Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 1 of 26 Edisi: 3 Tarikh: 8 Disember 2018 KAWALAN PROSES NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Tenaga Nasional Berhad Wisma TNB, 19 Jalan Timur 46200 Petaling Jaya Selangor Darul Ehsan, Malaysia PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NOMBOR DOKUMEN: ENGR-750-70 Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Edisi 1 2 Keterangan Isu untuk perlaksanan SPK MS 9001:2000 Realignment for function based on VUP Pindaan nama prosedur daripada ’Prosedur Perancangan Bekalan Elektrik untuk Pelanggan Kuasa Besar/Industri yang Mengambil Paras Voltan Sederhana Mematuhi Keperluan Standard Kualiti Kuasa’ ke ’Prosedur Pematuhan Syarat Lesen TNB Bagi Perancangan Bekalan Elektrik Untuk Pelanggan Industri yang Mematuhi Keperluan Standard Kualiti Kuasa’. Nombor Dokumen: ENGR-750-70 Mukasurat: Page 2 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Tarikh Effective date Pemula PBK(PA) Semak MR Kelulusan NP(P) 1.9.2016 HOU(AM) HOU(AM) SGM(DN) 8.12.2018 HOU(AM) HOU(AM) SGM(DN) Prosedur untuk muat turun format surat rasmi bagi pematuhan kepada piawaian kualiti kuasa. 3 Prosedur untuk muat turun format surat rasmi bagi tiada pematuhan kepada piawaian kualiti kuasa. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 3 of 26 Edisi: 3 Tarikh: 8 Disember 2018 PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA KANDUNGAN 1. Objektif 2. Definisi / Ringkasan 3. Skop & Latarbelakang 4. Rujukan 5. Tanggungjawab 6. Prosedur 7. Input / Sumber 8. Output / Penerima 9. Rekod Kualiti 10. Penanda Utama Prestasi (KPI) 11. Lampiran 12. Work Instruction Berkaitan Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN 1.0 Nombor Dokumen: ENGR-750-70 Mukasurat: Page 4 of 26 Edisi: 3 Tarikh: 8 Disember 2018 OBJEKTIF Dokumen ini bertujuan menerangkan prosedur keperluan kualiti kuasa untuk perancangan bekalan elektrik baru/ naik taraf untuk pelanggan kuasa besar (LPC) industri pada paras voltan sederhana (VS) yang mematuhi keperluan Syarat Lesen TNB No 30. Nota: Syarat Lesen TNB No 30: - Distribution supply security and power quality standards Selain dari pematuhan kepada Syarat Lesen TNB No.30, prosedur ini juga disediakan untuk memastikan semua perancangan bekalan bekalan elektrik baru/ naik taraf untuk pelanggan kuasa besar (LPC) industri akan mematuhi semua keperluan:- 2.0 Akta Bekalan Elektrik Pindaan 2015 (Klausa 40 iv) Peraturan Elektrik 1994 (Klausa 114C) ST Distribution Code (Klausa 5.4.5 hingga 5.4.8) TNB’s Electricity Supply Application Handbook (Klausa 1.3.1.5, 1.3.2.1 to 1.3.2.7) SKOP Dokumen ini bertujuan menerangkan prosedur keperluan kualiti kuasa untuk perancangan bekalan elektrik baru/ naik taraf untuk pelanggan kuasa besar (LPC) industri pada paras voltan sederhana (VS) yang mematuhi keperluan Syarat Lesen TNB No 30. Prosedur ini juga boleh diapplikasikan untuk permohonan penambahan beban tambahan oleh pelanggan industri sediada. Perlaksanaan prosedur ini dikhaskan untuk semua industri yang sensitif kepada kualiti voltan atau kualiti kuasa seperti industri elektronik/ semiconductor, industri logam, industri plastik, industri simen, industri kabel, industri kayu/ papan, industri makanan, industri aerospace, tren elektrik (traction), dan lain-lain. Perlaksanaan prosedur ini juga dikhaskan untuk semua industri yang boleh menghasilkan emisi kualiti kuasa seperti industri logam, tren elektrik (traction), industri simen dan lain-lain. Objektif utama prosedur ini adalah untuk memastikan semua peralatan fasiliti & produksi di dalam premis pelanggan kuasa besar (LPC) mempunyai tahap immuniti (immunity) dan emisi (emission) yang mematuhi/ melebihi piawaian yang ditetapkan oleh TNB bagi semua kejadian kualiti voltan (kuasa) yang wujud di sistem elektrik TNB. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN 2.1 Nombor Dokumen: ENGR-750-70 Mukasurat: Page 5 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Kesan kualiti kuasa kepada pelanggan Kejadian kualiti kuasa yang berlaku di sistem penghantaran/ pembahagian TNB khasnya kejadian ’voltage sag’ boleh menghentikan proses/ mesin didalam premis LPC. Kejadian ini akan memberi kerugian RM kepada LPC dan juga boleh merosakkan peralatan-peralatan elektronik di dalam premis LPC. Emisi kualiti kuasa (harmonik, flicker, voltage step change & unbalance) boleh memberi gangguan kepada pepasangan pelanggan lain yang mengambil bekalan dari punca yang sama (PMU/ PPU) dengan