COLD WATER SUPPLY SYSTEM Introduction Building water supply system is a system in plumbing which provides and distributes water to the different parts of the building or structure, for purposes such as drinking, cleaning, washing, culinary use, etc.; it includes the water distributing pipes, control devices, equipment, and other appurtenances. Introduction Cold water system provides water for the following purposes; 1. Drinking purpose. 2. Cooking purpose. 3. Sanitary purpose. 4. Washing purpose. 5. Gardening Definitions 1. Cistern - a container for water having a free water surface at atmospheric pressure 2. Feed cistern - any storage cistern used for supplying cold water to a hot water apparatus 3. Storage cistern - any cistern other than a flushing cistern, having a free water surface under atmospheric pressure, but not including a drinking trough or drinking bowl for animals. Definitions cont........ 3. Capacity of a cistern - the capacity up to the water line 4. Water line - a line marked inside the cistern to indicate the water level at which the ball valve should be adjusted to shut off 5. Overflowing level - the lowest level at which water can flow into that pipe from a cistern. Definitions cont...... 6. Warning pipe - an overflow pipe so fixed that its outlet end is in an exposed and conspicuous position and where the discharge of any water from the pipe may be readily seen and, where practicable, outside the building. 7. Communication pipe- any service pipe from the water main to the stop valve fitted on the pipe. 8. Service pipe - any pipe for supplying water from a main to any premises as is subject to water pressure from that main, or would be so subject but for the closing of some stop valve. Definitions cont.... 9 Distributing pipe - any pipe for conveying water from a cistern, and under pressure from that cistern. 10 Supply pipe - so much of any service pipe which is not a communicating pipe. 11 Main - a pipe for general conveyance of water as distinct from the conveyance to individual premises. Definitions cont.......... . 12 Hot water cylinder or tank - a closed container for hot water under more than atmospheric pressure. Note: a cylinder is deemed to include a tank. 13 Potable - water suitable for drinking. 14 Fitting - anything fitted or fixed in connection with the supply, measurement, control, distribution, utilization or disposal of water. Figl.1 Connection to water main Installed and maintained by water authority Installed and maintained by building owner Stop valve chamber Communication pipe 760mm (minimum) service pipe water main Water authorities stop valve Distribution systems There are two types of water supply systems; 1. non storage or direct and 2. storage or indirect systems Non storage or Direct Systems • It is a system whereby all the sanitary fittings are supplied with cold water direct from the main. In this system, a cold water feed cistern is usually required to feed the hot water supply system Fig 1.2 Direct cold water supply system . I I I ······ ··············-············· II � COid feed 10 dl1w j I I I I ··<><1- t t X, OR dhw l jWC 15mm basin 15mm sink 22mm storage vessel cold suP!lly 10 nvemed system u bath of dhw 22mm 22mm washing macnine basin -cistern WC Storage or Indirect Systems • It is a system whereby all the drinking water used in the building is supplied from the main and water used for all other purposes is supplied indirectly from a cold water storage cistern. • The cistern also supplies water to the hot water cylinder therefore its capacity will almost double the capacity required for the direct system Fig 1.3 Indirect cold water supply system service valve-��- WC 15mm -reed and storage clstem .