (configurable with 2 jumpers)
Signal setting
Temperature sensors
o Floating interface isolated from the main relay
and the serial interfaces
o Number of temperature sensors
Type
9
Temperature range
Connection terminals
Distance
Cable resistance
Accuracy
2 or 8
Pt100 or
Nil 00 or
Nil20
0 to 200°C
3 for each sensor
r 150 m
r 25 S2 pro wire
<
3 "C
I
MFR 7SJ551
1
# .2
Technical data
Electrical tests
Standards for general product testing
- Test standards
EN 5501 1
EN 68-2
IEC 255-5
IEC 255-22-1
IEC 255-6
IEC 801-2
IEC 801-3
IEC 801 -4
IEC 801-5
VDE 0435 part 303
DIN 40040
DIN 40048-8
Insulation tests
@High
voltage test (routine test)
injecting 50 Hz, 2 kV AC. for 1 minute between the
housing and one pair of shortened circuit terminals
(auxiliary power, current inputs, voltage input, external
control inputs and output contacts); all the other pairs
of circuit terminals are connected to the housing; this
successively for &I pairs of circuit terminals
- Measurement of insulation resistance
test voltage 500 V DC
- Impulse voltage test (type test)
injecting 3 positive and 3 negative 5 kV impulse
voltages both common mode and differential mode
(1.2150 ps between tested circuit and earth)
test voltage 500 V DC
-
Repeated measurement of isolation resistance
-
Conclusions
no flash-over or break-down between tested circuit
and earth or between tested circuit and any other
terminal; isolation resistance in all cases exceeded
100 Ms2
turbance immunity tests for the auxiliary supply voltage
- Proper operation range of input voltages
24
110
110
-
-
60 V DC
25OVDC
230VAC
19.2
88
88
-
Spike test (recommended by KEMA)
-
Rise time
Half amplitude width
R,
Differential mode voltage on auxiliary supply
voltage terminal
150 ns
50 ps
5Q
1 kV
72 V DC
300 V DC
276 V AC
MFR 7SJ551
I
Technical data
Disturbance immunity of the current and voltage frequency
-
Maintenance of accuracy
e for the 50 Hz model
for the 60 Hz model
Harmonic immunity
Immunity level to high frequency harmonic current
waveforms
- 10% 3th harmonic
- 10% 5th harmonic
influence on operating current c 1%
influence on operating current < 1%
High frequency disturbance test
- Standard
-
Test frequency
- Ri
- Repetition rate
-
Test duration
IEC 256-6/255-22-1
1 MHz
200 n
400 shotsls
2s
- Common mode voltage
- Differential mode voltage
Electrostatic discharge test
- Standard
- Level
-
Discharge voltage
IEC 801 -2
3
4 kV
Radiated electromagnetic fields test
- Standard
-
Level
- Test frequency
- Magnetic field strength
- Directions
IEC 801-3
3
0.1 5 - 300 Mhz
10 V/m
front, top and side
0
Electrical fast transient test
lmmunity to noise generated from high energy
transient generator
Standard
- Level
Rise time
- Half amplitude width
Ri
- Repetition rate
Burst duration
- Burst period
- Test duration
- Common mode voltage
between circuit and case
between auxiliary supply and case
-
IEC 801-4
3
5 ns
50 ns
50 R
5 kHz
15 ms
300 ms
10 s
MFR 7SJ551
Technical data
io frequency interference test
-
Standard
-
Radiation
- Line interference on all terminals
Surge test
- Standard
3.1.3
Mechanical stress test
Amplitude
- Acceleration
- Repetition rate
3.1.4
IEC 801-5
IEC 68-2-6 and DIN 40048-8
1 0 - 5 5 HZ
15 mm
2G
20 sweeps in 3 directions
Climatic stress tests
Permissible ambient temperature
-
During service
- During storage
- During transport
- Storage and transport
-10 "C to +55 "C
-25 "C to +70 "C
-25 "C to +55 "C
standard works packing
Humidity class
DIN 40040, Class F
IEC 68-2-30
Cyclic damp heat test
- Standards
-
Cycle number
- Temperature range
- Relative humidity
DIN 40040, Class F
IEC 68-2-30
6
25 "C to 55 "C
95%
Storage test (recommended by KEMA)
- Duration
16 hours at
16 hours at
-25 "C and
1.70 "C
We recommend that all units are installed such that they are not subjected to direct sunlight, nor to large
temperature fluctuations which may give rise to condensation.
~
I
Technical data
MFR 7SJ551
3.1.5
MFR 7SJ551 is designed for use in industrial
environment, for installation in standard relay
rooms and compartments so that with proper
installation electro-magnetic compatibility (EMC)
is ensured. The following should also be heeded:
-
All contactors and relays which operate in the
same cubicle or on the same relay panel as the
MFR 785551 should, as a rule, be fitted with
suitable spike quenching elements.
-
All external connection leads in substations
from 100 kV upwards should be screened with a
screen capable of carrying power currents and
should be earthed at both sides. No special
measures are normally necessary for
- Devices:
M F R 7SJ551 protective devices in housings or
in factory fitted subracks are always tested as
complete units and are interchangeable as
complete units without restrictions.
-
0
Service conditions
substations of lower voltages.
-
It is not permissible to withdraw or insert
individual modules under voltage. In the
withdrawn condition, some components are
electrostatically endangered; during handling
the standards for electrostatically endangered
components must be observed. The modules
are not endangered when plugged in.
WARNING! The relay is not designed for use in
residential, commercial or light-industrial
environment as defined in EN 50081.
When it is necessary to exchange a device or
module, the complete parameter assignment
should be repeated. Respective notes are
contained in Chapters 5 and 6.
Modules:
MFR 7SJ551 plug-in modules are
interchangeable.
3.1.7
Design
Housing
7XP20; refer to section 2.1
Dimension
refer to section 2.2
Weight
protection unit
- interface unit
approximately 4
approximately 0.5
-
Degree of protection according to DIN 40050
- Housing
-
Terminals
IPS1
IP21
kg
kg
0
MFR 7SJ551
l3l.i2
,
Technical data
Component data
Setting ranges Isteps
Full load current
- Setting range
- Steps
e
0
*
0.05
1
10
IIflc/ln
li~c/ln
<
5 IflCn <
5I c n 5
1
10
28
0.05
to
28
to
1
to
10
0.001
0.01
0.1
No load current (motors)
- Setting range
Ino ioad/ln
)S
Thermal overload protection
3.3.1
Rotor thermal overload protection
0.05
Setting ranges 1 steps
Permissible start-up current
- Setting range
- Steps
* 0.05
5 lstan/ln <
*
1
5I a n <
10
5I a n S
Istartfln
1
10
28
Permissible start-up time
- Setting range
- Steps
*
1
I
tstan
-
tstart
<
10 s
'ermissible number of starts
- from warm motor condition
-
from cold motor condition
,,,n
%old
Unbalance factor
kin"
Cooling down factor rotor
Cstop,rotor
1
(steps 0.001)
~
MFR 7SJ551
Technical data
@
Trip time calculation
2
2
fh,rotor (t) = loeating + [Itn,rotor(t = 0)-
!Latins
I. exP(+)
rot or
krotor
Trotor
1flc
lheating
!normal
Iinverse
Ith,rotor
eth,rotor
tirip
I
Accuracy trip time
overload factor rotor
thermal time constant rotor
full load current
equivalent heating current
normal component of the phase currents
inverse component of the phase currents '
thermal load current rotor
thermal reserve rotor
trip time
actual symmetric three phase step current
preload current rotor
the higher value of 1 s and 2% of zrot0,
"
MFR 7SJ551
I
Technical data
e.2 Stator thermal overload protection
,
I
Setting ranges / steps
Overload factor stator
b a t
Thermal time constant stator 1
Thermal time constant stator 2
- Steps for 71,stat and 22,stat
T ~ , , ~ ~ ~
a
*
1
10
100
,I
,,t
t
Itsta,
c
<
<
TI,^,,^
10 slminlh
I00 slminlh
999 slmin
Weighing factor
Pweight
Cooling down factor stator
Cstop.stator
&tr;inS
level
Setting range
*
0
o
0
1
10
5, , ,e
1 ow,
18w,,
owam
<
<
<
1 O/o
loO/o
95%
1
to
1.5
to 999 min
to 999 min
switchable between seconds, minutes
and hours
0.01
slminfh
0.1
slminlh
1
slmin
1s
I s
0
to
95
0.001
0.01
0.1
O/O
O/o
O/o
70
Trip time calculation
Ith,stator
thermal load current stator
largest True RMS phase motor current
lTNe
RMS
thermal reserve stator
IR C
full load current
ftnp
trip time
Accuracy trip time
the higher value of 1 s and
2% of [pweight Tl.stat f (1 - ~welght)'
'
72,statI
I
l
"
r
MFR 7SJ551
3.3.3
Technical data" '
Thermal overload protection of non-rotating objects
I
1
Setting ranges / steps
1
Overload factor
k
Thermal time constant 1
Thermal time constant 2
- Steps for 7, and 72
71
72
1
I
I
I
B
1
10
100
It,,,,
5,,t
5,,t
c
<
5
I0 slminlh
100 slminlh
999 slmin
Weighing factor
Pweight
Adjusting factor
Cad]
Warning level
- Setting range
- Steps
1 €Iwam
e
0
,5, , I€
0
1
5,wI€
e
10
1
to
1.5
1 s to 999 min
1 s to 999 min
switchable between seconds, minutes
and hours
0.01
s/rnin/h
0.1
s/min/h
1
slmin
0
to
1
0.01
to
10
0 ~ ~ 7
<
1%
<
5
loO/o
95%
Trip time calculation
t =t,,,
for
€4, =O
Ith
,,,I
RMS
0th
IRC
hip
Accuracy trip time
thermal load current
largest True RMS phase current
thermal reserve
full load current
trip time
the higher value of 1 s and 2% of [pweight
, 71+ (1
weight) ' 2211
-
MFR 7SJ551
Technical data
Ambient temperature biasing (optional)
Setting ranges 1 steps
Maximum ambient temperature , ,T
Nominal ambient temperature
Tmi,
- Steps for, ,T and Tmin
e
0
ST
<
1 "c
0
1
I T
<
10°C
0
10
I T
< I00 "C
0
100
ST
I 200 "C
0
0
0.001
0.01
0.1
1
to
to
200
200
"C
"C
"c
"C
"C
"C
Trip time calculation
@,
bient
-
ambient
'
'
ni,
. k2 . lf,c
Tmax m
.-.i
I
eth = 0
t = t,p
for
NOTE:
This trip time calculation applies to rotor
thermal overload protection, stator thermal
overload protection and thermal overload
protection for non-rotating objects.
Ith,amblent thermal load current adjusted with
ambient temperature
Ith
thermal load current
thermal load adjustment with ambient
Cambient
temperature
Tarnbient
measured ambient temperature
k
overload factor
I~IC
full load current
8th
thermal reserve
tt ri p
trip time
MFR 7SJ551
Technical data
Start inhibit
3.5
1
Setting ranges / steps
Stator start inhibit level
Setting range
-
estator
Steps
1 8stat,r
1 esta0,
1 es,,o,
0
1
10
e
e
Start inhibit release time
- Setting range
- Steps
<
<
I
1%
10%
100%
tinh
0 s to 166 min
switchable between seconds, minutes
and hours
siminlh
0.001
0.01
s/min/h
0.1
slmin
1
s/m i n
Calculation rotor start inhibit level
krotor =
=rotor
=
d
ncold
- nwarrn
"bold
-"cold
. f start
start
krotor
%old
nwarm
Trotor
tstm
I~IC
QrOtor=
a,:'
c o t or
.
.~
I C
istafi
Qrotor
overload factor rotor
permissible number of starts from cold
motor condition
permissible number of starts from warm
motor condition
thermal time constant rotor
permissible start-up time
full load current
permissible start-up current
rotor start inhibit level
MFR 7SJ551
Technical data
Locked rotor protection
Setting ranges / steps
Permissible locked rotor time
- Setting range
-
tl,
Steps
0
0
a
0
1
10
100
Itl,
I
t,,
Itl,
<tl,
<
<
<
I s
10s
100s
I 200 s
Trip time calculation
ttnp
Istart
I
s 5
Pick-up value
Delay time
3.7
trip time
permissible start-up current
largest phase motor current
% of setting value
maximum from 10 ms and 2% of tl,
Zero speed protection
Setting ranges / steps
Zero speed detection time
- Setting range
- Steps
a
0
1
10
100
I
,,,,t
I
,,,,t
I
,,t
I
,,t
~E,O
<
<
<
1 s/min/h
10 s/min/h
100 slmin
I 166 slmin
0 s to 166 min
switchable between seconds, minutes
and hours
0.001
s/min/h
0.01
s/min/h
0.1
s/min
1
s/min
Tolerances
Delay time
maximum from 10 ms and 2% of,,,,t
MFR 7SJ551
3.8
Technical data
Unbaiance protection
Setting ranges / steps
Unbalance pick-up
Izph
0.03
to
1
(steps 0.001 j
Unbalance time multiplier
Setting range
- Steps
I
tzp
<
Is
a
0
Itzp
<
10s
1
5tZp
I 25s
10
-
Bypass time (only for rotating objects)
Setting range
fbypass
- Steps
0
stzp
<
1S
ItPP
<
10s
0
1
Itzp
< 100s
o
10
I
tap
I 200 s
100
-
Trip time calcuiation
trip
linv
Reset time
trip time
inverse component of the phase currents
approximately 40 ms
Tolerances
Pick-up value
Delay time
% of setting value
maximum from 10 ms and 2% of t,",
I5
Drop off / pick up ratio
Referring to unbalance pick-up value I*,
0.95 zt 0.01
MFR 7SJ551
-
Steps
0
0.025
e
1
Technical data
<
<
5I
5 Iqdln
Time multiplier
- Setting range
- Steps
0
0
It,
e
1
S
1
1.4
~ O P
<
<
I s
10s
normally inverse
very inverse
extremely inverse,
long time earth fault
residual dependent time
custom curve
Characteristics
5% of setting value
Measuring tolerance
Time tolerance
maximum from 10 ms and 2% of time setting value
Drop-off ratio
0.95 h 0.01
Directional determination
Measurement
with Ieand Uo
Measuring principle
active power.(cos $ measurement) or
reactive power (sin 4 measurement)
Directional trip condition
forward or
backward
Rotation angle
- Setting range
- Steps
o
$e
0
S
<
I
1
I
' <
10
10
$
5
45
(negative range similar)
CT angle correction
1,s 100 mA
- 100 mA < 1,s 200 mA
,I > 200 mA
- Steps
56
<
0"
56
<
1"
61
62
53
1"
5"
"
r
Technical data
MFR 7SJ551
Q
Undercurrent protection
Setting ranges / steps
Undercurrent pick-up
Setting range
Steps
0
0.05
I
I
I
e
1
0
10
I
n
-
ldln
<
<
I
Undercurrent delay time
Setting range
Steps
-
&ass
1
10
28
t I<
0 s to 166 rnin
switchable between seconds, minutes
and hours
0.001
s/mi n/h
0.01
s/min/h
0.1
slmin
1
s/min
time (only for rotating objects)
tbypass
- Setting range
- Steps
a
0
1
10
I
t,,
I
t,,
<
<
It,,
<
1s
10s
100s
0
to
0.001
0.01
0.1
100
s
S
S
S
Tolerances
Pick-up value
Delay time
5
% of setting value
maximum from 10 ms and 2% of tl<
I:
Drop off / pick up ratio
Referring to undercurrent pick-up value I<
1.05 i 0.01
Technical data
MFR 7SJ551
3.1 0
Overtemperature protection (optional)
Setting ranges / steps
Type setting temperature sensor
Alarm level
- Setting range
- Steps
8
0
I T
I
IT
10
IT
a
100
ST
Trip level
- Setting range
- Steps
0
ST
a
1
ST
0
10
I T
100
ST
<
<
<
<
<
<
<
I
Pt100 or
Nil 00 or
Nil 20
"c
1
IOOC
100 OC
200 "C
1 "C
10°C
100 "C
200 "C
Tolerance
Pick-up value
5 3
"C
MFR 7SJ551
Technical data
@ )II
Low set overcurrent protection
3.1 1.I
Definite time overcurrent protection
Setting ranges Isteps
Phase overcurrent pick-up
- Setting range
- Steps
e
a
0.05
1
10
5I
I
I
n
n
n
<
<
I
1
10
28
Regular earth overcurrent pick-up
- Setting range
- Steps
le>/ln
Sensitive earth overcurrent pick-up
- Setting range
-
Steps
0.003
1
le>/ln
<
I
Illn
I
I
n
<
1
1.4
Overcurrent delay time
- Setting range
.t I>
t I,>
- Steps
a
0
1
10
100
It
<
st
I t
<
<
$1
I
1 slminlh
10 slminlh
100s/min
166slmin
0s
to 166 min
0s
to 166 min
switchable between seconds, minutes
and hours
0.001
s/min/h
0.01
s/min/h
0.1
slmin
1
slmin
approximately 30 ms
i
.teset time
approximately 40 ms
Tolerances
Pick-up value
Delay time
I5
% of I> or I,>
maximum from 10 ms and 2% of tl> or tl,>
Drop off / pick up ratio
Referring to overcurrent pick-up value I>
0.95 k 0.01
Technical data
MFR 7SJ551
3.11.2
?
inverse time overcurrent protection
Setting ranges / steps
Phase overcurrent pick-up
Setting range
- Steps
5 ,In
<
0.05
1
Ilp/ln
<
e
10
I /dln I
-
ldln
1
10
28
Regular earth overcurrent pick-up
- Setting range
- Steps
Q
o
0.05
1
10
2I e n
5 Ie>ln <
5I l n 5
Iedln
1
10
28
Sensitive earth overcurrent pick-up
- Setting range
1epJln
- Steps
0.025
5 Iep>/In <
1
•
1
I e n<
1.4
Overcurrent time multiplier
Setting range
- Steps
It,
<
0
st,
<
a
1
-
tP
1
10
Trip time calculation
i
Normallv inverse
Very inverse
Extrernelv inverse
trip time
phase or earth current
pick-up current (phase or earth)
time multiplier (phase or earth)
MFR 7SJ551
Technical data
qditionally for earth current:
Lona time earth fault
Residual de~endenttime
trip time
earth current
earth current pick-up
earth overcurrent time multiplier
residual dependent time pick-up
Reset time
approximately 40 ms
hck-up value
Delay time
I
5
% of setting value
maximum from 10 ms and 2% of ttnP
Drop off I pick up ratio
Referring to phase overcurrent pick-up value I, or
earth overcurrent pick-up value ,I
'in
C88700-GI176-U810-3
Technical data
MFR 7 ~ ~ 5 5 1
3.1 1.3
Custom curve overcurrent protection
@
Setting ranges / steps
Number of points
2-15
(11 ... 11s)
Phase overcurrent pick-up
- Setting range
-
Steps
* 0.05
a
1
0
10
Il/h
5I n
5/In
I
I
<
<
1
10
I 28
Regular earth overcurrent pick-up
- Setting range
-
Steps
* 0.05
Iel>/ln
5 lel>/ln <
1
Sensitive earth overcurrent pick-up
- Setting range
1e1>/1n
- Steps
0.05
5>/In <
1
1
5 Ie>/ln <
10
*
10
I
lel>/ln 5
28
Custom curve time points
- Setting range
- Steps
0
1
*
10
100
I
I
I
I
tll
t
t
t
t
<
<
<
5
... t\i5
1 s/min/h
10 s/rnin/h
100 s/min
166slmin
Reset time
0s
t o 166 min
switchable between seconds, minutes
and hours
s/min/h
0.001
s/min/h
0.01
0.1
s/min
1
sfmin
approximately 40 ms
Tolerances
Pick-up value
Delay time
5 5
% of setting value
maximum from 10 ms and 2% of ttri,
Drop off / pick up ratio
Referring to phase overcurrent pick-up value ll or
earth overcurrent pick-up value Ie1
0.95 zk 0.01
Technical data
MFR 7SJ551
High set overcurrent protection
012
Setting ranges Isteps
Phase overcurrent pick-up
- Setting range
- Steps
e
0
o
0.05
1
10
I>>/[,,
11>>/In
5 l>>/in
<
<
5 I>>/!,
1
1
10
28
0.05
to
28
0.001
0.01
0.1
Regular earth overcurrent pick-up
Setting range
1,>>/In
Steps
e
0.05
5 Ie>>/In <
I
0
1
11,>>/1,
<
10
o
10
5 I,>>/l,
5
28
-
0.05
0.001
0.01
0.1
earth overcurrent pick-up
- Setting range
- Steps
o
0.025
1
I,>>/l,
5 I,>>/!,
1 1,>>/1,
<
<
1
1.4
Overcurrent delay time
- Setting range
t I>>
t I,>>
- Steps
Pick-up time
to 166 rnin
0s
to 166 min
0s
switchable between seconds, minutes
and hours
slrninlh
0.001
0.01
slminlh
0.1
slmin
1
slmin
approximately 30 ms
approximately 40 ms
Pick-up value
Delay time
I5
%ofI>>or\,>>
maximum from 10 ms and 2% of tl>> or tl,>>
Drop off! pick up ratio
Referring to high set overcurrent pick-up value I>>
0.95 3.0.01
MFR 7SJ551
Technical data
Setting ranges / steps
Curve switch mode
continuous or
pulse or
motor status related (only for rotating objects)
Motor status (only for rotating objects)
startfstop or
running
Curve switch activation time
- Setting range
- Steps
a
a
e
0
1
10
100
Itcs
I
tcs
Itcs
I
tcs
tcs
lslminlh
10 slminlh
lOOs/rnin
I 166 slrnin
c
<
<
0s
to 166 min
switchable between seconds, minutes
and hours
0.001
slrninlh
0.01
slminlh
0.1
slmin
1
slmin
MFR 7SJ551
Technical data
Directional earth fault protection (optional)
6 4
Displacement voltage detection
Displacement voltage
Setting range
- Steps
* 0.05
< Ust,/Un <
1
s ustfi/un <
-
USt,/Un
I
1.2
Pick-up delay
- Setting range
-
tustn
Steps
*
0
1
10
100
5U
t,
5U
t,
5U
t,
5t
<
<
<
1 s/rnin/h
10 s/min/h
100 slrnin
I 166 s/rnin
0s
to 166 min
switchable between seconds, minutes
and hours
0.001
slminlh
0.01
siminlh
slmin
0.1
1
s/min
p-off ratio
5% of set value
Measurement tolerance
maximum from 10 rns and 2% of tU,
Time tolerance
Sensitive earth current detection
High set earth current pick-up
- Setting range
- Steps
0.025
1
I,+>/!"
< !,>>/In
<
<1+>/ln
<
1
1.4
Delay time
- Setting range
- Steps
@:
'
0
1
10
100
5 t I+>
It!+>
<tIg>
5t1+>
<
<
<
5
1 slminlh
10slminlh
100s/min
166slmin
Low set earth current pick-up (definite time)
l+/ln
- Steps
0.025
2Illn <
1
1
5 lm>/ln <
1.4
- Setting range
0s
to 166 min
switchable between seconds, minutes
and hours
slminlh
0.001
0.01
slminlh
0.1
slmin
1
s/min
0.0025
to
1.4
0.001
0.01
Delay time
- Setting range
-
' +t I
Steps
*
0
1
10
100
I
5t I
<ti+
l t I+
<
<
<
5
1 s/min/h
10 s/min/h
lOOs/min
166 slrnin
set earth current pick-up (definite time)
0I wSetting
range
lqp/ln
0s
to 166 rnin
switchable between seconds, minutes
and hours
0.001
slminlh
slminih
0.01
0.1
s/min
slmin
1
0.0025
to
1.4
*
*
Technical data
MFR 7SJ551
- Steps
o
<
<
<I,+,&
I Iodln
0.025
1
1
1.4
Time multiplier
- Setting range
-
~QP
Steps
0
1
0
0
5
5
<
<
I s
10s
normally inverse
very inverse
extremely inverse,
long time earth fault
residual dependent time
custom curve
Characteristics
5% of setting value
Measuring tolerance
Time to\erance
maximum from 10 ms and 2% of time setting value
Drop-off ratio
0.95 k 0.01
Directional determination
Measurement
with ,I and Uo
Measuring principle
active power (cos @ measurement) or
reactive power (sin (I measurement)
Directional trip condition
forward or
backward
Rotation angle
- Setting range
-
Qe
Steps
e
1
5 ,
<
0
10
I
' <
1
I 45
5
10
(negative range similar)
CT angle correction
1,s 100 mA
- 100 mA < I, 5 200 mA
I, > 200 mA
- Steps
0"
1 6
<
lo r 6
<
-
61
52
63
lo
50
8
MFR 7SJ551
@5
Technical data
Undervoltage protection (optional)
Setting ranges Isteps
Undervoltage pick-up
- Setting range
- Steps
* 0.05
5 Uc/U, <
e
1
I
UdU,
<
U</U,
0.05
to
1.2
0.001
0.01
1
1.2
Undervoltage delay time
- Setting range
- Steps
e
0
1
10
100
rtU<
r tU<
5tU<
I tU<
tUc
<
<
<
I
1 s/min/h
10 s/min/h
100s/min
166 s/min
0 s to 166 min
switchable between seconds, minutes
and hours
s/m inlh
0.001
0.01
s/m in/h
0.1
s/mi n
1
s/min
approximately 30 ms
Reset time
approximately 40 ms
Tolerances
Pick-up value
Delay time
I 5
% of setting value
maximum from 10 ms and 2% of tU<
Drop off 1 pick up ratio
Referring to undervoltage pick-up value U<
1.05 t- 0.01
MFR 7SJ551
Technical data
Qvervoltage protection (optional)
3.1 6
Setting ranges / steps
Overvoltage pick-up
- Setting range
U>/Un
U>>/U,
- Steps
0
e
0.05
I U/Un c
1
s U/Un <
(U = U> or U>>)
1
1.2
Overvoltage delay time
Setting range
-
- Steps
0s
to 166 min
0s
to 166 min
switchable between seconds, minutes
and hours
s/min/h
s/min/h
slmin
s/min
Pick-up time
approximately 30 ms
Reset time
approximately 40 ms
Tolerances
Pick-up value
Delay time
Oh of U> or U>>
maximum from 10 ms and 2% of tU> or tU>>
I5
Drop off 1 pick up ratio
Referring to overvoltage pick-up values U> or U>>
0.95
+ 0.01
MFR 7SJ551
Technical data
Breaker failure protection
;517
Setting ranges Isteps
Pick-up value of current
Setting range
- Steps
0
0
1
e
1
5 lbdIn
10
rl,JIn
-
stage
jbdh
<
<
o
0
1
10
st
st
I t
t Ibf
<
<
<
5
to
28
0.001
0.01
0.1
1
10
I 28
Time stage
- Setting range
- Steps
0
1 slminlh
10 stminlh
100 slmin
166 slmin
0s
to 166 min
switchable between seconds, minutes
and hours
slminlh
0.001
0.01
sfminth
0.1
slmin
1
slmin
Block
3.18
Setting ranges 1 steps
Block mode
continuous or
pulse or
motor status related (only for rotating objects)
Motor status (only for rotating objects)
starVstop or
running
Block activation time
$
g
z;
range
;
O
0
0
1
10
100
5 tBLoCK<
1 sfminth
2 tBLoCK<
10 stminlh
l tBLoCK < 100 slmin
I
tBLoCK I 166 slmin
Blockable functions
0s
to 166 min
switchable between seconds, minutes
and hours
0.001
s/min/h
0.01
sfminth
0.1
slmin
1
slmin
low set overcurrent
high set overcurrent
undercurrent
undervoltage
MFR 7SJ551
3.6 9
Technical data
External command
Setting ranges 1 steps
Delay time
- Setting range
-
Steps
0s
to 166 min
switchable between seconds, minutes
and hours
0.001
slminlh
0.01
slminlh
0.1
slmin
1
slmin
Tolerances
Delay time
3.20
maximum from 10 ms and 2% of,,t
I
Ancillary functions
Operational value measurements
Operational current values
- range
Operational voltage values (optional)
- range
Directional earth current value (optional)
range
-.
Thermal reserve values
- range
0 t h oth,rotor Or @th,stator
0 to 100% (or even higher in combination with ambient
temperature biasing)
Inverse component of the phase currents
12
- range
Operational temperature values (optional)
range
-
Motor status
Circuit breaker statistical data
Number of stored alarm or trip events
Last interrupted current
Total of tripped currents
stopped or
start or
running
MFR 7SJ.551
Technical data
':ault event data storage
Storage of annunciations of the last three faults
Reset
Automatic reset time (latched output relays)
- Setting range
treset
- Steps
e
0
0
1
10
100
,I
,,,t
<
I
tWset <
ItEset
5
,,,,t
1 s/min/h
I 0 s/min/h
< 100s/min
I 166 s/min
0s
to 166 min
switchable between seconds, minutes
and hours
0.001
s/m in/h
0.01
s/min/h
0.1
slmin
1
s/min
Demand amperemeter
8 minutes average
15 minutes average
maximum 8 minutes average
maximum 15 minutes average
Aunning hours counter
actual running hours (since previous start-up)
total running hours
General data
ordering code
serial number
software version
Data storage for fault recording (optional)
Activation criterion
alarm or
trip
Total recording time
3s
Sampling rate
- 50 Hz
:.. 60 Hz
600 s-'
720 s-'
Clock module
DALLAS type DS 1286
self-discharge time approximately 10 years
"
i
MFR 7SJ551
Method of o~eration
Method of operation
4.1
Operaalon of the complete unit
The multi-function protection relay MFR 7SJ551 is
equipped with a powerful and proven
microcontroller. This provides fully digital
processing of all functions from data acquisition of
measured values to the tripping of the circuit
breaker.
Fig. 4.1 shows the basic structure of the unit.
The measured currents are fed to the relay via the
input transducers for each phase. The inputs are
galvanically isolated against the electronic circuits
as well as against each other. For the earth current
input either the residual current of the phase
current transformers or a separate summation
current transformer can be connected.
0i
The measured voltage is fed to the voltage input
transducer. This can be a phase to phase voltage,
a phase to earth voltage or a zero sequence (open
triangle) voltage.
The measured value inputs ME transform the
currents and voltage from the measurement
transformers and match them to the internal
processing level of the unit. Apart from the galvanic
and low-capacitive isolation provided by the input
transformers, filters are provided for the
suppression of interference. The filters have been
optimized with regard to bandwidth and processing
speed to suit the measured value processing. The
matched analogue values are then passed to the
analogue input section AE.
Figure 4.1
Hardware structure of multi-function protection relay MFR 7SJ551
The analogue input section AE contains input
Apart from control and supervision of the measured
amplifiers, sample and hold elements for each
values, the microprocessor processes the actual
input, analogue-to-digital converters and memory
protective functions. These include in particular:
circuits for the data transfer to the microprocessor.
MFR 7SJ551
-
filtering and formation of the measured
quantities,
-
continuous calculation of the values which are
relevant for fault detection,
I
1
'
'
I
- determination of the faulted phases in case of a
fault,
-
calculation of True RMS values and symmetric
component values for overload detection,
- calculation of the directional earth fault data,
-
scanning of limit values and time sequences,
- decision about trip command activations,
- storage of measured quantities during a fault for
analysis.
Binary inputs and outputs to and from the processor are channelled via the inputfoutput elements.
From these the processor receives information
from other equipment (e.g. blocking signals).
Outputs include, in particular, trip commands to the
circuit breaker, signals for remote signalling of
important events and conditions as well as visual
displays (LED'S)and an alpha-numerical display on
the front.
4.2
Thermal overload protection
4.2.1
Theoretical background
MFR 7SJ551 uses thermal memories to resemble
the remaining thermal capacity of the protected
component. The remaining thermal capacity can be
calculated out of the measured currents.
For overload protection MFR 7SJ551 distinguishes
between rotating devices (motors) and non-rotating
devices (transformers, blow-out coils or cables).
Furthermore, for motors MFR 7SJ551 uses
different thermal models for the rotor (single-body
model) and the stator (two-body model). For nonrotating devices the same two-body model is used.
Both the single-bodv and the two-bodv thermal
sal ~ h ~ i i in
c the
s
Method of operation
An integrated keyboard in connection with a built-in
alpha-numerical LCD display enables
communication with the unit. All operational data
such as setting values, component data, etc., are
entered into the protection relay from this panel
(refer to sections 6.3 to 6.12). Using this panel the
parameters can be recalled and the relevant data
for the evaluation of a fault can be read out after a
fault has occurred (refer to section 6.14). The
dialogue with the relay can be carried out
alternatively via the serial interface (optional) by
means of a personal computer or a central
evaluation unit. During healthy operation,
measured values can be transmitted, e.g. of load
currents. Both interfaces are isolated; isolation and
interference suppression comply with the
requirements according to VDE 0435, part 303 and
IEC 255.
A power supply unit provides the auxiliary supply on
the various voltage levels to the described
functional units. + 24 V is used for the relay
outputs. The analogue input requires 2 15 V
whereas the processor and its immediate
peripherals are supplied with + 5 V. Transient
failures in the supply voltage, up to 500 ms, which
may occur during short-circuits in the supply
system of the plant are bridged by a voltage
storage element (refer to section 3.1 . l ) .
4.2.1 .I
Single-body thermal overload
model
A current flowing through a conductor will cause
electric losses proportional to the square value of
the current (refer to figure 4.2):
Pe = f . i2
with P,
- electric warmth dissipation
generated by the electric current I
f
- proportional factor
i
- electric current
MFR 7SJ551
Method of operation
with , ,T
- maximum temperature for current
I
We assume the current is a step function:
Figure 4.2
Electric losses in a single conducting
body
The electrical losses P, will cause temperature
rising of the body and the body itself will radiate
warmth into the surrounding environment:
Pe
= 'heating
From thermal physics the following relations apply:
dT
Pheating
= m - C .dt
A a ' (T - Tarnbient)
mass
specific warmth capacity
temperature
area
thermal transfer factor
ambient temperature
Foss =
rn
C
T
A
a
Tambieot-
'
When we fill in these relations exp;ession for P, we
get:
@
This is a first order differential equation in T with
the following solution:
with
z
- warming-up time constant,
rn.C
A.a
temperature at t = 0
'c=-
To
-
fort < 0
fort>O
Then, with P, = f . i2 we get:
+ Voss
with Pheating- thermal losses absorbed by the
body
P,I
- thermal losses radiated into the
environment
with
i(t) = lo
i(t)=I
As soon as P,I equals P, the body has reached its
maximum temperature (t -+ =):
and:
with
lo
- preload current
Figure 4.3 shows the step response of the
temperature of the body.