pelanggan yang menghasilkan emisi ini. 2.2 Pematuhan kepada prosedur PSI ENGR 750-70 Prosedur ini bermula dari perancangan bekalan elektrik baru/ naik taraf dari LPC/ jurutera perunding yang dimajukan ke pejabat TNB. SP11/SP33 akan membuat perancangan rekabentuk sistem bekalan elektrik dengan menurut keperluan kehendak maksima (MD) dari LPC/ jurutera perunding. Prosedur perancangan bekalan sediada perlu dipatuhi dalam membuat perancangan bekalan baru ini. SP11/SP33 akan berkongsi maklumat statistik (rekod) kualiti kuasa dan keperluan kualiti kuasa merujuk kepada standard kualiti kuasa yang telah dinyatakan dalam buku panduan permohonan bekalan ’TNB Electricity Supply Application Handbook’ (ESAH) & Kod Pembahagian ST (ST Distribution Code). LPC/ jurutera perunding perlu melaksanakan kajian kualiti kuasa dan membuat deklarasi pematuhan kualiti kuasa di borang Appendix 8 (Rujukan ESAH: Power Quality Declaration Form: Declaration of Electromagnetic Compatibility (EMC) Compliance). Kajian kualiti kuasa yang perlu dibuat adalah:Jenis kejadian kualiti kuasa Harmonik Flicker Unbalance Voltage Step Change Nilai terkini semasa operasi Pengesahan THDV Pengesahan PST & PLT Pengesahan % Voltage Unbalance Pengesahan ∆V % Deklarasi kualiti kuasa yang perlu dbuat Jenis kejadian kualiti kuasa Voltage sag Transient Deklarasi untuk peralatan yang sensitif Pematuhan kepada IEC 61000-4-11/34 Pematuhan kepada IEC 61000-4-5 Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 6 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Senarai piawaian kualiti kuasa telah ditetapkan di dalam buku panduan permohonan bekalan ’Electricity Supply Application Handbook (ESAH)’. Syarat untuk mematuhi keperluan kualiti kuasa ini juga dinyatakan dalam borang kontrak khas bekalan elektrik / permohonan bukan domestic (A-Form) iaitu para 39 di ‘Conditions of Supply for Business and Non Domestic Consumers’ (Lampiran 1) & Kontrak Khas Bekalan Elektrik (Lampiran 2). 2.3 Pengecualian kepada prosedur PSI ENGR 750-70 Sebarang pengecualian dari membuat kajian kualiti kuasa perlu dirujuk kepada Pakar Teknikal (Kualiti Kuasa & Kecekapan Tenaga) di AMSDS. Tiada pengecualian untuk membuat deklarasi kualiti kuasa untuk kejadian voltage sag. Sebarang pengecualian untuk membuat deklarasi kualiti kuasa untuk transient perlu dirujuk kepada Pakar Teknikal (Kualiti Kuasa & Kecekapan Tenaga) di AMSDS. Bagi deklarasi & keputusan kajian yang tidak mematuhi piawaian kualiti kuasa TNB, rujukan perlu dibuat kepada Pakar Teknikal (Kualiti Kuasa & Kecekapan Tenaga) di AMSDS untuk tindakan susulan. 3.0 RUJUKAN / POLISI - Akta Bekalan Elektrik Pindaan 2015 (Klausa 40 iv) Peraturan Elektrik 1994 (Klausa 114C) ST Distribution Code (Klausa 5.4.5 hingga 5.4.8) TNB’s Electricity Supply Application Handbook (Klausa 1.3.1.5, 1.3.2.1 to 1.3.2.7) Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Buku panduan ESAH Gambarajah 1: 4.0 ENGR-750-70 Mukasurat: Page 7 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Appendix 8: PQ declaration form Buku panduan ESAH & borang deklarasi kualiti kuasa TANGGUNGJAWAB 5.0 Nombor Dokumen: SP11 SP33 ME HEMP AMSDS DEFINISI/RINGKASAN AMSDS HEMP Flicker Asset Management Strategy Design Standard Head of engineer maintenance planner di zon. Kegoyangan sensasi visual disebabkan oleh rangsangan cahaya yang mengalami perubahan kecerahan yang kerap. (Impression of unsteadiness of visual sensation induced by a light stimulus Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 8 of 26 Edisi: 3 Tarikh: 8 Disember 2018 whose luminance or spectral distribution fluctuates with time). Flicker dipantau menggunakan indek PST dan PLT. Harmonic Voltan dan Arus yang mempunyai frekuensi pelbagai dari frekuensi 50 Hz. Voltan dan arus harmonik ini wujud dan boleh memberi kesan negatif kepada sistem pembekalan elektrik. Harmonic dipantau menggunakan indek THD (Total harmonic distortion). ME Maintenance Executor Kualiti Kuasa Kejadian kualiti kuasa elektrik ditakrifkan sebagai perubahan bentuk voltan yang sempurna (sinewave) kepada bentuk voltan terganggu (deformed/distorted) dalam tempoh masa yang singkat (short duration). LPC Pelanggan Kuasa Besar Industri PQMSWeb Laman sesawang PQMSWeb (http://10.163.160.32/pqmsweb) RM Ringgit Malaysia RMS Adalah ukuran statistik bagi magnitud kuantiti yang berbeza-beza. Ia amat berguna apabila variat positif dan negatif, contohnya, sinusoid voltan. Contoh nilai RMS adalah voltan 230 Volt, 