______, , COklfeedtOdhw ' / ...._,._ / �(ventedsystem) 22-28 mm runway cold dlstJibutlongaievalVe 22-28 mm or ballvalve dhw storage vessel basin baU, 22mm 15mm 22mm supply maln sink washing machine doc :t><- l-1>¢doc stop valve WC service ---'--'---' valVe Table 1.1 Advantages of Direct and Indirect cold water systems S/No Direct or non storage 1 Less pipework and smaller or no cistern, making it easier and cheaper to install. 2 Drinking water is available at all draw-off points. S/No Indirect or storage Large capacity cistern provides a reserve of water during interruption of supply. 2 Water pressure on the taps supplied from the cistern is reduced, which minimizes wear on taps and noise. Fittings supplied with water from the cistern are prevented from causing pollution of the drinking water by back siphon age Lower demand on the water main 1 3 Smaller cisterns which may be sited below the ceiling. 3 4 In systems without cistern there is no risk of polluting the water from this source 4 Prevention of Back Siphonage • Back siphonage is the back flow of water, which may be contaminated, into the drinking water supply. • The condition for back siphonage to happen is the creation of negative pressure or partial vacuum in the pipe connected to an appliance having its outlet submersed in water, which may be contaminated. Prevention of Back Siphonage cont... • Back pressure is the result of water pressure in the system being greater than that in the supply. Higher system pressures can be caused by the expansion of water in unvented domestic hot water supplies, or in systems where a pump is used. • Negative pressures in the supply main may be caused by a major leak in the main or the fire services drawing off vast amounts of water. The points which must be observed for prevention of risk of back siphonage 1. The ball valves in the cisterns must be above the overflow pipe and if the silencer pipe is fitted must discharge water above the ball valve through a spray. 2. The outlets of taps connected to sanitary appliances must be well above the flooding level of the appliance. The points which must be observed for prevention of risk of back siphonage cont ..... 3. Flushing valves for WCs must be supplied from a cold water storage cistern. 4. Appliances having low-level water inlets, for example bidets and certain types of hospital appliance, must be supplied from a cold water storage cistern and never direct from the main Water Storage Purposes of water storage DProvide for an interruption of supply DAccommodate peak demand DProvide a pressure (head) for gravity supplies Design factors DType and number of fittings DFrequency and pattern of use Dlikelihood and frequency of breakdown of supply (often design for 12- or 24-hour reserve capacity) According to regulations, the installed cistern must be; 1. Watertight, adequate strength, and manufactured from plastic, galvanized steel, asbestos cement or copper. 2. Sited at a height that will provide sufficient head and discharge of water to the fittings supplied. 3. placed in a position where it can be readily inspected and cleansed According to regulations, the installed cistern must be; 4. Provided with dust proof but not air tight cover and protected from damage by frost. 5. Fitted with an efficient overflow pipe which should have a fall as great as practicable not less than 1 in 10. Fig 1.4 Method of installing cold water storage or feed cistern Inlet •llen<or vont pipe from hOl•w.tter cylinder •Ommi ,40mm 25mm1 1 50mm , Wetnll'!-1) or overflow pipe Stop valve Full-way oatov11tve 50mm' 1 Coiling Jots-ts 01,1rlbutlng plS)lt to ..a.nltary appfbmcos Fig 1.6 Method of duplicating cold water storage cisterns Cold..water Feed pipes Table 1.2 Provision of cold water storage to cover 24 Hours interruption of supply Type of building Dwelling houses and flats Storage (L) per resident 90 Hostels per resident 90 Hotels per resident 140 Offices without canteens per head 40 Offices with canteens per head 45 Restaurants meal Day schools per head/per 10 per head 30 Boarding schools per head 90 Nurses homes and medical