MFR 7SJ551
Method of operation
-
--f ~ n p
t~
T ma----------------
~$,(t~,,,)=k~~~,,
=(I:
,t
TO/
-12).e
+12
= 7 . In
Figure 4.4 illustrates the above equations.
/"
/
tT
/'
TLbI.,
Figure 4.3
- - - - - - - - -- - - - - - - - -
, ,T
t -
~ u r r e n e 3 e @ r e s ~ o nof
s ethe
temperature
The solution of the differential equation changes to:
12).e
--t
7
+-.
A .a
/
l2
/'
~rn/bI.nt
Now a calculation quantity is introduced: the
'thermal current' lth.
T(t) - Tarn,,t
with
It,
f
A.a
= -. fh(t)
Figure 4.4
II
1I
I
I
I
f tnp-2
ttrip-1
t "
Warming up to trip temperature
Figure 4.5 shows the relation between the trip time
and the temperature for different preload currents.
- thermal current
This leads to the basic equation for the 3parameter thermal model:
For electric network components the maximum
allowable current is:
with , , I
k
hC
- maximum allowable current
-
safety factor
- full load current
6,
When the current exceeds k . the temperature
will rise to the maximum allowable tem~erature
Ttnp.At this time point MFR 7SJ551 wili trip the
electric component. In the model this is
represented by:
Figure 4.5
~ h e j w ( , $ r n i tcurve
I~IC
Another way of expressing the trip condition is by
using the remaining thermal capacity Bth:
Ith= k . Ific
Filling in the'basic equation for the thermal model
gives:
with
eth
-
thermal reserve
For T = Ttnpthe thermal reserve is 0%:
I
-
I
Method of operation
MFR 7SJ551
With this we have completed the single-body
model. It is built with the three parameters lRcrk and
The single-body model can be represented by an
electric analogon (refer to figure 4.6):
Figure 4.7
Electric analogon for two-body
model
The following solution for T(t) is achieved:
Figure 4.6
Electric analagon for single-body
model
with
71
- ambient temperature
- warming-up time constant of
mi . Ci
material 1, T, = -
72
-
P
- weighing factor representing the
Tamb
4.2.1.2 Two-body thermal overload model
The single-body model is reasonably accurate for
homogenous bodies. When bodies consist of
different materials, like copper and iron the singlebody can be insufficient. MFR 7SJ551 therefore
provides the possibility to simulate the thermal
behaviour of an electric network component more
accurately with a two-body model. This makes it
possible to utilize the network component to the full
because the overload protection can be set more
critical, avoiding premature tripping.
A1 . a1
warrning-up 'time constant of
2
'
" - C2
material 2, Z* = A2
- a2
mutual warrning-up influence of
the two materials of the body
In analogy with the derivation of the thermal current
of the 3-parameter model we obtain the basic
equation for the 5-parameter thermal model:
From:
Pheat~ng
. --m . C . - dT
dt
we can see that for a body with two different
materials with thermal warming-up capacities C,
and C2 a differential equation for T consisting of
two differential parts is applicable.
The 5-parameter model can be derived in the same
manner as the 3-parameter model and results in
the following electric analogon (refer to figure 4.7):
For T = T,,, the remaining thermal reserve is 0%
Ith= k . Iflc
or:
eth(ttrip) = k2 '
6~ - 1&,(ttrip).10Ooh = 0%
k2 . lFlc
With this y e have completed the two-body model.
It is b u i l W , h e five parameters lfl,, k, z,, z2 and p.
4.2.2
Rotor thermal overload protection
I
I
r
Method of operation
The rotor thermal overload protection is available
when the user chooses the rotating device
parameter set. Although the two thermal overload
functions work at the same time, the rotor thermal
overload protection protects the rotor completely
independent from the stator thermal overload
protection. It uses a separate thermal memory,
represented during operation by the separate
display quantity 'rotor thermal reserve'. The rotor
thermal overload protection primarily acts on higher
currents during start, during which the rotor thermal
reserve decreases. When the motor has passed a
successful start and is running at full load current
the rotor thermal reserve will increase again
according to the changes of the nominal
temperature.
When putting the operating condition from MFR
7SJ551 from 'off line' to 'on line' the thermal
memory is initiated at 0%.
MFR 7SJ551 computes the temperature rise of the
rotor according to the single-body model. The rotor
safety factor and the rotor warming-up time
constant are computed indirectly out of the motor
manufacturer data. Under assumption that the
start-up time is much smaller than the rotor
warming-up time constant the following formulas
can be derived:
In the rotor model the equivalent heating current is
introduced. This current can be calculated
according to the following formula:
with
Iheating - equivalent heating current
- normal component of the three
,,,I
phase currents
kin,
- inverse factor representing the
extra warming up due to
asymmetric currents
linv
- inverse component of the three
phase currents
The calculation of,,,I
and I, depends on how
many current phases are connected. For threephase connection,,,I
and li, are calculated with
the symmetric components method. As direction of
the vectors either 'clockwise' or 'counterclockwise'
can be externally selected by means of a binary
input. When the direction is reversed, the
calculation of the inverse current and the
calculation of the normal current are reversed, too.
For two-phase connection the following formulas
are applicable:
with , , I
lmin
-
the largest of the two phase
currents
the smallest of the two phase
currents
The rotor thermal model basic iterative equation
becomes (motor status 'start' or 'running'):
with
krOtor - rotor safety factor
n,
- permissible number of starts from
cold condition
, , ,n
- permissible number of starts from
warm condition
T,,,,,
- (fictive) rotor warming-up time
constant
,,,,t
- start-up time at nominal voltage
1~ I C
- full load current
,,I
- start-up current at nominal
voltage
with
Ith,rotor - thermal rotor current
MFR 7SJ551 calculates the thermal rotor current
periodically and compares it with k,,
lRc.
When
these quantities are equal, the tripping condition is
fulfilled:
These relations for the rotor safety factor and the
rotor warming-up time constant express the
influence of the slip on the rotor warming-up during
start.
with
eth,rotor -
rotor thermal reserve
MFR 7SJ551
I
For currents higher than,,,k,
reserve will decrease to 0%.
Method of operation
. Incthe rotor thermal
Theoretically, with this rotor thermal model formed
tstart,ncoldand, , ,n
we achieve that we
with
can start and stop the motor exactly nColdtimes
from cold motor condition with a (constant) starting
current,,,I , when we let each start last exactly
t,~, without pausing between the starts. Than the
thermal reserve will be exactly 0%.
From the formula for, , , ,T
it follows that MFR
7SJ551 allows a motor to be started from cold
condition more of-ten,than qcoid.For example, when
the starting time is halved for each start, or when
the starting current is halved, the motor may be
started 2 nColdfrom cold condition! The same
accounts for starts from warm condition.
@
When the motor status is 'stopped' the basic
iterative equation changes to:
4.2.3
0
t
l~h,rot,,(t) = (lth,roto,(t
2
= 0) -
-
with
e C**m''mOr
+ /:eating
rotor cooling down factor
Cooling down the rotor to the original temperature
after switching if off takes csto,,t times longer than
warming it up to the original temperature.
As soon as the thermal reserve reaches 0% the
rotor thermal overload protection will step into the
TRlP condition. The TRlP LED and the output relay
TRlP 8th will be energized.
When the auxiliary voltage drops out during on line
operating condition and is switched on after a
certain amount of time, the contents of the thermal
memory is calculated using the real time clock as if
the motor had stopped during this time, i.e. as if
lheating
was zero.
Stator thermal overload protection
The stator thermal overload protection is available
when the user chooses the rotating device
parameter set. Although the two thermal overload
functions work at the same time, the stator thermal
overload protection protects the stator completely
independent from the rotor thermal overload
protection. It works with a separate thermal
memory, represented during operation by the
separate display quantity 'stator thermal reserve'.
The stator thermal overload protection primarily
acts on relatively low overcurrents when the motor
is running. When the motor passes a successful
start and is running at full load current the stator
thermal reserve will decrease to an equilibrium
level.
with
When putting the operating condition from the MFR
7SJ551 from 'off line' to 'on line' the thermal
memory is initiated at 0%.
MFR 7 ~ ~ 5 calculates
51
the thermal stator current
When
periodically and compares it with kStat lflc.
these quantities are equal, the tripping condition is
fulfilled:
%,stat
(t) = (fh,stat(t = 0) - l2 .
Ith,stat - thermal stator current
- highest true root mean square
I
value of the phase currents
Pweight - weighing factor
T,~,,
- stator warming-up time constant
1
~ 2 , ~ ~ ~stator
t
warming-up time constant
2 .
MFR 7SJ551 computes the temperature rise of the
stator according to the two-body model,
2
Oth,stat (ttrip)
using as measuring input the highest true root
mean square value of the phase currents.
The stator thermal model basic iterative equation
becomes (motor status 'start' or 'running'):
=
. k : t a t ~ ~ ~ ~ c - I t , s t a t ( f t ~0%
~).~~~~
2
Gat
with
eth,stat
, ,k
IR C
-
. lflc
o
=
stator thermal reserve
stator safety factor
full load current
For currents higher than,,k,
. lflcthe stator thermal
reserve will decrease to 0%.
I
Method of operation
MFR 7SJ551
LED'S PRE-ALARM and ALARM and the output
relay PRE-ALARM will annunciate this condition.
This makes it possible to reduce load in an early
stage.
When the motor status is 'stopped' the basic
iterative equation changes to:
t
Cstop.aa'i.stat
with
t
+
(A -
,
)
w e~ght
.
Cstop,statTa.stat
+ 12
c,~~,,,,~~ - stator cooling down factor
Cooling down the stator to the original temperature
after switching if off takes c,~~,,,~,~ times longer than
warming it up to the original temperature.
When the stator thermal reserve decreases under
,w,
the stator thermal overload
the warning level ,O
protection will step into the ALARM condition. The
4.2.4
As soon as the thermal reserve reaches 0% the
stator thermal overload protection will step into the
TRlP condition. The TRlP LED and the output relay
TRlP Oth will be energized.
When the supply voltage drops out during on line
operating condition and is switched on after a
certain amount of time, the contents of the thermal
memory is calculated using the real time clock as if
the motor had stopped during this time, i.e. as if, , I
was zero.
Thermal overload protection of transformers, blow-out coils and cables
When the user chooses the non-rotating device
parameter set one thermal overload protection
function is available. It works with a thermal
memory, represented during operation by the
display quantity 'thermal reserve'. The thermal
overload protection is meant primarily for protection
against relatively low overcurrrents when the
electric network component is loaded to a
maximum. When the network component is
operated at full load current the stator thermal
reserve will decrease to an equilibrium level.
When putting the operating condition of the MFR
7SJ551 from 'off line' to 'on line' the thermal
memory is initiated at 0%
MFR 7SJ551 computes the temperature rise of the
network component according to the fiveparameter model, using as measuring input the
highest true root mean square value of the phase
currents.
MFR 7SJ551 calculates the thermal current
periodically and compares it with k . llc.When
these quantities are equal, the tripping condition is
fulfilled:
2
Oth(t trip)
with
Oth
k
IRC
=
k
2
c
2
t
t
i
,
ooy
k2 .
o
=
-
thermal reserve
safety factor
- full load current
For currents higher than k . IRcthe thermal reserve
will decrease to 0%.
When the binary input 'z adjust' is energized, the
basic iterative equation changes to:
The thermal model basic iterative equation
becomes:
--
t
1
with
Cadj
+ (1 - pweight
. ) .e
- adjustment factor for warming-up
time constants
with
It,
I
- thermal current
-
highest true root mean square
value of the phase currents
Pweig~- weighing factor
71
- warming-up time constant 1
72
- warming-up time constant 2
For a constant input current this means that the
time it takes to warm up is cadi times larger than for
inactive binary input '7 adjust'. This can be used for
example for network components with forced
cooling. When the cooling is switched on larger
warming-up time constants are needed.
When the thermal reserve decreases under the
warning level
,,,,e
the thermal overload protection
MFR 7SJ551
@
M e t h o d of o p e r a t i o n
will step into the ALARM condition. The LED'S
PRE-ALARM and ALARM and the output relay
PRE-ALARM will annunciate this condition. This
makes it possible to reduce load in an early stage.
As soon as the thermal reserve reaches 0% the
thermal overload protection will step into the TRIP
condition. The TRlP LED and the output relay TRlP
€IU, will be energized.
Am Men%temperature biasing (optional)
4.3
4.8): for nominal ambient temperature T,
With the function ambient temperature biasing the
thermal reserve can be adjusted according to the
actual ambient temperature. Therefore a sensor
measuring the ambient temperature is necessary.
The sensor is connected to one of the temperature
sensor inputs of the (optional) interface unit.
@
When the supply voltage drops out during on line
operating condition and is switched on after a
certain amount of time, the contents of the thermal
memory is calculated using the real time clock as if
the network component was unloaded during this
time, i.e. as if I was zero.
the
thermal reserve is 100%. When the ambient
temperature increases to a maximum allowable
level,,T
,
the thermal reserve of the network
component decreases to 0%. When the ambient
temperature decreases below nominal ambient
temperature Tmi, the thermal reserve will be larger
than 100%.
We consider a cold network component, i.e. the
preload is 0%, without load current (refer to figure
Carnbient
0%
(b
1
Tm,
Tunbtenl
+
Figure 4.8
min
Tmax -Tmin
- k2 - I&
Offset in cold condition
For a warm network component under load
condition the temperature rise caused by electrical
heating and the ambient temperature rise are
added.
Ambient temperature biasing causes the thermal
current to increase with an amount proportional to
the ambient temperature rise:
fh,ambient
i
-
MFR 7SJ551 calculates the thermal load current
per~odicallyand compares it with k . IRc.When
these quantities are equal, the tripping condition is
fulfilled:
0
4.4
ambient
with lth,ambie-,t
- thermal load current adjusted
with ambient temperature
Ith
- thermal load current
Camblent - thermal load adjustment to
ambient temperature
Tarnbient- measured ambient temperature
k
- overload factor
lflc
- full load current
\
Tm,,
--
th
with
Oth
tt,,
-k
-
2.2
2
Iflc - Ith.mb1ent , I 00% = 0%
k2 . lflc
- thermal reserve
- trip time
This trip time calculation applies to thermal
overload protection for non-rotating objects as well
as rotor thermal overload protection and stator
thermal overload protection.
(t) = ~ ? h=( ~O) + Carnbient
Start inhibit
After the thermal overload protection has tripped,
the motor has to cool off before it can be put in
operation again. The start inhibit function can be
used to prevent the motor from being started until it
has regained sufficient thermal reserve. For that
purpose MFR 7SJ551 energizes a start inhibit
.
Method of o~eration
I
MFR 7SJ.551
output relay that must be used to prevent the circuit
breaker from being closed. As long as the motor is
to warm to complete a start this signal will make it
impossible to start it. (Only the emergency restart
function makes it possible to override this signal.)
For the rotor thermal overload model a new start of
the motor is blocked until the thermal reserve has
increased to the rotor start inhibit level emlor:
@rotor -
temperature
with ,,,8,
I
,,,k,
Ific
t
, , , ,T
trip
Figure 4.9
st art release
t
Start inhibit principle
-
rotor start inhibit level
permissible start-up current
overload factor rotor
- full load current
- permissible start-up time
- thermal time constant rotor
For the stator thermal overload model a new start
of the motor is blocked until the thermal reserve
has increased to the settable stator start inhibit
level %tatorThe time until the start inhibit output is released
can be extended with the start inhibit release time
tinh.The two thermal models (rotor and stator)
serve both at the same time as input for
determining whether a start can be released. ~ p a h
from that an additional delay time can be set.
When the motor is stopped (automatically or
manually) and at that moment the remaining rotor
or stator thermal capacities are smaller than the
respective rotor or stator inhibit levels a new start of
the motor is blocked.
4.5
Emergency restart
The emergency restart function can only be
activated in combination with the start inhibit
function. The emergency restart function makes it
possible to override the start inhibit blocking signal
by energizing the emergency restart binary input.
By energizing this binary input the thermal rotor
reserve and the thermal stator reserve are set back
to 1OOO/!,thus releasing the start inhibit output.
This means that a new start is released in spite of
the possible danger of reaching a too high
temperature of the motor! The function is only
4.6
meant for use in situations where the motor is less
important than the process it is driving.
The user only has to activate the function
emergency restart, no parameters need to be set.
The emergency restart order will be executed wHen
the emergency restart binary input is energized
while the motor status is 'stopped' and the thermal
reserve is smaller than the start inhibit level.
Together with the start inhibit output the LED 'start
inhibit' will be deactivated.
Locked rotor protection
The locked rotor protection protects the motor from
damage caused by excessively long start-up. This
may occur when, for example, the rotor is locked,
the driving torque is too high, or impermissible
voltage break down occurs.
If the permissible start-up time is longer than the
permissible locked rotor time the locked rotor
protection function is inadequate: then the zero
speed function has to be used (refer to section
4.7).
The tripping time depends on the magnitude of the
largest phase of the starting current. The following
formula is valid:
Method of operation
MFR 7SJ551
7SJ551 energizes the locked rotor (trip) output. If
the motor status becomes 'running' or 'stopped' the
locked rotor function becomes inactive.
with
ttip
,,I
I
qr
-
tripping time
permissible start-up current
motor current (largest phase)
locked rotor time
The locked rotor protection only works during start.
If the motor status stays 'start' during ttip, MFR
4.7
Zero speed protection
The zero speed function protects the motor from
damage caused by a locked rotor, when the
permissible start-up time is longer than the
permissible locked rotor time. In that case the
locked rotor protection cannot be used and a binary
tachometer built in the motor has to provide a zero
speed signal. This signal is connected to the zero
speed binary input.
4.8
The zero speed protection only works during start.
When the motor is starting and the rotor is stalled,
the binary tachometer energizes the zero speed
binary input and the zero speed protection function
jumps into the alarm condition. If the binary input
stays energized during the detection time,,,t the
zero speed (trip) output will be energized.
Motor start-up protection
Three different protection functions work at the
same time to protect the motor against overheating
during start-up:
stator thermal overload protection
e
rotor thermal overload protection
locked rotor protection
By showing an example case the method of
operation of the start-up protection will be
explained.
@
The formula for the locked rotor protection allows
starting for a longer time for smaller starting
currents. This is a practical situation: when the
motor is started with lower motor voltage, the
starting takes longer, but the starting current is
smaller.
From rest condition ('stopped') MFR 7SJ551
recognises a start-up when the motor current is
higher than the top current ,,I (refer to figure 4.10):
status becomes 'running'. When the motor is
overloaded now to current values higher than ltop
the motor status will stay 'running': it can only
become 'start' again when it becomes 'stopped'
first.
if the motor current gets smaller than
motor status becomes 'stopped' again.
O
'no load
-
top current
full load current
The motor status will become 'start'. It stays 'start'
as long as the motor current is larger than .,,I
From start condition MFR 7SJ551 recognises a
normal running state when the motor current
crosses ,I downwards again; then the motor
Itop
'stan
- 1
Figure 4.1 0
with ,,I
lfic
Ilk
the
Motor status
Normal starting behaviour for most motors is that
the motor current jumps to the starting current very
fast. As the rotor slowly begins to turn the motor
current slowly decreases. The more turning speed
the rotor achieves, the faster the motor current
decreases, until it reaches normal load level (refer
to figure 4.1 1).
i
"
I
Method of operation
MFR 7SJ551
normal starting behaviour
.
\
rotor thennal overload curve
. - -:-- - ----.---.,
-stator
K
I rotor
Figure 4.1 1
Normal starting behaviour
Figure 4.13
Rotor thermal overload curve during
start
The stator thermal overload protection primarily
acts on relatively low overcurrrents when the motor
is running. It becomes active for currents higher
Iflc(refer to figure 4.12).
than ,k,
stator thermal -overload curve
stator
rotor
normal
Figure 4.1 4
Figure 4.12
Stator thermal overload curve
during start
The rotor thermal overload protection primarily acts
on higher currents during start. In most cases (for
start from cold condition) the rotor thermal overload
protection will trip earlier than the stator thermal
overload protection (refer to figure 4.1 3).
When the manufacturer data prescribe a maximum
locked rotor time (often denominated t,) the locked
.rotor protection can be activated. The locked rotor
protection is active only during motor status 'start'.
For a start from cold condition the locked rotor
curve will earlier cause a trip in most cases than
the rotor and stator thermal overload curves (refer
to figure 4.1 4).
Locked rotor curve
When the motor passes a successful start and is
running at full load current the rotor and stator
thermal reserves will decrease to an equilibrium
level (refer to figure 4.15). The locked rotor curve is
inactive when the motor status is 'running'. Notice
that the rotor and stator thermal curves are not
'rigid': they 'float' to equilibrium depending on the
magnitude the load current.
When the motor is stopped now the remaining rotor
and stator thermal capacities will slowly increase
again from equilibrium level (refer to figure 4.1 6).
Only after a long time the motor will have cooled off
completely and the rotor and stator thermal
reserves will be back at 100%.
"
f
MFR 7SJ551
Method of operation
' a t
I
!
.
..
.
,
,
kstaor
x 111,
...
.
.
.
krotor
Figure 4.15
x liis
I>
kstaor
x lhc
,
krotor X
lric
I>
lnm
Running at nominal current
Figure 4.17
Start from warm condition
If the rotor would lock at this moment, i.e. motor
current will stay at,,,I
level, the stator thermal
overload function will trip the motor (refer to figure
4.1 8).
- - - - - - - - - _ _ _ _---_
-- - - -..
-....-_._...-_ ./ _
---- - -
Figure 4.1 6
:
rotor
---.
..-2 locked rotor
Stopped motor in warm condition
stator
Q
I
i
If we would start again shortly after stopping the
motor, the rotor and stator thermal reserves will not
have increased noticeably. Figure 4.17 shows the
start from this warm condition. The 'rigid' locked
rotor protection curve is activated again but in this
case it is no longer the first function which trips the
motor.
4.9
Unbalance protection
4.9.1
General
MFR 7SJ551 is equipped with unbalance
protection, protecting all electric network
components against phase unbalance.
Furthermore, the unbalance protection detects
interruptions, short-circuits and swapped phase
connections of the current transformer circuits.
Single-phase and two-phase short-circuits can be
detected even when the fault current is too small to
be detected by the overcurrent protection.
Figure 4.1 8
Blocked rotor in warm condition
For three-phase connection MFR 7SJ551 filters out
the fundamental wave of the phase currents and
separates it into symmetrical components (negative
The
sequence ,il and positive sequence.),,,I
unbalance protection evaluates the magnitude of
linv.
The sequence of connections can be externally
selected either clockwise or counterclockwise, by
means of a binary input. When the sequence
direction is reversed, the calculation of the inverse
current and the calculation of the normal current
are exchanged.
-
6
MFR 7SJ551
!
Method of operation
For two-phase connection the following formula is
applicable:
with
,il
-
inverse component of the phase
currents
,,I
- the largest of the two phase currents
lmi, - the smallest of the two phase
currents
When the negative sequence current exceeds the
unbalance pick-up the unbalance protection jumps
into the alarm condition. Then every sample period
the tripping time is calculated according to an
extremely inverse characteristic:
4.9.2
Unbalance protection of motor*
The unbalance protection especially protects
motors switched by vacuum contactors with
-associatedfuses. When running on single phase
the motor develops small and pulsating torques.
With unchanged torque load the motor will quickly
be thermally overloaded.
Furthermore, thermal overloading of the motor can
arise by asymmetrical system voltage. Even small
unbalanced system voltages may lead to large slip
load currents because of the small negative
sequence reactances.
During start-up (motor status is 'start') unbalance
may occur because of closing time differences of
the circuit breaker phase contacts. Tripping the
motor for this reason is undesirable, therefore for
'rotating objects' MFR 7SJ551 provides the
possibility to set a delay time fbypass. This bypass
1
time is started at the moment the motor status
changes from 'stopped' to 'start'. During the bypass
time the unbalance protection is inactive.
a
with
ti,
- tripping time
IPp - unbalance pick-up
tPD - unbalance time multiplier
When the inverse current stays larger than the
unbalance pick-up during the tripping time, the
unbalance (trip) output is energized. The passed
time is distracted from the calculated actual tripping
time.
When the inverse current becomes smaller than
the pick-up value, the unbalance function jumps
back into the 'no alarm' condition.
When the motor status is still 'start' after the
bypass time has expired, pick-up takes place with
I"' , (with
,,I
the root mean square value of the
3
largest phase current) in stead of 12p. When one
phase drops out during start this is detected
immediately because the inverse current will be
larger than
then. The calculation of the
3
tripping time stays unchanged (withthe original
unbalance pick-up IPp).
After the motor status has changed to 'running' the
function picks up with .12,
1
4.1 8
Undercurrent protection
1
4.1 0.1
General
The undercurrent protection protects network
components against a decrease in current flow.
For motors this can be caused by a loss of or
decrease in motor load. Examples of such
situations are: loss of suction of pumps, loss of
airflow for fans or a broken belt in conveyors.
Because the cooling is limited severely these
situations may result in excessive overheating of
the motor, even when the motor is protected by
(current dependent) thermal overload protection.
For non-rotating objects the most customary
application of undercurrent protection is the
protection of capacitor banks against their being
switched on. Only when the undercurrent protection
picks up (no remaining capacitive current) the
circuit breaker may be closed (figure 4.1 9).
For the undercurrent protection MFR 7SJ551
computes the fundamental wave of the phase
currents.
"
c
MFR 7SJ551
Method of operation
4.1 Q.2
Figure 4.1 9
Protection of capacitor banks
Motor undercurrent protection
Before start-up (motor status is 'start') the current
is zero: this is a pick-up condition for the
undercurrent protection. Tripping the motor for this
reason is undesirable, therefore for 'rotating
objects' the undercurrent protection is inactive
when the motor status is 'stopped'.
During operation the function can be blocked
dynamically via a binary input even during pick up
of the protection. Refer to section 4.1 9 'Block' for
detailed information.
Furthermore, MFR 7SJ551 provides the possibility
to set a delay time tbypass.his bypass time is
started at the moment the motor status changes
from 'start' to 'running'. During the bypass time the
undercurrent protection function is inactive.
Each phase current is compared with the pick-up
e I< which is applicable for all three phases.
ck-up is separately indicated for each phase.
.'ick-up occurs when the measured value is
smaller than the pick-up value. After pick-up the
undercurrent protection jumps into the alarm
condition and the delay timer is started. After the
delay time ti< has elapsed the undercurrent (trip)
output is energized. When the phase currents
become larger than the pick-up value, the
undercurrent protection function jumps back into
the 'no alarm' condition.
If the motor status is 'running' during the bypass
time and after expiration of the bypass time all
phase currents decrease under the undercurrent
pick-up value I<, the undercurrent protection
function jumps into the alarm condition. If the motor
status stays running and all phase currents stay
smaller than the undercurrent pick-up value I<
during tlc, the undercurrent (trip) output is
energized. When the phase currents become
larger than the pick-up value or if the motor status
becomes 'stopped', the undercurrent protection
function jumps back into the 'no alarm' condition.
e
Overtemperature protection (optional)
4.1 1
MFR 7SJ551 provides the possibility to measure
the temperature of network components directly.
This is especially useful for protecting nonparts of network components against
erheating.
For overtemperature protection temperature
sensors are necessary. The sensors is connected
to the temperature sensor inputs of the (optional)
interface unit. Depending on the ordered type the
interface unit has 2 or 8 inputs for temperature
sensors. Temperature sensors are normally
mounted in:
- bearings,
stator windings,
- transformer cores,
coolants,
lubrication oil.
-
For each temperature sensor an alarm pick-.up and
a trip can be set individually. Pick-up values of 999
"C should be set to prevent unwanted pick-ups of
an unused temperature sensor.
When one of the temperatures exceeds the corresponding alarm pick-up value the overtemperature
protection function jumps into the alarm condition.
When one of the temperatures exceeds the corresponding trip pick-up value the overtemperature
protection (trip) output is energized.
When all temperatures become smaller than the
alarm pick-up value, the overtemperature function
jumps back into the 'no alarm' condition.
bow set overcurrent protection
4.1 2
m
Temperature sensor inputs that are not connected
to a temperature sensor should be closed with a
resistor (50 - 100 a)to maintain the display value.
e low set overcurrent protection protects network
lomponents against high impedance short-circuits.
07
It can be used as definite time or inverse time
overcurrent protection. Three standardized inverse
G88700-C3527-07-7600
1
I
"
I
Method of o~eration
MFR 7SJ551
time characteristics are available for inverse time
mode. In addition, a user specified characteristic
(custom curve) can be defined. Two more
characteristics are available for earth faults. The
trip time characteristics and the applied formula are
given in the Technical data, refer to section 3.1 1.
For phase currents and for earth currents separate
characteristics can be set.
For the low set overcurrent protection MFR 7SJ551
computes the fundamental wave of the phase and
earth currents.
During operation the characteristics can be
switched over or blocked dynamically via binary
inputs even during pick-up of the protection. By
switching over to an instantaneous characteristic
(delay time is zero) rapid trip is provided. Refer to
section 4.1 4 'Curve switch' and section 4.1 9 'Block'
for detailed information.
The measured currents are fed to the relay via the
input transducers for each phase. The inputs are
galvanically isolated against the electronic circuits
as well as against each other.
To the earth current input either the residual
current of the phase current transformers or a
separate summation current transformer can be
connected. The earth current input is either a
regular earth current input (for high magnitude
earth currents) or a sensitive earth current input
(for low magnitude earth currents).
4.1 2.1
Definite time overcurrent
protection
Each phase current is compared with the pick-up
value I> which is applicable for all three phases.
Pick-up is separately indicated for each
phase. Pick-up occurs when one of the phase
currents exceeds the pick-up value. After pick-up
the overcurrent protection jumps into the alarm
condition and the delay timer is started. After the
delay time tl> has elapsed the overcurrent (trip)
output is energized. When the phase currents
become smaller than the pick-up value, the low set
overcurrent protection function jumps back into the
'no alarm' condition.
The residual (earth) current is processed
separately and compared with the earth
overcurrent pick-up value I,>. The delay time tie>
can be set individually.
4.1 2.2
Inverse time overcurrent
protection
Each phase current is compared with the pick-up
value I, which is applicable for all three phases.
Pick-up is separately indicated for each phase.
Pick-up occurs when one of the phase currents
exceeds the pick-up value. After pick-up the
overcurrent protection jumps into the alarm
condition and the trip time delay is calculated from
the inverse time characteristic and the magnitude
of the fault current. The passed time is distracted
from the calculated actual delay time. After the
calculated delay time has elapsed the overcurrent
(trip) output is energized. When the phase currents
become smaller than the pick-up value, the low set
overcurrent protection function jumps back into the
'no alarm' condition.
The residual (earth) current is processed
separately and compared with the earth
overcurrent pick-up'value .,I The earth overcurrent
characteristic may differ from the phase
overcurrent characteristic; the associated
parameters can be set individually.
4.1 2.3
Custom curve overcurrent
protection
When the definite or inverse time overcurrent
protection function cannot cover the short-circuit
characteristic of the network component a user
specified characteristic can be defined. Minimum 2
and maximum 15 I-t co-ordinates (I, ... Il5) can be
defined. The MFR 7SJ551 will construct an I-t
curve by using these co-ordinates and assuming
straight lines between the co-ordinates.
Each phase current is compared with the pick-up
value I, which is applicable for all three phases.
Pick-up is separately indicated for each phase.
Pick-up is separately indicated for each phase.
Pick-up occurs when one of the phase currents
exceeds the pick-up value. After pick-up the
overcurrent protection jumps into the alarm
condition. The trip time delay is calculated every
sample period out of the line drawn between the
two I-t co-ordinates that lie closest to the measured
current. The passed time is distracted from the
calculated actual delay time. After the calculated
delay time has elapsed the overcurrent (trip) output
is energized. When the phase currents become
smaller than the pick-up value, the low set
overcurrent protection function jumps back into the
'no alarm' condition.
The residual (earth) current is processed
separately and compared with the earth
Method of operation
MFR 7SJ551
overcurrent pick-up value Iel. The earth overcurrent
characteristic may differ from the phase
4.1 3
overcurrent characteristic; the associated
parameters can be set individually.
High set overcurrent protection
The high set overcurrent protection protects
network components against low impedance shortcircuits.
overcurrent pick-up value I,>>. The delay time tie>>
can be set individually.
For phase currents and for earth currents separate
parameters can be set.
For the high set overcurrent protection MFR
7SJ551 computes the fundamental wave of the
phase and earth currents.
During operation the characteristic can be switched
over or blocked dynamically via binary inputs even
during pick-up of the protection. By switching over
to an instantaneous characteristic (delay time is
zero) rapid trip is provided. Refer to section 4.14
'Curve switch' and section 4.1 9 'Block' for detailed
information.
The measured currents are fed to the relay via the
input transducers for each phase. The inputs are
galvanically isolated against the electronic circuits
as well as against each other.
For the earth current input either the residual
current of the phase current transformers or a
separate summation current transformer can be
connected. The earth current input is either a
regular earth current input (for high magnitude
earth currents) or a sensitive earth current input
(for low magnitude earth currents).
@
4.1 3.1
The high set overcurrent protection can be blocked
via a binary input of the relay. A setting parameter
determines whether the binary input operates in the
normally open mode (i.e. energize input to block) or
in the normally closed mode (i.e. energize input to
release). Thus the high set overcurrent protection
can be used as a fast bus bar protection in star
connected networks or in open ring networks (ring
open at one spot), using the reverse interlock
principle. This is used in high voltage systems.
Reverse interlocking means that the high set
overcurrent protection can trip within time tl>>,
which is independent of the low set overcurrent
protection time tl> if it is not blocked by pick-up of
one of the next downstream feeder protections
(figure 4.*). Therefore, the protection which is
closest to the fault will always trip within a short
time, as it cannot be blocked by a relay behind the
fault location. The low set overcurrent time stages
tl> or I, operate as delayed back-up stages.
Each phase current is compared with the pick-up
value I>> which is applicable for all three phases.
Pick-up is separately.indicated for each phase.