11 kV dan 33 kV. SP11 Supply planner 11 kV di sub zon. SP33 Supply planner 33 kV di zon Transient Kejadian perubahan voltan yang terlalu singkat (< 10 ms). Unbalance Kejadian voltan tidak seimbang. VS Voltan sederhana (11 hingga 33 kV) Voltage sag Penurunan voltan rms di antara 10 % hingga 90 % dalam tempuh 10 ms hingga 1 minit (A decrease to between 0.1 and 0.9 pu in rms voltage or current at the power frequency for durations of 0.5 cycle to 1 min). Statistik voltage sag di lapurkan dengan menggunakan indek SARFI (System Average RMS Frequency Index). Voltage step change Satu perubahan nilai RMS atau puncak voltan di antara dua peringkat berturut-turut dikekalkan untuk jangka masa yang pasti tetapi tidak diperincikan. (A variation of the RMS or peak value of a voltage between two consecutive levels sustained for definite but unspecified durations) Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 9 of 26 Edisi: 3 Tarikh: 8 Disember 2018 6.0 PROSEDUR 6.1 Peta proses bagi prosedur perancangan bekalan elektrik untuk pelanggan industri (LPC) pada paras voltan sederhana untuk mematuhi keperluan standard kualiti kuasa di Semenanjung Malaysia adalah seperti di Lampiran 3. Prosedur ini dikhaskan untuk permohonan bekalan elektrik baru (new supply application) bagi kategori industri pada paras voltan sederhana (VS). Prosedur ini juga boleh diapplikasikan untuk penambahan beban tambahan oleh pelanggan industri sediada. Perlaksanaan prosedur ini dikhaskan untuk industri berikut: Jenis industri pada paras voltan sederhana Semiconductor Industri logam Industri simin Industri data center Tren elektrik Industri aerospace Lain-lain Deklarasi voltage sag Ya Ya Ya Ya Deklarasi Kajian transient harmonik Ya Tidak Tidak Ya Ya Ya Ya Ya Kajian voltage step change Tidak Ya Ya Tidak Kajian flicker Kajian unbalance Tidak Ya Ya Tidak Tidak Tidak Tidak Tidak Ya Ya Ya Tidak Ya Ya Ya Tidak Ya Tidak Ya Tidak Ya Tidak Ya Tidak Tidak Tidak Sebarang pengecualian dari membuat kajian kualiti kuasa perlu dirujuk kepada Pakar Teknikal (Kualiti Kuasa & Kecekapan Tenaga) di AMSDS. Tiada pengecualian untuk membuat deklarasi kualiti kuasa untuk kejadian voltage sag. Sebarang pengecualian untuk membuat deklarasi kualiti kuasa untuk transient perlu dirujuk kepada Pakar Teknikal (Kualiti Kuasa & Kecekapan Tenaga) di AMSDS. Bagi deklarasi yang tidak mematuhi piawaian kualiti kuasa TNB, rujukan perlu dibuat kepada Pakar Teknikal (Kualiti Kuasa & Kecekapan Tenaga) di AMSDS untuk tindakan susulan. Bagi deklarasi & keputusan kajian yang tidak mematuhi piawaian kualiti kuasa TNB, rujukan perlu dibuat kepada Pakar Teknikal (Kualiti Kuasa & Kecekapan Tenaga) di AMSDS untuk tindakan susulan. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 10 of 26 Edisi: 3 Tarikh: 8 Disember 2018 6.1.1 LPC/ jurutera perunding memajukan permohonan bekalan elektrik ke pejabat TNB. 6.1.2 SP11/SP33 akan menentukan punca bekalan elektrik iaitu PMU/ PPU. Sila rujuk kepada PSI ENGR-750-51 (Prosedur perancangan projek bekalan dan sistem 22 kV dan ke bawah) dan PSI ENGR-750-56 (Prosedur perancangan projek bekalan dan sistem 33 kV). 6.1.3 SP11/SP33 akan mendaftarkan pelanggan dan memuat turun statistik kualiti kuasa dari laman sesawang PQMSWeb (http://10.163.160.32/pqmsweb). Sekiranya PMU/PPU berkenaan mempunyai sistem PQMS, SP11/SP33 akan rujuk Arahan Kerja ENGR-750-70-WI-01: Tatacara muat turun statistik kualiti kuasa bagi lokasi yang mempunyai sistem pemantauan kualiti kuasa (PQMS). Contoh rekod pendaftaran di laman PQMSWeb adalah seperti di Lampiran 4. (ENGR-750-70-QR01). Sila ke prosedur 6.1.6. Sekiranya PMU/PPU berkenaan tidak mempunyai sistem PQMS, SP11/SP33 akan meminta HEMP/ME untuk membuat tindakan berikut: HEMP/ME perlu membuat anggaran statistik ‘voltage sag’ atau SARFI menurut prosedur di dalam arahan Kerja ENGR-750-70-WI-02: Tatacara menyediakan statistik kualiti kuasa bagi lokasi yang tidak mempunyai sistem pemantauan kualiti kuasa (PQMS). Bagi data harmonik, flicker dan unbalance, HEMP/ME akan memasang alat perakam kualiti kuasa di PMU/ PPU. Sila ke prosedur 6.1.4. 6.1.4 HEMP/ME akan memasang alat perakam kualiti kuasa di PMU/ PPU untuk tempuh 7 hari. Sila rujuk kepada prosedur kerja ENGR-750-70-WI-02: Tatacara menyediakan statistik kualiti kuasa bagi lokasi yang tidak mempunyai sistem pemantauan kualiti kuasa (PQMS). 