quarters per resident 115 Table 1.3 Recommended minimum storage of cold and hot water systems e of buildin Hostel Hotel Office premises: - with canteen facilities - without canteen facilities Restamant Day school: - nursery or primary - seconda or technical Minimum cold water 15 per pupil 20 ii Children's home or residential nurse 135 120 Nurses' home Nursing or convalescent 135 er bed s ace home {Source: Garrett, R. H., 2008. Hot and Cold Water Supply) Minimum hot water 4.5 per pupil LI ii 5.0 23 25 45 45 Note: Minimum cold water storage shown includes that used to supply hot water outlets Table 1.4 Estimation of cold water storage per occupant Type of building Hospitals, per staff on duty Hostels Hotels Houses and flats Offices with canteens Offices without canteens Restaurant (* per meal) Schools, boarding Schools, day Storage per occupant (litres) 45 90 135 135 45 35 7 90 30 Table 1.5 Provision of cold water storage to cover 24 Hours interruption of supply. Based on sanitary appliances Sanitary appliance Water closet (WC) Sink Water basin Shower Urinal Storage (L) 180 135 - 225 90 - 250 135 - 225 135 - 250 Table 1.6 Access to storage cistern locati1on Around Between. tanks Above. all1CWJlllQ beams to lntruoe Below. between suooorts For ouUet oioe work. incl. access Tank ocmstnrouoni thickness 111nsulation 1f rnav form oairt of tank) IRatseo float va!ve housino Entry to tank (mm)1 750 750 1000 160) 1500 100 . 25 300 a001 d1a Table 1. 7 Water storage plant room area Sto:r.a,ge (Li1res} .. 5.000 10,00 , 0 20.•,000 I 40,:000 601,,000 100,0001 lank Keight 3 metre 1.5 metn 2me1re 18,m2 31rn2 o0m 2 2 72m - - 16m2 23m2 40m2 2 60m.. 80m1! . 10m2 - 5 50m . 60m 2 80m,2 Design principles I. Cold water system A: Potable water • Drinking purpose. • Cooking purpose. s: Non-potable water • Flushing water(fresh or salt water) • Cleansing water • Fire service • Swimming-pool filtration for • lrrigation(e.g. landscape) • Fountain circulation • Air-conditioning water, etc. II. Hot water system (e.g. in hotels & hospitals Design principles cont .... Major tasks of water systems design: 1. Assessment & estimation of demands 2. Supply scheme & schematic 3. Water storage requirements 4. Piping layout 5. Pipe sizing 6. Pump system design Water demand Water demand depends on: OType of building & its function ONumber of occupants, permanent or transitional DRequirement for fire protection systems OLandscape & water features Typical appliances using the cold water Owe cistern, wash basin, bath, shower, sink OWashing machine, dishwasher OUrinal flushing cistern Water demand cont...... Simultaneous demand DMost fittings are used only at irregular intervals Dlt is unlikely that all the appliances will be used simultaneously . Therefore there is no need to size pipe work on continuous maximum Key factors to consider: OCapacity of appliance (L) 0Draw-off flow rate (L/s) 0Draw-off period, or time taken to fill appliance (sec) DFrequency of use, time between each use (sec) Water demand cont...... Loading Unit {LU) : A factor given to an appliance relating the flow rate at its terminal fitting to DLength of time in use OFrequency of use for a particular type OUse of building NOTE DEvaluate the 'probable maximum' DRelates the flow rate to the probable usage Oconsider design & minimum flow rates Table 1.8 Design flow rates and loading units Otsign flow mtt (1/s) '.\fiuimum Dow mie (Its) Loading units 0.13 0.05 2 WC trough cistern 0.15pcrWC 0.10 2 Wash basin tap size Y,-DN 15 0.15pertap 0.10 1.5-3.0 Spray rap orspray mixer 0.05 per tap 0.30 - Bidet 0.2 per tap 0.10 I Bath tap. %-DN 20 0.30 0.20 10 Bath tap. 1-DN 25 0.60 0.40 22 0.2 hot or cold 0.10 3 Sink rap. V,-DN 15 0.20 0.10 3 Sink tap. %-DN 20 0.30 0.20 5 0.2 hot or cold 0.15 - 0.15 0.10 3 0.004 per position 0.002 Outlti firtiug WC flushing cistern single or dual fl11sh (to 611.Ill -? nuu. . ) Shower he.id (will \"ary \\�th type of head) Washing machine size-ON 15 Dishwasher size-ON 15 Urinal flushing cistern (Sour«: G,ma. R. H., 200S. Hor and Cold ffali'T �) - ·- 8000 "'... QI 0 ..."' :;: 5000 "° .!: 2000 soo ""' ..Q I "' 200 .c u • -.... cleaners' sink 0 3 2 100 'i?! QI 1.0 > C 0 50 ": 0.8 06 . "2 •§ � o. I e 0.5 � go '6 • 0,4 ·; 20 _.3 10 .5 0.3 2 urinal bowls "-. · 12 wash basins x 1.5 = 18 10 WCs x 2 = 20 = 2 urinal bowls x 2 cleaners' sinks x 3 =6 Total loading units =44 4 1.5 C ... "° ii: 8 wash basins � 10 5 "' QI ::J 20 8 1000 ::J ... 