Pick-up occurs when one of the phase currents
exceeds the pick-up value. After pick-up the high
set overcurrent protection jumps into the alarm
condition and the delay timer is started. After the
delay time tl>> has elapsed the high set
overcurrent (trip) output is energized. When the
phase currents become smaller than the pick-up
value, the high set overcurrent protection function
jumps back into the 'no alarm' condition.
The residual (earth) current is processed
separately and compared with the high set earth
4.14
Curve switch
Fast bus bar protection using
the reverse interlock scheme
I
Figure 4.20
-
tfault detectic
-
& fault detectic
Reverse interlock principle
MFR 7SJ551
With the curve switch function MFR 7SJ551
provides the possibility to adapt the overcurrent
characteristics during motor or transformer inrush
by setting the pick-up values higher. Furthermore,
by switching over from a time delayed to an
instantaneous characteristic (delay time is zero)
rapid trip is provided.
For low set overcurrent protection and for high set
overcurrent protection two sets of I-t co-ordinates
can be defined. With the curve switch function the
MFR 7SJ551 can be parametrized to use set 1 or
set 2, controlled by motor status or a binary input.
Three curve switch modes can be selected:
continuous mode: MFR 7SJ551 switches
from curve 1 to curve 2 during the activation
of the curve switch binary input,
4.65
Method of operation
-
-
pulse mode: MFR 7SJ551 switches from
curve 1 to curve 2 during the curve switch
time tcs, after the activation of the curve
switch binary input,
status mode (only for motors): depending on
motor status MFR 7SJ551 automatically
switches from curve 1 to curve 2. For the
status mode two different options can be
selected:
status = stopped/start: when the motor
status is 'stopped' or 'start' curve 2 is
active, when the motor status is 'running'
curve 1 is active,
e
status = running: when the motor status is
'running' curve 2 is active, when the
motor status is 'stopped' or 'start' curve 1
is active.
Directional earth fault protection (optional)
The directional earth fault protection can be used in
isolated or arc compensated networks to
discriminate the earth fault direction. Trip
commands for earth fault overcurrent will only be
activated if the direction of the earth fault current
corresponds with the selected direction.
The residual voltage Uo is one of the two conditions
for release of the directional determination. Uo is
the voltage measured at the terminals of an open
delta voltage transformer.
In order to detect earth currents, the two-stage low
set overcurrent protection (refer to section 4.12) or
high set overcurrent protection (refer to section
4.1 3) must be set. When the earth fault direction
function is enabled, the denomination of the pickup values changes to I d , I+, and I+> (in stead of
12, ,,I and I,>>).
The earth fault direction protection does not
process the magnitude of the earth current but the
component which is at right angle to a settable
directional symmetry axis. A precondition for
determination of the fault direction is that one of the
current magnitude stages has picked up and that
the residual voltage exceeds the displacement
voltage.
When the measured residual voltage Uo exceeds
the pick-up value Us, during the pick-up delay tUSt,
the directional determination is released.
The directional earth fault protection picks up as
soon as
- the directional determination is released
- the earth fault direction current
exceeds the
overcurrent threshold value I p
- the direction of the earth fault is in the selected
direction.
The trip delay time is calculated according to the
selected time characteristic.
After pick-up the directional earth fault protection
jumps into the alarm condition and the delay timer
is started. After the delay time t l p has elapsed the
directional earth fault (trip) output is energized.
When the zero sequence voltage Uodecreases
below ,U
, or when the earth fault direction current
I, decreases below lp or when the direction
changes, the directional earth fault protection
function jumps back into the 'no alarm' condition.
The same is valid for the inverse time
characteristics and for the high set overcurrent
stage IG>.
4.1 5.1
Cos $ determination
For resistance-earthed networks or networks
earthed with a Petersen coil cos 41 determination is
used.
When an earth fault occurs the Petersen coil
superimposes a corresponding inductive current on
the capacitive earth fault current, so that this
capacitive current at the fault spot is compensated.
However, dependent upon the point of
measurement in the network the resultant
"
€
MFR 7SJ551
sured current can be inductive or capacitive
eht ! ! !
reactive current is therefore not suitable for
the determination of direction. In this case only the
ohmic residual current which results from the
losses of the Petersen coil can be used for
directional determination. This earth fault ohmic
current is only a few percent of the capacitive earth
fault current.
Method of operation
with
P
- active power in the earth current
path
Uo - residual voltage
- earth current
I,
I$ - component of the earth current
which is at a right angle with the
directional symmetry axis
It must be noted that, dependent upon the location
of the protective relay, a considerable reactive
component may be superimposed, which, in the
most unfavourable cases, can attain a value of fifty
times the value of the active component. Despite
the extremely high accuracy the calculation
algorithm is then inadequate if the current
transformers do not exactly convert the primary
values.
I
e
se of cos 9determination the active power P is
decisive factor. The direction is forwards if P is
i
.~ositive:
The earth fault component is calculated according
to the following formula:
f
I' capacif ive earth
fault load
inductive earth fault
load
backward
Figure
-
Q
4.dp0' Sin
4.15.2
I I$
f o ~ y
e ermination
Sin $ determination
For isolated networks sin I$determination is used.
The earth fault current flows as capacitive current
from the healthy lines via the measuring spot to the
fault spot. This capacitive current determines the
direction.
In case of sin 9 determination the reactive power Q
is the decisive factor. The direction is forwards if Q
is positive. The earth fault component is calculated
according to the following formula:
MFR 7SJ551
with Q
path
Method of operation
-
reactive power in the earth current
I
'9
forward
(Q>O)
/7'~capaciy fault load
earth
inductive earth fault
load
I
I
Figure 4.22
4.15.3
Dependent of the value of the expected earth
current I, the angular error of the core balance
current transformer can be corrected in three
ranges:
0
backward
(Q<O1
Cos (g determination
4.15.5
Earth fault location
By means of the directional indication the earthfaulted line in radial networks is located. Since all
circuits on a bus bar carry a capacitive partial
current, the measuring spot on the faulted line in a
isolated network covers almost the entire
prospective earth fault current of the network; in
compensated networks the wattmetric residual
current from the Petersen coil flows through the
measuring spot. For the faulted line or cable a
definite 'forwards' decision will result, whilst in the
remaining circuit a 'reverse' indication will be given
unless the earth current is so small that no
measurement can be performed. In any case the
faulted cable can be clearly determined.
0,
Sensitivity improvement by
shif ing the symmetry axis
The symmetry axis can be shifted by up to t 4 5 "
(settable rotation angle $, refer to figure 4.23).
Thus it is possible to achieve maximum sensitivity.
Correcting the angular error of
4.1 5.4
the core balance transformer
The sensitive measurement input circuit of the
relay for directional earth fault protection permits an
extremely high sensitivity for the directional
determination of the wattmetric residual current. In
order to utilize this sensitivity it is recommended
that a core balance current transformer is used for
the earth fault detection. As even these
transformers have an angle error, MFR 7SJ551
allows the setting of factors which, dependent on
the reactive current, will correct the error angle.
4.1 6
backward
IPc01
Figure 4.23
Undervoltage protection (optional)
@w
Shifting the symmetry axis
,
MFR 7SJ551
1
Method of operation
The undervoltage protection protects network
components against too low voltage.
of the protection. Refer to section 4.1 9 'Block' for
detailed information.
For the undervoltage protection MFR 7SJ551
contains one voltage input. This means only one
phase voltage can be measured. The user
determines whether the measured voltage Ui, is a
phase to phase voltage by parametrizing it as U,, a
phase to earth voltage by parametrizing it as UP,,
and a residual voltage by parametrizing it as Uo.
The measured voltage is compared with the pickup value U<. Pick-up occurs when the measured
value is smaller than the pick-up value. After pickup the undervoltage protection jumps into the alarm
condition and the delay timer is started. After the
delay time tU< has elapsed the undervoltage (trip)
output is energized. When the measured voltage
becomes larger than the pick-up value, the
undervoltage protection function jumps back into
the 'no alarm' condition.
During operation the function can be blocked
dynamically via a binary input even during pick-up
MFR 7SJ551
4.1 7
Overvoltage protection (optional)
The overvoltage protection protects network
components against too high voltage.
For the overvoltage protection MFR 7SJ551
contains one voltage input. This means only one
phase voltage can be measured. The user
determines if the measured voltage Ui, is a phase
to phase voltage by parametrizing it to U,, a phase
to earth voltage by parametrizing it to Uphand a
residual voltage by parametrizing it to Uo.
8
For the low set stage the measured voltage is
compared with the pick-up value U>. Pick-up
occurs when the measured value exceeds the pickup value. After pick-up the overvoltage protection
jumps into the alarm condition and the delay timer
is started. After the delay time tU> has elapsed the
4.18
For the high set stage the measured voltage is
compared with the pick-up value U>>. Pick-up
occurs when the measured value exceeds the pickup value. After pick-up the overvoitage protection
jumps into the alarm condition and the delay timer
is started. After the delay time tU>> has elapsed
the overvoltage (trip) output is energized. When the
measured voltage becomes smaller than the pickup value, the overvoltage protection function jumps
back into the 'no alarm' condition.
Instead of by the algorithm described above, start
of the breaker failure protection can be initiated by
an external protection relay. The trip signal of the
external protection device is coupled into MFR
7SJ551 via a binary input. The timer tbf is started. If
the measured current is higher than a settable level
Ibfafter tbf has elapsed, the breaker failure
protection energizes the breaker failure protection
relay output to cause the circuit breaker to clear the
fault. The breaker failure protection function can
only be deactivated if the measured current
becomes smaller than Ibf.
Block
With the block function MFR 7SJ551 provides the
possibility to block the overcurrent, undercurrent
and undervoltage characteristics during motor or
transformer inrush.
Three block modes can be selected:
continuous mode: MFR 7SJ551 activates the
block function during the activation of the
block binary input,
pulse mode: MFR 7SJ551 activates the block
after the
function during the block time tBLOC~,
activation of the block binary input,
-
4.20
overvoltage (trip) output is energized. When the
measured voltage becomes smaller than the pickup value, the overvoltage protection function jumps
back into the 'no alarm' condition.
Breaker failure protection
In order to supervise correct functioning of the
circuit breaker, MFR 7SJ.551 checks whether the
current becomes zero after a trip signal has been
given. When the trip command is generated a timer
tbf is started. The timer continues to run for as long
as the trip command is maintained. If the circuit
breaker does not respond to the trip command the
timer runs to its set limit. If the then measured
current is higher than a settable level Ibfthe breaker
failure protection energizes a second relay output
to trip the upstream circuit breaker to clear the
fault.
4.19
Method of o~eration
External command
-
status mode (only for motors): depending on
motor status MFR 7SJ551 automatically
activates the block function. For the status
mode two different options can be selected:
status = stoppedlstart: when the motor
status is 'stopped' or 'start' the block
function is active, when the motor status
is 'running' the block function is inactive,
status = running: when the motor status is
'running' the block function is active,
when the motor status is 'stopped1or
'start' the block function is inactive.
MFR 7SJ551
With the external command function an immediate
trip can be generated by activating a binary input,
for example to make an emergency stop.
4.21
After the circuit breaker position binary input is
activated the circuit breaker position LED indicator
will be energized.
Ancillary functions
The ancillary functions of MFR 7SJ551 include:
- processing of annunciations
- storage of short-circuit data for fault recording
- operational measurements
- test routines
- monitoring functions
4.22.1
After activating the external command binary input
a delay timer ten is started. If the binary input
the external
continues to be activated during tm
command output will be energized after Lxr has
elapsed.
Circuit breaker position
With the circuit breaker position function the
position of the circuit breaker can be indicated.
4.22
Method of operation
Processing of annunciations
After a fault in the protected component information
concerning the response of the protective device
and knowledge of the measured values are
important for an exact analysis of the history of the
fault. For this purpose the MFR 7SJ551 provides
annunciation processing which is effective in three
directions.
Indicators and binary outputs (signal relays)
Important events and conditions are indicated by
optical indicators (LED) on the front pIate. MFR
7SJ551 also contains signal relays for remote
signalling. All of the signals and indications can be
marshalled freely. In section 6.1 1 the marshailing
facilities are described in detail.
The output relays can be arranged to latch or to be
self-resetting. The general alarm LED, the prealarm LED and the general trip LED are
memorized. The four freely programmable LEDs
(optional) can be arranged to be memorized or to
be self-resetting.
The memories of the LEDs can be reset
locally, by pushing the 'reset indicators' button
(RI) on the front plate;
- remotely, by energizing the remote reset binary
input;
- via the operating interface.
-
The latching of the output relays can be reset:
-
locally, by pushing the 'reset indicators' button
(RI) on the front plate
- remotely, by energizing the remote reset binary
input
- via the operating interface
- automatically, after elapsing of a settable reset
ti me
Sometimes indicators and relays indicate
conditions, which naturally should not be stored. In
these cases the indicators cannot be reset until the
originating criterion has disappeared.
A green LED indicates readiness for operation ('on
line'). This LED is illuminated when the
microcontroller is working correctly, the unit is not
faulty and performing its protection task. The LED
extinguishes when the self-checking function of the
microcontroller detects a fault or when the auxiliary
voltaae is absent. The 'on line' LED will flash when
theriis a non-fatal defect in the real time clock
module, for example an empty battery.
With the auxiliary voltage present but with an
existing internal fault or with the unit in off line
(programming) mode a red LED ('monitor')
illuminates and the outputs will be blocked.
Information on the display panel, t o a personal
computer or t o a substation automation system
Events and conditions can be either read off in the
display on the front plate of the unit (using the
keyboard) or transferred to a personal computer or
a substation automation system connected to the
serial interface (optional). MFR 7SJ551 outputs
selectabte operating information like operational
measured values or motor status and also contains
several event buffers for operating messages or
fault annunciations. The fault inception is indicated
with the absolute time of the operating system. The
sequence of events is tagged with the relative time
referred to the pick-up time.
I
*,
f
MFR 7SJ551
Method of operation
For using a personal computer or communication
with a substation automation system the MFR
7SJ551 interface module has to be connected. This
module can either be ordered together with the
relay unit by choosing the appropriate ordering
number (refer to section 2.3.1) or be ordered
separately later on (refer to section 2.3.2). Normally
no special arrangements are necessary to operate
the relay after connecting the interface module.
When the data are transmitted to a personal
computer or to a substation automation system,
read out can proceed automatically, optionally after
pick-up or after trip. The following then applies:
- the interface unit of the relay signals the
availabijity of fault record data
- the data remain available for recall until they are
overwritten by new data
- a transmission in progress can be aborted by
the central unit of the control system.
For setting and evaluating MFR 7SJ551 the
personal computer has to be loaded with the
software program 'Communication Utility MFR
7SJ551'. This allows the user to comfortably set
the relay and analyze events and faults by means
of systematic screen use and graphical aids.
Additionally, the data can be documented on a
printer or stored on a floppy disk.
Alternatively, the fault recording can be triggered by
applying an external binary input signal. The
recording time is fixed a t ~ 3seconds, directly after
the triggering.
4.22.3
Operational value
measurements
MFR 7SJ551 stores the data of the last three
events; if a fourth event occurs the first event is
overwritten in the event memory.
For local recall or transmission of data, the first
harmonic values of the phase currents, the earth
current and the voltage (optional) are available.
When the thermal overload protection is active, the
calculated thermal resewe and the largest true root
mean square current value can be read out. For
motors the rotor thermal reserve, the stator thermal
reserve and the motor status are displayed. With
an interface unit containing RTD inputs the
measured temperatures can be read out.
One of the binary input signals can be transmitted
via the serial interface ('serial event') to the
substation automation system.
4.22.2
Fault event data storage and
transmission (optional)
The instantaneous values of the measured values
are sampled at 1 ms intervals (for 50 Hz) and
stored in a circulating shift register. In case of a
fault, the data are stored over a selectable time
period, with a maximum of 3 seconds. Only one
fault record is stored at a time. If the interface unit
is connected to the relay unit during the fault, the
fault data are available for fault analysis. For each
new event the old event is overwritten by the new
fault data.
The following items can be recalled:
'
phase and earth currents in
primary amperes
voltage in primary volts
thermal reserve in %
largest true root mean square
current value in primary
amperes
inverse current in primary
amperes
temperatures measured by
the 2 or 8 RTD elements in
degrees Celsius
three possible modes: stop
start - running
-
The data can be transferred to a connected
personal computer via a serial interface (optic fiber
or RS485, selectable) on the interface unit and
evaluated by the 'Communication Utility MFR
7SJ551' program. The currents are referred to their
maximum values, normalizes to their rated values
and prepared for graphic visualization.
-
The fault record data can also be transmitted to a
substation automation system via one of the serial
interfaces. Evaluation of the data is made in the
substation automation system, using appropriate
software programs.
The demand ampere meter allows the user to
check correct dimensioning of network components
and makes special external arrangements
unnecessary.
motor status
4.22.4
Demand ampere meter
The demand ampere meter displays
1
-
the dynamic 8 minutes average of the
measured currents
- the maximum 8 minutes average of the
measured currents since the last reset
- the dynamic 15 minutes average of the
measured currents
- the maximum 15 minutes average of the
measured currents since the last reset.
1
Method of operation
MFR 7SJ551
4.22.5
Test facilities
MFR 7SJ551 allows simple checking of the tripping
circuit and the circuit breaker as well as
interrogation of the state of all binary inputs and
outputs. Initiation of the test can be given from the
front keyboard or via one of the serial interfaces
with a personal computer.
4.22.6
Hardware monitoring
MFR 7SJ551 incorporates comprehensive
hardware monitoring functions.
The hardware is monitored for faults and
inadmissible functions, from the measured value
inputs to the output relays. In detail this is
accomplished by monitoring:
- Auxiliary and reference voltages
Failure or switch-off of the auxiliary voltage
automatically puts the system out of operation;
this status is indicated by the breaking contact
of the 'monitor' relay and the illumination of the
'monitor' LED. Transient dips in supply voltage
of less than 40 milliseconds (for rated auxiliary
voltage higher than 110 V DC) will not disturb
the functioning of the relay.
Output channels
The output relays are controlled by two
command and one additional release channel.
As long as no pick-up condition exists, the
microcontroller makes a cyclic check of these
output channels for availability, by exciting each
channel one after the other and checking for
change in the output signal level. Change of the
feed-back signal to low level indicates a fault in
one of the control channels or in the relay coil.
This condition automatically leads to alarm and
blocking of the output.
- Memory modules
After the relay has been connected to the
auxiliary supply voltage, the RAM memory is
checked by writing a data bit pattern and
reading it.
The further memory modules are periodically
checked for fault by
0
formation of the modulus for the EPROM
program memory and comparison of it with a
reference program modulus stored there
formation of the modulus of the values
stored in the EEPROM parameter memory
and comparison of it with a newly determined
modulus after each parameter change.
1
MFR7SJ551
Installation instructions
installation insbuctions
A Warning
The successful and safe operation of this device is dependent on proper handling and installation by
qualified personnel under observance of all warnings and hints contained in this manual.
In particular the general erection and safety regulations (e.g. IEC, DIN, VDE and the national standards)
regarding the correct use must be observed. Non-observance can result in death, personal injury or
substantial property damage.
@
Unpacking and repacking
When dispatched from the factory, the equipment is
packed in accordance with the guidelines laid down
in DIN 40046 part 7, which specifies the impact
resistance of packaging.
This packing shall be removed with care, without
force and without the use of inappropriate tools. The
equipment should be visually checked to ensure that
there are no external traces of damage.
It must also be checked whether the order number
(on the top of the housing) of the relay corresponds
with the ordered relay type. A possibly ordered
optional interface unit will be packed separately, but
shipped in the same box as the relay unit.
The packing can be re-used for further transport
en applied in the same way. If alternative packing
sed, this must provide the same degree of
grotection against mechanical shock, as laid down in
DIN 40046 part 7 (class 23).
F.
5.2
Preparations
The operating conditions must comply with VDE
010015.73 and VDE 0105 part 117.83, or
corresponding national standards for electrical power
installations.
/L,
Caution!
The modules of digital relays contain CMOS
circuits. These shall not be withdrawn or
inserted under live conditions! The modules
must be handled in such a way that any
possibility of damage due to static electrical
discharges is excluded. During any
necessary handling of individual modules
the recommendations relating to the
handling of electrostatically endangered
components (EEC) must be observed.
In installed conditions, the modules are in no danger.
Installation instructions
MFR 7SJ551
5.2.1
Mounting and connections
Panel flush mounting or cubicle installation
- Lift up both the labelling strips on the lid of the
unit and remove the cover to gain access to the
four holes for the fixing screws.
-
lnsert the unit into the panel cut-out and secure it
with the fixing screws. For dimensions refer to
figure 2.3.
- Connect the earthing screw on the rear of the
relay unit to the protective earth of the panel or
the cubicle.
-
Make a solid low-ohmic and low-inductive
operational earth connection between the
earthing surface at the rear of the unit using at
least one standard screw M4 and the earthing
continuity system of the panel or cubicle;
recommended grounding strap DIN 72333-form
A, e.g. order number 15284 of Messrs Druseidt,
Remscheid, Germany.
- Make connections via the screwed or snap-in
terminals of the sockets of the housing. Observe
labelling of the individual connector modules to
ensure correct location: observe the maximum
permissible conductor cross-sections. The use of
the screwed terminals is recommended; snap-in
connection requires special tools.
Auxiliary voltage
The auxiliary supply voltage is
24V60VDCor
- 110V- 250VDCand110V-230VAC
The supply voltage selection is fixed according to the
order designation. The power consumption is about
22 W maximum.
Rated currents
MFR 7SJ551 has three (PI, T and e) or four (R, S, T
and e) current input modules with a rated current ,I
of 1 A or 5 A. On the backside the relay is fitted with
connection terminals for 1 A and connection
terminals for 5 A. The current inputs must be
connected to the secondary windings of a current
transformer with a minimum accuracy of 10P10. The
current transformer ratio can be set as a parameter
value. For sensitive ,I measuring a different current
circuit is available only suited for a rated current I,=
1 A. The selection for a normal or a sensitive earth
current input is fixed according to the order
designation.
*
Control DC voltage of binary inputs
The minimal version of MFR 7SJ551 is fitted with
two binary control inputs. MFR 7SJ551 with
extended I10 has 5 binary control inputs. The control
voltage range is 24 V - 250 V DC or 110 V - 230 V
AC. The inputs can be configured either normally
open or normally closed.
Panel surface mounting using a 7SJ55 surface
mounting bracket
-
Assemble the surface mounting bracket to the
panel. For the dimensions refer to figure 2.4.
5.2.3
Checking the (optional)
interface unit transmission
link
...
- Insert the unit into the surface mounting bracket
cut-out and secure it with the fixing screws.
- Mount the interface unit to the relay unit
according to figure 2.1
5.2.2
Checking the rated data
- Connect the earthing screw of the interiace unit
to the protective earth of the panel or the cubicle.
The rated date of MFR 7SJ551 must be checked
against the plant data. This applies in particular to
the auxiliary supply voltage, the rated current of the
current transformers, the input range of the binary
control inputs and the switching capacity of the
output relay contacts.
-
Make connections via the male connector for the
RTD temperature sensors (optional). Observe
labelling of the female connector to ensure
correct location.
-
Make connection with a 9-pole make D connector
for the RS-485 interface for the data
communication with a personal computer.
- Make connection with the fibre optic interface:
unscrew the protective caps at both FSMA
connectors
a.
j
MFR 7SJ551
6.
0
plug on the optical fibre cable terminal
carefully; observe the designation of
transmitter and receiver end; the transmitter
terminal of MFR 7SJ551 (light grey) must be
connected to the receiver terminal and the
receiver terminal of MFR 7SJ551 (dark grey)
must be connected to the transmitter terminal
tighten the cap nuts without force and without
use of tools
observe the permissible bending radius of the
fibre optic cable.
Installation instructions
measures and pay due attention to them.
Non-observance can result in severe
personal injury.
-
Switch off the circuit breakers for the auxiliary
supply voltage.
-
Check the continuity of all the current
transformer circuits and the (optional) voltage
transformer circuit against the plant and
connection diagrams:
- Check if the fibre optic interface is set to the
,
0
desired signal position:
e
the factory setting for the fibre optic interface
is 'light off'
0
if the normal signal position should be
changed in 'light on' open the serial interface
housing and change the position of the plug
jumpers X3 and X4 each from 1 - 2 to 2 - 3
according to figure 5.1. The jumpers are
situated on the main board of the serial
interface near the connection terminals of the
optical fibre cable; close the housing.
0
Are the current and voltage transformers
earthed correctly?
Are the polarities of the current and voltage
transformer connections consistent?
Is the phase relationship of the current
transformers correct?
Is the polarity of the voltage transformer
correct?
- If test switches have been fitted in the
secondary circuits, check their function. Check if
the current transformer secondary circuits are
automatically short-circuited in the 'test'
position.
- Fit a corresponding ampere meter in the
auxiliary power circuit, range approx. 1 A.
- Close the auxiliary voltage supply circuit
r
breaker, check the polarity (for the DC version)
and the magnitude of the voltage at the
terminals of the unit.
ure 5.1
Jumper setting optical interface
- The measured current consumption should
correspond to a power consumption of 14 -18
W. Transient movement of the ampere meter
pointer only indicates the charging current of the
storage capacitors.
5.2.4 Connections
General and connection diagrams are shown in
Appendix A and B. The marshalling possibilities of
the binary inputs and outputs are described in
section 6.1 1.
5.2.5
Coming from the manufacturer the display will
show:
Checking the connections
/!\Warning
i
-
Some of the following test steps are carried
out in presence of hazardous voltages. They
shall be performed by qualified personnel
only which is thoroughly familiar with all
safety regulations and precautionary
and the red 'monitor' LED will light up a few
seconds after applying the auxiliary
voltage.
-
Open the circuit breaker for the auxiliary power
SUPP~Y.
-
Remove the current ampere meter and
reconnect the auxiliary voltage supply leads.
~
MFR 7SJ551
-
Thoroughly check the tripping command output
circuits to the circuit breaker.
- Thoroughly check the control wiring to and from
other devices including the signal circuits.
Installation instructions
- For setting mode and for operative ('on line')
@,'
mode the auxiliary supply voltage circuit breaks.
should be closed.
I
MFR 7SJ551
Operating instructions
9
Operating instructions
6.1
Safety precautions
//
-
Warning
All safety precautions which apply for work in
electrial installations are to be observed
during tests and commissioning.
Dialogue with the relay
6.2
8
ing, operation and interrogation of MFR 7SJ551
,an be carried out via the keyboard, display panel
and LED'Slocated on the front plate. All the
necessary operating parameters can be entered and
all the information can be read out from the
frontplate. Additionally, operation is possible via the
serial interface by means of a personal computer.
6.2.1
Display panel
The display panel is a 32 character display (two lines
of 16 characters) and is used to visualize all
communication to and from MFR 7SJ551. The language is English or German. In the display clearly
understandable text is displayed, which makes
comfortable parametrization and evaluation ~ossible.
*
display can also be used for ampere metering.
6.2.2
Keyboard
Arrow keys
With the arrow keys I&', '+' and '+'the user can
move to the different menu parts, following the menu
map. These keys can be depressed with closed front
cover.
Some parameters only have distinct values. For
setting these parameters a right arrow (3)
in the
right most digit will appear. Selection of such a value
key.
occurs with the
A continuous depressing of the 4 and keys will
cause a fast presentation of the menu, in
accordance with the existing setting.
+
@!set indicators key
With the key for resetting indicators 'RI' memorized
indicators and output relays can be reset. This key
can be depressed with closed front cover.
+
Decimal keys ' 0 9'
Function:
The decimal keys allow the user to
alter the currently selected parameter
value or setpoint value.
Effect:
A figure in accordance with the decimal
key will be inserted at the right most
digit of the second row of the display
while already present digits (or a decimal point) are shifted one position to
the left. Depressing these keys while
MFR 7SJ551 is 'on line' has no effect.
Decimal point key '.'
Function:
The decimal point key allows the use of
a decimal point in the currently
selected parameter value or setpoint
value.
Effect:
A decimal point will be inserted at the
right most digit at the second row of the
display, while already present digits are
shifted one position to the left. The
decimal point key can only be used
once in a parameter value or a set
point value. The first digit may be a
decimal point so 0.015 can be entered
as .015. Depressing this key while
MFR 7SJ551 is 'on line' has no effect.
Backspace key 'BS'
Function 1: The backspace key allows the user to
delete the right most digit or decimal
point of the currently selected
parameter value or setpoint value.
Effect 1:
Deletes the right most digit or decimal
point of the currently selected
parameter value or setpoint value of
the second row of the display, while
already present digits and decimal
point are shifted one position to the
right.
Function 2:
Effect 2:
With the backspace key the user
confirms the setting if MFR 7SJ551
asks for confirmation with the text
"TYPE BACKSPACE".
MFR 7SJ551 accepts the execution of
special actions such as switching from
'on line' to 'off line' and vice versa.
Depressing any other key will cancel
the confirmation action.
Representation of numerical values
1
O~eratinainstructions
MFR 7SJ551
If any a l a n condition is detected by MFR 7SJ551
the ALARM indicator will light up.
Numerical values can have the following
appearance:
range
>
number of decimals
100
100
example
16.8
742
0
If a time needs more than 4 digits before the decimal
point the unit s (seconds) can be changed to m
(minute) or h (hours) with the key.
+
If negative values are possible the sign of the value
can be changed with the
key.
+
6.2.3
LED indicators
e
Trip (red)
If any trip condition is detected by MFR 7SJ551 the
TRIP indicator will light up.
Monitor (red)
Whenever MFR 7SJ551 is not performing its protection functions, the MONITOR indicator will light up. It
indicates that MFR 7SJ551 is in 'off line' mode,
which allows parameters to be changed, or that MFR
7SJ551 has detected an internal fauit and is out of
operation for that reason.
LED 1 to LED 4 (yellow, optional)
These 4 LED indicators can be used to indicate specific alarm or trip conditions, among other things. It is
advisable to indicate the chosen meaning of each
LED indicator on its left side using the special sticke
delivered together with the relay.
8
I
On line (green)
Whenever MFR 7SJ551 is performing its protection
functions, the ON LINE indicator will light up. If a
non-fatal internal fault is detected this indicator will
blink.
6.2.4 Operation with a personal
computer
Pre-alarm (yellow)
If the remaining thermal capacity has decreased
under the adjustable alarm value, the PRE-ALARM
indicator will light up, indicating that the protected
device will get into thermal overload in the near
future if no special measures are taken or no load
decrease occurs.
A personal computer (industrial standard) allows all
the appropriate setting, initiation of test routines
and read-out of data, with the comfort of screenbased visualisation and a menu-guided procedure.
The PC Program 'Communication Utility MFR
7SJ551' is available for setting and processing of
all digital protection data.
Alarm (yellow)
All data can be read in from, or copied onto
diskette or documented on a connected printer.
1
/
'.,
MFR7SJ551
(L.5
Operating instructions
Front view of the relay
Two line display (LCD)
with 16 characters
,
Indication operative
mode (green)
8
/
Overload indication
(yellow)
/
Alarm indication
(yellow)
Trip indication (red)
Reset microcontroller
hole
'
indication OFF LINE
mode / indication unit
faulty (red)
LED 1 to 4 (yellow) can
be marshalled
Arrow keys
, I
I
A
Reset indicators key
1
1 9 1 0 1 * 1 4
V
Figure 6.1
Front view with operating keyboard and display panel
Numerical keyboard
MFR 7SJ551
Operating instructions
Parameterizing procedure
6.3.1
Menu structure
The operating interface is built up by a
hierarchically structured menu tree, which can be
passed through by means of the scrolling keys '&',
'/t" and '+'.Thus, each operation object can be
reached.
In figure 6.2 the menu structure is shown.
From the initial display, the key \L is used to switch
to the first operation item SETTINGS, which contains
all setting and configuration blocks of the device (see
figure 6.3). Key is pressed to change to the next
operation level. The display shows the first item
DEVICE DATA, which is described in section 6.6.
Further parameter blocks can be called up with the
scrolling keys J/ or
Figure 6.2
+
+.
Menu structure
+
Pressing the key leads to the third operation level
where the individual functions and values are set;
refer to figure 6.3. They are explained in detail in thf
following sections.
OPERATING
OFF L I N E
n
NON-ROTATING
CHANNELS
J.
Figure 6.3
Setting example
In the following sections each menu item is
explained. There are three forms of display:
-
Menu items without request for operator input
These menu items guide you through the menu.
No input is expected. By using keys \L or /f\ the
next or previous menu item can be selected. By
using the key 3 the next operation level can be
reached.
-
Menu items which require numerical input
These menu items display parameters that have
a numerical value. When the relay is delivered a
value has been preset. In the following sections,
this value is shown. If this value is to be retained,
no other input is necessary. If the value needs to
be altered, you can use the numerical keyboard,
as described in section 6.2.2.
O~eratinainstructions
MFR 7SJ551
&en"
items which require a choice
These menu items display parameters which only
have a limited number of possible values or
applicable text inputs. When the relay is
delivered, a value or text has been preset. In the
following sections, this setting is shown. If this
settina is to be retained. no other i n ~ uist
necessary. If the setting needs to b; altered, you
can use the key
+.
After altering a setting, scrolling down with the key 4
causes the setting to be saved. The altered
parameters are permanently secured in EEPROMs
and protected against power outage.
For each of the menu items, the possible
parameters and text are given in the following
sections.
6.3.2
initial display
When the relay is switched on, shortly some startup messages appear. After that, the initial display
appears.
The SETTINGS block is reached by pressing the
key 4.
6.4
Main menu (OFF LINE)
OPERATING
OFF L I N E
This menu item is used for changing the OFF LlNE
programming mode into the ON LlNE protective
mode and vice versa. Refer to section 6.13 for a
detailed description.
If there are any unallowed settings the relay will ask
for a change of the concerning settings.
OFF L I N E
4
.1-
OFF LINE
ALARMITRI P
OFF L I N E
pE!Tq+
OFF L I N E
UFACT.
;OFF L I N E
In the SETTINGS menu all relay parameters can
be set. Refer to section 6.8 for a detailed
description.
In the COUNTERS menu statistical data about the
circuit breaker can be seen. Refer to section 6.1 4.3
for a detailed description.
In the ALARMfrRiP DATA event recordings of the
last three fault detections and the last three trips
can be seen. Refer to section 6.14.4 for a detailed
description.