6.1.5 HEMP/ME akan memasukkan data harmonik, flicker dan unbalance ke sistem PQMSWeb dan memberi makluman kerja telah di siapkan kepada SP11/SP33. Sila rujuk kepada prosedur kerja ENGR-750-70-WI-02: Tatacara menyediakan statistik kualiti kuasa bagi lokasi yang tidak mempunyai sistem pemantauan kualiti kuasa (PQMS). Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 11 of 26 Edisi: 3 Tarikh: 8 Disember 2018 6.1.6 SP11/SP33 akan muat turun lapuran statistik kualiti kuasa (Lampiran 5: ENGR 75070-QR-02). & borang Appendix 8 (Lampiran 6: Declaration of Equipment Conformity on Power Quality Requirement). Sila rujuk kepada prosedur kerja ENGR-750-70-WI-03: Tatacara muat turun statistik kualiti kuasa dan menilai laporan kajian & deklarasi kualiti kuasa oleh LPC/ jurutera perunding. Lapuran statistik kualiti kuasa ini perlu ditandatangani oleh SP11/SP33. Borang Appendix 8 boleh juga di dapati dari buku ‘TNB’s Electricity Supply Application Handbook’ dan boleh dimuat turn (download) dari laman PQMSWeb. Semua lapuran statistik kualiti kuasa dan borang Appendix 8 ini dimajukan ke LPC/ jurutera perunding berkenaan. SP11/SP33 akan melaksanakan prosedur 6.1.15. 6.1.7 LPC/ jurutera perunding akan menilai statistik kualiti kuasa dan membuat penilaian kualiti kuasa terhadap cadangan sistem pendawaian dan peralatan elektrik yang akan dipasang di premis LPC. 6.1.8 Seterusnya, LPC/ jurutera perunding membuat kajian kualiti kuasa & deklarasi kualiti kuasa bagi semua sistem pepasangan yang akan di buat dalam premis pelanggan (pendawaian, peralatan fasiliti, produksi dll). Semua keputusan kajian dan deklarasi perlu di dilapurkan menggunakan borang Appendix 8 (Power Quality Declaration Form: Declaration of Equipment Conformity on Power Quality Requirement). Nota: Projek memberi bekalan elektrik tidak boleh dimulakan sekiranya LPC/ jurutera perunding gagal melaksanakan kajian kualiti kuasa dan membuat deklarasi kualiti kuasa. 6.1.9 LPC / jurutera perunding kemudiannya memajukan laporan kajian kualiti kuasa, dokumen deklarasi (certificate) kualiti kuasa & borang Appendix 8 yang lengkap kepada SP11/SP33. 6.1.10 SP11/SP33 menerima laporan kajian kualiti kuasa, dokumen deklarasi (certificate) kualiti kuasa & borang Appendix 8. Untuk rekod, dokumen Appendix 8 yang diterima dari LPC/Jurutera perunding perlu di muatnaik (upload) ke laman sesawang PQMWeb. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 12 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Dokumen lain perlu disimpan dalam fail projek. SP11/SP33 memeriksa semua dokumen ini dan menilai maklumat tahap immuniti dan emisi kualiti kuasa untuk kejadian ’voltage sag’, ’transient, ’harmonic’, ’voltage change’, ’flicker’ dan ’unbalance’ yang dilaporkan dalam dokumen ini. Sila rujuk kepada prosedur kerja ENGR-750-70-WI-03: Tatacara muat turun statistik kualiti kuasa dan menilai laporan kajian & deklarasi kualiti kuasa oleh LPC/ jurutera perunding. Tahap emisi yang dibenarkan adalah:Kejadian kualiti kuasa Standard teknikal Harmonic Engineering Recommendation (E/R) G 5/4 Voltage step change Engineering Recommendation P28 Tahap emisi yang dibenarkan Voltan 0.400 6.6 kV, 11 kV and 20 kV 22 kV to 400 kV THDV (%) 5.0 4.0 3.0 Indices Acceptable permissible values at point of common coupling (PCC) ∆V % 1% - Frequent starting/ switching and/ or disconnection of load. 3 % - Infrequent single starting/ switching or disconnection of Load – once in two hours or more hours. 6 % - Starting/switching once or twice a year . Flicker Unbalance Engineering Recommendation P28 Engineering Recommendation P29 Voltage ≤ 132 kV > 132kV PST 1.0 0.8 PLT 0.8 0.6 2% Tajuk Prosedur: PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA Jenis Dokumen: Aras II KAWALAN PROSES NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 13 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Tahap immunity minima yang dibenarkan adalah:Kejadian kualiti kuasa Voltage Sag (Peralatan Fasiliti) Standard teknikal Tahap minima immuniti yang dibenarkan IEC 61000-4-11 (Class 3) & IEC 61000-4-34 (Class 3) % Graph A 100 90 % of nominal voltage 80 70 60 50 40 30 20 Graph B 10 ms 0 20 50 100 150 200 300 400 500 600 700 1000 2000 3000 4000 5000 Duration of Voltage Sag (ms) IEC 61000-4-11 / 34 (Class 3) Voltage Sag (Peralatan produksi) Transients IEC 61000-4-11 (Class 1) & IEC 61000-4-34 (Class 1) Voltage % Based on equipment requirement for protection against voltage sags Duration (ms) Based on equipment requirement for protection against voltage sags General requirement 0% General requirement 1000 ms IEC 61000-4-5 Declaration of compliance Test & immunity classification: Class 0 to class 5 Critical equipment Facility / Production Facility / Production Facility / Production Facility / Production Facility / Production Compliance Class 1 2 3 4 5 Sekiranya tahap kualiti kuasa bagi LPC menepati tahap emisi / immuniti kualiti kuasa yang dibenarkan, sila ke prosedur 6.1.11. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 14 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Sekiranya tahap kualiti kuasa bagi LPC tidak menepati tahap emisi / immuniti kualiti kuasa yang dibenarkan, sila ke prosedur 6.1.12. 6.1.11 SP11/SP33 muat turun (download) surat status penilaian dan pematuhan piawaian kualiti kuasa untuk diberi kepada LPC/ jurutera perunding. Format surat boleh dimuat turun dari PQMSWeb. Semua surat yang telah ditandatangan perlu dimuat naik di laman sesawang PQMSWeb. 6.1.12 Sekiranya tahap kualiti kuasa bagi LPC tidak menepati tahap emisi / immuniti kualiti kuasa, SP11/SP33 akan memberi surat kepada LPC/ jurutera perunding untuk mengambil tindakan untuk mematuhi standard kualiti kuasa. Format surat boleh dimuat turun dari laman sesawang PQMSWeb. Semua surat yang telah ditandatangan perlu dimuat naik di laman sesawang PQMSWeb. Salinan surat diberi kepada pejabat Suruhanjaya Tenaga (ST) di Putrajaya & Pakar Teknikal (Kualiti Kuasa & Kecekapan Tenaga). Di dalam laporan kajian kualiti kuasa mesti mencadangkan mitigasi yang sesuai untuk memastikan LPC mematuhi piawaian kualiti kuasa TNB. 6.1.13 Proses tamat 7.0 INPUT / SUMBER Permohonan bekalan baru atau permohonan penambahan beban dari LPC / jurutera perunding. 8.0 OUTPUT / PENERIMA Borang Appendix 8. Lapuran kajian kualiti kuasa Deklarasi kualiti kuasa Laporan Rekod Kualiti ENGR-750-70-QR-04: Senarai pelanggan dan status pematuhan standard kualiti kuasa. Tajuk Prosedur: PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA Jenis Dokumen: Aras II KAWALAN PROSES NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN 9.0 Nombor Dokumen: ENGR-750-70 Mukasurat: Page 15 of 26 Edisi: 3 Tarikh: 8 Disember 2018 REKOD KUALITI Rekod Nombor Borang Tempat Simpanan Tempoh Simpanan Senarai pendaftaran pelanggan industri baru untuk muat turun statistik kualiti kuasa. ENGR-750-70-QR-01 PQMS Web 5 Tahun Statistics on Power Quality for New Supply Application for use by customers Rekod pelanggan dan pematuhan kepada standard kualiti kuasa ENGR-750-70-QR-02 ENGR-750-70-QR-04 Fail projek bekalan baru di pejabat zon/ subzon. Fail projek bekalan baru di pejabat zon/ subzon. 5 Tahun 5 Tahun PQMS Web 10.0 PENANDA UTAMA PRESTASI (KPI) Penanda Utama Prestasi Rekod pelanggan dan pematuhan kepada standard kualiti kuasa Pengukuran Semua pelanggan LPC industri di daftar dan diberi makluman mengenai keperluan standard kualiti kuasa. Semua pelanggan LPC industri melaksanakan kajian & deklarasi kualiti kuasa. 11.0 LAMPIRAN Lampiran 1: Para 39 di ‘Conditions of Supply for Business and Non Domestic Consumers’ (A-Form) Lampiran 2: Contoh borang kontrak Bekalan Khas (Customized Supply Contract) Lampiran 3 : Peta Proses Perancangan Bekalan Elektrik Untuk Pelanggan Industri Yang Mematuhi Keperluan Standard Kualiti Kuasa Lampiran 4: Borang Kualiti ENGR-750-70-QR-01 Contoh rekod pendaftaran LPC di laman PQMSWeb Lampiran 5: Borang Kualiti ENGR-750-70-QR-02 Format penyerahan ringkasan data kualiti kuasa kepada pelanggan/ jurutera perunding untuk melaksanakan kajian kualiti kuasa Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Lampiran 6: Nombor Dokumen: ENGR-750-70 Mukasurat: Page 16 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Borang Kualiti ENGR-750-70-QR-03 Borang Appendix 8 (Power Quality Declaration Form: Declaration of Equipment Conformity on Power Quality Requirement). 12.0 WORK INSTRUCTION BERKAITAN ENGR-750-70-WI-01 : Tatacara muat turun statistik kualiti kuasa bagi lokasi yang mempunyai sistem pemantauan kualiti kuasa (PQMS). ENGR-750-70-WI-02 : Tatacara menyediakan statistik kualiti kuasa bagi lokasi yang tidak mempunyai sistem pemantauan kualiti kuasa (PQMS). ENGR-750-70-WI-03: Tatacara muat turun statistik kualiti kuasa dan menilai laporan kajian & deklarasi kualiti kuasa oleh LPC/ jurutera perunding. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 17 of 26 Edisi: 3 Tarikh: 8 Disember 2018 LAMPIRAN 1 Clause (Established with the new ESAH) Para 39 di borang permohonan bekalan (A-Form) The customer shall ensure all its electrical installations have sufficient immunity against short duration voltage events (sags & swells) and transient events, and shall not generate other significant power quality voltage signatures that might have detrimental effects to the electrical supply systems. The related power quality technical standards are defined in TNB Electricity Supply Application Handbook (ESAH). Versi Bahasa Malaysia Para 35 di borang permohonan bekalan (A-Form) Pelanggan hendaklah memastikan semua pepasangan elektrik mempunyai imuniti yang mencukupi terhadap kejadian voltan pendek tempoh (sags & swell) dan kejadian voltan fana, dan tidak boleh menjana kejadian kualiti kuasa lain yang mungkin mempunyai kesan yang memudaratkan sistem bekalan elektrik. Standard kualiti kuasa yang berkaitan adalah ditakrifkan dalam buku panduan permohonan bekalan elektrik (ESAH) Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 18 of 26 Edisi: 3 Tarikh: 8 Disember 2018 LAMPIRAN 2 Annexure E OPERATING GUIDELINES AND POWER FACTOR FOR ALL VOLTAGE LEVELS E1. OPERATING GUIDELINES E1.1 The consumer shall have an obligation to ensure the following operational requirements are satisfied in the operation of the consumer’s installation. (i) Nominal voltage & steady state voltage regulations Nominal voltage (kV) 500 275 132 33 22 11 0.400 & 0.230 (ii) % Variation +10%,- 5 % +10%,- 5 % +10%,- 5 % ±5% ±5% ±5% +10%, -6% Short duration voltage disturbances All voltage sensitive/critical equipment and control system within the consumer’s premises shall be designed to be able to ride through or be immune to all short duration voltage disturbances i.e. voltage sags, short duration overvoltage (voltage swells) and very short duration overvoltage (transients) that exist in TNB’s power system electromagnetic environment. The standards to refer to ensure all voltage sensitive/critical equipment and control systems are immune to voltage sags are IEC 61000-2-8, IEC 61000-4-11 & IEC 61000-4-34.The selection of the immunity classes (C1, C2, C3) are based on the sensitivity and criticality of each equipment. The standards to refer to ensure all voltage sensitive/critical equipment and control systems are immune to short duration overvoltage & very short duration overvoltage are IEC 61000-214, IEC 61000-4-2, IEC 61000-4-4, IEC 61000-4-5 etc. (iii) Basic Insulation Level (BIL) Electrical power and distribution apparatus must be assigned a given insulation class and capable of withstanding, without flashover or apparent damage, an impulse test of specified crest kV. This specified crest voltage is the basic insulation level (BIL) of the equipment. Overall, the consumer’s electrical power and distribution apparatus shall be compatible with the BIL requirement. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN System voltage (kV) 500 275 132 33 22 11 & 6.6 (iv) Nombor Dokumen: ENGR-750-70 Mukasurat: Page 19 of 26 Edisi: 3 Tarikh: 8 Disember 2018 BIL (kV) 1425 1050 450 150 125 75 Voltage step change A voltage change is a single variation of the RMS voltage ( V RMS ) or peak value ( V P ) of the voltage signal in time domain. RMS is the root mean square. The RMS voltage, VRMS is calculated by taking the square root of the mean average of the square of the voltage signal in time domain in an appropriately chosen interval and is given by, VRMS 1T v(t ) 2 dt T 0 where, T : period of a voltage signal v(t ) : continuous function of a voltage signal in time domain The allowable % RMS ( V RMS ) or peak value ( V P ) voltage change values are defined as follows:Type Of Disturbance Voltage Step Change (v) Indices ∆V % Acceptable permissible values at Reference point of common coupling (PCC) Document 1% - Frequent starting/ switching and/or disconnection of motor/ load. 3 % - Infrequent single starting/ Engineering switching or disconnection of Recommendation motor/load – once in two hours or (E/R) P28 more hours. 