6WCs 2S 15 0 .�C 30 � J £ How about urinals? 0.004L/s/urinal continuous Required design flow (from graph) = 0.7 L/s + 0.008L/s = 0.71 L/s i ...... si -� 11'1 C :J 1:11) C - ,:, 111 0 0 QI 11'1 :J 0 QI a. E 111 )( k � Design flow considerations DA small increase in demand over design level will cause a slight reduction in pressure/flow (unlikely to be noticed by users) Exceptional cases: OCleaners' sinks (depends on one's behavior) DUrinal flushing cisterns (continuous small flow) DTeam changing rooms at sport clubs (high demand) 0Special events (ad hoc demand) Pipe sizing-Introduction Correct pipe sizes will ensure adequate flow rates at appliances and avoid problem caused by over sizing and under sizing; Over sizing will mean: - additional and unnecessary installation costs; - delays in obtaining hot water at outlets; - increased heat losses from hot water distributing pipes. Under sizing may lead to: - inadequate delivery from outlets and possibly no delivery at some outlets during simultaneous use; - some variation in temperature and pressure at outlets, especially showers and other mixers; - some increase in noise levels. Fig 1.8 Pipe sizing-Introduction lo) flow nne o through pipe unde, consldom1lon o 11t point of delivery I Ill bead= 9.81 kPa = 98. l mbar A,'l\Uable head (from cistern) ��/ lbl ovelleble heod c vertical distance in metrcS from water line in cistern 10 point Wider consideration A,-nj]able head (mains supply) "'head at ru.,in minus height above main =20m-4 m = 16mbcad (pressure) o at the wornr ma,n o from the storage cistern o ot po,nt of dollvory cwsc ..... � ----=- 31 Sizing procedure for supply pipes • The procedure below is followed by an explanation of each step with appropriate examples. (1) Assume a pipe diameter. (2) Determine the flow rate: {a) by using loading units; {b) for continuous flows; {c) obtain the design flow rate by adding {a) and {b). {3) Determine the effective pipe length: {d) work out the measured pipe length; {e) work out the equivalent pipe length for fittings; {f) work out the equivalent pipe length for draw-offs; {g) obtain the effective pipe length by adding {d), {e) and {f). Sizing procedure for supply pipes cont... (4) Calculate the permissible loss of head: (h) determine the available head: (i) determine the head loss per metre run through pipes; (j) determine the head loss through fittings; (k) calculate the permissible head loss. (5) Determine the pipe diameter: (I) decide whether the assumed pipe size will give Equivalent pipe length • Equivalent pipe length Is the expression of friction resistances to flow through valves and fittings in terms of pipe lengths having the same resistance to flow as the valve or fitting. • For example, a 20 mm elbow offers the same resistance to flow as a 20 mm pipe 0.8 m long. • Effective pipe length. The effective pipe length is the sum of the measured pipe length and the equivalent pipe lengths for fittings (e) and draw-offs (f). Fig 1.9 Equivalent pipe length cont... - L. . 0 .-4 .-4 ca a,. .-4 -.c .... VI Cl.I C'D Cl.I Cl.I VI A r 20 mm elbow= 0.8 m pipe length 20 mm tee= 1.0 m pipe length 20 mm draw-off tap - 3.7 m pipe length 20 mm stopvalve= 7.0 m pipe length -{><)20 mm check valve= 4.3 m pipe length Table 1.9 Equivalent pipe lengths (copper, stainless steel and plastics) Equh·aleot pipe length (m) Bore of pipe (mm) Elbow Tee Stopvnh·e Check vain 12 0.5 0.6 4.0 2.5 20 0.8 1.0 7.0 4.3 25 1.0 1.5 10.0 5.6 32 1.4 2.0 13.0 6.0 40 1.7 2.5 16.0 7.9 ? ' 3.5 11.5 3.0 4.5 22.0 ... 