In the DEMAND AMMETER menu the demand
ampere meter can be read out. Refer to sections
4.22.4 and 6.14.5 for a detailed description.
MFR 7SJ551
Operating instructions
In the MANUFACTURER DATA various
information is provided, for example about the
ordering code and the serial number of the relay.
6.5
s
Furthermore, in this menu block a reset to the
factory settings can be initiated. Refer to section
6.14.7 for a detailed description.
SETTINGS menu
The SETTINGS menu part is used for setting the
parameters of MFR 7SJ551. SElTlNGS contains 7
sublevels. This description is only fully applicable to
the maximum version of the relay.
OFF L I N E
+
pr=J+
+
D E V I C E DATA
In the DEVICE DATA information about the
protected component is programmed, to match the
protection functions to the component data. Refer
to section 6.6 for a detailed description.
$
I
In the CHANNELS menu the operator determines
which current and voltage inputs are used and
matches them to primary values. Refer to section
6.7 for a detailed description.
1-
PROTECTIONS
+
In the PROTECTIONS menu all protection
functions are set. Refer to section 6.8 for a detailed
description.
In the TRANSIENT DATA the operator determines
how the fault recording is started. Refer to section
6.9 for a detailed description.
In the REAL TIME CLOCK menu date and time can
be altered. Furthermore, time synchronisation can
be activated here. Refer to section 6.1 0 for a
detailed descgption.
In the MARSHALLING menu all inputs, outputs ar
freely programmable LED indicators can be
designated to all protective input and output
signals. Refer to section 6.1 1 for a detailed
description.
1
In the SERIAL COMMUNlCATlON menu the serial
communication facility can be matched to the
connected personal computer or station
management system. Refer to section 6.12 for a
detailed description.
6.6
Settings foe DEVICE DATA
In the DEVICE DATA information about the
protected component is programmed, to match the
protection functions to the component data.
a.
MFR 7SJ551
Operating instructions
Uiil":;i-i
D E V i C E DATA
+ 3 L FREOUENCY
L t v =
fn
r n
1-
[Hz1
~ - f l c~ 1 n 1
'//
Nominal frequency of the protected device.
50 Hzor 60 Hz
Full load current of the protected device.
Setting range:
0.05 to 28 . I,
The rated current provided by the manufacturer of
the protected component should be filled in here.
The full load current value is used by MFR 7SJ551
for the thermal overload protection and the start
inhibit function.
The full load current is converted in accordance with
the current transformers and expressed in the
secondary current value of the current input
transformers (1 A or 5 A).
Example I
A device with a nominal full load current of 88 A
and a current transformer with a ratio of 100 : 1
needs an If!, value of 1/100 x 88 = 0.88 . I, (this
current can be connected to the 1 A current input).
Example 2
A device with a nominal full load current of 88 A
and a current transformer with a ratio of 100 : 5 will
cause a current of 5/100 x 88 = 4.4 A. This current
should be connected to the 5 A current input and
the setting value is again 4.415 = 0.88 . I,.
D E V I C E TYPE:
ROTATING
Type of the protected device.
NON-ROTATING or ROTATING
Choose NON-ROTATING for transformers, blow-out
coils, cables, overhead lines and capacitor banks.
Choose ROTATING for motors.
Depending on the device type two different menu
parts will appear.
MFR 7SJ551
6.6.1
Operating ins.tructions
Non-rotating device
For a non-rotating device only the overload factor
and the type of the temperature sensors have to be
set.
N O N -R O T A T I N G
JI
Overload factor
Setting range:
1 to 1.5
The overload factor determines the maximum
allowable continuous current (k x Inc).
In most cases the overload factor is mentioned in the
data of the manufacturer. If k = 1.05 it means that a
current of 1.05 x IRcwill not cause a thermal
overload.
TEMPERATURE
Temperature sensor type
100
This menu part determines the kind of temperature
sensor used for performing the ambient temperature
biasing and the overtemperature protection.
6.6.2
Rotating device
For motors several motor data have to be set.
Together with the full load current these data are
used to determine if the motor is standing still,
starting or running; furthermore these settings are
used by the rotor and stator thermal overload
functions.
rn
DEVICE TYPE:
No-load current
Setting range:
0.05 to 1 . ,I
The motor will be regarded stopped when all the
phase currents are below the setpoint value Inoload.
In
most cases the no-load current value is provided by
the motor manufacturer. The motor status
'STOPPED' is used by MFR 7SJ551 for several
functions (for example for 'Curve switch' and
'Block').
MFR 7SJ551
Operating instructions
Permissible start-up current
Setting range:
,,I
0.05 to 2 8 . I,
must be set higher than IRc.
MFR 7SJ551 uses,,I for the calculation of z,,,,,. In
most cases the permissible start-up current value is
provided by the motor manufacturer. Often values of
lSt, are given for 80% and 100% rated motor
voltage. For setting the manufacturer value of I,,,, for
100% rated motor voltage is preferable, even if the
actual motor start-up current is different.
Permissible start-up time
t - s t a r t Csl
\I,
Setting range:
1 to 200 s
MFR 7SJ551 uses &
,t for the calculation of .r,,.
In
most cases the permissible start-up time is provided
by the motor manufacturer. Often values of,,,t are
given for 80°h and 100% rated motor voltage. For
setting the manufacturer value of Gta,for 100% rated
motor voltage is preferable, even if the actual motor
start-up time is different.
Overload factor stator
Setting range:
1 to 1.5
The stator overload factor determines the maximum
x IRc).
allowable continuous stator current (kStat
In most cases the stator overload factor is
mentioned in the data of the manufacturer. If k, =
1.10 it means that a current of 1.I 0 x lfl, will not
cause a stator thermal overload.
For most motors a minimum setting level for k,
1.05.
is
Unbalance factor
Setting range:
0 to 10
The unbalance factor represents the extra warming
up of the rotor due to asymmetric currents. Practical
values can be calculated out of:
Permissible number of starts from warm condition.
Setting range:
1 to 15
i
MFR 7SJ551
Operating instructions
In most cases the permissible number of starts from
warm condition is provided by the motor
manufacturer.
Permissible number of starts from cold condition.
Setting range:
1 to 15
In most cases the permissible number of starts from
cold condition is provided by the motor
manufacturer.
TEMPERATURE
Temperature sensor type.
100
This menu part determines the kind of temperature
sensor used for performing the ambient temperatur
biasing and the overtemperature protection.
':
6.7
Settings for CHANNELS
In the CHANNELS menu measuring inputs can be
selected. Here primary and secondary values are
linked together. Three submenus, 'PHASE
CIRCUITS', 'EARTH CIRCUIT' and 'VOLTAGE
CIRCUIT' must be entered.
Operating instructions
MFR 7SJ551
o g i n n i n g of the submenu CHANNELS and of the
submenu PHASE CIRCUITS
Disabling measuring of input phase current lL3
Enabling measuring of input phase current lL3
Disabling measuring of input phase current lLl
Enabling measuring of input phase current lL,
Maximum three and minimum two phases must be
enabled to make processing of measured input
currents possible.
Disabling measuring of input phase current Ii,
Enabling measuring of input phase current Iw
Rated current
IAor5A
I in
:
J
1'
IA1
This is the rated secondary current transformer
current.
Current transformer ratio.
CIRCUITS CT-
Setting range:
1 to 9999
J
Be aware that this is a ratio, not the primary current
transformer current.
Example
For a 500 : 5 current transformer the rated current
must be set to 5 A and the current transformer ratio
must be set to 100.
Full scale phase current
Imax
[In]
The full scale phase current is of influence on the
accuracy of the measured current values. As the
sampling of the current amplitude is discrete, the
available number of sampling steps is distributed
over the programmed full scale. This means the
accuracy is highest for a full scale of 7 A and a
factor 4 lower for 28 A. In practice, this has no
significant effect on the performance of the
protection functions, but is noticeable only for fault
recording momentary values. Set the full scale
phase current higher than the expected maximum
current. (For currents higher than the programmed
full scale phase current MFR 7SJ551 uses the
maximum value instead. As the relay works on the
ground harmonic only, the work value will be lower
than the real value.)
Example
If the programmed full scale phase current is 7 A
(RMS), a phase current of 10 A (RMS) will be cut
off when the sinus momentary value reaches 62 . 7
A.
I
MFR 7SJ551
Operating instructions
Disabling measuring of input earth current I,
Enabling measuring of input earth current I,
Beginning of the submenu EARTH CIRCUIT
Rated earth current
E A R T H CIRCUIT
IAor5A
This is the rated secondary current transformer earth
current.
&
For ordering types MFR 7SJ5513 and MFR 7SJ5514
(sensitive earth current) only 1 A is possible.
Earth current transformer ratio
CT-RATIO
Setting range:
1 to 9999
\L
EARTH C I R C U I T
Full scale earth current
7Aor 14Aor28A
(regular earth
current)
0.35 A or O.7A or 1.4 A(sensitive earth current)
Set the full scale earth current higher than the
expected maximum earth current.
Beginning of the submenu VOLTAGE CIRCUIT
Disabling measuring of input voltage Ui,
Enabling measuring of input voltage Ui,
ENABLED
Voltage circuit type
U select:
/
/
Uoor
Ynselect:
U-tl
tIhsel e c t :
U-f(
J/
U,,or Uph
Here residual voltage, line-to-linevoltage or phase to
earth voltage can be selected. These are merely text
indications, no functional difference is made by the
relay.
MFR 7SJ551
Operating instructions
Rated voltage
100
p q
6
VT- R A T I O
100 V o r 110 V
Voltage transformer ratio
Setting range:
1 to 9999
Operating instructions
MFR 7SJ551
6.8
Settings for
PROTECTIONS
In the PROTECTIONS menu all protection
functions are set. PROTECTIONS contains 16
sublevels. This description is only fully applicable to
the maximum version of the relay.
m,
PROTECTIONS
+
+
THERM.OVERLOk
+
m
LOW S E T O . C .
+
3
p5mq
H I G H S E T O.C.+
3
PROTECTION
EARTHFAULT
1-
.
I
,
L O C K E D ROTOR a
+
pm%==J+
ZERO S P E E D
)PROTECTION1
+ +
UNDERVOLTAGE
OVERVOLTAGE
&
p i h q+
CURVE S W I T C H a
PROTECTION
MFR 7SJ551
Operating instructions
6.8.1
THERMAL OVERLOAD protection
6.8.1.I
Thermal overload protection for rotating objects
For motors MFR 7SJ551 uses different thermal
models for the rotor and the stator.
Most parameters for the rotor thermal overload
protection are set already in DEVICE DATA.
The parameters set in the submenu THERMAL
OVERLOAD (ROTATING OBJECTS) are
combined with the motor manufacturer data as set
in the DEVICE DATA menu to form the rotor and
stator thermal overload models.
Most parameters for the stator thermal overload
protection are programmed in the submenu
THERMAL OVERLOAD described here.
1:;'"""'
THERM.OVEi?LO&
+
OVERLOAD
Beginning of the submenu THERMAL OVERLOAD
I
DISABLED
)I
AMBIENT TEMP. 11
1
DISABLED
1
ENABLED
1'
Enabling the thermal overload protection
Disabling the thermal overload protection
Disabling the AMBIENT TEMPERATURE BIASING
Enabling the AMBIENT TEMPERATURE BIASING.
Refer to section 6.8.2 for a detailed description.
Thermal time constants stator
~ 1 , s t a tCsl
1-
Setting range:
1 s to 999 rain
.L
OVERLOAD
MFR 733551 uses two time constants for the stator
thermai overload protection. Each time constant
determines an exponential curve. These two curves
are added up, weighted by a weighing factor Pweism.
Weighing factor
p-wei g h t
Setting range:
0 to 1
\L
The parameters rlmstat,
T
~and, p w~e i g
are
~~ set
~
according to the stator thermal withstand curve
supplied by the motor manufacturer. Use the
operating and evaluation software program
'Communication Utility MFR 7SJ551' to calculate the
three parameters out of three current-time points.
Operating instructions
MFR 7SJ551
1
Example
1
Figure 6.3
For the three current-time points of figure 6.3 k(,
1.05, preload = 0%) 'Communication Utility MFR
7SJ551' calculates:
TI,S~~ =
861
s
%,stat =
195
s
Pweisht =
0.61
=
With no thermal withstand curve (or three operating
points) available it makes no sense to use all three
t ~ t pwerght
Just set P w e i g ~to 1;
parameters ~ 1 . ~a 2~, ~and
then onlyzl is effective. To set Tl,stat only one
operating point is needed (besides the stator
overload factor k,,,).
Example
Only one operation point is available:
if the current step response I is 1.5 x Inc, the motor
has to be tripped in ttdP= 20 minutes (cold condition).
Then the formula for the tripping time (refer to
section 4.2.3) changes to:
t trip = T~,sta: . I.(,.
1
j
- kstat .~:lc
Filling in all known values leads to T~,,~, =26 minutes.
Cooling-down factor stator
Setting range:
1 to 10
Cooling-down factor rotor
Setting range:
1 to 10
When the motor is stopped it begins to cool down.
Cooling down from an attained
MFR 7SJ551
Operating instructions
temperature generally lasts longer than warming up
to this temperature. How many times longer can be
set with these factors. In most cases the cooling
down factors are provided by the motor
manufacturer.
Warning level stator thermal overload protection
Setting range:
0 '10 to 95 O h
By setting this warning level a pre-alarm will be given
to enable the network operator to disconnect load
from the electric network.
Set the warning level in accordance with the normal
load current. For a continuous load current I smaller
than, ,k x Ifi, the thermal reserve will eventually
attain an equilibrium value:
The warning level must be set lower than this
equilibrium value, to be sure there will be a warning
for overload only.
For I = Iflcthe formula changes to:
Example
The normal load of a motor is full load current. k , =
1.05. The equilibrium value of the thermal reserve
will be 9.3 %. The warning level is set to 5 %.
START
I
INHIBIT
ENABLED
'1
Disabling the start inhibit function
Enabling the start inhibit function
Refer to section 6.8.3 for a detailed description.
0
MFR 7SJ551
6.8.1.2
Operating instructions
Thermal overload protection for non-rotating objects
In the submenu THERMAL OVERLOAD (NONROTATING OBJECTS) parameters are set for
thermal overload protection of transformers, blowout coils, cables and capacitor banks.
THERM.OVERLOA,
+
OVERLOAD
I
DISABLED
?I
f
AMBIENT TEMP.
DISABLED
ml
TrueRMS:
IL;;fiMS:
\L
21
Disabling the AMBIENT TEMPERATURE BIASING
Enabling the AMBIENT TEMPERATURE BIASING
Refer to section 6.8.2 for a detailed description.
Measuring circuit for thermal overload protection
PHASEor EARTH
This menu part determines whether the phase
currents or the earth current are used for the thermal
overload protection of the device.
Choose 'PHASE' if the protected device is a
transformer, cable or capacitor bank. Connect the
current transformer currents to the phase inputs of
the relay.
Choose 'EARTH' if the protected device is a blowout coil. Connect the ring core transformer to the
earth current input of the relay.
Thermal time constants stator
Setting range:
1 s to 999 rnin
MFR 7SJ551 uses two time constants for the
thermal overload protection of non-rotating objects.
Each time constant determines an exponential
curve. These two curves are added up, weighted by
a weighing factor pWeig~.
Weighing factor
p-weight
\L
Setting range:
Oto1
The parameters TI,TZ and P
~,,~
are set according to
the thermal withstand curve supplied by the
manufacturer of the network component. Use the
operating and evaluation software program
'Communication Utility MFR 7SJ551' to calculate the
three parameters out of three current-time
I
Operating instructions
MFR 7SJ551
points. Refer to the preceding paragraph for an
example of how to calculate .rl, 2 2 and &eight with this
program.
With no thermal withstand curve (or three operating
points) available it makes no sense to use all three
paranIeters TI, 7 2 and Pweig~.
Just set Pweight
to 1; then
only T, is effective. To set z,only one operating point
is needed (besides the stator overload factor .),k,
Refer to the preceding paragraph for an example of
how to calculate z, in this situation.
pgq
ENABLED
Enabling the adjustment of the time constants
Disabling the adjustment of the time constants
Adjusting factor
Setting range:
0.01 to 10
When the network component is switched off it
begins to cool down. Cooling down from an attained
temperature can last longer than warming up to this
temperature, for example when the cooling pump of
a cable is switched off. Also, the cooling pump can
break down while the cable is warming up. In this
case the warming-up goes faster.
How many times shorter or longer warming-up or
cooling down takes, can be set with the adjusting
factor. By energizing the binary 7,dj input (via a
control system or by hand) the time constants are
multiplied each with the Cadi factor.
Warning level thermal overload protection for nonrotating objects
Setting range:
Oto95%
By setting this warning level a pre-alarm will be given
to enable the network operator to disconnect load
from the electric network.
Set the warning level in accordance with the normal
load current. For a continuous load current I smaller
than k x lfl, the thermal reserve will eventually attain
an equilibrium value:
*
6
MFR 7SJ551
Operating instructions
The warning level must be set lower than this
equilibrium value, to be sure there will be a warning
for overload only.
For i = IRcthe formula changes to:
Example
The normal load of a network component is full load
current. k = 1.05. The equilibrium value of the
thermal reserve will be 9.3 %. The warning level is
set to 5 %.
)
6.8.2
AMBIENT TEMPERATURE BIASING (optional)
The AMBIENT TEMPERATURE BIASING menu is
a submenu of the THERMAL OVERLOAD menu.
With these parameters MFR 7SJ551 adjusts the
values in the thermal reserve buffers according to
1
the actual ambient temperature. This menu part is
only applicable in relays equipped with an interface
module containing temperature sensor connectors.
Beginning of the submenu AMBIENT
TEMPERATURE BIASING
DISABLED
Enabling the ambient temperature biasing
Disabling the ambient temperature biasing
A M B I E N T TEMP.
\L
Maximum ambient temperature
Setting range:
0 to 200 OC
This menu part determines the maximum allowable
temperature of the used isolation material of the
device (and not the expected maximum environment
temperature!). Set this value to 120 "C if isolation is
in accordance with class B, and to 140 "C for class
F.
Nominal ambient temperature
AMBIENT TEMP.
****
Setting range:
0 to 200 "C
This menu part determines the nominal environment temperature (and not the minimum allowed
environment temperature!). In most cases this
MFR 7SJ551
Operating instructions
value is set to 40 O C (refer to manufacturer data).
, ,T must always be higher than Tmin.
Input sensor number
I "I N P U T
1
6.8.3
SENSOR pl
Choose the number of the input sensor that is
measuring the ambient temperature.
I
ANPUT SENSOR 1)
START IkdHlBlT
The START INHIBIT menu is a submenu of the
THERMAL OVERLOAD menu. With the
parameters set in this menu, MFR 7SJ551 inhibits
starting of the motor until the motor has regained
sufficient thermal reserve.
ml-1
THERM.OVERLOA,
+
OVERLOAD
Beginning of the submenu START INHIBIT
START I N H I B I T
Enabling the start inhibit function
Disabling the start inhibit function
START I N H I B I T
Start inhibit release extension time
\L
Setting range:
0 s to 166 min
This is an additional release time of the start inhibit
output relay after the thermal reserve has reached
the threshold value. With this parameter the total
time the start inhibit output
prevents
the motor from
.
.
starting is extended.
0
"
I
MFR 7SJ551
Operating instructions
Example
A motor has been tripped upon rotor thermal
overload. The stator thermal reserve is above the
stator inhibit level. The rotor warming-up time
constant is 200 s. The rotor inhibit level is 30% (refer
to sections 3.* and 4.* for calculations). The rotor
cooling down factor is 2. According to the
manufacturer data a start has to be inhibited for 10
minutes after trip. How long must the start inhibit
release extension time be set? As the load current is
x lRc,
the formula
zero and the preload current is k,
for the rotor thermal reserve changes to:
After -400 x In 0.7 = 143 s the rotor thermal reserve
will reach 30%. So tinh must be set to 10 x 60 - 143
START I N H I B I T
@-stator[%]
Stator start inhibit level
Setting range:
0 to 100%
The stator start inhibit level only works upon the
stator thermal reserve buffer. Be aware that the start
inhibit function works for both rotor thermal reserve
and stator thermal reserve buffers. Both thermal
reserves must exceed the release thresholds before
the start inhibit output is released. (The rotor start
inhibit level cannot be set separately from the stator
start inhibit level; it is calculated by the relay as
described in section 4.4.)
Set the stator inhibit level in accordance with motor
manufacturer recommendations. The time needed
for reaching the inhibit level after trip, is related to the
stator start inhibit level according to the following
formula.
Example 1
For a motor with ~,,~t, = 100 S, 22,stat = 200 S, Pwelght
=
0.5 and ~,c,
= 2 the manufacturer recommends to
inhibit a start for 5 minutes after stator overload trip.
How must the stator start inhibit level be set? Filling
in the release time gives a stator start inhibit level of
54.1 %. (The
6
MFR 7SJ551
Operating instructions
start inhibit release extension time can be set to 0 s.)
Example 2
For a motor with T,,,, = 100 S, %,,tat = 200 S, Pweigm=
0.5 and c,~,~,
= 2 the stator start inhibit level is set
to 50% and the start inhibit release extension time is
set to 0 s. How long does it take to release a start?
Filling in different release times:
release time
275 s
276 s
277 s
278 s
279 s
280 s
stator start inhibit level
49.6%
49.8%
50.0%
'0
50.11
50.3%
50.5%
gives a release time of 277 s.
Enabling the emergency restart function
Disabling the emergency restart function
When the start inhibit function is enabled, here the
emergency restart function can be activated.
6.8.4
EMERGENCY RESTART
The EMERGENCY RESTART menu is a submenu
of the START INHIBIT menu. With setting the
EMERGENCY RESTART parameter the start
inhibit can be overruled.
MFR 7SJ551
Operating instructions
START I N H I B I T
l ENABLED
41
Beginning of the submenu EMERGENCY RESTART
Enabling the emergency restart function
Disabling the emergency restart function
ENABLED
8
6.8.5
No further parameters have to be set. To overrule
the start inhibit the binary emergency restart input
has to be energized. Then the thermal reserve
buffers will be reset to 100%.
OVERTEMPERATURE protection (optional)
i
I
For OVERTEMPERATURE PROTECTION the
relay has to be equipped with an interface module
containing temperature sensor connectors. Two
types RTD interface modules are available: with
two or with eight temperature sensor con-nec-tors.
Temperature sensor inputs that are not connected to
a temperature sensor should be closed with a
resistor (50 - 100 Q) to fix the display value.
Beginning of the submenu OVERTEMPERATURE.
Enabling the overtemperature protection.
Disabling the overtemperature protection.
Overtemperature alarm level
Setting range:
TRIP 1
["C]
0 to 200 OC
Overtemperaturetrip level
Setting range:
0 to 200 "C
For each temperature sensor an alarm pick-up and a
trip pick-up can be set individually (only integers).
Unused temperature sensor pick-ups should be set
to 999 "C to prevent unwanted pick-up. The trip
value must be set higher than the alarm value.
OVERTEMPERATU
TRIP 8
C°CI
I
-
6
MFR 7SJ551
6.8.6
Operating instructions
UNDERCURRENT protection
UNDERCURRENT PROTECTION can be applied
to all network components. For motors the function
1 ""'i'-:""-i
UNDERCURRENT +
needs one parameter more (tbypass)
than for nonrotating objects.
Beginning of the submenu UNDERCURRENT
+
Enabling the undercurrent protection
Disabling the undercurrent protection
UNDERCURRENT
t-bypassisl
\L
Bypass time
Setting range:
0 to 100s
The undercurrent bypass time is applicable for
motors only. The bypass time is started at the
moment the motor status changes from 'start' to
'running'. During the bypass time the undercurrent
protection function is inactive.
Undercurrent pick-up
Setting range:
0.05 to 28 . I,
For motors the pick-up value must be set higher than
the no-load current. Pick-up occurs in case of a loss
of or decrease in motor load. Examples of such
situations are: loss of suction of pumps, loss of
airflow for fans or a broken belt for conveyors.
For capacitor banks the pick-up value must be set
minimum to (0.05 . I,), to be sure the relay does not
pick up if there is remaining capacitive current.
Undercurrent delay time
Setting range:
0 s to 166 min
3
Operaiing instructions
MFR 7SJ55i
I
6.8.7
LOW SET B\/ERCURRENT protection
For low set overcurrent protection, MFR 7SJ551
distinguishes between
- phase fault overcurrent
- earth fault overcurrent.
The possible characteristics for low set phase and
earth fault overcurrent protection are:
- definite time overcurrent
- inverse time overcurrent
- custom curve overcurrent.
Two different characteristics for phase overcurrent
protection and two different characteristics for earth
fault overcurrent protection can be programmed.
During operation the CURVE SWITCH function
determines which of the two is effective. Refer to
section 6.8.1 6 for a detailed description.
Beginning of the submenu LOW SET
OVERCURRENT
Enabling the low set phase fault overcurrent
protection
Disabling the low set phase fault overcurrent
protection
I,,,,I:
L O W SET O . C .
pFq
DEFINITE
1 ;tlIR:NORMAL
21
VERY
11
ERR
'1
:
R
I
:
Choose the type of phase fault overcurrent
characteristic for CURVE 1.
DEFINITE
Refer to section 6.8.7.1
NORMAL INVERSE
VERY INVERSE
EXTREMELY INVERSE Refer to section 6.8.7.3
CUSTOM CURVE
Refer to section 6.8.7.5
C UH SA TR O: M
m
L O W SET O . C .
LOW SET O . C .
ENABLED
The same procedure is followed for setting phase
fault CURVE 2.
Enabling the low set earth fault overcurrent
protection
Disabling the low set earth fault overcurrent
protection
1
"
I
MFR 7SJ551
Operating instructions
h L O WS E T
O.C.
11
Choose the type of earth fault overcurrent
characteristic for CURVE 1.
DEFINITE
R
ICHAR:
I
VERY
11
EXTR
21
NORMAL INVERSE
VERY INVERSE
EXTREMELY INVERSE
LONG TIME EARTH FAULT
RESIDUAL DEPENDANT TIME
NV
CUSTOM CURVE
l
CHAR:
RD
.L
I~LOW
SET B.C.
21
11
m,m,
6.8.7.1
Refer to section
6.8.7.2
Refer to section
6.8.7.4
Refer to section
6.8.7.5
The same procedure is followed for setting earth
fault CURVE 2.
Definite time phase fault overcurrent protection
LOW S E T O . C .
+
+
PHASE:
Beginning of the submenu LOW SET
OVERCURRENT PHASE
Enabling the low set phase fault overcurrent
protection
Disabling the low set phase fault overcurrent
protection
LOW SET O . C .
J,
Beginning of the settings for phase fault CURVE 1.
If the CURVE SWITCH function is disabled, this
menu line will not appear.
Beginning of the phase fault DEFINITE TIME
overcu rrent settings
DEFINITE
J,
MFR 7SJ551
Operating instructions
Pick-up value of the phase fault overcurrent stage
I>
Setting range:
0.05 to 28 . I,
The maximum load current determines the setting of
the overcurrent stage I>. Pick-up on overload must
be excluded since the low set overcurrent is a shortcircuit protection with adequate short tripping time.
Therefore the overcurrent stage is set to 120% for
feeder lines, and 150% for transformers or motors
referred to maximum overload current.
Trip time delay for the overcurrent stage I>
Setting range:
0 s to 166 min
The time delay tl> depends on the grading plan for
the network. For modern circuit breakers minimum
0.3 s time difference between two grading levels
can be used. Use 0.5 s for older circuit breakers.
The setting times are pure delay times which do
not include the relay operating time.
LOW SET O . C .
For curve 2 an alternative characteristic or an
alternative pick-up value or delay time can be set.
CURVE 2 is available only if the CURVE SWITCH
function is activated.
For motor protection it is beneficial to set the
CURVE SWITCH function in the mode STATUS. In
this case, for high speed clearing of motor phase
faults the following conditions must be fulfilled for
the setting of the pick-up value I> of CURVE 2:
- the minimum pick-up value must be greater
than 1.6 times motor locked rotor current
(maximum inrush due to asymmetry)
- the minimum pick-up value must be smaller
than the minimum short-circuit current.
Differential protection should be provided if the
above criteria are not met! In practice the
maximum pick-up current must be smaller than
circa 113 of the maximum occurring 3-phase shortcircuit current. Program the STATUS mode to
STOPISTART; then CURVE 2 is activated
automatically when the relay recognizes a start or
stand-still.
For transformer protection CURVE 2 can be used
to lift up the pick-up value temporarily
MFR 7SJ551
Operating inst ructions
during transformer inrush. To activate CURVE 2 a
binary input is energized.
Refer to section 6.8.16 for a more detailed
description of the CURVE SWITCH function.
6.8.7.2
Definite time earth fault overcurrent protection
Beginning of the submenu LOW SET
OVERCURRENTEARTH
LOW SET O . C .
ENABLED
LOW S E T O . C .
DEFINITE
Enabling the low set earth fault overcurrent
protection
Disabling the low set earth fault overcurrent
protection
Beginning of the settings for earth fault CURVE 1.
If the CURVE SWITCH function is disabled, this
menu line will not appear.
Beginning of the earth fault DEFINITE TIME
overcurrent settings
&
Pick-up value of the earth fault overcurrent stage
I,>
Setting range:
0.05 to 28 . I, for regular earth current detection
0.003 to 1.4 - ,I for sensitive earth current detection
The minimum earth fault current determines the
setting of the overcurrent stage 12.
With DIRECTIONAL EARTHFAULT PROTECTION
enabled, the denomination of the pick-up value
changes to 19.
Trip time delay for the overcurrent stage I,>
Setting range:
0 s to 166 min
The time delay tl,> depends on the grading plan for
the network which can be separate for earth faults.
For modern circuit breakers minimum 0.3 s time
difference between two grading levels can be used.
Use 0.5 s for older circuit
MFR 7SJ551
Operating instructions
breakers. The setting times are pure delay times
which do not include the relay operating time.
With DIRECTIONAL EARTHFAULT PROTECTION
enabled, the denomination of the time delay changes
to t l p .
LOW
@
11
SET O . C .
For curve 2 an alternative characteristic or an
alternative pick-up value or delay time can be set.
CURVE 2 is available only if the CURVE SWITCH
function is activated.
6.8.7.3 Inverse time phase iauit overcurrent protection
Beginning of the submenu LOW SET
OVERCURRENT PHASE
I
+I
PHASE:
Enabling the low set phase fault overcurrent
protection
Disabling the low set phase fault overcurrent
protection
Beginning of the settings for phase fault CURVE 1.
If the CURVE SWITCH function is disabled, this
menu line will not appear.
Type of INVERSE characteristic for CURVE 1
NORMAL INVERSE
ICHAR:
VERY
21
R
EXTR
21
I NV
:
1 CHAR:
. . . -+I
VERY INVERSE
EXTREMELY INVERSE
time lag according to
IEC 255-3, type A
time lag according to
IEC 255-3, type B
time lag according to
IEC 255-3, type C.
A choice can be made between three tripping
characteristics defined in IEC 255-3.
Pick-up value of the phase fault overcurrent stage
,1
Setting range:
0.05 to 28 . I,
Time multiplier for the overcurrent stage ,I
Setting range:
0 to 10
i
"
MFR 7SJ551
For curve 2 an alternative characteristic or an
alternative pick-up value or delay time can be set.
CURVE 2 is available only if the CURVE SWITCH
function is activated.
LOW S E T O . C .
6.8.7.4
'
Operating instructions
inverse time earth fault overcurrent protection
Beginning of the submenu LOW SET
OVERCURRENT EARTH
Enabling the low set earth fault overcurrent
protection
Disabling the low set earth fault overcurrent
protection
LOW S E T O . C .
ENABLED
I
EARTH:
DISABLED
[ L O W SET O.C.
11
'"4
C H A R : NORMAL
1
1
R
:
VERY
?/
R
:
EXTR
21
CHAR:
I CHAR:
I CHAR:
Beginning of the settings for earth fault CURVE 1.
If the CURVE SWITCH function is disabled, this
menu line will not appear.
Type of INVERSE characteristic for CURVE 1
NORMAL INVERSE
time lag according to
IEC 255-3, type A
VERY INVERSE
time lag according to
IEC 255-3, type B
EXTREMELY INVERSE time lag according to
IEC 255-3, type C.
LONG TIME EARTH FAULT
RESIDUAL DEPENDANT TIME
RD
...
...
2
2
A choice can be made between three tripping
characteristics defined in IEC 255-3 and two
additional characteristics.
Pick-up value of the earth fault overcurrent stage
Ie,
Setting range:
0.05 to 28 - I, for regular earth current detection
0.003 to 1.4 . I, for sensitive earth current detection
MFR 7SJ551
Operating instructions
With DIRECTIONAL EARTHFAULT PROTECTION
enabled, the denomination of the pick-up value
changes to .,I For the RESIDUAL DEPENDANT
TIME curve the denomination of the pick-up value
changes to 12.
Time multiplier for the overcurrent stage ,I
Setting range:
0 to 10
With DIRECTIONAL EARTHFAULT PROTECTION
enabled, the denomination of the time multiplier
changes to 6,.
For curve 2 an alternative characteristic or an
alternative pick-up value or delay time can be set.
CURVE 2 is available only if the CURVE SWITCH
function is activated.
LOW S E T O . C .
6.8.7.5
Custom curve overcurrent protection
The description of the CUSTOM CURVE
overcurrent protection is valid for both phase and
earth fault overcurrent protection. For earth fault
overcurrent protection 'earth' should be read where
'phase' is used.
Beginning of the submenu LOW SET
OVERCURRENT PHASE
I
~E!::~LED
\L
'1
LOW SET O . C .
mi
\L
CUSTOM
pF-1
#/ OF P O I N T S
Enabling the low set phase fault overcurrent
protection
Disabling the low set phase fault overcurrent
protection
Beginning of the settings for phase fault CURVE 1.
If the CURVE SWITCH function is disabled, this
menu line will not appear.
Beginning of the phase fault
overcurrent settings
CUSTOM CURVE
,
I
Operating instructions
MFR 7SJ551
Number of current-time points
Setting range:
2 to 15
Up to 15 pairs of values of current and time can be
programmed. The relay calculates intermediate
values by linear interpolation. It is permitted to
program less current-time points.