6 % - Starting/ switching once or twice a year. Flickers constraints Flicker is the name given to changing light intensity caused by fluctuations in the voltage. It is a common power quality problem causing both irritation and possible medical consequences to users exposed to its effects. Tajuk Prosedur: PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA Jenis Dokumen: Aras II KAWALAN PROSES NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN The maximum flicker level Recommendation (E/R) P28. System voltage (kV) 500, 275 and 132kV Less than 132kV Mnemonic PST PLT (vi) shall be within Absolute short term flicker severity (PST) 0.8 1.0 the limits Nombor Dokumen: ENGR-750-70 Mukasurat: Page 20 of 26 Edisi: 3 Tarikh: 8 Disember 2018 specified in Engineering Absolute long term flicker severity (PLT) 0.6 0.8 Definition Short Term Flicker Perceptibility Long Term Flicker Perceptibility Harmonics constraints Harmonic distortion is the departure of a waveform from sinusoidal shape that is caused by the addition of one or more harmonics to the fundamental waveform due to the existence of non-linear electric loads etc. Harmonic frequencies in the power system are a frequent cause of power quality problems. Harmonics in power systems result in increased heating in the equipment and conductors, misfiring in variable speed drives, capacitor damage, torque pulsations in motors etc. The harmonic distortion level at the Point of Common Coupling (PCC) shall be within the limits specified in the Engineering Recommendation (E/R) G5/4 based on the respective voltage levels as shown below. Harmonics Planning Limits -Total Harmonic Distortion (THD) Voltage (kV) 0.400 6.6 kV, 11 kV and 20 kV 22 kV to 400 kV (vii) THD (%) 5.0 4.0 3.0 Voltage unbalance The magnitude of the negative phase sequence component (NPS) at the Point of Common Coupling (PCC) must be within 2% of the positive phase sequence component. The limits imposed at PCC are made reference to Engineering Recommendation (E/R) P29. (viii) Short Circuit Levels The consumer’s installation shall be planned such that the maximum subtransient three phase symmetrical short circuit fault levels are not greater than 90 % of the design short circuit break and make capacity of switchgear connected to TNB’s power system and within 90 % of the short time current rating of equipment connected to the TNB’s power system. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nominal Voltage (kV) 500 275 132 33 11 0.4 E1.2 E1.3 Nombor Dokumen: ENGR-750-70 Mukasurat: Page 21 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Fault Current (kA) 50 40 31.5 25 20 31.5 Compensating/ mitigation equipment (i) Whenever the operation of the consumer’s facilities, plants and/or equipment leads to the violation of the limits in Clauses E1.1 (iv), (v), (vi) & (vii), a compensating / mitigation equipment shall be installed and provided by the consumer at its own cost and expense to reduce the power quality disturbances to be below the stipulated limits. The consumer shall ensure that no resonance phenomenon is induced due to the interaction between the consumer’s Installation (after the installation of the compensating/ mitigation equipment) and TNB’s power system. (ii) The consumer shall warrant that no violation of the limits stipulated under Clauses E1.1 (iv), (v), (vi) & (vii), shall occur in all situations during the consumer’s operations including but not limited to during any emergency feeding conditions, changes of the consumer’s operational parameter, faulty equipments, maintenance of the consumer’s equipments or due to the consumer’s equipments having been switched-off. Disconnection of Electricity Supply (i) If the limits stipulated in Clauses E1.1 (iv), (v), (vi) & (vii), above are violated under any situation, including emergency feeding conditions, the consumer shall rectify the said violation within stipulated time as requested by TNB. In the event the consumer fails to rectify the said violation, TNB has the right to disconnect the electricity supply without prior notice to the Said Premises. (ii) In the event that TNB has exercised its rights under clause E1.3 of the Agreement, TNB shall not be liable to the consumer for such disconnection, cessation, interruption, reduction or defect in the supply of electricity or for any loss, damage, cost or expenses resulting there from which includes but not limited to for any loss of profits, business, goodwill, opportunity or special, exemplary, indirect, incidental, consequential or punitive damages of any kind for any reason, whether such liability is asserted on the basis of contract, tort (including negligence and strict liability) or otherwise, even if TNB has been advised of the possibility of such damages. Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN Nombor Dokumen: ENGR-750-70 Mukasurat: Page 22 of 26 Edisi: 3 Tarikh: 8 Disember 2018 E2. POWER FACTOR E2.1 The consumer shall obtain the highest power factor possible in the operation of the consumer’s Installation. E2.2 The consumer shall be subject to supplementary charge(s) as provided in Annexure D for failure to maintain certain level(s) of power factor. E2.3 If the consumer's power factor is found to be constantly below 0.90 lagging (for 132 kV and above) or below 0.85 lagging (for 132 kV below) for a period of three (3) months and after written notice to improve its power factor has been issued, TNB may consider taking action to disconnect the electricity supply. Reconnection of the electricity supply shall only be restored after TNB is satisfied that the power factor has improved to the acceptable value. Tajuk Prosedur: PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA Jenis Dokumen: Aras II KAWALAN PROSES NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN LPC / Jurutera Perunding Mula SP11 / SP33 6.1.2 Menentukan rekabentuk sistem & punca bekalan elektrik 6.1.7 Menilai statistik kualiti kuasa 6.1.3 Daftar pelanggan di laman PQMSWeb & muat turun data 6.1.8 Membuat kajian kualiti kuasa & deklarasi kualiti kuasa. 6.1.6 Menyediakan lapuran statistik kualiti kuasa & muat turun borang Appendix 8 ENGR-750-70 Mukasurat: Page 23 of 26 Edisi: 3 Tarikh: 8 Disember 2018 PETA PROSES BAGI PROSEDUR PEMATUHAN SYARAT LESEN TNB BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA 6.1.1 Majukan permohonan Nombor Dokumen: LAMPIRAN 3 6.1.9 Memajukan laporan, deklarasi & borang Appendix 8 6.1.10 Menerima laporan, deklarasi & borang Appendix 8 6.1.12 Upload semua dokumen ke PQMSWeb & muat turun surat tiada pematuhan untuk LPC Tidak Ya Ada data sag, harmonic, flicker & unbalance? Patuhi standard kualiti kuasa? Ya 6.1.13 Tamat HEMP / ME Tiada 6.1.4 Memasang alat perakam selama 7 hari 6.1.5 Muat naik data ke PQMSWeb 6.1.11 Upload semua dokumen ke PQMSWeb & muat turun surat pematuhan untuk LPC Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN LAMPIRAN 4 Nombor Dokumen: ENGR-750-70 Mukasurat: Page 1 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Contoh borang rekod kualiti ENGR-750-70-QR-01 Tajuk Prosedur: PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA Jenis Dokumen: Aras II KAWALAN PROSES NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN LAMPIRAN 5 Page 1 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Contoh borang rekod kualiti ENGR-750-70-QR-02 Site’s details Source (PMU/PPU) Voltage level (kV): Fault Level: Type 3-phase 1-phase 2.0 3.0 kA Voltage sags statistics (SARFI) Parameters SARFI 90 80 70 60 50 40 Harmonics statistics Parameter Harmonic Harmonic Harmonic Harmonic Harmonic 3 5 7 11 13 THDV % Values 4.0 Voltage Change, Flickers & Unbalance statistics Power Quality parameters Voltage Change (%) Flickers Existing values at source Non Applicable (Equipment starting & Arc furnace) Index PST PLT Unbalance (%) Prepared by Engineer Supply Planner Signature: ……………………………… Name: ……………..…………………… Date: ………………………..………… Value ENGR-750-70 Mukasurat: Power Quality Statistics for New Supply Applications 1.0 Nombor Dokumen: Tajuk Prosedur: Jenis Dokumen: Aras II KAWALAN PROSES PROSEDUR PEMATUHAN SYARAT LESEN TNB NO 30 BAGI PERANCANGAN BEKALAN ELEKTRIK UNTUK PELANGGAN INDUSTRI YANG MEMATUHI KEPERLUAN STANDARD KUALITI KUASA NAIB PRESIDEN BAHAGIAN PEMBAHAGIAN LAMPIRAN 6 Nombor Dokumen: ENGR-750-70 Mukasurat: Page 2 of 26 Edisi: 3 Tarikh: 8 Disember 2018 Contoh borang rekod kualiti ENGR-750-70-QR-03 APPENDIX 8 Power Quality Declaration Form Declaration of Electromagnetic Compatibility (EMC) Compliance 1.0 Name of customer 2.0 Area / State: 3.0 Type of industry: 4.0 Declared Maximum Demand (MW): Types Of PQ Disturbances Reference Standards Declaration / Results of PQ study/ Compliance Voltage Step Change Engineering Recommendation ERP28 Voltage Flicker Engineering Recommendation ERP28 Location Point of common coupling Harmonic Distortion Engineering Recommendation ER G5/4 Location Point of common coupling THDV (%) Voltage Unbalance Engineering Recommendation ERP29 Location Point of common coupling % Type of equipment Category ∆V % PST PLT Declaration of compliance Voltage sags IEC 61000-4-11 & IEC 61000-4-34 Critical equipment Compliance Class Test & immunity classification: Class 1 to class 3 Declaration of compliance Transients IEC 61000-4-5 Critical equipment Test & immunity classification: Class 0 to class 5 Prepared by Signature: Approved by Signature: Name: Date: Name: Date: Compliance Class Compliance (Yes/No)