3.4 5.8 34.0 ... 50 65 73 -·" (Source: Garrett, R.H., 2008. Hot and Cold Water Supply) ... Equivalent pipe lengths (copper, stainless steel and plastics) cont ... Notes: 1. For tees consider change of direction only. For gate valves losses are insignificant. 2. For fittings not shown, consult manufacturers if significant head losses are expected. 3. For galvanized steel pipes in a small installation, pipe sizing calculations may be based on the data in this table for equivalent nominal sizes of smooth bore pipes. For larger installations, data relating specifically to galvanized steel should be used. BS 6700 refers to suitable data in the Plumbing Engineering Services Design Guide published by the Institute of Plumbing. Table 1.10 Typical head losses and equivalent pipe lengths for taps �ominal size of tap Flow rate (l/s) Head loss (m) EquiY. pipe len�h (m) Gl/2· DN 15 0.15 0.5 3.7 Gl/2· DN 15 0.20 0.8 3.7 G3/4· DN20 0.30 0.8 l l.8 Gl-DN25 0.60 1.5 22.0 16 (Source: Garrett, R. H., 2008. Hot and Cold Water Supply) Fig 1.10 Example of measured and effective pipe length Assumed pipe diameter 20 mm. double check valve assembly "°"\' \ �� pipe bend �IJ 0.25m draw-f off taps Measured pipe length 4.75m. Measured pipe length= 4.75 m Note: There is no need Equivalent pipe lengths: to consider both branch elbows 2 x 0.8 = 1.6 m pipes to taps. tee 1 x 1.0 = 1.0 m Stop valve 1 x 7.0 = 7.0 m taps 2 x 3.7 = 7.4 m check valves 2 x 4.3 =8.6m Effective pipe length = 30.35 m Figure 1.11 Example of permissible head loss tee I -o � (1J +-' +-' (1J QJ st double check valve � _,assembly \ Ke v op a.. i Flow rate for 2 taps 0.4 Vs .... :::, V) V) QJ � pipe bend Permissible head loss= available head (45 m) effective pipe length (30.65 m) = 1.48 m/m run This formula is used to determine whether the frictional resistance in a pipe will permit the required flow rate without too much loss of head or pressure. Figure 1.10 illustrates the permissible head loss for the example in figure 1.9. Figure 1:12 Head loss through stop valves 9 9999 0 j iSi@:.. 1.1 I I!1 o N o c-, o ... o ill o 000 0. :...O,io- ..., l1lelsl1l1l,IIIII M.e1d la11 in meues (will friction gradient) �iii;� III,IelIIII e 0 0 00 0 w •aios o, - III+etIIIIIe!IIII Flow Jn litres per second ,; • "" W • CII O. ._.CD I .I I II IIti I I ..., w • 111oi CDO , ,1e,,I,I,I.I II11 "' ti' N Nominal silo of stopv111Ne Note Gate valves and spherical plug valves offer little or no resistance to flow provided they are fully open. 20 0.5 VI cu .2 > � cu "' ....� cu a. ...."' 0 15 .& f• e � 2 35 30 0 2 ;:;:: .c 3 25 20 � QO ... .... ::::, 0 .c 6 VI VI 8 "'cu 10 0 � :c M II .-4 .-4 20 � ::::, 30 QO u: 10 5 25 •o 50 ' I .. i ;; ,9 ·= � a !l ..• 0 :,: "'3 8 � 5 -� 0 .. ,,,, .,.. .,. .,, '" !I ii 1 'I, � i5 3 6 • 5 3 2 I 0.8 0.6 0.5 o.. 'I • .. • ·,� 6 10 8 ,,, 0.2 0.1 0.08 0.06 0.05 0.0, 0.03 � I !. = � E "'8 0.02 � -6, � 0 0.01 ... � R Figure 1.14 Determination of pipe diameter i i i iii i� 0 0 ��n � 0 0 000 § �� 2 ;;(;§ §� � � Ho:a,d loss in mtcre, p•1 m.ire run � .. ? "' 3 ;. a�i � 3 g "' ' 3 E. � �· g !: .- '2B Ji- .. I' g: � � I II � � � 0 Hn chese llmlts ont,, � i [ i f! 01.Hlde dlimeter of ccpper pJpe In mUllmet:r• � p ul 0 \4tloeitv In moues i>ef second 0 ir ii'. .. "'� 0 � � 0 ;:; I' I I' Act:141 bore of pbe In mlli'notros 0 .. I .; I I iI I I .; • II ti IC N Ii I"IiIIiiiipllijIIIIIJI I I' 'IIIIII Ii/' I I II I � � t � g : g Notes Figures shown are for cold water at 12 ° C. Hot water will show slightly more favorable head loss results. BS 6700 gives head loss in kPa. 1 m head = 9.81 kPa. g: Table 1:11 Maximum recommended flow velocities Water te1nperature ° ( C) 10 50 70 90 Flow velocitv Pipes readily accessible Pipes not readily (mis) accessible (mis) 3.0 3.0 2.5 2.0 2.0 1.5 1.3 1.0 ... cwsc E ... m servicrlg valves G) I double chedc vnlve assembtv / t.