Pick-up value of the custom curve overcurrent
stage 1
0.05 to 28 . I, for regular earth current detection
0.003 to 1.4 . I, for sensitive earth current detection
Trip time delay for the custom curve overcurrent
stage 1
Setting range:
0 s to 166 min
The relay has the following preset values:
2.50
MFR 7SJ551
6.8.8
Operating instructions
HlGH SET OVERCURRENT protection
For high set overcurrent protection MFR 7SJ551
distinguishes between:
- phase fault overcurrent
- earth fault overcurrent
H l G H SET O.C.+
3 PHASE:
&
x
HIGH SET O.C.
Two different characteristics for phase overcurrent
protection and two different characteristics for earth
fault overcurrent protection can be programmed.
During operation the CURVE SWITCH function
determines which of the two is effective. Refer to
section 6.8.16 for a detailed description.
Beginning of the submenu HlGH SET
OVERCURRENTPHASE
Enabling the high set phase fault overcurrent
protection
Disabling the high set phase fault overcurrent
protection
Beginning of the settings for phase fault CURVE 1.
If the CURVE SWITCH function is disabled, this
menu line will not appear.
Pick-up value of the phase fault overcurrent stage
1>>
Setting range:
0.05 to 28 . 1,
This stage is often used for current grading before
high impedances, e.g. transformers or motors. This
stage is always a definite time stage, independent of
which characteristic is set for the low set overcurrent
stage. It protects against short-circuits taking place
in this concentrated impedance, e.g. for
1
If ,I
transformers up to 1.5 times -.
UK transi In c.t.
Trip time delay for the overcurrent stage I>>
Setting range:
0 s to 166 min
HIGH SET O.C.
\L
For curve 2 an alternative characteristic or an
alternative pick-up value or delay time can be set.
CURVE 2 is available only if the CURVE SWITCH
function is activated.
"
MFR 7SJ551
'
Operating instructions
Beginning of the submenu HIGH SET
OVERCURRENT EARTH
Enabling the high set earth fault overcurrent
protection
Disabling the high set earth fault overcurrent
protection
All further settings for the high set earth fault
overcurrent protection are similar to the settings of
the high set phase fault overcurrent protection.
6.8.9
A further application of the high set overcurrent
protection is the reverse interlocking principle. The
I>> stage is used for rapid tripping in case of a bus
bar fault, with only a short safety time. The low set
overcurrent stage is the back-up for faults on an
outgoing feeder. The relays protecting the outgoing
feeders block the I>> stage via the binary input when
the fault is in their protection area (refer to figure
4.20). Set the pick-up value I>> at the same value as
I> or I,.
UNBALANCE protection
UNBALANCE PROTECTION can be applied to all
network components. For motors the function
than for nonneeds one parameter more (bypass)
rotating objects.
Beginning of the submenu UNBALANCE
Enabling the unbalance protection
Disabling the unbalance protection
UNBALANCE
Bypass time
t-bypass[sl
&
Setting range:
0 to 100 s
The unbalance bypass time is applicable for motors
only. The bypass time is started at the moment the
motor status changes from 'stopped' to 'start'.
During the bypass time the unbalance protection
function is inactive. A practical value is 1.0 s.
I
Operating instructions
MFR 7SJ551
UNBALANCE
.zoo
\L
Unbalance pick-up
0.05 to 28 . I,
Setting range:
For motors a practical setting value can be
calculated out of:
mi
UNBALANCE
Unbalance time multiplier
0 to 25
Setting range:
For motors a practical setting value can be
calculated out of:
with tc, the thermal copper warming-up time
constant as provided by the motor manufacturer.
6.8.1.8
C
DlRECT10NAE EARTHFAULT protection (optional)
The DIRECTIONAL EARTHFAULT protection can
be used in isolated or arc compensated networks
to detect an earth fault and to determine the earth
fault direction. Because of its high sensitivity it is
not suited for detection of higher earth fault
currents (from 1 A and above at the relay terminals
for sensitive earth current detection). For those
+ 3 EARTHFAULT
EARTHFAULT
ENABLED
pjq
applications use the relay ordering option with
terminals for regular earth current detection.
The directional earth fault protection function uses
the two-stage current time characteristic which is
set in the submenus LOW SET OVERCURRENT
EARTH and HIGH SET OVERCURRENT-EARTH.
Beginning of the submenu DIRECTIONAL
EARTHFAULT
Enabling the directional earth fault protection
Disabling the directional earth fault protection
Measuring principle
CONTROL:
COSlNE
SINE
active power measurement
reactive power measurement
MFR 7SJ551
Operating instructions
In isolated systems earth fault measurement with
SINE is used because the capacitive current is
decisive for the earth fault direction.
In compensated systems earth fault measurement
with COSINE is used because the ohmic current is
decisive for the earth fault direction.
In earthed systems earth fault measurement with
COSINE is used with a correction angle of -45"
because the earth current is ohmic-inductive.
In electrical machines in bus-bar connection with
an isolated system, COSINE measurement can be
selected with a correction angle of +4S0because
the earth current is often composed of a capacitive
component from the system and an active
component from an earth fault load resistor.
EARTH FAULT
U - s t r t [Un]
Displacement voltage
Setting range:
0.05 to 1.2 . U,
\L
The residual voltage Us,, initiates earth fault
detection and is one condition for release of
directional determination. Since, for earth faults in
isolated or compensated networks, the full
displacement voltage appears, the setting value is
not critical; it should lie between 30 V and 60 V. In
earthed networks, the set value of the earth voltage
Us,, can be more sensitive (smaller); but it should
not be exceeded by operational asymmetry of the
voltages of the power system.
EARTH FAU LT
t U-strt[sl
Pick-up delay
Setting range:
0 s to 166 min
Earth fault is detected and annunciated only when
the displacement voltage has been present for the
t.,
duration U
pLq
FORWARD
Directional trip condition for low set earth current
stage
FORWARD or BACKWARD
*
I
MFR 7SJ551
Operating instructions
mi
FORWARD
Directional trip condition for high set earth current
stage
FORWARD or BACKWARD
Rotation angle
EARTHFAULT
[a]+****
Setting range:
-45" to +45"
Set the rotation angle to -45' in earthed systems
using COSINE earth fault measurement which is
used for angle correction for ohmic-inductive earth
currents.
In electrical machines in bus-bar connection with
an isolated system, COSINE measurement can be
selected with a correction angle of +45" because
the earth current is often composed of a capacitive
component from the system and an active
component from an earth fault load resistor.
EARTHFAULT
Current transformer angie correction for I, 2 100
mA
** **
\L
EARTHFAU L T
Setting range:
0"to 5"
Current transformer angle correction for 100 mA <
,I 5 200 mA
****
&
EARTH FAU LT
Setting range:
On to 5"
Current transformer angle correction for I, > 200
mA
**r*
Setting range:
0"to 5"
The high reactive current component in
compensated networks and the unavoidable air gap
of the window-type current transformers often make
compensation of the angle error of the current
transformer necessary. With the programmed angle
corrections the relay adapts the measurement
results to the characteristic of the transformer. In
isolated or earthed networks this angle error
compensation is not necessary.
~
I
MFR 7SJ551
6.8.1 1
Operating instructions
LOCKED ROTOR protection
/1 -
Beginning of the submenu LOCKED ROTOR
protection
LOCKED ROTOR + 3
Enabling the locked rotor protection
Disabling the locked rotor protection
LOCKED R O T O R
Permissible locked rotor time
Setting range:
0 to 200 s
In most cases the permissible locked rotor time is
mentioned in the data of the manufacturer. As the
locked rotor condition is very critical, take a safety
margin of 1 s.
If the permissible start-up time is longer than the
permissible locked rotor time the locked rotor
protection function is inadequate: then the zero
speed function has to be used.
6.8.1 2
ZERO SPEED protection
If the permissible start-up time is longer than the
permissible locked rotor time the locked rotor
protection function is inadequate: then the zero
speed function has to be used.
Beginning of the submenu ZERO SPEED protection
Enabling the zero speed protection
Disabling the zero speed protection
,
Zero speed detection time
Z E R O SPEED
Setting range:
0 s to 166 min
If, during zero speed alarm, the binary zero speed
input (connected to a binary tachometer) stays
energized during,,,t , the relay will issue a trip
command.
MFR 7SJ551
@
6.8.13
Operating instructions
UNDERVOLTAGE protection (optional)
Beginning of the submenu UNDERVOLTAGE
protection
UNDERVOLTAGE + 3
Enabling the undervoltage protection
Disabling the undervoltage protection
m
UNDERVOLTAGE
Undervoltage pick-up
Setting range:
0.05 to 1.2 . U,
Depending on the programmed voltage circuit type
Uo<, UI,< or Uph<is displayed. As a default Uo< is
displayed.
Undervoltage delay time
UNDERVOLTAGE
0 s to 166 min
Setting range:
6.8.1 4
OVERVOLTAGE protection (optional)
Beginning of the submenu OVERVOLTAGE
protection
1 DISABLED
-
Enabling the overvoltage protection
Disabling the overvoltage protection
\L
p!pqEq
I
I1
./3U
\L
Pick-up value of the low set stage U>
Setting range:
0.05 to 1.2 . U,
Depending on the programmed voltage circuit type
Uo>, U,,> or Uph>is displayed. As a default Uo> is
displayed.
OVERVOLTAGE
4
Trip time delay of the low set stage U>
Setting range:
0
s to 166 min
MFR 7SJ551
Operating instructions
OVERVOLTAGE
1. o o
OVERVOLTAGE
L
.
Pick-up value of the high set stage U>>
Setting range:
0.05 to 1.2 . U,
Trip time delay of the high set stage U>>
Setting range:
O s t o 166rnin
6.8.65
BREAKER FAILURE
PROTECTION
p m q l + ~ ]
ENABLED
EXTERN: D I S A B L +
Beginning of the submenu BREAKER FAILURE
PROTECTION
Enabling the breaker failure protection
Disabling the breaker failure protection
Disabling the external control
Enabling the external control
Start of the breaker failure protection can be
initiated by an external protection relay. The trip
signal of the external protection device is coupled
into MFR 7SJ551 via a binary input.
Pick-up value of current stage
Setting range:
0 to 28 . I,
Time stage
Setting range:
0 s to 166 min
When the trip command is generated timer tbfis
started. The timer continues to run for as long as
the trip command is maintained. If the circuit
breaker does not respond to the trip command the
timer runs to its set limit. If the then measured
current is higher than Ibfthe breaker failure
protection energizes a second relay output to trip
the upstream circuit breaker to clear the fault.
MFR 7SJ551
Operating instructions
external protection device is coupled into MFR
7SJ551 via a binary input. The timer tbfis started. If
the measured current is higher than lbf after tbf has
elapsed, the breaker failure protection energizes
the breaker failure protection relay output to trip the
circuit breaker to clear the fault. Deenergizing of
the binary breaker failure protection input only has
effect as soon as the measured current becomes
smaller than fbf.
The submenu CURVE SWITCH only appears when
low set overcurrent protection or high set overcurrent
protection is enabled.
';""I':"Im
i
CURVE S W I T C H +
+
Beginning of the submenu CURVE SWITCH
Enabling the curve switch function
Disabling the curve switch function
~
Curve switch mode.
CONTlNUOUS
PULSE
STATUS
MFR 7SJ551 switches from
curve 1 to curve 2 during the
activation of the curve switch
binary input
MFR 7SJ551 switches from
curve 1 to curve 2 during the
curve switch time tcs, after
the activation of the curve
switch binary input
only for motors; depending
on motor status MFR 7SJ551
automatically switches from
curve 1 to curve 2
If the curve switch mode CONTINUOUS is set, no
further menu item appears.
CURVE SWITCH
10.0
Curve switch activation time
Setting range:
0 s to 166 min
If the curve switch mode PULSE is set, this menu
item appears.
a
J
MFR 7SJ551
Operating instructions
CURVE SWITCH
RUNNING
6.8.17
Curve switch status
If the curve switch mode STATUS is set, this menu
item appears.
RUNNING
when the motor status is
RUNNING, curve 2 is active,
when the motor status is
STOPPED or START curve
1 is active
STOPPED/START
when the motor status is
STOPPED or START, curve
2 is active, when the motor
status is RUNNING curve 1
is active
BLOCK
With the BLOCK function MFR 7SJ551 provides the
possibility to block the overcurrent, undercurrent and
undervoltage characteristics during motor or
transformer inrush.
The submenu BLOCK only appears when
undercurrent protection, low set overcurrent
protection, high set overcurrent protection or
undervoltage protection is enabled.
p=i&q+rnI
Beginning of the submenu BLOCK
ENABLED
Enabling the block function
Disabling the block function
BLOCK mode
CONTINUOUS
PULSE
STA TUS
M F R 7SJ551 activates the
block function during the
activation of the block binary
input
MFR 7SJ551 activates the
block function during the
block time tBLoCK,
after the
activation of the block binary
input
only for motors; depending
on motor status MFR 7SJ551
automatically activates the
block function
if the BLOCK mode CONTINUOUS is set, no
further menu item appears.
MFR 7SJ551
Operating instructions
BLOCK activation time
Setting range:
p z q
RUNNING
0 s to 166 min
Block status
If the block mode STATUS is set, this menu item
appears.
RUNNING
STOPPED/START
when the motor siatus is
STOPPED or START, the
block function is active, when
the motor status is
RUNNING, the block function
is inactive
when the motor status is
RUNNING, the block function
is active, when the motor
status is STOPPED or
START, the block function is
inactive
Disabling the BLOCK TIMERS ('block on pick-up').
There will be no alarm and no trip indication.
Enabling the BLOCK TIMERS ('block on timers').
There will be an alarm indication after pick-up, but no
trip.
B L O C K U.C.
I<:
ENABLED
BLOCK O.C.
Enabling BLOCK UNDERCURRENT
Disabling BLOCK UNDERCURRENT
Enabling BLOCK LOW SET OVERCURRENT
PHASE
Disabling BLOCK LOW SET OVERCURRENT
PHASE
DISABLED
BLOCK O . C .
ENABLED
/:i""":
ENABLED
1-
DISABLED
ENABLED
Enabling BLOCK HlGH SET OVERCURRENT
PHASE
Disabling BLOCK HlGH SET OVERCURRENT
PHASE
Enabling BLOCK LOW SET OVERCURRENT
EARTH
Disabling BLOCK LOW SET OVERCURRENT
EARTH
\
MFR 7SJ551
1
Operating instructions
Enabling BLOCK HIGH SET OVERCURRENT
Disabling BLOCK HIGH SET OVERCURRENT
EARTH
BLOCK U . V .
ENABLED
6.8.18
'
Enabling BLOCK UNDERVOLTAGE
Disabling BLOCK UNDERVOLTAGE
EXTERNAL COMMAND
With the external command function an immediate
trip can be generated by activating a binary input,
for example to make an emergency stop
i
m[
E X T . COMMAND
9
+
I I I I
Beginning of the submenu EXTERNAL COMMAND
Enabling the external command
Disabling the external command
EXT. COMMAND
Delay time
Setting range:
0 s to 166 min
After activating the external command binary input,
the delay timer tEXTis started. If the binary input
continues to be activated during tEXrl the external
command output will be energized after tEXrhas
elapsed.
6.8.19
ClRCUlT BREAKER POSITION
With the circuit breaker position function the
position of the circuit breaker can be indicated.
i'"""'I:""i
Beginning of the submenu CB POSITION
CB P O S I T I O N
+
+
Enabling the circuit breaker position annunciation
Disabling the circuit breaker position annunciation
*
MFR 7SJ551
I
Operating instructions
After the circuit breaker position binary input is
activated the c,ircuit breaker position LED indicator
will be energized.
Operating instructions
MFR 7SJ551
6.9
Settings for TRANSIENT DATA
mi-
In the TRANSIENT DATA the operator determines
how the fault recording is started.
TRANSIENT
+
+
Beginning of the submenu TRANSIENT DATA
DATA
Enabling the internal triggering of the data storage
(triggering by fault)
Enabling the external triggering of the data storage
(triggering by binary input)
INTERN
1
E.TERN
.
J.
Data storage can be initiated by any protection
function (INTERN). The actual storage time begins
prematurely by a fixed pre-trigger time. Total
storage time is three seconds.
Data storage can also be initiated via a binary
input. The storage is triggered dynamically, in these
cases. Total storage time is three seconds.
Storage criterion
DATA STORAGE
FAULT DETECTION
TRIP
The storage criterion can be the general fault
detection (FD) or the trip command (TRIP).
Especially for delay times larger than 3 seconds
storage by trip can be desirable, as for storage by
fault detection MFR 7SJ551 will not record sampling
values at the trip instant.
MFR 7SJ551 is equipped with a real time clock. In
the REAL TIME CLOCK menu date and time can
be altered. Furthermore, time synchronisation can
be activated here.
Beginning of the submenu REAL TIME CLOCK
Setting the date format to day - month - year
Setting the date format to month - day year
FORMAT: OD-MM--
I [PRMAT:
MM-DO-?
-
I
I
MFR 7SJ551
Operating instructions
Date.
Depending on the date format the date is set using
the numerical keyboard. The dashes are put in
automatically. The day after 31-12-99 will be 01-0100.
Time
The time is in European format (00:00:00 to
23:59:59). The colons are put in automatically.
Disabling the real time clock synchronization
Enabling the real time clock synchronization
MFR 7SJ551 provides the possibility to synchronize
the real time clock via a binary input. For this
purpose a mother clock or a receiver for a DCF
pulse must be connected. Energizing the binary
input will set the seconds to zero. The minutes will
be set to the nearest value.
Example 1
A synchronizing pulse at 13:27:18 will set the real
time clock to 13:27:00.
Example 2
A synchronizing pulse at 13:27:48 will set the real
time clock to 13:28:00.
MARSHAkkiNG of binary inputs, binary outputs and LED
indicators
6.1 1.I
General
As a factory setting the binary inputs, the binary
outputs and the LED indicators are not marshalled.
This means the relay will not be able to perform
any protection function. The assignment of the
different input and output criteria must be
marshalled according to on-site conditions.
When the firmware programs are running, the
specific logic functions will be allocated to the
physical input and output modules or LEDs in
accordance with the selection.
Exampie
An earth fault is registered from the low set earth
overcurrent time protection. This event is
generated in the device as a START (logical
function) and should be available at one or more of
the output contacts, for example output relay 3.
The microcontroller must be advised that the
logical signal START E> should be transmitted to
the output relay 3.
Thus, when marshalling is performed two
statements of the operator are important:
1. Which logical annunciation generated in the
protection unit program should trigger an output
relay?
2. Which output relay should be triggered by this
logical annunciation?
The trip relays can be assigned to more than one
function. Up to 33 logical annunciations can trigger
!
hAFR 7SJ551
I
I
@
Operating instructions
one relay (maximum version), although this is not a
realistic situation.
One logical annunciation can be assigned to more
than one output relay, up to the maximum number
of output relays available.
(namely blocking). The corresponding question to
the operator is then:
1. Which signal to a binary input should initiate a
reaction by the device?
2. Which reaction should be initiated?
A similar situation applies to binary inputs. In this
case external information (for example blocking of
the I>> stage) is connected to the unit via an input
module and should initiate a logical function
The (optional) marshallable LED indicators can be
assigned to more than one function. Up to 30
logical annunciations are permitted. Marshalling
LED indicators is performed similar to marshalling
output relays. One logical annunciation can be
assigned to only one LED indicator.
~SETTIN~SI
pmq+
+
Beginning of the submenu MARSHALLING and of
the submenu BINARY INPUT
MARSHALLING
+
BINARY INPUT
pOUTPUT
% R E LTA Y S , q+
Beginning of the submenu OUTPUT RELAYS
-
,
MARSHALLING
Beginning of the submenu LED INDICATOR
When the MARHALLING menu is left, the settings
are permanently secured on EEPROM and
protected against power outage
6.1 1.2
Marshalling of the BINARY INPUTS
The unit contains 2 or 5 binary inputs (dependent
on model) which are designated BINARY INPUT 1
to BINARY INPUT 5. They can be marshalled in
the submenu MARSHALLING BINARY INPUT.
1
NORMALLY :
:/EN
MFR 7SJ551
Operating instructions
NORMALLY CLOSED
Beginning of the submenu MARSHALLING
BINARY INPUT
First a choice can be made for each individual input
as to whether the assigned function should become
operative in the NORMALLY OPEN mode or in the
NORMALLY CLOSED mode:
NORMALLY OPEN
The control voltage at the
input terminals activates
the function.
BINARY INPUT
BLOCK:
Control voltage present
at the terminals turns
off the function, control
voltage absent activates
the function.
As a next step, each input function must be
assigned to one binary input. Scrolling down the
MARSHALL1NG BINARY INPUT menu the different
functions appear. The normally open or normally
closed status is displayed by 'NO' or 'NC' in the
right upper corner of the display. By pushing the
arrow right key 3 the binary input number can be
set.
E.ampie
For assigning the BLOCK input signal to a binary
input the menu appears as showed on the left.
Binary inputs 2 and 4 are set normally closed.
BINARY INPUT
BINARY INPUT
BINARY INPUT
BINARY INPUT
\L
The following input functions will appear if the
concerning protection functions have been
enabled. Otherwise these functions will not appear.
Refer to section 4 and 6.8 for a detailed description
of these input functions
REMOTE RESET
For resetting the relay via a binary input instead of
the RI key at the front.
To obtain this possibility set the REMOTE RESET
function to EXTERN.
REMOTE RESET
ENABLED
a
i
MFR 7SJ551
Operating instructions
This menu item will appear in the submenu
MARSHALLING BINARY INPUT. If disabled no
binary input assignment is requested.
Enabling the remote reset
Disabling the remote reset
?-adjust
For adapting the warming-up time constants to onsite conditions.
CURVE SWITCH
For switching from overcurrent curve set 1 to
overcurrent curve set 2.
BLOCK
For blocking the overcurrent, undercurrent or
undervoltage characteristics.
CW/CCW INPUT
For adapting the calculation of inverse current and
unbalance to the reverse rotation direction.
First a choice has to be made in the
MARSHALLING BlNARY INPUT menu whether the
clockwise/counterclockwise determination is
performed internally or externally.
Rotating direction determination MODE
CW/CCW
INPUT
INTERN
INTERN
MODE:
E.TERN
E.TERN
3,
CW/CCW I N P U T
IlFiREcT:oN:
The direction of rotation is determined
in the ne-t menu line.
The direction of rotation is normally
clockwise. The binary input signal will
reverse the direction of rotation to
counterclockwise,
Rotating direction
CLOCKWISE
COUNTERCLOCKWISE
After setting the mode to INTERN the rotating
direction can be set. For reversing the direction the
relay has to be reprogrammed.
EMERGENCY RESTART
For resetting the thermal reserve buffers to 100%.
ZERO SPEED
For protecting the motor against stalled rotor by
connecting a binary tachometer to this ZERO
SPEED binary input.
BREAKER FAILURE TRlP
For initiating start of the breaker failure trip by an
external protection relay. The trip signal of the
external protection device is coupled into MFR
7SJ551 via the BREAKER FAILURE TRlP binary
input.
E.TERNAL COMMAND
For generating an immediate trip, for example to
make an emergency stop.
CIRCUIT BREAKER POSITION
For indicating the position of the circuit breaker.
When the binary circuit breaker position input is
energized one of the rnarshallable LED indicators
(assigned to circuit breaker position) will be
illuminated.
FAULT RECORDING
For initiating data storage.
SERIAL EVENT
For passing on a binary signal serially to the station
control system.
*
MFR7SJ551
'
I
Operating instructions
Example
The input function SERIAL EVENT is assigned to
normally open binary input 3. If binary input 3 is
energized the relay will send away a serial
message via its serial interface to the control
system that binary input 3 has been energized. In
the control system this message can be given a
special meaning, for e,ample "cubicle door open".
'
RTCSYNC
For synchronizing the real time clock.
6.1 1.3
Marshalling of the OUTPUT RELAYS
Dependent on the ordered model the unit contains
4 output relays or 6 output relays (with output 1
doubled). These outputs are make contacts. One
(breaker) output contact signals the availability of
the relay (MONITOR), its allocation cannot be
changed. The six make contacts are designated
OUTPUT-1 to OUTPUT 6 and can be marshalled in
the menu MARSHALLING OUTPUT RELAYS.
Multiple designations are possible, i.e. one logical
annunciation function can be routed to several
output relays and several logical annunciation
functions can be routed to one output relay.
Beginning of the submenu MARSHALLING
OUTPUT RELAYS and of the submenu LATCH
TIMERS
Enabling the latching timer
Disabling the latching timer
If enabled output signals will be locked for a limited
amount of time.
MFR 7SJ551
Operating instructions
Latching time
t - r e s e t [sl
Setting range:
0 s to 766 min
The output relay will be locked until tEsethas elapsed.
This menu line will only appear if the latching timer is
enabled.
First a choice can be made for each individual
output relay as to whether it has to be locked after
excitation or not:
UNLATCHED
1
'1
LATCHED
&
UNLATCHED
i
I
LATCHED
After disappearing of the output
condition the output relay will
drop off.
After disappearing of the output
condition and elapsing of the
latching time the output relay will
drop off.
OUTPUT R E L A Y
Ne.t each output function must be assigned to one
or more output relays. Scrolling down the
MARSHALLING OUTPUT RELAYS menu the
different functions appear to the left and the
concerning output matrix lines to the right. The
latched or unlatched status is displayed by ' - ' or '1 '
in the upper line of the display. By pushing the 0 to
6 numerical keys the desired output relay numbers
can be set. By pushing the 0 to 6 numerical keys a
second time the setting disappears.
UNLATCHED
Example
For assigning the TRIP L>> output signal to output
relays the menu appears as follows. Outputs 2 and
4 are set latched.
mi
T R I P L>>:
---
T R I P L>>: 1 - -
T R I P L>>:
To assign output 1 and output 4 to the high set
overcurrent trip signal push 1 and 4 once.
If output 4 is set incorrectly and output 2 has to be
set, push 4 again and push 2 once.
12-
The following output functions will appear if the
concerning protection functions have been
enabled. Otherwise these functions will not appear.
Refer to section 4 and 6.8 for a detailed description
of these output functions.
I
MFR7SJ551
PRE-ALARM
For annunciating the pre-alarm condition. The
output will be energized after the thermal reserve
has decreased to the warning level.
TRIP 8-th
For thermal overload trip and annunciation. The
output will be energized after th,e thermal reserve
has decreased to zero.
START L I>
For annunciating pick-up of the low set overcurrent
protection function due to overcurrent in phase 1.
START L2>
For annunciating pick-up of the low set overcurrent
protection function due to overcurrent in phase 2.
START L3>
For annunciating pick-up of the low set overcurrent
protection function due to overcurrent in phase 3.
START L>
For annunciating pick-up of the low set overcurrent
protection function due to overcurrent in one or
more of the phases,
TRlP b
For low set phase overcurrent trip and
annunciation. The output will be energized after the
low set phase overcurrent delay time has elapsed.
Operating instructions
For directional earth fault trip and annunciation.
The output will be energized after the low set earth
overcurrent delay time has elapsed.
START b>
For annunciating pick-up of the high set
overcurrent protection function due to short-circuit
in one or more of the phases.
TRlP L>>
For high set phase overcurrent trip and
annunciation. The output will be energized after the
high set phase overcurrent delay time has elapsed.
START e>>
For annunciating pick-up of the high set stage of
the directional earth fault protection function due to
earth overcurrent in the protective direction.
START
For annunciating pick-up of the directional earth
fault protection function due to earth overcurrent in
the protective direction.
TRlP e>>
For high set earth overcurrent trip and
annunciation. The output will be energized after the
high set earth overcurrent delay time has elapsed.
TRIP @>>
For directional earth fault trip and annunciation.
The output will be energized after the high set earth
overcurrent delay time has elapsed.
START e>
For annunciating pick-up of the low set overcurrent
protection function (or the directional earth fault
protection function) due to earth overcurrent.
ALARM UB
For annunciating pick-up of the unbalance
protection function.
START @>
For annunciating pick-up of the low set stage of the
directional earth fault protection function due to
earth overcurrent in the protective direction.
TRlP UB
For unbalance trip and annunciation. The output
will be energized after the calculated unbalance
delay time has elapsed.
TRlP e>
For low set earth overcurrent trip and annunciation.
The output will be energized after the low set earth
overcurrent delay time has elapsed.
ALARM U c
For annunciating pick-up of the undervoltage
protection function.
TRlP @>
TRlP U<
For undervoltage trip and annunciation. The output
will be energized after the undervoltage delay time
has elapsed.
MFR 7 ~ ~ 5 5 1
,
ALARM U>
For annunciating pick-up of the low set overvoltage
protection function.
TRlP U>
For low set overvoltage trip and annunciation. The
output will be energized after the low set
undervoltage delay time has elapsed.
ALARM U>>
For annunciating pick-up of the high set
overvoltage protection function.
TRlP U>>
For low set overvoltage trip and annunciation. The
output will be energized after the low set
undervoltage delay time has elapsed.
7
i
a
I
Operating instructions
TRlP Ic
For undercurrent trip and annunciation. The output
will be energized after the undercurrent delay time
has elapsed.
le DIRECTION ->
For annunciating the forward direction as
determined by the directional earth fault protection.
Be aware that this output function is not the trip
condition of the directional earth fault protection!
le DlRECTlON <For annunciating the backward direction as
determined by the directional earth fault protection.
Be aware that this output function is not the trip
conditiori of the directional earth fault protection!
START INHlBlT
For preventing the motor circuit breaker to close
before the motor regained sufficient thermal
reserve again.
ALARM ZERO SPEED
For annunciating pick-up of the zero speed
protection function. The output will be energized
after the binary tachometer has energized the zero
speed binary input.
LOCKED ROTOR
For locked rotor trip and annunciation. The output
will be energized after the calculated locked rotor
trip delay time has elapsed.
TRlP ZERO SPEED
For zero speed trip and annunciation. The output
will be energized after the zero speed trip delay
time has elapsed.
ALARM T
For annunciating temperature increase above the
overtemperature alarm level.
BREAKER FAILURE TRlP
For breaker failure trip of the upstream circuit
breaker and for annunciation. The output will be
energized after the breaker failure trip time stage
has elapsed.
TRlP T
For overtemperature trip and annunciation. The
output will be energized as soon as the measured
temperature crosses the overtemperature trip level.
ALARMlc
For annunciating pick-up of the undercurrent
protection functibn.
E.TERNAL COMMAND
For immediate or delayed trip after the binary
e.ternal command input is energized. The output
will be energized after the external command trip
delay has elapsed.
1
MFR785551
1
6.11.4 Marshalling of the BED INDICATORS (optional)
I
Operating instructions
Dependent on the ordered model the unit contains
4 marshallable LED indicators. The allocation of
the five standard LED indicators cannot be
changed. The 4 marshallable LED indicators are
designated LED 1 to LED 4 and can be marshalled
in the menu MARSHALLING LED INDICATOR.
Beginning of the submenu MARSHALLING LED
INDICATOR
MEMORIZED
First a choice can be made for each individual LED
indicator as to whether it has to be memorized after
excitation or not:
Ul'itl
MEMORIZED
I
MEMORIZED
'1
NO#-MEMORIZED After disappearing of the
excitation condition the LED
indicator will drop off.
MEMORIZED
After disappearing of the
excitation condition the LED
indicator will stay illuminated
until it is reset.
As a next step, each excitation condition must be
assigned to one LED indicator. Scrolling down the
MARSHALLING LED INDICATOR menu the
different functions appear. The memorized or nonmemorized status is displayed by 'NM' or 'ME' in
the upper line of the display. Initially the excitation
functions are not marshalled, designated by '.'. By
pushing the arrow right key
the binary input
number can be set.
+
Example
For assigning the TRIP b>excitation signal to a
LED indicator the menu appears as follows. LED
indicators 2 and 4 are set latched.
LED INDICATOR
LED I N D I C A T O R
-1
LED INDICATOR
1
:RIP
L>>:
'1
INDICATOR
TRIP
> :
MFR 7SJ551
Operating instructions
The following excitation functions will appear if the
concerning protection functions have been
enabled. Otherwise these functions will not appear.
The excitation of the LED indicators is similar to a
large extent to the energizing of the output relays.
Refer to the output functions described briefly in the
preceding section 6.1 1.3. Refer to section 4 and
6.8 for a detailed description of these output
functions.
8
TRlP 8-th
START L,
TRlP b
START e>
START
TRlP e>
TRlP @>
STARTb>
TRlP b>
START,>>
START @>>
TRlP e>>
TRlP @>>
ALARM UB
TRlP UB
ALARM U<
TRlP U<
ALARM U>
TRlP U>
ALARM U>>
TRlP U>>
START INHIBIT
LOCKED ROTOR
ALARM T
TRlP T
ALARM I<
TRlP I<
le DIRECTION ->
le DIRECTION <ALARM ZERO SPEED
TRlP ZERO SPEED
BREAKER FAILURE TRlP
EXTERNAL COMMAND
One excitation function is available for LED
indication only:
CIRCUIT BREAKER POSITION
For indicating the position of the circuit breaker.
The LED indicator will be illuminated when the
binary circuit breaker position input is energized.
There is no use in setting a memorized LED
indicator for CIRCUIT BREAKER POSITION.
6.12
Settings for SERIAL COMMUNICATION (optional)
In the SERIAL COMMUNICATION menu the serial
communication facility can be matched to the
connected personal computer or station
management system.
Address number
Setting range:
0 to 254
I
"
t
MFR 7SJ551
Operating instructions
With the relay address different relays incorporated
in a control system can be distinguished from each
other.
Subaddress number
Setting range:
0 to 254
The subadress is needed when the relay is
incorporated in an elder Siemens SINAUT LSA
station control system.
Baudrate
S E R I A L COMM.
1
A
T
E
:
21
BAUDRATE:
138400
1
;RATE:
21
BAUDRATE:
Type of serial interface
RS-485 or optical
Both interfaces can be used for communicating
with a personal computer or a control system. It is
not possible to communicate with both interfaces at
a time. The type of the serial interface set in this
menu line should correspond to the communication
link desired at that moment.
Often the optical interface is connected to an
inputloutput unit of the control system and the RS485 interface to a notebook. The normal type
setting is OPTICAL then; only for setting and
commissioning using a notebook the type setting is
changed to RS-485.