-·IHt,,©,i,,,-, - C Q) Q) :,: 0 'la ::::, E � n, 0) U C - © 'O Q) u£ Q) .c ___,......,._....__, ...__� .s::. .r. (/) (/) C «s o­ ·«s ·.;; :::J - . •...E .... ... ... .c .c ... - .x Q) �l� wb b.J O.Sm 2m-j,:}.�C 0 Q) :::J Cl� i;:: ,- w< © _J 5 2 + ...lA + 10 0.55 + .JI.§ + 2.1_ a11:. = '.'W1 =o. o. "- E � Ill) .!l! 3 +13.5 e Jf sink litres pe second 'ii:i' "C ••• Ill) :a C + 9.::!... = 0.1 ti& Ill (lj CL a: Assume draw-offs on each branch ,1110 be ., th• tln'Mt s.v,t Size for largett draw-off at each br•nch. l.t. bath. ::::,..-..- 0 5 3m C'l .C IO Cl .... loading units ... © --I•-•� m 2m WC wb b_l O.Sm ,±me 2 + 1.5 + 10 = 13.5 1-Elbow; 1-DN20, 0.31/s Tap 0.3 v, Q) .x u Q) �' {i' ..-N 1/'1 <-4 <-4 (lj ::::, ... .!!!> u.. Enter pipe reference on calculation sheet (1) Pipe reference (2) Loading Determine loading Units (Table 1.8) Units (3) Flow rate Convert loading units to flow rates (Fig. 1.7) (Us) (4) Pipe size Make assumption as to pipe size (Inside (mm diameter) diameter) Work out frictional resistance per metre (5) Loss of head {m/m run) {Fig.1.14) (6) Flow velocity Determine velocity of flow (Fig 1.14) (mis) (7) Measured Measure length of pipe under consideration pipe run (ml 'o} 2: ........ 11) N m 1ij 3 "2. acu 11) VI C: ;:;: cu C" ii'" Q n C: Consider frictional resistances in fittings (Table 1.9 and Figures 1.12 & 1.13) Add totals in columns 7 & 8 (8) Equivalent pipe length (m) (9)Effeclive pipe lenath {ml (10) Head consumed (m) Head consumed: Multiply column 5 by column 9 Add head consumed in column 10 to (11) Progressive progressive head in previous row of column head (m) 11 (12) Available Record available head at point of delivery head 1ml Compare progressive head with available head to confirm pipe diameter or not (13) Final Pipe size (mm) Notes (14) Remarks cu !:!'. 0 ::s VI :I" 11) 11) ... ;::;: :I" 11) X "ti iii ::s cu ... <::s ... 0 11) VI Table 1.13 Calculation sheet J!! ., .,,.. ., "' ., C -2 e�- '"N,-� .!c C 0 &� 0 Cl) !� o c ·<L � - ., .... :, - :,, <L- _._ 0 'iii "C � ti) .. • t: LL - § § � i!" ·.; l .,Q ·a .,,., *f lf .. -2 § '3., E Q) C .Q. Q i� .. .s:: :, er C ., � C § .� 5, u. - :!! w_ Jg C § 1 30 0.85 32 0.05 1.2 2.8 1.4 5 13.6 0.35 20 0.095 1.25 5.5 12.0 2 16.5 0.7 25 0.12 1.5 2.4 6 3 0.3 20 0.07 1.0 3.5 3 13.6 0.65 26 0.1 1.4 2.4 7 13.6 0.35 20 0.096 1.25 0.3 20 0.07 1.0 4 - '" .Q. Q., E >·.s:: ts 5, w.s! -e�-_g �- ., - .. "' .,, .. .. ";i-; ;., �l :c .§ -- - - ;;;- ::: E ":,C .,,8 0 � 0 .. � <L .s:: Q) - - E := "C .Q. E QE .S: .� u. Cl) ;:; 4.2 0.21 0.21 2.8 32 - 17.5 1.66 1.87 3.3 20 2.4 0.29 2. 16 6.2 26 10.4 - 13.9 0.97 3.13 6.7 20 2.4 0.. 24 3.37 7.6 26 5.5 12.0 17.6 1.66 5.03 8.1 20 2.9 1.6 4.6 0.31 5.34 10.0 20 � E Pipe sizing cont... Pipe sizing for hot water systems is the same as cold water, except cold feed pipe must also be considered Useful formulae for pipes: 1. Thomas Box formula Where; d 5 xH q= � 25xLxl0) d = pipe diameter (mm) q = flow rate (l/s) H = head or pressure (m) L = effective length of pipe (actual length+ allowance for bends, tees, etc.) Example: Determine the pipe size using Thomas Box formula. Answer: Using Thomas Box formula, �------ Oiidliige 1 �s (1) 2 x25x20xl05 3 = 27.83 mm ------- -- -- -... ... -----eneccive pipe lenglh "20 m J, Hence, the nearest commercial size is 32 mm bore steel or 35 mm outside diameter copper. 3mhoad 2. Relative discharge of pipes where N = munber of sho1t branch pipes D = diameter of main pipe (llllll) d = diameter of sho11 branch pipes(=) Example: (a) Compute the number of 32 mm short branches that can be served from 150 mm main. = ( 150 ' = 47 Answer: N ) 32 'rm (b) Determine the size of water main required to supply 15 nos. 20 mm short branch pipes. Answer: D = d x ifiii = 20 x 5Jisi = 59 Hence, the nearest commercial size is 65 mm. � 0 0 .;::: l C a:.... :J tU ..., tU tU u 'ii � U) '"'4• '"'4 u: b.O