Most personal computers only provide a RS-232
interface for communication with the relay. To
achieve communication the selected interface
should be connected via a converter to RS-232.
S E R I A L , COMM.
DISABLED
Enabling the SERIAL EVENT
Disabling the SERIAL EVENT
For passing on a binary 'serial event' input signal to
the station control system. In the control system
this message can be given a special meaning, for
e.ample "cubicle door open".
@
i
Operating instructions
MFR 7SJ551
Communication protocol
P R T C L : VDEW- 2
LSA
VDEW
VDEW-erw
S E R I A L COMM.
DISABLED
ILSA-protocol according to DIN 19244
international protocol according to
IEC 870-5
international protocol according to
IEC 870-5, e.tended with edra
annunciations specific for
MFR7SJ551
Disabling the serial communication BLOCK
Enabling the serial communication BLOCK
For commissioning it can be useful to prevent the
relay from serial sending of analogue signal values.
This is achieved by enabling the serial
communication block. Thus, these messages cannot
be confused with messages which occur during real
operation.
6.13
Putting the relay into operative mode (ON LINE)
When the relay is fully parametrized it must be set
into ON LlNE mode to enable it to perform its
protection tasks. All settings should be carefully
checked.
After starting in the OFF LlNE mode and selecting
the OPERATING MODE the display will present the
initial disolav.
OPERATING
OFF L I N E
+
Depressing the key will activate the operating
mode menu part and the display will show:
The symbol in the right corner of the lower te.t row is
flashing. Depressing the backspace key will change
the mode from OFF LlNE to ON LlNE and the
display will present:
O P E R A T i NG
ON L I N E
The red MONITOR LED indicator will drop off and
the green ON LlNE LED indicator will illuminate. It is
not possible to change any setting in the ON LlNE
mode.
Depressing any other key instead of the backspace
key will cancel the setting to ON LlNE and the initial
display will appear again.
A R E YOU SURE
and after appro.imately two seconds:
ON L I N E OK ?
BACKSPACE
To set the relay back to OFF LlNE mode this
identical procedure has to be followed again.
I
I
I
I
Operating instructions
MFR 7SJ551
6 4
Annunciations
6.1 4.1
Introduction
After a network fault, annunciations and messages
provide a survey of important fault data and the
function of the relay, and serve for checkina
sequences of funciional steps during testing and
commissioning. Further, they provide information
about the relay itself during normal operation.
The annunciations generated in the relay are
present in various ways:
-
LED indications in the front plate of the relay
(figure 6.1).
I
-
Binary outputs via the connections of the relay.
- Indications in the display on the front plate or on
the screen of a personal computer, via the serial
interface (optional).
-
Transmission via the serial interface to local or
remote control facilities
Most of these annunciations can be relatively freely
allocated to the LED indicators and binary outputs
(see section 6.1 1).
To call up annunciations on the operator panel
scroll to the concerning submenus.
I
I
pq.+
ON L I N E
MEASURED VALUES
lndication of operational measured values
(currents, voltage, thermal reserve, etc.).
COUNTERS
Annunciation for circuit breaker operation statistics,
that is counters for tripping commands and
accumulated short-circuit currents.
ALARMITRIP DATA
Event annunciations for the last three network
faults.
I/ONl+
RUNNING HOURS
MANUFACT.
ON L I N E
DEMAND AMPERE METER
Dynamic and maximum 8 minutes and 15 minutes
averages of the measured currents.
RUNNING HOURS
Actual running hours (since previous start-up) and
total running hours.
MANUFACTURING DATA
Ordering code, serial number and software version.
i
MFR 7SJ551
@
6.14.2
Operating instructions
MEASURED VALUES
The steady state RMS operating values can be
read out any time in the submenu MEASURED
VALUES.
submenu CHANNELS as described in section 6.7.
In the following menu description only values zero
are shown. In practice the actual values appear.
The data are displayed in absolute primary values.
To ensure correct primary values, the rated data
must have been entered to the device in the
Some of the described menu items only appear
when corresponding functions are enabled or
available (if ordered as option).
Operational current values
Depending on the magnitude the current unit is A or
kA.
8
.ooo
I
RMS V A L U E S
.ooo
J,
1-
RMS V A L U E S
.ooo
+
Operational voltage value
Depending on selected circuit type, residual voltage,
line-to-line voltage or phase to earth voltage is
displayed. Depending on the magnitude the voltage
unit is V or kV.
RMS V A L U E S
nnn
Earth fault component for directional earth fault
protection.
Depending on the selected measuring principle
(COSINE or SINE) here the value 1,. cos $ or I,
sin Q is displayed.
Thermal reserve
ON LINE
8-rotor
[%I
For motors the rotor thermal reserve and the stator
thermal reserve are displayed. For non-rotating
objects there is only one thermal reserve buffer,
denominated with "8- t h".
'
MFR 7SJ551
I
Operating instructions
I
][THERMAL
---- -. .-
The
displayed true root mean square current is
.
. .
t-.h. -e hinhest
n
. .lomentary phase current used by the
. .,
\L
-
True RMS current
-
thermal overload function. As this contains all
harmonic components a small noise current will
be displayed even when there is no actual
operation current.
Inverse current
The inverse current is calculated out of the three
phase currents according to the symmetric
components method.
.I.
1
+
TEMP 1
L O C I
TEMPERATURES
TEMP 2 C ° C l
Temperatures
The temperatures are measured by the 2 or 8 RTD
elements and processed in the interface unit
(optional). When these menu lines are recalled, the
interface unit will send the temperature values to the
relay unit. This will take a short moment, in which 4
stars "****"are shown instead of a temperature
value.
TEMPERATURES
TEMP 8 [ O C l
\I/
TEMPERATURES
AMBIENT[OCI
&
m//+ml
Motor status
I
I
-
STOPPED, START or RUNNING
Refer to section 4.8 for a detailed description.
"
MFR 7SJ551
6.14.3
'
Operating instructions
COUNTERS
The submenu COUNTERS provides circui.t breaker
operation statistics. Counter status and stores are
secured against auxiliary voltage failure.
.
m+ml
rn
08-97
4
+
ALARM COUNTER
GENERAL: n=
the
Beginning
last time
of the
the counters
submenuwere
COUNTERS.
reset is displayed.
After that,
The alarm counters show the total number of alarms
since the last reset date, and further the number of
alarms due to phase current faults, earth current
faults and voltage faults.
ALARM COUNTER
EARTH: n=
VOLTAGE: n=
\L
The number of trip commands initiated by 7SJ551
is counted. Additionally the interrupted currents are
accumulated and stored.
To reset the counters the backspace key has to be
used. Resetting counters is possible in ON LINE
mode.
RESET
The symbol in the right corner of the lower text row is
flashing. Depressing the backspace key will set all
counters back to zero. A new COUNTERS RESET
DATE is stored.
Depressing any other key instead of the backspace
key will cancel the reset and the COUNTERS
RESET display will appear again.
6.14.4
ALARM I TRIP DATA
The annunciations which occurred during the last
three networks faults can be read off in the front
panel or via the serial interface. When a further
fault occurs, the data relating to the eldest are
I
erased. These annunciations can be read off in the
submenu ALARMrrRlP DATA. Only fault
annunciations related to available and enabled
functions will appear in this menu.
I
1
8
MFR 7SJ551
Operating instructions
I
I
There are two separate fault data buffers, one for
the last three alarms and one for the last three
trips. The different alarms and trip buffers are
numbered separately.
Example
Alarm number 23 has nothing to do with trip
number 23 (or only by coincidence). In most cases
more alarms than trips occur, so alarm protocol
number 23 will probably concern the same fault as
trip protocol number 15.
To match the alarm protocol and the trip protocol
concerning the same network fault the RTC
ALARM TlME and the RTC TRIP TlME should be
compared.
The submenu ALARM DATA gives an overview of
the status of all enabled protection functions.
Beginning of the menu ALARM/TRIP DATA and of
the submenu ALARM DATA. Display of the most
recent alarm number, designated with In'. Depress
key to recall the two preceding alarm
the
protocols, designated with 'n-1' and 'n-2'.
+
Alarm date and time
Refers to the moment of pick-up of one of the
protection functions.
ALARM C I R C U I T
Alarm circuit
\L
In this menu part the measuring circuits are
indicated via which a fault has been detected.
1.000
\L
OVERTEMPERATU
UNBALANCE
.ooo
4
UNDERCURRENT
LOW S E T O . C .
.ooo
H I G H SET O . C .
I
I
:
LOW S E T O . C .
•
,
MFR 7SJ551
\
Function status and alarm or trip duration time.
In these menu lines all enabled functions and their
states at the moment of pick-up are displayed. The
following three states are possible:
8
---
No alarm. The concerning function did not
detect a fault.
ALM
Alarm. The concerning function had
detected a fault but did not trip. The
displayed time is the time between pick-up
of the function and drop off of the alarm
condition.
TRP
Trip. The concerning function had detected
a fault and tripped. The displayed time is
the time between generation of the trip
signal and drop off of the trip signal.
Be aware that the displayed time is not the reaction
time of the relay, but the total time a
Operating instructions
MFR7SJ551
o p e r a k g instructions
LOCKED ROTOR
function is in ALARM state or the total time a
function is in TRlP state. This means the displayed
time contains the circuit breaker reaction time.
.OOO
ZERO SPEED
.OOO
\L
UNDERVOLTAGE
,000
For the thermal overload protection the tripping
time recording differs. Counting of the TRlP time
starts when the thermal reserve has decreased to
the warning level Ow,,. Counting stops when the
thermal overload function has taken up the TRlP
state and the thermal reserve has increased to the
again.
warning level, , ,8
m:
OVERVOLTAGE
>
OVERVOLTAGE
.ooo
E.T. COMMAND
.ooo
\L
Beginning of the submenu TRlP DATA and display
of the most recent trip number, designated with 'n'.
key to recall the two preceding trip
Depress the
protocols, designated with 'n-1' and 'n-2'.
+
RTC T R I P DATE
08-97
J
Trip date and time
Refers to the moment of trip of one of the
protection functions.
Operational values at the moment of trip
For each recorded operational quantity the value is
displayed at the moment of trip by one of the
protection functions.
Refer to section 6.14.2 for a description of the
operational measurements.
a
i
"
r
MFR 7.9551
Operating instructions
Calculated values of the current components
accordinq to the symmetrical components method.
For 2-phase connection the menu item ' I - T R I P -
:
0 s eq" disappears and an e.tra menu item appears,
namely "UB 1 2 - T R I P".
/11
~ ~ 0 - ~ ~ 1 ~ - r o t o For
r
anooo
[%I
8-TRIP-stator
motors the rotor thermal reserve and the stator
thermal reserve are displayed. For non-rotating
objects only one value is displayed, denominated
by " 6 - T R I P".
.ooo
Temperature values at the moment of trip
.ooo
TEMPERATURE 2
.ooo
J,
TEMPERATURE 8
.ooo
6.14.5
DEMAND AMPERE METER
The submenu DEMAND AMPEREMETER provides
display of
- the dynamic 8 minutes average of the
measured currents
- the maximum 8 minutes average of the
measured currents since the last reset
-
-
the dynamic 15 minutes average of the
measured currents
the maximum 15 minutes average of the
measured currents since the last reset.
Beginning of the submenu DEMAND
AMPEREMETER. After that, the last time the meter
was reset is displayed.
Eight minutes average of the measured currents
This is the calculated average of the three root mean
square phase currents over the last eight minutes.
Eight minutes maximum of the measured currents.
AMMETER
0
&
This is the highest eight minutes average since the
last reset. This allows the user to check correct
dimensioning of network components.
,
G88700-C3527-07-7600
147
I
MFR 7SJ551
Operating instructions
Fifteen minutes average of the measured currents
This is the calculated average of the three root mean
square phase currents over the last fifteen minutes.
"
r
Operating instructions
MFR 7SJ551
Fifteen minutes maximum of the measured currents
This is the highest fifteen minutes average since the
last reset. This allows the user to check correct
dimensioning of network components.
15m-MA CAI
3.
I
~
I
1
AMMETER KESET,
+
A R E YOU S U R E
RESET
COUNTERS ?
BACKSPACE
8
To reset the demand ampererneter the backspace
key has to be used. Resetting the demand
amperemeter is possible in ON LINE mode.
I
RUNNING HOUWS
The submenu RUNNING HOURS provides display
of the actual running hours (since previous startup) of the motor and of the total running hours
since last reset. This menu will only appear when
the DEVICE TYPE is set to ROTATING.
Beginning oi the submenu RUNNING HOURS. After
that, the last time the meter was reset is displayed.
RUNNING HOURS
ACTUAL [ h l
\I,
R U N N I N G HOURS
\I,
I
,
The symbol in the right corner of the lower text row is
flashing. Depressing the backspace key will set the
values back to zero. A new DEMAND AMMETER
RESET DATE is stored.
Depressing any other key instead of the backspace
key will cancel the reset and the DEMAND
AMMETER RESET display will appear again.
6.14.6
I
Actual running hours since previous start-up
The time unit is minutes or hours. The value will be
reset to zero automatically when MFR 7SJ551
detects a new start.
Total running hours since last reset.
The time unit is minutes or hours. The value can only
be set to zero by resetting it in the next menu line.
1
MFR 7SJ551
Operating instructions
El+
R U N N I N G HOURS
RESET RUN
HRS?
ARE Y O U SURE
RESET RUN
HRS? T Y P E
BACKSPACE
To reset the running hours counter the backspace
key has to be used. Resetting the running hours
counter is possible in ON LlNE mode.
I
The symbol in the right corner of the lower text row is
flashing. Depressing the backspace key will set the
values back to zero. A new RUNNING HOURS
RESET DATE is stored.
Depressing any other key instead of the backspace
key will cancel the reset and the RUNNING HOURS
RESET display will appear again.
1
6.14.7
MANUFACTURER DATA
In the submenu MANUFACTURER DATA, ordering
code, serial number and software version can be
read out.
I
In OFF LINE mode the submenu DEFAULT
VALUES will be part of the MANUFACTURER
DATA menu. Refer to section 6.15 for a detailed
description of how to reset all settings to default
values.
Beginning of the submenu MANUFACTURER DATA
Ordering code
I
As an example here the maximum version with
sensitive earth current measurement is shown.
The last character of the ordering code can be A, 8,
C or D, depending on the ordered interface unit. If
the interface is ordered later or if this relay is part of
a batch delivery, this character will be A. In this case,
after mounting the interface unit the displayed last
character of the ordering code will stay " A . This has
no influence on the good operation of the relay.
Serial number
Here the serial number of the relay unit is displayed.
If the relay unit is inserted in an other housing the
serial number of the relay unit and the housing wiil
differ. Refer to this menu read-out serial number in
your correspondence. (This serial number is also
registered on a sticker on the draw-out module.)
I
MFR 7SJ551
Operating instructions
Firmware version relay unit
Behind the firmware version the date of release of
this firmware is shown.
Firmware version interface unit
This menu line will only appear when there is an
interface unit connected. Behind the firmware
version the date of release of this firmware is shown,
together with the ordering type (the last character of
the ordering code: B, C or D).
Self-monitoringannunciation
Normally here "NO ERRORS" can be read. The
following messages are shown when the relay has
an internal failure. (Refer to section 7.3 for a detailed
description.)
HW: AUX. SUPPLY
HW: EZPROM
H W: RAM
HW: REF.VOLTAGE
HW: ROM
HW: TRIP COIL
SW: MLFB
SW: SW ERROR
6.15
I
Resetting all settings to factory settings
MFR provides the possibility to reset a parameters
back to factory settings. Therefore the submenu
DEFAULT VALUES has to be recalled. This
submenu will only be available in OFF LINE mode.
Initialization of the parameter memory has to be
executed always after firmware exchange (EPROM
set).
1
MFR 7SJ551
Operating instructions
pql+
I N I T MEMORY
To initialize the memory the backspace key has to
be used.
A R E YOU SURE
Depressing the backspace key will lead to a new
dialogue line, in which the initialization action has to
be reconfirmed.
I N I T MEMORY
BACKSPACE n
RECONFIRM
The symbol in the right corner of the lower text row is
flashing. Depressing the backspace key will set all
parameters back to initial settings.
A R E Y O U SURE
I N I T MEMORY
BACKSPACE
I
1
Depressing any other key instead of the backspace
key will cancel the initialization and the INIT
MEMORY display will appear again.
While initializing, the display will look as showed on
the left; the lowest line shows a 'running' row of
symbols.
*****
DONE
After approximately 15 seconds the display will
show that it is finished. After pressing a key the
relay will start up again.
After initialization the relay must be parametrized
according to on-site conditions.
The default values are used in the settings
description of the preceding sections.
*
MFR 7SJ551
0
6.16
Testing and commissioning
6.16.1
General
Prerequisite for commissioning is the completion of
the preparation procedures detailed in sections 5
and 6.
/;\ Warning
Hazardous voltages are present in the
electrical equipment during operation.
Non-observance of the safety rules can
result in personal injury or
damage.
Only qualified personnel shall work on
and around this equipment after
becoming thoroughly familiar with all
warnings and safety notices of this
manual as well as with the applicable
safety regulations.
Particular attention must be drawn to the
following:
- The earthing screw of the device must
be connected solidly to the protective
earth conductor before any other
connection is made.
- Hazardous voltages can be present on
all circuits and components connected
to the supply voltage or to the
measuring and test quantities.
- Hazardous voltages can be present in
the device even after disconnection of
the supply voltage (storage
capacitors!).
- The limit values given in the Technical
data (section 3) must not be exceeded
at all, not even during testing and
commissioning.
When testing the unit with a secondary injection test
set, it must be ensured that no other measured
values are connected and that the tripping leads to
the circuit breaker trip-coils have been interrupted.
m
A
DANGER!
i
Operating instructions
Secondary connections of the current
transformers must be short-circuited
before the current leads to the relay are
interrupted!
If a test switch is installed which
automatically short-circuits the current
transformer secondary leads, it is sufficient
to set this switch to the "Test" position. The
short-circuit switch must be checked
beforehand.
It is recommended that the actual setting for the
relay be used for the testing procedure. If these
values are not (yet) available, test the relay with the
factory settings or reasonable alternatives.
In the following description of the test sequence
values will be used that will be stated with each test.
For almost all functional tests a single-phase current
source is sufficient. However, if asymmetrical
currents occur during the test and the unbalance
protection has been selected, it is likely that the
unbalance protection will frequently operate. This is
of no concern because the condition of steady-state
measured values is monitored and, under normal
operating conditions, these are symmetrical: under
short circuit conditions the unbalance protection will
normally not activate a trip command (depending on
the concerning delay timers).
For testing the rotor thermal overload function and
the unbalance function a three phase current source
IS necessary.
NOTE!The accuracy which can be achieved during
testing depends on the accuracy of the testing
equipment. The accuracy values specified in the
Technical data can only be reproduced under the
reference conditions set down in IEC 255 or VDE
0435/ part 303 resp. and with the use of precision
measuring instruments. The tests are therefore to
be iooked upon purely as functional tests.
During all the tests it is important to ensure that the
output relay contact(s) close (during a trip command
activation), that the proper indications appear at the
LED'S and the output relays for remote signalling. If
the 7SJ551 relay is connected to a central memory
device via the serial interface, correct
communication between the relay and the master
station must be checked.
one hundred fifty-one and 00/100
E
I
MFR 7SJ551
i
Operating instructions
Stored indications are not erased automatically with
a new pick-up of the relay or replaced by new
annunciations. For a clear overview the LED
indicators should therefore be reset after each test.
Reset at least once by both of the possible methods:
the reset key RI on the front plate or via the remote
reset binary input (if this function has been selected).
All described tests are done with a setting for a
ROTATING device, because than all the protection
functions are available.
1
6.16.2
Parameter
L1
L2
L3
In
CT RATIOph
e
Uin
U select
un
VT-RATIO
I
i
// Caution
For the normal current circuits, test currents
larger than 6 times I, and for the I, sensitive
current circuit, test currents larger than 4
times In may overload and damage the relay
current input channels if applied
continuously. Observe a cooling period if
necessary.
Move to the menu part MEASURED VALUES (ON
LINE) and select the menu part RMS-values on the
display.
Setting
CHANNELS
[en
0
Testing the measurement of operational values
Parametrize the relay according to the following
settings.
CT RATIO,
For a NON-ROTATING device the described
methods of testing are equally valid, in some cases
however they will be simpler.
ENABLED
ENABLED
ENABLED
I
150
ENABLED
I
On injecting the nominal value In = 1 A alternately in
the different 1 A phase and earth leads, the correct
RMS value of 150 A must be calculated and shown
on the display.
On administering the nominal secondary value of
110 V to the 110 V lead, the correct RMS value of
6.6 kV must be calculated and shown on the display.
150
ENABLED
U,, or Uph or Uo
110
60
2
one hundred fifty-two and 00/100
G88700-C3527-07-7600
MFR 7SJ551
6.16.3
Operating instructions
Testing the motor status
Parametrize the relay according to the following
settings.
Setting
Parameter
DEVICE DATA
Iflc
DEVICE TYPE
lno load
CHANNELS
L1
L2
L3
6.16.4
1.oo . I,
ROTAT ING
.I00 A
ENABLED
, ENABLED
ENABLED
Move to the menu part MEASURED VALUES (ON
LINE) and select the menu part MOTOR STATUS
on the display. With no current injected the display
shows: 'STOPPED'.
MFR 7SJ551 derives the motor status out of the
level,,I = 1.I 25 . I, and the level ,I ol ,d.
On injecting the value I = 1. I 2 A in one of the 1 A
leads, the display should still show: 'STOPPED'.
Raise the injected current over 1.I25 A. The display
should show: 'START'. Decrease the current to In,
(1.OO A). The relay should show: 'RUNNING'.
Decrease the current under
InOload.
The display should show 'STOPPED'.
Testing the rotor thermal overload protection
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
Ific
DEVICE TYPE
Istart
tsart
kin"
nwarm
bold
CHANNELS
L1
L2
L3
1,
PROTECTIONS
THERMAL OVERLOAD
7.1
,stat
Pweight
cstop,mt
START INHIBIT
EMERGENCY RESTART
( Setting
1.oo . ,I
ROTATING
4.00 . I,
10.0 s
5.00
2
3
For testing the rotor thermal overload function a
three-phase test case is required. Disable all other
protection functions. Set the stator thermal overload
to a very large time constant to be sure it will not trip
earlier than the rotor thermal overload protection.
Marshall the thermal overload protection to one of
the output relays.
For test-purposes it is recommended to marshall the
emergency restart function to one of the inputs, in
order to be able to reset the rotor thermal reserve
manually back to 100%.
ENABLED
ENABLED
ENABLED
ENABLED
999 min
1.oo
2.00
ENABLED
ENABLED
Checking the steady state rotor thermal reserve
Move to the menu part MEASURED VALUES (ON LINE) and select the menu part THERMAL RESERVE
ROTOR on the display. Initially the displayed value will be 100% (Ipreload.rOtor
= 0).
Inject a symmetric three-phase current I = 1.20 A. The rotor thermal reserve will decrease. The steady state value
can be calculated out of the formulas for the rotor thermal overload protection:
G88700-C3527-07-7600
one hundred fifty-three and 00/100
*
I
Operating instructions
MFR 7SJ551
Trotor
. f start
-"cold
=
In(l
-
-3'10'0
- 3 . I-OO)"
'Kc -
-r;o;"
1
=144,5s
(4.00)'
start
First the equivalent heating current is calculated. For a symmetric current only a normal component will result:
= liorm+ kin, . ltv= liorm+ 5 . ifnv= 1' = (120)~= 1.44
Substituting this value in the basic iterative equation gives:
steady state value of the thermal rotor current will be the injected current:
The formula for the rotor thermal reserve is:
eth,rotor (t) =
k?otor
2
- lth,rotor (t) . O o S
-3
0 G o t o r .CI:I
~?lc
-1 ,r o t o r
oOoo
,
3.0 0
The steady state thermal reserve will be:
Check if the displayed value for the rotor thermal reserve decreases to 52.0%.
Checking the trip time (cold condition)
Check the trip time with cold condition (8th,rotor= 100%). Inject a symmetric three-phase overload current I = 3.00 A
(step function). The equivalent heating current will be 3.00 A, as there is no inverse component.
The trip time follows out of the formula:
After trip the thermal reserve can be set back to 100% by energizing the emergency restart input.
Checking the trip time (warm condition)
Now check the trip time with a preload of 80%. The preload current Ipreload,rotor
can be calculated out of the
From:
preload percentage 6preload,rolor.
it follows:
epreload,rotor
- erel load, rotor
-
k:otor
'
0°%
.I?IC
Ipreload,rotor = krotor . l f l c
epreload, rotor
'
p = -10O0h
&.1.00~=1.55
A
Applying the preload current I = 1.55 A for a long time will eventually result in a steady state rotor thermal reserve
of 20%. For test purposes a higher current can be injected until the display value is 20%.
one hundred fifty-four and 00/100
G88700-C3527-07-7600
MFR 7SJ551
Operating instructions
Starting from 20 % rotor thermal reserve, raise the symmetric three-phase current stepwise to I = 3.00 A. The trip
time will be:
Checking the trip time characteristic
lnject the following symmetric three phase injecting currents and check the tripping times. Be sure the thermal
reserve is back at the initial value before each time measurement.
'1
(s)
preload = 0
376.1
94.5
58.6
40.6
30.0
23.2
I (A)
ftrip
1.80
2.50
3.00
3.50
4.00
4.50
ttrip (s)
preload = 80%
180.6
24.4
13.7
9.0
6.5
4.9
Checking the trip time with asymmetrical current
Start with cold condition (Bth,,,or = 100%). Inject a asymmetric overload current by injecting only two phases with
lphase
= -' 3.00 = 2.60 A (step function). This simulates the situation in which one phase of a symmetric three
2
phase current of 3.00 A is interrupted. The normal and inverse components are 1.50 A then.
First the equivalent heating current is calculated.
The trip time follows out of the formula:
t trip = Trotor ' In
~Eeating- ~ ~ r e i o arotor
d.
Ceating
1
- kktor 1';c
=14'4.5 .In
1 3.5
-(o)~
13.5 - 3 . (1.00)~
= 36.3 s
Checking the rotor cooling down time
lnject a symmetric three phase current of 3.00 A for 26.3 s. The stator thermal reserve will decrease to 50%.
Then decrease the current to 1.22 A. The steady state stator thermal reserve will be 50% then:
Now take away the current. The motor status will change to 'STOPPED', which means the rotor cooling down
factor will be incorporated. Check if the time to cool down to 75% is approximately 200 s:
tcoal down
2
l?h,rotor(t cool down = Ipreload,rotor '
G88700-C3527-07-7600
'=,~~.rot '%tor
--
cool down
= 1.50 . e 2.00.'44.5 = 0.75
t cool
= 200.3 s
one hundred fifty-five and 00/100
MFR 7SJ551
6.16.5
Operating instructions
Testing the stator thermal overload protection
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
lflc
DEVICE TYPE
b a t
CHANNELS
L1
L2
L3
In
PROTECTIONS
THERMAL OVERLOAD
71,stat
%,stat
PweighI
Cstop,stat
am
START INHIBIT
EMERGENCY RESTART
Setting
1.oo . I,
ROTATING
1.10
For testing the stator thermal overload function a
single-phase test case is sufficient. Disable all other
protection functions. Marshall the thermal overload
protection to one of the output relays.
For test-purposes it is recommended to marshal1the
emergency restart function to one of the inputs, in
order to be able to reset the stator thermal reserve
manually back to 100%.
ENABLED
ENABLED
ENABLED
I
ENABLED
100 s
200 s
500
2.00
25%
ENABLED
ENABLED
Checking fhe sfeady sfate stator thermal reserve
Move to the menu part MEASURED VALUES (ON LINE) and select the menu part THERMAL RESERVE
STATOR on the display. Initially the displayed value will be 100% (Ipreload,stator
= 0).
Inject a current I = 0.80 A in one of the phase leads. The stator thermal reserve will decrease. The steady state
value can be calculated out of the formulas for the stator thermal overload protection. The basic iterative equation
Fort = 03 the steady state value of the thermal stator current will be the injected current:
The formula for the stator thermal reserve is:
The steady state thermal reserve will be:
Check if the displayed value for the stator thermal reserve decreases to 47.1%.
one hundred fifty-six and 001100
G88700-C3527-07-7600
"
I
Operating instructions
MFR 7SJ551
Checking the trip fime (cold condition)
Check the trip time with cold condition (Bth,sta,or
= 100%). Inject an overload current I = 1.50A (step function).
I
The trip time follows out of the basic iterative equation for the thermal stator current /th,stat- The trip condition is:
By filling in different trip times the corresponding injecting current can be found. In this case the trip time will be
108 s.
After trip the thermal reserve can be set back to 100% by energizing the emergency restart input.
Checking the trip time (warm condition)
Now check the trip time with a preload of 80%. The preload current Ipreioad,stator
can be calculated out of the
preload percentage 8prejoad,statar.
From:
Efth,stator(t =
kEtat
m,
=
. ~ f l c- ~Ereload,stator
kgtat
. i00%
.l?Ic
it follows:
epreload,stator
- Itreload,stator
kztat . ~:,c
'
Ipreload,stator = kstat
00%
,/
ro ; ; ; ; l ; r "
'
lflc
'
= 1.1 .1.00.
= 0.98 A
Applying the preload current I = 0.98 A for a long time will eventually result in a steady state stator thermal reserve
of 20%. For test purposes a higher current can be injected until the display value is 20%.
Starting from 20 Oh stator thermal reserve, raise the current stepwise to I = 1.50A. The trip time will be 29 s.
Checking the trip time characteristic
lnject the following currents and check the tripping times. Be sure the thermal reserve is back at the initial value
before each time measurement.
I
Check via the MEASURED VALUES menu if the PRE-ALARM and ALARM LED indicators light up when the
stator thermal reserve reaches 25%.
(s)
1 (A)
trip
1.15
1.25
1.50
1.75
2.50
3.00
381.9
21 7.3
107.7
69.0
29.0
19.4
preload = 0
ttrip (s)
preload = 80%
167.2
73.6
29.0
17.0
6.5
4.2
Checking the stator cooling down time
lnject a current of 2.00A for 22.1 s. The stator thermal reserve will decrease to 50%. Then decrease the
current to 0.78A. The steady state stator thermal reserve will be 50% then:
)
G88700-C3527-07-7600
one hundred fifty-seven and 0011 00
MFR 7SJ551
Operating instructions
Now take away the current. The motor status will change to 'STOPPED', which means the stator cooling down
factor will be incorporated. Check if the time to cool down to 75% is approximately 193 s:
tcwldown
]%,stat(t coal
2
dew" = IIpreioad,stator
0.500 . e
--boo1down
2.00~100
Cstop,stat
.?l.stat + (1 -
'
+ 0.500 . e
one hundred fifty-eight and 001100
= 0.3025
tcool down
,
weight
).
Cstop.sta1 '72.stat
1
=
t cool down = 192.5
s
G88700-C3527-07-7600
Operating instructions
MFR 7SJ551
*
6.16.6
Testing the thermal overload protection of non-rotating objects
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
Iflc
DEVICE TYPE
k
CHANNELS
L1
L2
L3
In
1 Setting
1.oo . I"
NON-ROTATING
1.I0
1
For testing the thermal overload function a singlephase test case is sufficient. Disable all other
protection functions. Marshall the thermal overload
protection to one of the output relays.
ENABLED
ENABLED
ENABLED
1
ENABLED
PHASE
I00 s
200 s
,500
ENABLED
2.00
25%
Checking the steady state thermal reserve
Move to the menu part MEASURED VALUES (ON LINE) and select the menu part THERMAL RESERVE on the
display. Initially the displayed value will be 100% (Ipreioad
= 0).
Inject a current I = 0.80 A in one of the phase leads. The thermal reserve will decrease. The steady state value
can be calculated out of the formulas for the thermal overload protection. The basic iterative equation is:
Fort = = the steady state value of the thermal current will be the injected current:
2
Ith(t
= m) = 0.64
The formula for the thermal reserve is:
The steady state thermal reserve will be:
Check if the displayed value for the thermal reserve decreases to 47.1%.
G88700-C3527-07-7600
one hundred fifty-nine and 001100
i
MFR7SJ551
-Operatinginstructions
Checking the trip time (cold condition)
Check the trip time with cold condition (eth= 100%)- Inject an overload current I = 1.50 A (step function).
1
The trip time follows out of the basic iterative equation for the thermal current It. The trip condition is:
By filling in different trip times the corresponding injecting current can be found. In this case the trip time will be
108 s.
Checking the trip time (warm condition)
Now check the trip time with a preload of 80%. The preload current
percentage
.,1,,8
From:
1
can be calculated out of the preload
Applying the preload current I = 0.98 A for a long time will eventually result in a steady state thermal reserve of
20%. For test purposes a higher current can be injected until the display value is 20%.
1
Starting from 20 % thermal reserve, raise the current stepwise to I = 1.50 A. The trip time will be 29 s.
i
Checking the trip time characteristic
lnject the following currents and check the tripping times. Be sure the thermal reserve is back at the initial value
before each time measurement.
Check via the MEASURED VALUES menu if the PRE-ALARM and ALARM LED indicators light up when the
thermal reserve reaches 25%.
1
,
1 (A)
ttnp (s)
ttnp (s)
1.15
1.25
1.50
1.75
2.50
3.00
381.9
217.3
107.7
69.0
29.0
19.4
167.2
73.6
29.0
17.0
6.5
4.2
preload = 0
preload = 80%
Checking the adjustment factor
Inject a current of 2.00 A for 22.1 s. The thermal reserve will decrease to 50%. Then decrease the current to
0.78 A. The steady state thermal reserve will be 5O0/0then:
one hundred sixty and 00/100
G88700-C3527-07-7600
MFR 7SJ551
Operating instructions
Now energize the binary tadjinput. As the thermal reserve is in steady state this will have no influence. Now take
away the current. Check if the time to cool down to 75% is approximately 193 s:
tcoal down
--tcooi down
f h (t cool down)
2
= lpreioad .
0.500 . e
6.16.7
--tcooldown
2.oo.lao
cadi .'=I
+
- Pweight )
- 1
'
tcoal down
+ 0.500 . e
*.00.2°0
= 0.3025
tcooldown
= 192.5 s
Testing the ambient temperature biasing
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
Iflc
DEVICE TYPE
k
PROTECTIONS
THERMAL OVERLOAD
AMBIENT TEMPERATURE
Tm,
Tmin
INPUT SENSOR
Setting
1.oo . I,
NON-ROTATING
1.10
Disable all other protection functions.
Connect an RTD sensor simulator to input sensor
connection 1. The thermal protection will take into
account the simulated temperature by the RTD
simulator in determining the thermal reserve. Refer
to section 4.3 for a detailed description.
ENABLED
ENABLED
120 "C
40 "C
1
--
Simulate a temperature above 120 "C.Check if the thermal reserve is 0%.
Make sure the input currents are zero and there is no preload. Simulate a temperature of 20 "C.
'ambient
- Tarnbient - Tmin . k2 . 1Ec =
Tmax -Trnin
- 40 . (1.1 C))2 . (1.00)~= -0,3025
120 - 4 0
Check if the thermal reserve in cold condition is 125%.
6.16.8
Testing the start inhibit
G88700-C3527-07-7600
one hundred sixty-one and 001100
Operating instructions
MFR 7SJ551
Parametrize.the relay according to the following
settings.
Parameter
DEVICE DATA
Iflc
DEVICE TYPE
Istart
tstart
nwarrn
n ~ ~ l d
CHANNELS
L1
L2
L3
1"
PROTECTlONS
THERMAL OVERLOAD
Setting
1 .oo . In
ROTAT ING
4.00 . In
10.0 s
2
3
ENABLED
ENABLED
ENABLED
1
%,stat
Pweig~
START INHIBIT
tinh
ENABLED
999 min
200 s
1.OO
ENABLED
5s
@stator
50.0%
71.stat
Marshall one of the output relays to the protection
function start inhibit. Disable all other protection
functions.
Checking the rotor start inhibit
For testing the rotor thermal overload function a three-phase test case is required.
1
The rotor start inhibit level is calculated out of:
Inject the relay with a three-phase current of 3.00 A. Take away the current when the rotor thermal reserve is
smaller than 35.7%. Check if the start inhibit output relay closes. After cooling off again to a thermal reserve of
35.7% the delay time of 5 seconds starts. Check this delay time.
Checking the stator start inhibit
Now change the stator thermal overload settings to:
Parameter
71,stat
%,stat
Pweiaht
1
Setting
I00 s
200 S
.500
For testing the stator start inhibit a single-phase test case is sufficient.
I
Inject the relay with a current of 2.00 A. Take away the current when the stator thermal reserve is smaller than
50.0%. Check if the start inhibit output relay closes. After cooling off again to a thermal reserve of 50.0% the delay
time of 5 seconds starts, after which the start inhibit output is released again. Check this delay time.
6.1 6.9
Testing the emergency restart
I
Parametrize the relay according to the settings of the
preceding section 6.1 6.8.
one hundred sixty-two and 00/100
Enable the EMERGENCY RESTART function.
Marshall the EMERGENCY RESTART function to
one of the binary inputs.
G88700-C3527-07-7600
MFR 7SJ551
Operating instructions
Inject a current of 2.00 A and take away the current
when the stator thermal reserve is smaller than
50%.
6.16.10
Energize the binary emergency restart input. Check
if the rotor thermal reserve and the stator thermal
reserve are set back to 100%.
Testing the 6velltemperature protection
Parametrize the relay according to the following
settings.
Parameter
PROTECTIONS
OVERTEMPERATURE
ALARM 1
TRIP 1
ALARM 2
TRIP 3
Setting
ALARM 8
TRIP 8
ENABLED
70 "C
100 "C
70 "C
I 0 0 "C
1
70 "C
100 "C
6.16.1 6
Testing the undercurred78 protection
i
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
lflc
DEVICE TYPE
lno load
CHANNELS
L1
L2
L3
In
PROTECTIONS
UNDERCURRENT
fbypass
I<
t I<
Setting
1.OO . In
ROTATING
0.1 A
ENABLED
ENABLED
ENABLED
I
ENABLED
5.00 s
.500
3.00 s
Marshall the OVERTEMPERATURE ALARM
condition to one of the output relays. Marshall the
OVERTEMPERATURETRlP condition to one of the
other output relays. Disable all other protection
functions.
The tested sensor must be disconnected and
replaced by a RTD sensor simulator.
Check the performance of the overtemperature
protection by simulating different temperature
vatues. Check the alarm and trip level.
UNDERCURRENT TRIP condition to one of the
other output relays. Disable all other protection
functions. For testing the undercurrent protection a
single-phase test case is sufficient.
Checking the undercurrent protection for motors
When the motor status is 'STOPPED' or 'START'
the undercurrent protection is inactive. Inject a
current higher than 1.I25A to change the motor
status from 'STOPPED' to 'START'. Now lower the
current to 1.OO A. The motor status will change to
'RUNNING' and the bypass timer will start. After 5 s
the undercurrent protection will be active.
Check the performance of the undercurrent
protection by injecting different current values.
Check the pick-up level and the delay time. Do not
lower the current under 0.1 00 A, as the motor status
will change to 'STOPPED' then.
Marshall the UNDERCURRENT ALARM condition to
one of the output relays. Marshall the
Checking the undercurrent protection for nonrotating objects
Change the device type to NON-ROTATING. After
changing the operating mode to ON LINE the relay
will pick-up. After injection of a current higher than
0.500 A the pick-up condition will vanish and the
LED indicators can be reset.
G88700-C3527-07-7600
one hundred sixty-three and 001100
MFR 7SJ551
Operating instructions
Check the performance of the undercurrent
protection by injecting different current values.
1
Check the pick-up level and the delay time.
Testing the low set overcurrent protection
6.16.12
I
Parametrize the relay according to the following
settings.
Parameter
CHANNELS
L1
L2
L3
1"
e
,I
6.16.12.1
Setting
ENABLED
ENABLED
ENABLED
1
ENABLED
1
Marshall the LOW SET OVERCURRENT START L>
condition to (m e of the output relays. Marshall the
LOW SET 01VERCURRENT TRlP L> condition to a
second outpiut relay. Marshall the LOW SET
OVERCURFlENT START e> condition to a third
output relay. Marshall the LOW SET
OVERCURFIENT TRlP e> condition to a fourth
output relay. Disable all other protection functions.
For testing ttl e low set overcurrent protection a
single-phase! test case is sufficient.
Testing the definite time overcurrent protection
Parametrize the low set overcurrent protection
according to the following settings.
Parameter
PROTECTIONS
LOW SET OVERCURRENT
PHASE
CHARACTERlSTiC
I>
tl>
EARTH
CHARACTERISTIC
1
2
tl2
Setting
ENABLED
DEFINITE
1.50 . I,
5.00 s
ENABLED
DEFINITE
,500 ,,I
5.00 s
For test currents below 6 x ,1 (4 x I, for sensitive
earth current input) , slowly increase the test
current over one phase and earth until the
protection picks up. For test currents above 6 x I,
(4 x I, for sensitive earth current input)
measurement shall be performed dynamically.
Inject a test current of 1.OO x I, via one phase and
the earth path. Check if the START e> output picks
up and if the TRlP e> output closes after expiry of
the delay time.
Inject a test current of 2.00 x I, via one phase and
the earth path. Check if the START L>
1
one hundred sixty-four and 00/100
G88700-C3527-07-7600
Operating instructions
MFR 7SJ551
@
output picks up and if the TRlP b output closes
after expiry of the delay time.
Reset occurs at approximately 95% of the pick-up
value.
6.16.1 2.2
Be aware that the parametrized times are pure
delay times; operating times of the measurement
functions are not included.
Testing the inverse time overcurrent protection
Parametrize the low set overcurrent protection
according to the following settings.
Parameter
PHASE
CHARACTERISTIC
IP
,t
EARTH
CHARACTERISTIC
lep
teo
Setting
ENABLED
NORMAL INVERSE
1.50 . I,
1.oo
ENABLED
NORMAL INVERSE
.500 . Ien
1.OO
For test currents below 6 x ,1 (4 x I, for sensitive
earth current input) , slowly increase the test
current over one phase and earth until the
6.16.12.3
1
protection picks up. For test currents above 6 x I,
(4 x I, for sensitive earth current input)
measurement shall be performed dynamically.
lnject a test current of 1.OO x I, via one phase and
the earth path. Check if the START e> output picks
up and if the TRlP e> output closes after expiry of a
delay time of 10.0 s. The expected delay times can
be calculated from the formula given in the
technical data.
lnject a test current of 2.00 x I, via one phase and
the earth path. Check if the START L> output picks
up and if the TRlP L> output closes after expiry of a
delay time of 10.0 s.
Testing the custom curve overcurrent protection
I
Parametrize the [ow set overcurrent protection
according to the following settings.
Parameter
PHASE
CHARACTERISTIC
# OF POINTS
11
t 11
I
115
t11s
EARTH
CHARACTERISTIC
It31
tlel
I
IBIS
Setting
ENABLED
CUSTOM
15
1.50 . In
100 s
I
6.00 . In
SO0 s
ENABLED
CUSTOM
0.50 . Ien
100 s
I
6.00 . Ien
Choose convenient current-time points for the
phase and earth custom curves.
For test currents below 6 x I, (4 x I, for sensitive
earth current input) , slowly increase the test
current over one phase and earth until the
protection picks up. For test currents above 6 x I,
(4 x I, for sensitive earth current input)
measurement shall be performed dynamically.
Inject different test currents via one phase and the
earth path. Check if the START e> output picks up
and if the TRlP e> output closes after expiry of the
corresponding delay times. Check if the START L>
output picks up and if the TRlP L> output closes
after expiry of the corresponding delay times.
I
G88700-C3527-07-7600
one hundred sixty-five and 001100
Operating instructions
MFR7SJ551
6.1 6.13
Parametrize the relay according to the following
settings.
Parameter
CHANNELS
L1
L2
Ien
PROTECTIONS
HlGH SET OVERCURRENT
PHASE
ENABLED
L3
1,
e
I>>
2.00
.500s
tl>>
EARTH
12>
ENABLED
1 .oo .,,I
2.50 s
Marshall the HlGH SET OVERCURRENT START
L>> condition to one of the output relays. Marshall
the HIGHHSET OVERCURRENT TRlP
L>> condition to a second output relay. Marshall the
HlGH SET OVERCURRENT START e>> condition
to a third output relay. Marshall the HlGH SET
OVERCURRENT TRlP e>> condition to a fourth
For test currents below 6 x ,1 (4 x I, for sensitive
earth current input) , slowly increase the test
current over one phase and earth until the
protection picks up. For test currents above 6 x I,
(4 x I, for sensitive earth current input)
measurement shall be performed dynamically.
Inject a test current of 1.50x ,I via one phase and
the earth path. Check if the START e> output picks
up and if the TRlP e> output closes after expiry of
the delay time.
Inject a test current of 3.00x I, via one phase and
the earth path. Check if the START L> output picks
up and if the TRlP L> output closes after expiry of
the delay time.
Reset occurs at approximately 950h of the pick-up
value.
Be aware that the parametrized times are pure
delay times; operating times of the measurement
functions are not included.
Testing the unbalance protection
Parametrize the relay according to the following
settings.
best results are achieved with a three-phase test
case.
Parameter
DEVICE DATA
Iflc
DEVICE TYPE
Checking the unbalance protection for motors
Inject a current higher than 1.I25 A to change the
motor status from 'STOPPED' to 'START1.The
bypass timer starts. Now lower the current to 1.OOA.
The motor status will change to 'RUNNING'. During
the bypass time the unbalance protection is inactive.
Af-ter 5 s the unbalance protection will be active.
11-10load
CHANNELS
L1
L2
L3
,1
PROTECTIONS
UNBALANCE
fbypass
12
Setting
1 .oo. I,
ROTATlNG
0.1 A
ENABLED
ENABLED
ENABLED
1
ENABLED
1.oo s
.200
.200
Marshall the UNBALANCE ALARM condition to one
of the output relays. Marshall the UNBALANCE TRlP
condition to one of the other output relays. Disable all
other protection functions. For testing the unbalance
protection a single-phase test case is sufficient, but
1
output relay. Disable all other protection functions.
For testing the high set overcurrent protection a
single-phase test case is sufficient.
Setting
ENABLED
ENABLED
ENABLED
1
ENABLED
1
6.1 6.1 4
*
Testing the high set overcurrent protection
one hundred sixty-six and 0011 00
'I
Check the performance of the unbalance protection
by injecting different asymmetric currents. Check the
pick-up level. Do not lower the current under 0.100
A, as the motor status will change to 'STOPPED'
then.
Be aware that the unbalance protection function
calculates the delay time out of absolute values and
not out of relative values.
Example 1
lap= 0.2x I,. The injected current is I .OO x I,. The
function picks up with 20% asymmetry.
G88700-C3527-07-7600
0
?
~
MFR 7SJ551
Operating instructions
Example 2
Izp= 0.2 x I,. The injected current is 2.00 x In. The
function picks up with 10% asymmetry.
A convenient test is injecting 1.00 A in one phase.
The unbalance current will be 0.33 A then, which
leads to a trip delay time (extremely inverse) of 9.0 s.
phase current instead of with Izp.Check this pick-up
behaviour.
Checking the unbalance protection for non-rotating
objects
Change the device type to NON-ROTATING.The
bypass time and the motor status dependent
behaviour do not apply. All further tests and
examples are valid.
If the motor status is 'START' the unbalance
protection picks up with one third of the largest
6.16.15
Testing the Pocked rotor protection
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
Iilc
DEVICE TYPE
!no load
Istart
CHANNELS
L1
L2
L3
1"
PROTECTIONS
LOCKED ROTOR
4r
G88700-C3527-07-7600
Setting
1.oo . I"
ROTATING
0.1 A
4.00 . I,
ENABLED
ENABLED
ENABLED
1
Marshall the LOCKED ROTOR condition to one of
the output relays. Disable all other protection
functions. For testing the locked rotor protection a
single-phase test case is sufficient.
The locked rotor protection is only active for motor
status 'START'. Check the performance of the
locked rotor protection by injecting different current
values higher than 1.1 25 A. Check the delay times.
A convenient injecting current is the start current of
4.00 A. The locked rotor protection should trip in the
locked rotor time of 5.00 s then.
ENABLED
5.00 s
one hundred sixty-seven and 00/100
MFR 7SJ551
6.1 6.16
Operating instructions
Testing the zero speed protection
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
Iflc
DEVICE TYPE
lno load
halt
CHANNELS
L1
L2
L3
In
PROTECTIONS
ZERO SPEED
6.16.6 7
Setting
1.oo . I,
ROTATING
0.1 A
4.00 - 1,
ENABLED
ENABLED
ENABLED
I
ENABLED
Parameter
CHANNELS
L1
L2
e
len
U,n
un
PROTECTIONS
LOW SET OVERCURRENT
EARTH
CHARACTERISTIC
I?
ti+
DIRECTIONAL
EARTHFAULT
CONTROL
turn
Id
> ' +I
@e
81
s,
83
110.0 s
Marshall the ZERO SPEED ALARM condition to one
of the output relays. Marshall the ZERO SPEED
TRIP condition to one of the other output relays.
Marshall the ZERO SPEED function to one of the
binary inputs. Disable all other protection functions.
For testing the ZERO SPEED protection a singlephase test case is sufficient.
1
The ZERO SPEED protection is only active for motor
status 'START'. Check the performance of the
ZERO SPEED protection by injecting a current value
of 4.00 A. Energizing the binary zero speed input will
cause the zero speed function to pick up. If the
binary input stays energized for 10.0 s the zero
speed function will trip. Check this behaviour.
Testing the directional earth fault protection
Parametrize the relay according to the following
settings.
Ustn
1 ZERO
Setting
ENABLED
ENABLED
ENABLED
I
ENABLED
I00 v
ENABLED
DEFINITE
.500 . Ien
5.00 s
ENABLED
COSINE
0.1 . U,
8.5 s
FORWARD
FORWARD
0"
0"
0"
0"
Marshall the LOW SET OVERCURRENT START $>
condition to one of the output relays. Marshall the
LOW SET OVERCURRENT TRIP $> condition to a
second output relay. Marshall the HIGH SET
OVERCURRENT START I$>> condition to a third
one hundred sixty-eight and 00/100
output relay. Marshall the HIGH SET
OVERCURRENT TRIP $>> condition to a fourth
output relay. Marshall the EARTH CURRENT
DIRECTION FORWARD condition to a fifth output
relay. Marshall the EARTH CURRENT DIRECTION
BACKWARD condition to a sixth output relay.
Disable all other protection functions. For testing the
directional earth fault protection a single-phase test
case is sufficient.
The directionai earth fault protection is tested in a
similar way as the low set earth overcurrent time
protection (section 6.16.12). But the following must
be observed.
The test current is injected on the sensitive earth
current input. Otherwise this function cannot operate.
This input is specially designed for highly sensitive
measurement. Thus, restricted threshold values up
to 1.4 A are available only.
The voltage which is needed for directional
determination is applied to the voltage input (open
delta voltage).
For directional determination the direction indicator
outputs can be useful. For any voltage and earth
current one of these two outputs will close, indicating
the forward or backward direction. Be aware that
these direction indicator outputs are not the alarm or
trip output!
Testing of the earth fault protection for non-earthed
networks is not completely possible with
conventional test sets, since the simulation of an
G88700-C3527-07-7600
MFR 7SJ551
!
Operating instructions
earth fault requires a complete displacement of the
voltage triangle. The correct relationship and polarity
of the measuring transformer connections, essential
6.16.18
for proper earth fault detection, can only be tested
when primary load current is available during
commissioning.
Testing the undervoBtage protection
Parametrize the relay according to the following
settings.
Parameter
CHANNELS
Setting
Ll
un
ENABLED
ENABLED
ENABLED
10ov
UNDERVOLTAGE
U<
t U<
ENABLED
250 . U,
5.00 s
L2
U,n
PROTECTIONS
6.16.1 9
Marshall the UNDERVOLTAGE ALARM condition to
one of the output relays. Marshall the
UNDERVOLTAGE TRlP condition to one of the
other output relays. Disable all other protection
functions. For testing the undervoltage protection a
single-phase test case is sufficient.
After changing the operating mode to ON LINE the
relay will pick-up. After applying a voltage higher
than 25.0 V the pick-up condition will vanish and the
LED indicators can be reset.
Check the performance of the undervoltage
protection by applying different voltage values.
Check the pick-up level and the delay time.
Testing the overvoltage protection
Parametrize the relay according to the following
settings.
Parameter
Setting
CHANNELS
L1
L2
U,n
U"
ENABLED
ENABLED
ENABLED
I00 v
Marshall the OVERVOLTAGE ALARM U> condition
to one of the output relays. Marshall the
OVERVOLTAGE TRlP U> condition to a second
output relay. Marshall the OVERVOLTAGE ALARM
U>> condition to a third output relay. Marshall the
OVERVOLTAGE TRlP U>> condition to a fourth
output relay. Disable all other protection functions.
For testing the overvoltage protection a single-phase
test case is sufficient.
PROTECTIONS
OVERVOLTAGE
U>
t U>
u>>
t U>>
G88700-C3527-07-7600
ENABLED
.750 . U,
5.00 s
1.oo . U,
1.oo s
Check the performance of the overvoltage protection
by applying different voltage values. Check the pickup levels and the delay times.
one hundred sixty-nine and 001100
1
l
MFR 7SJ551
6.1 6.20
Operating instructions
Testing the breaker failure protection
Parametrize the relay according to the following
settings.
Parameter
CHANNELS
L1
L2
L3
In
PROTECTlONS
LOW SET OVERCURRENT
PHASE
CHARACTERISTIC
I>
tl>
BREAKER FAILURE
PROTECTION
EXTERN
Ibf
tbf
Setting
ENABLED
ENABLED
ENABLED
I
ENABLED
DEFINITE
1.so . In
5.00 s
ENABLED
DISABLED
.500 . In
10.0 S
BREAKER FAILURE PROTECTION condition to
one of the other output relays. Disable all other
protection functions. For testing the breaker failure
protection a single-phase test case is sufficient.
Checking the internal mode
lnject a current of 2.00 A. The low set overcurrent
protection will pick up. After 5.00 s the low set
overcurrent protection trips. Make sure, however,
that the current stays higher than 0.500 A. Check
whether the breaker failure protection output closes
after 10.0 s.
Checking the external mode
Marshall the breaker failure protection function to
one of the binary inputs. Enable the external mode of
the breaker failure protection function.
.
.
lnject a current of 1.OO A. Energize the breaker
failure protection input. Check if the breaker failure
protection output closes after 10.0 s.
Marshall the LOW SET OVERCURRENT TRlP
condition to one of the output relays. Marshall the
6.16.21
Testing the curve switch
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
lflc
DEVICE TYPE
lno load
CHANNELS
L1
L2
L3
In
PROTECTIONS
CURVE SWITCH
LOW SET OVERCURRENT
PHASE
CURVE 1
CHARACTERISTIC
1>1
tl>,
CURVE 2
CHARACTERISTIC
1>2
tI>*
Setting
LOW SET OVERCURRENT TRIP b condition to a
second output relay. Disable all other protection
functions. For testing the curve switch a singlephase test case is sufficient.
1.oo . In
ROTATING
0.1 A
Checking the continuous mode
Parametrize the curve switch function according to
the following settings.
ENABLED
ENABLED
ENABLED
1
Parameter
CURVE SWITCH
MODE
ENABLED
ENABLED
DEFINITE
1.50 . I,
5.00 s
DEFINITE
3.00 . In
0.50 s
Marshall the LOW SET OVERCURRENT START L>
condition to one of the output relays. Marshall the
one hundred seventy and 001100
Setting
ENABLED
CONTINUOUS
Marshall the curve switch function to one of the
binary inputs.
lnject a test current of 2.00 x I, via one phase lead.
Check if the START L> output picks up and if the
TRlP L> output closes after expiry of the delay time
of 5.00 s.
Energize the binary curve switch input. lnject a test
current of 2.00 x ,1 via one phase lead. Check if the
relay stays in rest.
lnject a test current of 4.00 x I, via one phase lead.
Check if the START L> output picks up and if the
a
i
G88700-C3527-07-7600
MFR 7SJ551
Operating instructions
TRIP b output closes after expiry of the delay time
of 0.500 s.
Checking the pulse mode
Parametrize the curve switch function according to
the following settings.
Parameter
CURVE SWITCH
MODE
tcs
Setting
ENABLED
PULSE
10.0 s
Marshall the curve switch function to one of the
binary inputs.
8
!
Inject a test current of 2.00 x I, via one phase lead.
Check if the START L> output picks up and if the
TRIP b output closes after expiry of the delay time
of 5.00 s.
Energize the binary curve switch input just before
injecting a test current of 2.00 x I, via one phase
lead. Check if the relay stays in rest during 10.0
seconds after energizing the binary input. Thus a
transformer or motor inrush is simulated.
Repeat this test with a current of 4.00 A. Check if
the relay trips after 0.500 s.
G88700-C3527-07-7600
Checking the status mode
Parametrize the curve switch function according to
the following settings.
Parameter
CURVE SWITCH
STATUS
Settin
ENABLED
STATUS
STPISTRT
Curve 2 will be active when the motor status is
'ST0 PPED' or 'START'.
Move to the menu part MEASURED VALUES (ON
LINE) and select the menu part MOTOR STATUS
on the display. Check if the motor status is
'STOPPED'.
Inject a test current of 2.00 A via one phase lead.
The motor status will change to 'START'. Check if
the relay stays in rest.
Lower the current to 1.OO A. The motor status will
change to 'RUNNING'. Curve 1 will be active from
now on.
Raise the current to 2.00 A again. Check if the
START L> output picks up and if the TRIP b
output closes after expiry of the delay time of 5.00
s.
one hundred seventy-one and 001100
MFR 7SJ551
6.16.22
Operating instructions
Parametrize the relay according to the following
settings.
Parameter
DEVICE DATA
DEVICE TYPE
CHANNELS
L1
L2
L3
In
Uin
Un
PROTECTIONS
UNDERCURRENT
I<
t I<
UNDERVOLTAGE
U<
t U<
BLOCK
BLOCK I<
BLOCK U<
Setting
NON-ROTATING
ENABLED
ENABLED
ENABLED
I
ENABLED
I00 V
ENABLED
.500
3.00s
ENABLED
-250. U,
5.00 s
ENABLED
ENABLED
ENABLED
As a test example here the block function will be
applied to the undercurrent and undervoltage
protection stages. Marshall the UNDERCURRENT
TRIP condition to one of the output relays. Marshall
the UNDERVOLTAGE TRIP condition to a second
output relay. Disable all other protection functions.
For testing the block function a single-phase test
case is sufficient.
This test shows how the block function can be used
to overcome the initial voltage- and currentless
condition of a transformer or motor.
Checking ihe continuous mode
Parametrize the block function according to the
following settings.
--
Parameter
BLOCK
MODE
Setting
ENABLED
CONTINUOUS
Marshall the block function to one of the binary
inputs.
6.16.23
a
Testing the block function
i
After changing the operating mode to ON LINE the
relay will pick-up. After applying a voltage higher
than 25.0 V and a current higher than 0.500 A the
pick-up condition will vanish and the LED indicators
can be reset.
lnject a test current of 1.OO x 1, via one phase lead
and apply a voltage of 100 V. Check if the relay
picks up when the current or the voltage is taken
away.
lnject a test current of 1.OOx Invia one phase lead
and apply a voltage of 100 V. Energize the binary
block input. Check if the relay stays .in rest when
the current or the voltage is taken away.
Checking the pulse mode
Parametrize the block function according to the
following settings.
Parameter
BLOCK
MODE
BLOCK
Setting
ENABLED
PULSE
10.0s
Marshall the block function to one of the binary
inputs.
After changing the operating mode to ON LINE the
relay will pick-up. After applying a voltage higher
than 25.0V and a current higher than 0.500A the
pick-up condition will vanish and the LED indicators
can be reset.
lnject a test current of 1.OOx I, via one phase lead
and apply a voltage of 100 V. Check if the relay
picks up when the current or the voltage is taken
away.
lnject a test current of 1.OOx Invia one phase lead
and apply a voltage of 100 V. Energize the binary
curve switch input just before taking away the
current or the voltage. Check if the relay stays in
rest during 10.0 seconds after energizing the binary
input.
Checking the status mode
The block status mode can be tested similar to the
curve switch status mode. It is applicable only to
rotating devices. Refer to 6.16.21.
Testing the external command
Parametrize the relay according to the following
settings.
one hundred seventy-two and 0011 00
G88700-C3527-07-7600
t
MFR 7SJ551
Parameter
CHANNELS
L1
L2
PROTECTIONS
EXTERNAL COMMAND
t ~ ~ r
6.16.24
Operating instructions
Setting
ENABLED
ENABLED
ENABLED
5.00 s
Marshall the EXTERNAL COMMAND function to
one of the binary inputs. Marshall the EXTERNAL
COMMAND condition to one of the output relays.
Disable all other protection functions. For testing the
external command a test case is not necessary.
Energize the binary external command input. Check
if the external command output closes after 5.00 s.
Testing the circuit breaker position
Parametrize the relay according to the following
settings.
Parameter
CHANNELS
Settin
ENABLED
ENABLED
I
PROTECTIONS
CB POSITION
G88700-C3527-07-7600
ENABLED
Marshall the CIRCUIT BREAKER POSITION
function to one of the binary inputs. Marshall the
EXTERNAL COMMAND condition to one of the LED
indicators. Disable all other protection functions. For
testing the circuit breaker position a test case is not
necessary.
Energize the binary circuit breaker position input.
Check if the circuit breaker position LED indicator
lights up.
one hundred seventy-three and 001100
MFR 7SJ551
6.17
Cammissioning using primary tests
All secondary testing sets and equipment must be
removed. Reconnect current transformers. For
testing with primary values the protected object
must be energized.
/;\ Warning
Primary tests shall be performed only by
qualified personnel which is trained in
commissioning of protection systems and
familiar with the operation of the protected
object as well as the rules and regulations
(switching, earthing, etc.)
6.17.1
Operating instructions
Current circuit checks
Connections to current transformers are checked
with primary values. For this purpose a load current
of at least 10% of the rated current is necessary.
Currents can be read off on the display in the front
or via the serial interface and compared with the
actual measured values. If substantial deviations
occur, then the current transformer connections are
incorrect.
/r\ DANGER!
Secondary connections of the current
transformers must be short-circuited
before any current ieads to the relay are
interrupted!
No further tests are required for overcurrent time
protection; these functions have been tested under
section 6.16.1 1. For checking the trip circuits at
least one circuit breaker live trip should be
performed (refer to section 6.17.4).
one hundred seventy-four and 00/100
6.1 7.2
Checking the reverse
interlock scheme (id used)
For use and tests of the reverse interlock scheme it
is necessary that one of the binary inputs has been
assigned to-the block function. Set the block
function to continuous mode and enable BLOCK
I>>.
Binary inputs can be programmed 'normally open'
or 'normallv closed'. The followina ~rocedureis
valid forth; 'normally open mod2 as preset by the
factory.
The protection relay on the incoming feeder and
those on all outgoing circuits must be in operation.
At first the auxiliary voltage for reverse interlocking
should not be switched on.
Apply a test current which leads to pick-up of the
I>> stage as well as the I> or I, stage. Because of
the absence of the blocking signal the relay trips
after the short delay time tl>>.
A Caution
For the normal current circuits, test currents
larger than 6 times I, may overload and
damage the relay current input channels if
applied continuously. Observe a cooling
period if necessary.
Now switch on the DC voltage for the reverse
interlocking. The test as described above is
repeated, with the same result.
Simulate a pick-up on each protective device on all
outgoing feeders. Simultaneously, a short-circuit is
simulated on the incoming feeder (as described
before). Tripping now occurs after the delayed time
tl> or according tot, (calculated delay time).
If applicable repeat test for the earth current
stages.
Simultaneously these tests prove that the wiring
between the protection relays is correct.
G88700-C3527-07-7600
-
~
Operating instructions
MFR 7SJ551
!
6.17.3
Testing the switching of
binary inputs and outputs
Caution
As soon as the test mode is activated the
relays stops protecting the network
component.
The relay contains a test routine with which the
binary inputs and outputs can be checked. This test
mode can only be entered in ON LlNE mode.
The test mode can be reached in the ON LlNE
main menu.
A R E YOU S U R E
After typing backspace the green ON LlNE LED
indicator goes out to indicate there is no protection.
1 ENTER
TES~MODE?
BACKSPACE
1-
1-+-
+
Choose the 110 test mode.
OUTPUTS
Checking the output relays
A R E YOU SURE
1l:YP;
BACKSPACE
1
+I[
[TOGGLE OUTPUT
Type BACKSPACE. Check if output 1 closes. By
repeating above procedure output 1 can be opened
again.
Follow this procedure for all available output relays.
Checking the binary inputs
Energize input 1. Check if the indication 'OFF'
changes to 'ON'. Release input 1. Check if the
indication 'ON' changes to 'OFF'.
Follow this procedure for all available binary inputs.
G88700-C3527-07-7600
one hundred seventy-five and 00/100
"
i
Operating instructions
MFR 7SJ551
Leaving the test mode
ARE Y O U S U R E
TESTMODE ?
After the I10 test it is important to leave the test
mode.
After typing backspace the relay is back in the main
menu of the protective ON LlNE mode.
BACKSPACE
6.1 7.4
Tripping test including circuit
breaker
MFR 7SJ551 allows simple checking of the tripping
circuit and the circuit breaker. For this, the circuit
breaker can be tripped by initiation from the
operator keyboard. For this purpose the ON LlNE
TEST function is used.
Refer to section 6.17.3 for a description of how to
close and open the trip command output. Activate
the CIRCUIT BREAKER POSITION indication to
scan the operation of the breaker and the success
of the procedure on a LED indicator.
6.17.5
Putting the relay into
operation
All setting values should be checked again, in case
they were altered during the tests. Particularly
check if all desired protection and ancillary
functions have been enabled.
I
Stored indications on the front plate should be reset
by pressing the RI key on the front so that from
then on only real faults are indicated.
Check if the module is properly inserted and fixed.
All terminal screws - even those not in use - must
be tightened.
If a test switch is available this must be set in the
operating position.
Put the relay in ON LlNE mode. The green ON
LlNE LED indicator must light up. The red
MONITOR LED indicator has to be dark.
MFR 7SJ551 is ready for operation now.
one hundred seventy-six and 0011 00
G88700-C3527-07-7600
R
MFR 7SJ551
Maintenance and trouble shooting
Maintenance and trouble shooting
7
j
7.11
F o r the normal current circuits, test currents
larger than 6 times ,I and for the ,I sensitive
current circuit, test currents larger than 4
times I, may overload and damage the relay
current input channels if applied
continuously. Observe a cooling period if
necessary.
General
Siemens digital protection relays are designed to
require no special maintenance. All measurement
and signal processing circuits are fully solid state
and therefore completely maintenance-free. Input
modules are static, relays are hermetically sealed or
provided with protective covers.
-
Only the internal real time clock module which has
an integrated battery back-up device may have to be
serviced after approximately 10 years after
manufacturing of the relay. We recommend to
replace the real time clock module in accordance
with your maintenance philosophy.
Don't forget to restore the settings to the original
ones, and to check the status of the current
terminais.
7.2
Routine checks
The planned maintenance intervals for checking and
maintenance can be used to perform operational
testing of the protection equipment. This
maintenance serves mainly for checking the
interfaces of the unit, i.e. the coupling with the plant.
The following procedure is recommended:
- Read-out of the operational values and
comparison with the actual values for checking
the analogue interfaces.
-
Simulation of an internal short-circuit with 4 x I,
for checking the analogue input at high currents.
/;\ Warning
Hazardous voltages can be present on all
the electrical circuits and components
connected with the supply voltage or with the
measuring and test test voltages/currents!
Non-observance of the safety rules can
result in personal injury or property damage.
A Caution
Circuit-breaker trip circuits are tested by actual
live tripping. The overcurrent function can be
tested by secondary injection of a current (see
section 6.1 6.12).
7.3
Self-test
One of the benefits of a microprocessor system is
the self-testing of the system. When a malfunction is
located, MFR 7SJ551 will record the cause, if
possible. The malfunction cause is displayed in the
manufacturing data menu (see section 6.1 4.7). The
'NO ERRORS' message will appear if MFR 7SJ551
has no failure messages. An error message will
appear if MFR 7SJ551 has located an internal
failure.
The meaning of the different error messages is:
HW: AUX. SUPPLY
The auxiliary supply voltage was below the allowed
value for a certain time. Normal operation will still be
possible
HW: EZPROM
The EEPROM memory contains the default values
and the setting values. The test is carried out by
adding the data in the EEPROM and comparing the
sum values with fixed values. Contact the Siemens
service department if MFR 7SJ551 has this failure.
HW: RAM
The RAM memory contains the actual values. The
test is carried out by write and read cycles in order to
verify that each bit in every location can be modified
under program control. Switch off the auxiliary supply
voltage and switch it on again after a few seconds.
Contact the Siemens service department if the
failure remains.
Instead of switching off the auxiliary supply voltage
you can also reset the microcontroller with a fine pin
on the front panel.
1
Maintenance and trouble shooting
MFR 7SJ551
HW: REF. VOLTAGE
The internal reference voltage is used for a correct
reading of all the analogue signals. A failure of the
internal reference voltage will cause incorrect values
in the system. Contact the Siemens service
department if MFR 7SJ5.51 has this failure.
!
I
,
HW: ROM
The ROM memory contains the control program and
fixed data, which should not be changed. The test is
carried out by adding the data in the ROM and
comparing the sum values with fixed values. Switch
off the auxiliary supply voltage and switch it on again
after a few seconds. Contact the Siemens service
department if the failure remains.
lnstead of switching off the auxiliary supply voltage
you can also reset the microcontroller with a fine pin
on the front panel.
Recommended RTC chip:
Manufacturer: DALLAS
Order number: DS 1286
This chip is mounted on the processor board and is
replaceable by anyone who is familiar with the
handling of electronic components.
For replacing the RTC chip the relay unit has to be
removed from its metal housing.
The RTC chip is located at the underside of the relay
to the backside next to the EPROMS (see figure 7.1.
Replacement procedure:
- Prepare area of work; provide conductive surface
for the basic module.
HW: TRIP COIL
A disconnection is observed in the circuit to output
relay number 1. Probably a trip command activation
of MFR 7SJ551 will not close the contacts of output
relay 1. Contact the Siemens service department if
MFR 7SJ551 has this failure.
SW: MLFB
There is a specific failure in the EEPROM which has
occurred between the last check of the EEPROM
and the check of the order number of the 7SJ551
relay. Contact the Siemens service department if
MFR 7SJ551 has this failure.
SW: SW ERROR
There is an unexpected failure situation. Switch off
the auxiliary supply voltage and switch it on again
after a few seconds. Contact the Siemens service
department if the failure remains.
lnstead of switching off the auxiliary supply voltage
you can also reset the microcontroller with a fine pin
on the front panel.
If the real time clock (battery performance) is not
working properly, the ON LlNE LED indicator will
start to flash. Only storing of statistical data will be
affected. The relay will perform all other functions
well.
7.4
Replacing the real time
clock module
MFR 7SJ551 is equipped with a real time clock
module which should last for approximately 10
years. After this time the RTC chip must be
replaced. Malfunction of the real time clock is
indicated by a flashing ON LlNE LED indicator.
-
Open front cover.
-
Note down all the settings (or check them with
the already filled-in form) or save them on hard
disk using the '7SJ551 Communication Utility'
software program.
- Prepare the RTC chip, do not place it on the
conductive surface.
A Caution
Do not short-circuit the RTC chip! Do not
reverse the RTC chip polarities! Do not
charge the RTC chip!
- Put the device in OFF LlNE mode.
-
Switch of the device, and wait till the red monitor
LED has completely gone out.
-
Unscrew, in the correct order, both screws on the
7SJ551 relay.
Warning
Hazardous voltages can be present on all
the electrical circuits and components
connected with the supply voltage or with the
measuring and test voltages/currents!
Non-observance of the safety rules can
result in personal injury or property damage.
I
Maintenance and trouble shooting
MFR 7SJ551
-
Pull out the 7SJ551 basic module of the housing
with the handle, whilst supporting it on the
bottom-side.
/!\Caution
Electrostatic discharges via the component
connections, the PCB tracks or the
connecting pins of the modules must be
avoided under all circumstances by
previously touching an earthed surface and
by connecting via an bracelet to a highohmic discharge cord to earth.
-
Place the 7SJ551 module on the conductive
surface.
-
Remove the RTC chip with a pair of tweezers, do
not place it on the conductive surface.
- Insert the new RTC chip with a pair of tweezers in
the correct way.
Firmly push in the 7SJ551 module in its housing,
whilst supporting it on the bottom side.
- Fasten the two screws in the correct order,.
- Switch on the device.
-
Switch off the supply voltage to zero. The red
LED indicator MONITOR will go out.
- Return the supply voltage to its normal operating
level. Verify that the 7SJ551 relay resumes its
normal ON LlNE operation.
- Check the power fail memory circuit by verifying
that set points and statistical data have not been
altered.
9.6
Trouble shooting
When MFR 7SJ551 seems to have a defect, various
checks can be made by the user himself. In case
none of the LED indicators lights up when turning on
the mains supply, the following checks can be
performed:
-
Is the relay unit properly inserted in the metal
case, are both screws fastened?
- Is the auxiliary supply connected to the correct
input position (XC-IV-1 and XC-IV-2)?
- Is the connected auxiliary supply in accordance
with the 7SJ551 supply range? Check the sticker
at the top of the metal case.
- Check if all settings are OK.
- Set the day and time as described in section
6.10.
- Place front cover
7.5
Power failure test
The 7SJ551 relay has an internal power fail
detection circuit. To test this circuit, the following
steps have to be made:
-
Make sure the 7SJ551 relay operates in the ON
LlNE mode and start with decreasing the supply
voltage.
- When the supply voltage drops below its
specified operating range, MFR 7SJ.551 ceases
to operate. The relay has insufficient voltage to
continue to monitor the protected device
accurately. The green LED indicator ON LlNE will
go out and the red LED indicator MONITOR will
light up. All output relays will be in the power-off
state.
- Is the mini-fuse in the power supply section
intact? If not, replace the fuse in accordance with
section 7.6.1.
When the red MONITOR LED indicator lights up the
internal memory might contain incorrect data. Press
the RES PC button with a small object. MFR 7SJ551
will initialize its memory, and this can lead to proper
performance.
When MFR 7SJ5.51 seems to work properly (e.g. the
green ON LlNE LED indicator lights up), but does
not respond to the keyboard functions, one of the
keys may be jammed by the metal front during
transportation or installation. Check all keys by
pressing them individually, and try to move the metal
front gently.
7.6.1
Replacing t h e mini-fuse
For replacing the mini-fuse the relay unit has to be
removed from its metal housing. The fuse screw
holder is located at the backside of the basis unit.
1
Maintenance and trouble shooting
MFR7SJ551
Replacement procedure:
-
Select a replacement fuse. For an auxiliary
voltage of DC 24 60 V we recommend a 5 x 2 0
mm glass fuse, 1.6A, slow. For an auxiliary
voltageof DC 1 1 0 - 2 5 0 V / A C 1 1 0 - 2 3 0 V w e
recommend a 5 x 20 mm glass fuse, 0.5 A, slow.
-
-
Prepare area of work; provide conductive surface
for the basic module.
Open front cover.
Put the relay in OFF LINE mode.
-
Switch of the device and wait till the red
MONITOR LED is completely off.
/;\ Warning
Hazardous voltages can be present on all
the electrical circuits and components
connected with the supply voltage or with the
measuring and test voltages/currents!
Non-observance of the safety rules can
result in personal injury or property damage.
-
Pull out the 7SJ551 basic module of the housing
with the handle, whilst supporting it on the
bottom-side.
A Caution
Electrostatic discharges via the component
connections, the PCB tracks or the
connecting pins of the modules must be
avoided under all circumstances by
previously touching an earthed surface and
by connecting via an bracelet to a highohmic discharge cord to earth.
Figure 7.1
Replacing the mini-fuse
-
Place the 7SJ551 module on the conductive
surface.
-
Remove blown fuse from the screw holder at the
middle in the back of the device (see figure 7.1).
- Fit new fuse into the holder.
-
Firmly push in the 7SJ551 module in its housing,
whilst supporting it on the bottom-side.
- Fasten the two screws in the correct order.
Switch on the device again. If a power supply failure
is still signalled, a fault or short-circuit is present in
the internal power supply. The device should be
returned to the Siemens service department.
MFR 7SJ551
naarnhoofdstuk
Repairs
Self-repair of defective modules is not
recommended, because specially selected
electronic components are used which must be
handled in accordance with the procedures
required for electrostatically endangered
components (EEC). Furthermore, special
manufacturing techniques are necessary for any
work on the printed circuit boards in order to
prevent damage of the bath-soldered multi-layer
boards, the sensitive components and the
protective finish.
Therefore, if a defect cannot be corrected by
operator procedure as described in Chapter 7, it is
recommended that the complete relay is returned
to the manufacturer.
It is unavoidable to replace individual modules, it is
imperative that the standards related to the
handling of electrostatically endangered
components are observed.
//
Warning
Hazardous voltages can be present on all
the electrical circuits and components
connected with the supply voltage or with the
measuring and test voltages/currents!
Non-observanceof the safety rules can
result in personal injury or property damage.
/;\ Caution
Electrostatic discharges via the component
connections, the PCB tracks or the
connecting pins of the modules must be
avoided under all circumstances by
previously touching an earthed surface and
by connecting via an bracelet to a highohmic discharge cord to earth.
Components and modules are not endangered as
long as they are installed within the relay.
Should it become necessary to exchange any device
or module, the complete parameter assignment
should be repeated. It is convenient to save all
parameters on hard disk or diskette using the
'7SJ551 Communication Utility' software program.
These can be transmitted into the replacing relay.
We urgently advise to use a transport housinq for
7SJ55 relays that are sent back for repair.
Otherwise mechanical damages can occur.
A transport housing (order number G88700-C3526L153) is deliverable by Siemens Netherlands:
The form 'advice of return 7SJ55' (Appendix E) can
be sent together with the defective relay.
Siemens Nederland N.V.
Industrial Centre Zoetermeer
Department PI PROD EPS (Room B3.0.17)
Werner von Siemensstraat 1
NL-2712 PN ZOETERMEER
The Netherlands.
Send or fax this form also to the purchase
department EV TD in The Hague, so that the repair
process can be prepared before the relay arrives:
Siemens Mederland N.V.
Department EV TD
P.O. Box 16068
NL-2500 BB THE HAGUE
The Netherlands
31 70 333 3225
fax number
telephone number 31 70 333 3134
In this manner repair times can be minimized.
Be sure to fill in:
sender data
your order number
* MLFB code
* serial number
firmware version
error description
desired action
0
return address
MFR 7SJ551
9
Repairs
Storage
Solid state protective relays shall be stored in dry
and clean rooms. The temperature range for
storage of the relays or associated spare parts is
25 "C to +55 "C or -12 "F to 130 "F.
-
The relative humidity must be within limits to avoid
condensation or ice forming.
After extended storage it is recommended that the
relay is connected to its auxiliary voltage source for
one or two days prior to taking it into actual service.
This serves to regenerate the electrolytic capacitors
of the auxiliary supply. In extreme climatic
conditions (tropics) pre-warming will thus be
achieved and condensation avoided.
"
MFR 7SJ551
B
1
c
Typical wiring diagrams
Motor application example
D
Default values
F
Advice of return 7S455
I
Appendix
MFR 7SJ551
A
Appendix
General diagrams
XC-IV
MONITOR
XE-IV
XD-IV
XE-Ill
XC-IV
'd
XB-II
XD-Ill
XE-I I
OUTPUT
XD-I1
OUTPUT
XE-I
XD-1
OUTPUT
OUTPUT
8
XB-I I1
XB-IV
xB-lv
------- 1
-,-,-
I
I
Interface
I
I
I
Temperature sensor
I
I
I
I
I
I
I
I
RxD
Gnd
I
1
1
I
1
I
I
I
I
RxD
I
I
I
;
,
,
,
,
,
Figure A.l
G e n e r a l diagram for 7SJ551*-**A*O-g
I
,
,
,
1,,
1
I
MFR7SJ551
Appendix
XC-IV
XC-IV
MONITOR
OUTPUT 1
XE-Ill
/A
XD-Ill
XE-II
OUTPUT 2
XD-ll
XE-I
OUTPUT 3
XD-l
OUTPUT 4
XC-Ill
XB-1
4
f
XB-Ill
XB-IV
XB-V
OUTPUT 5
XC-I
OUTPUT 6
XC-I
INPUT 3
Temperature sensor
(8~)
XB-I
INPUT 4
TxD
Gnd
RxD
G nd
XB-l l
TxD
RxD
Figure A.2
-
General diagram for 7SJ551*-**A*O-I*
MFR 7SJ551
Appendix
XC-IV
XC-IV
XE-IV
XD-IV
XB-Ill
XE-Ill
XB-II
XD-Ill
XE-ll
XB-Ill
XD-II
XE-l
XD-l
OUTPUT 4
~
l
N
pI
u
~
OUTPUT 5
OUTPUT 6
f
f
f f- - - - - - - XB-I,
XC-I
XC-I
-
interface
1
f
Temperature sensor
I
(8x1
XB-I
RS-485
RxD
XB-II
t
I
I
,-
-
Fibre
i2c
Optic
f
*
TxD
RxD
I
I
Figure A.3
General diagram for 7SJ551'-**A*O-2*
-
and 7SJ551 *-**A*O-3*
MFR 7SJ551
CONNEC~UNSPLUGS (REAR VIM)
Figure A.4
Lay-out of the connection terminals
Appendix
MFR 7SJ551
Appendix
I
I
I
I
I
I
I
I
I
I
I
1
1
i
I
I
I
A, , ,L
Figure A.5
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Terminal denomination
XD
*
'
MFR 7SJ551
Typical wiring diagrams
2 c.t. connection
for isolated, resonant earthed or high-ohmic earthed systems
MENU:
L1 ENABLED
L3 ENABLED
2 c.t. connection with additional core balance c.t.
for isolated, resonant earthed or high-ohmic earthed systems
MENU:
t i ENABLED
13 ENABLED
e ENABLED
Appendix
MFR 7SJ551
3 c.t. connection (Holmgreen connection)
for low-impedance earthed systems
MENU:
L1 ENABLED
L2 ENABLED
L3 ENABLED
e ENABLED
3 c.t. connection with additional core balance c.t.
for isolated, resonant earthed or high ohmic earthed systems
MENU:
L1 ENABLED
L2 ENABLED
L3 ENABLED
e ENABLED
Appendix
*
i
MFR 7SJ551
Appendix
Motor application example
In this section an example is presented of how to configure and apply the MFR 7SJ551 relay as a motor
protection relay.
Data delivered by motor manufacturer
Motor specification
Value
61
Description
Rated current
Rated frequency
No-load current (0,43 x rated current)
rting current (5 x rated current)
50
26
305
60:l
A
Parameter
IR
Hz
A
A
A
lno load
Istart
S
T i ,stat
A
kstat
Motor thermal capacity data
Description
Thermal warming-up time constant (copper)
Maximum allowable continuous current
Permissible starts
from cold motor condition
from warm motor condition
Running-up time at nominal voltage
Maximum allowable running-up time
from cold motor condition
from warm motor condition
Maximum allowable locked rotor time at nominal voltage
Thermal cooling-down time constant
jircuit configuration
I
Calculations
I
MFR 7SJ551
I
I
Parameter
Value
294
318
3
1
10
30
10
10
1176
bold
nwarrn
S
fstafi
S
~ C O I b~ a
S
nwarm . tstart
s
S
.
CSIOO.
stat
it
MFR 7SJ551
Appendix
Thermal stator model
MFR 7SJ551 uses a thermal stator model consisting of a short thermal time constant and a long thermal time
constant to approximate the thermal behaviour in running mode accurately.
For this motor only one time constant is available.
Description
Overload factor
Thermal time constant 1
Thermal time constant 2
Weighting factor (interaction between two exponential curves)
Value
1.08
294
unused
1
Parameter
kstat
S
Ti,stat
%stat
Pweioht
This means that the maximum allowable continuous current is 1.08 x 61 = 318 A.
1
For the stator thermal overload function the following formula is applicable.
The only 'active' thermal time constant is T,,,,,, because pWeig,= 1 means that the second exponential part in
the above formula disappears.
When we load the motor at t = 0 with a constant continuous current
, , I that is greater than kStatx lfl,, the relay
will trip in a time ttd,. For different currents the following tripping times can be calculated:
lrms (X
IRC)
constant continuous current beo~nnlnqat t=O
1.10
2.00
3.00
4.00
5.00
6.00
7.00
ttrip
(s)
preload = 0
980,O
101,O
40,9
22,2
14,1
9,7
7,1
itrip (s)
preload = 60%
722,7
44,8
17,O
9,1
57
3,9
2,9
When the motor is stopped, it will cool down. The cooling down of the stator takes 4 times as long as the
"
I
MFR 7SJ551
Appendix
It is allowed to start 3 times from cold motor condition and 1 time from warm motor condition with starting time
,,,t
= 10 s and starting current lsta, = 305 A.
From these parameters the rotor thermal model is built according to the following formulas:
Trotor
=
8
- n c o ~ d* t start
+ 2
In(1 - o r 1
=
1
-3*10
= 465 s
In(-, - 1,5 * 1 ~ 0 2 ~
5
&art
.)ram the 3 phase currents the normal and inverse components are calculated using the symmetric
components method. These normal and inverse components are used to calculate the heating current. For this
purpose we calculate the inverse factor k, out of:
l?IC
kinv ~ 2 3 0 . E t art
I
Description
Inverse factor
Value
9.2
1 Parameter
1 kinv
This factor makes sure that asymmetric currents contribute additionally to the calculated heating of the motor:
[:eating=
l;orrn+
kin" *
l$v
When we start and load the motor at t = 0 with a constant symmetric continuous current,,,I that is greater than
, , ,k
x In,, the relay will trip in a time tt",. For different currents the following tripping times can be calculated
according to:
I
MFR 7SJ551
lheat!ng (X Iflc)
constant svmrnetrlc continuous current beq~nn~np
at b 0
1.23
2
3
4
5
6
7
Appendix
ttrlp (s)
preload = 0
231 1
228
88
48
30
21
15
ttrlp (s)
preload = 50 %
1899
122
44,4
23,5
14,6
10,O
7,3
When the actual starting time is less than 10 s, for example 5 s, it is allowed to make
10/5 x 3 = 6 starts from cold motor condition and
1015 x 1 = 2 starts from warm motor condition.
When the motor is stopped, it will cool down. We assume that the cooling down of the rotor also takes 4 times
as long as the warming up.
Description
Cooling down factor rotor
\
Value
4.00
1
1 Parameter
I CS~OD.~OI
i
Locked rotor protection
The locked rotor protection works only during the motor status "start" and sees to it that the motor is tripped in
time when the rotor is stuck and the thermal rotor model would allow a too long starting time.
According to the customer data the permissible locked rotor time is 10 s, at maximum allowed starting current
= 305 A.
The tripping time is calculated according to:
As the locked rotor condition is very critical, we take a safety margin of 1 s:
Description
Locked rotor time
I
1
Value
9.00
( Parameter
I s I tlr
With this we calculate:
Short circuit protection
For high-speed clearing of motor phase faults the following conditions must be fulfilled for the setting of the
instantaneous elements I>>:
a
1
"
I
MFR 7SJ551
Appendix
p i n i m u m pick-up current greater than 1.6 times motor locked rotor current (maximum inrush due to
asymmetry)
- minimum pick-up current smaller than the minimum short-circuit current
Differential protection should be provided if the above criteria are not met!
In practice the maximum pick-up current must be smaller than circa 1/3 of the maximum occurring 3-phase
short-circuit current.
The locked rotor current equals 5 x IRc,SO I>> must be set on
1,6 x 5 x lac
= 9 x It,, = 549 A.
+
Description
Instantaneous pick-up current
Value
549
[A
Parameter
I>>
For motor protection it is beneficial to enable the 'curve switch' function in the mode 'status'.
If we choose the motor status 'stop/start', this means that when the motor is at standstill or starting, the curve
2 will be active for overcurrent condition. When the motor is running, curve sets 1 will be active. In this way
an adapt the overcurrent settings to the actual motor status.
E
I
Fxample
In the following example the overcurrent level during running mode is set at 200 A.
Curve 2 (during stop/start)
Description
Low set overcurrent
Low set overcurrent delay time
High set overcurrent
High set overcurrent delay time
Curve 1 (during running mode)
Description
Low set overcurrent
Low set overcurrent delay time
High set overcurrent
High set overcurrent delay time
1
Value
548
0.5
549
0.01
A
s
A
s
Parameter
I>
tI>
I>>
tl>>
A
s
A
s
Parameter
I>
tl>
I>>
tl>>
Value
200
0.5
549
0.01
MFR 7SJ551
Appendix
Setting table
For setting the relay 7SJ551 all current values must be transformed to match the nominal secondary current
transformer current In= 1 A. As the motor currents are transformed by the current transformer with CT ratio 60 :
1 all current values have to be divided by 60. With this we get the following setting table.
Parameter group
DEVICE DATA
Parameter
LINE FREQUENCY
Iflc
DEVICE TYPE
Motor value
50
61
MFR 7SJ551
50
1-02
ROTATING
0.43
Hz
A
setting
Hz
X In
26
A
X In
305
A
5.08
X In
10
s
f0
s
tstafl
1.08
1.08
kstat
9.2
9.2
kin"
1
1
nwarrn
3 ................................................--.....--.
3 ".""...................................... ".........
............................................................... "....."........-..-..
........d!,!.
.....................".."........................... ............................
CHANNELS
L1
E
L2
E
E
L3
1
A
I"
CT temperature
60
sensor RATIOphase
28
X In
.-......................... ........--........
....I~!-!ase.rnax
"......................................................................... .................................................................
-...
THERMAL OVERLOAD
294
s
294
s
'h ,stat
3000
s
3000
s
%,stat
1
1
Pweight
4
4
Cstop.stator
4
4
.-....-.....-.--.. -................................... ..~.~~~~!,rotor
.....................................................................
....................................................
.......-....-.....
LOW SET OVERCURRENT CHAR
DEF
200
A
CURVE 1
X In
3.33
!>I
0.5
s
0.5
s
ti>
...... ............
................................ .......- .!
..................................... .-............................ .................................... .
........................... .....................
LOW SET OVERCURRENT CHAR
DEF
548
A
CURVE 2
X In
9.13
1>2
0.5
s
0.5
s
tl>
......".......................................... "
." ........2............................................ "-....... ..-..........."............................................... ............................................................................
HIGH SET OVERCURRENT I>>,
549
A
9.1 5
A
1
0.01
s
0.01
s
tl>>l -.............................""
.-CURVE
......................................
"......................................................
........-........................................
"..," -. ...........
"
HIGH SET OVERCURRENT I>>*
549
A
9.15
A
s
CURVE 2 .........". . ."........................
0.01
0.01
s
.......................................
2'.'.!!..
........."................-"..............".-.. ......-.......
"...........................................................................................................................
ROTOR "........"..................... t!1.
9
s
9
s
....LOCKED
"..........................................
"-......-....................
"..................... .............................. "
".........................................."....-.............-.
CURVE SWITCH
MODE
S
STATUS
STPISTRT
lno load
istart
"
"
"
"
"
"
"
"
Marshalling
The 7SJ551 relay consists of 2 or 5 binary inputs and 4 or 6 output relays.
The binary inputs can be set normally open or normally closed. One of the binary inputs can be used for
example for 'remote reset'.
The output relays can be set latched ('lock out'), temporarily latched or unlatched. We suggest to marshall all
tripping conditions to output 1 and to connect output 1 to the circuit breaker. Output 2 can be used to
annunciate an overload. Output 3 can be used to annunciate a locked rotor condition. Output 4 can be used to
annunciate a short-circuit. (Optionally, output 5 can be used to annunciate earth faults separately. This leaves
optional output 6 unmarshalled.)
!
I
'
I
MFR7SJ551
@is
\
Appendix
way we obtain the following software matrix.
Output 1 I Output 2 1 Output 3 1 Output 4 ( (Output 5) 1 (Output 6)
X ............. ............................................
x
. "....................... j .................................... .................".................... -.......................................
Trip thermal overload -. ............"..."
Trip b
x
I
x "...........:;
................................... *................................... ..............".................... I:.......................
.................... +................................... ....
X
Trip e>
................ "x ...............i ............................ .:........... ................. "......................................
I
x
i:...................................
.............
Trip L>>
....._....
_ ....-X...............i................................... ..............................................................................................................
;
x
.i
.
.......................
.............
:
X
Trip e>>
X
:
i....................................
i.......................
x .......................................
j
-:
.......................................
Trip locked rotor
X
i
!
X
I
!
".!
:
*.
A
...
"
"
i
-.i
A
"
"
1
MFR 7SJ551
1
D
Default vaikses
The 7SJ.551 relay will be delivered with a setting in
accordance with a default setting. This default
setting in not a very sofisticated setting which
normaly can be used for a very wide range of
protection functions. Normally an adjusting of the
default setting should be necessary. We
recommend to check all the setting values, also
in the cases that a setting value is equal with a
default value.
Appendix
MFR 7SJ551
Ao~endix
off line
tl
p-weight
t-adj
c-adj
Q-warn
100 s
200 s
0.5
disabled
2
25 %
OVERTEMPERATURE
overtemperature
alarm (all sensors)
trip (all sensors)
disabled
80 CO
100 CO
UNDERCURRENT
undercurrent
t-bypass [motor]
I<
t I<
disabled
5s
0.5 x In
3s
LOW SET OVERCURRENT
low set O.C.phase
phase char.
I> def, time
t I> def. time
Ip inv. time
tp inv. time
# of points (cust, curve)
II
t I1
12
t 12
13
t 13
14
t 14
15
t 15
16
t 16
17
t 17
18
t 18
19
t 19
110
t 110
111
t I11
112
t 112
113
t 113
114
t 114
115
t 115
low set O.C. earth
earth char.
le> def. time
t le> def. time
lep inv. time
disabled
definite
1.5 x In
5s
1.5 x In
1
15
1.5 x In
100 s
2.5 x In
90 s
3.0 x In
80 s
4.0 x In
70 s
5.0 x In
60 s
6.0 x In
50 s
7.0 x In
40 s
8.0 x In
30 s
9.0 x In
20 s
10.0 x In
15 s
12.5 x In
10 s
15.0 x In
5s
17.5 x In
2.5 s
20 x In
1.0 s
25 x In
0.5 s
disabled
definite
0.5 x In
5s
0.5 x In
12
DEVICE DATA
line frequency (fn)
full load (I-flc)
device type
lnoload [motor]
I-starl [motor]
t-start [motor]
k-stat [motor]
k [non-rotating]
k-inv [motor]
n-warm [motor]
n-cold [motor]
temperature sensor
CHANNELS
L1
AT-ratio
lmax
e
len
CT-ratio
lemax
lemax (sensitive)
Uin
U select
Un
VT-ratio
parameter
50 Hz
Ix In
non-rotating
0.1 x In
4.0 x In
10 s
1.I
1.I
5
2
3
Pt 100
disabled
disabled
disabled
1A
1
28 x In
disabled
1A
1
28 x len
1.4 x len
disabled
Uo
100 v
1
default setting
PROTECTIONS
THERMAL OVERLOAD [motor]
disabled
disabled
ti-min
input sensor
t l ,stat
t2,stat
p-weight
c-stop,stat
c-stop,rot
Q-warn
start inhibit
t-inh
Q-stator
emerg. restart
190 CO
40 C"
1
100 s
200 s
0.5
2
2
25 O/o
disabled
5s
50 %
disabled
THERMAL OVERLOAD [non-rotatingdevice]
thermal overload
disabled
ambient temp.
disabled
190 CO
T-max
40 C"
1
phase
)ue RMS
"
MFR 7SJ551
tep inv. time
# of points (cust. curve)
lel
t lel
l e2
t le2
le3
t Ie3
le4
t le4
le5
t le5
le6
t le6
le7
t le7
le8
t le8
leg
t leg
lelO
t lelO
le?1
t lell
le12
t le12
Ie13
t le13
le14
t lel4
le15
t le15
1
15
0.50 x len
200 s
0.55 x len
150 s
0.60 x len
I00 s
0.65 x len
90 s
0.70 x len
80 s
0.75 x ten
70 s
0.80 x len
60 s
0.85 x len
50 s
0.90 x len
40 s
0.95 x len
30 s
1.0 x len
25 s
1.1 x len
20 s
1.2 x len
15 s
1.3 x len
10 s
1.35 x len
5s
HIGH SET OVERCURRENT
high set O.C. ph.
I>>
t I>>
high set O.C. earth
le>>
t le>7
disabled
10 x In
0.5 s
disabled
Ix l n
2.5 s
UNBALANCE
unbalance
t-bypass
12
t2P
disabled
Is
0.2 x In
10 s
DIRECTIONAL EARTH FAULT DETECTION
directional earthfault
disabled
control
cosine
U-strt
0.1 x Un
t U-strt
5s
If>
forward
If>>
forward
0"
fe
dl
0"
d2
0"
d3
0"
LOCKED ROTOR
locked rotor
f
Appendix
disabled
t-lr
ZERO SPEED
zero speed
t-zero
disabled
10 s
UNDERVOLTAGE
undervoltage
~xxx<"
t uxxxc')
disabled
0.25 x Un
5s
OVERVOLTAGE
overvoltage
t urn>''
~xxx>>"
t UXXX>>"
BF TRIP
BF trip
extern
I-bf
t-bf
disabled
0.75 x Un
5s
1 xUn
1s
disabled
disabled
CURVE SWITCH
curve switch
mode
t-CS (pulse mode)
status (status mode)*)
disabled
continuous
10 s
running
BLOCK
block
mode
t-BLOCK (pulse mode)
status (status mode)"
timers
1<
I>
I>>
le>
le>>
U<
disabled
continuous
10 s
running
disabled
enabled
enabled
disabled
enabled
disabled
enabled
EXTERNAL COMMAND
ext. command
t- EXT
disabled
5s
CB POSITION
CB POSITION
disabled
TRANSIENT DATA
start
t-trip
t-alarm
intern
1.5 s
1.5 s
REAL TIME CLOCK
format
rtc sync
dd-mm-yy
disabled
1
MFR 7SJ551
BINARY INPUTS
binary input 1
binary input 2
binary input 3
binary input 4
binary input 5
extern (remote reset)
remote reset
t-adjust3'
curve switch
block
mode (CW/CCW)
CW/CCW
emerg restart
zero speed
@md
-13position
dult rec
serial event
rtc sync
OUTPUT RELAYS
latch timer
t-reset
output relay 1
output relay 2
output relay 3
output relay 4
output relay 5
output relay 6
pre-alarm
trip Q-th
start L1>
2iart e> or f>
trip e> or f>
start L>>
trip L>>
start e>> or f>>
trip e>> or f>>
alarm UB
trip UB
alarm Uc
trip U<
alarm U>
trip U>
.
alarm U>>
trip U>>
start inh (motor)
Ikd rotor (motor)
alarm T
Appendix
open
open
open
open
open
disabled
I (bin, input)
1 (bin, input)
1 (bin. input)
1 (bin. input)
intern
1 (bin. input)
I (bin. input)
1 (bin. input)
1 (bin. input)
1 (bin. input)
1 (bin. input)
I(bin, input)
1 (bin. input)
1 (bin. input)
disabled
600 s
unlatched
unlatched
unlatched
uniatched
unlatched
unlatched
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
le dir @
ie dir
alarm zsp
trip zsp
BF trip
ext. cmd
not connected
not connected
not connected
not connected
not connected
not connected
LED INDICATORS
LED1
LED2
LED3
LED4
trip Q-th
start L>
trip L>
start e> or f>
trip e> or f>
start L>>
trip L>>
start e>> or f>>
trip e>> or f>>
alarm UB
trip UB
non-memorized
non-memorized
non-memorized
non-memorized
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
not connected
alarm Uc
trip Uc
alarm U>
trip U>
alarm U>>
trip U>>
start inh (motor)
Ikd rotor (motor)
alarm T
trip T
alarm I<
trip Ic
le dir @
le dir 7
alarm zsp
trip zsp
BF trip
ext. cmd
CB position
not connected
not connected
not connected)
not connected)
not connected)
not connected)
not connected)
not connected)
not connected)
not connected)
not connected)
not connected)
not connected
not connected
not connected
not connected
not connected
not connected
not connected
SERIAL COMMUNICATION
adress
baudrate
event
prtcl
block
0
2400~)
RS-485
disabled
LSA
disabled
COUNTERS
this menu part has no default setting
ALARM/TRIP DATA
alarm event nr.
trip event nr.
n (last one)
n (last one)
DEMAND AMMETER
this menu part has no default setting
.
MFR 7SJ551
RUNNING HOURS
this menu part has no default setting
MANUFACTURlNG DATA
this menu part has no default setting
Appendix
1) U u x = Un-In for the phase to phase voltage or
U-Ph for the phase to earth voltage or Uo for the
zero sequence voltage
2) Only for rotating device
3) non rotating device
4) factory value but will not change with a reset
i
SIEMENS
advice of return 7SJ55
from
number
adress for advice of return
original reference Siemens The Hague
Siemens Nederland N.V.
Department EV TD
mrs. C. Groos
P.O. Box 16068
NL-2500 BB THE HAGUE
The Netherlands
date
38...................
original dispatch note number
date
D8.. ................
your order number
name of sender
date
department
forward~ngaddress for return of reiay(s) to repair
ordering date
date of sending
teiephone number
fax number
mode of dispatch
Siemens Nederland N.V.
Industrial Centre Zoetermeer
Department PI PROD (Room 83.0.17)
mister R. Boender
Werner von Siemensstraat 1
NL-2712 PN ZOETERMEER
The Netherlands
custom value of goods
reason for returning goods
item
description / MLFB code 1 serial number / firmware version / error description1
quantit action desired
cross)
Y
(please mark w~tha
credit note
replacement free of
charge
repair under
guarantee
repair against charge
(Ih~sadvhce of return counts a s
repair order)
El
cost estimate desired
return of goods on
loan
17 repair report
forwarding address for return of replacement or reparred goods
end customer
*
MFR 7SJ551
1
F
Advice of return 78555
I
Appendix
Download