Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 1 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Installation and cabling of Small Node Access Ramp, MUS/MUA - COA/BFE 30813 Abstract This instruction describes methods for wiring, handling and installation of Small Node Access Ramp cabinet, BFE 30813/n, supporting both PSTN and ISDN accesses. Keywords EAR, NB, BYB502 Contents 1 1.1 1.2 1.3 2 3 3.1 3.2 3.3 3.4 3.5 3.6 4 4.1 4.2 4.3 4.4 4.5 5 5.1 5.2 5.3 6 6.1 6.2 6.3 6.4 Introduction..........................................................................................4 Target Group .......................................................................................4 Prerequisites .......................................................................................4 Precautions .........................................................................................4 Installation Document Overview ..........................................................6 Equipment Overview ...........................................................................7 Cabinet base .......................................................................................7 SIS Subrack ........................................................................................8 Cable Shelf..........................................................................................8 Fan Unit...............................................................................................9 Fire Enclosure ...................................................................................10 Connection and Conversion Field, CCF ............................................11 Cabinet Installation............................................................................12 Validation...........................................................................................12 Mounting of rails ................................................................................13 Settings operations............................................................................15 Alignments.........................................................................................17 Tightening torque ..............................................................................17 Rail mounting of the base unit...........................................................19 Preparation of cabinet base ..............................................................19 Assembly bolt preparation .................................................................19 Positioning of the cabinet ..................................................................20 Accessories and covers ....................................................................22 Cable access .....................................................................................22 Grounding the base unit ....................................................................22 Connecting the ESD strap .................................................................23 Mounting the covers ..........................................................................23 Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 2 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 7 7.1 7.2 7.3 7.4 7.5 8 8.1 8.2 8.3 9 10 Equipment Installation .......................................................................24 Subrack .............................................................................................24 Fan Unit.............................................................................................25 Cable Shelf........................................................................................25 Fire Enclosure ...................................................................................25 CCF ...................................................................................................26 Electrical Connections of Units..........................................................27 Board connectors ..............................................................................27 Internal cabling ..................................................................................27 External cabling.................................................................................31 Glossary ............................................................................................36 References ........................................................................................36 Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 3 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Table of Figures Figure 3-1 - Cabinet base dimensions .............................................................7 Figure 3-2 - SIS subrack ..................................................................................8 Figure 3-3 - Cable Shelf ...................................................................................9 Figure 3-4 - Parallel cooling .............................................................................9 Figure 3-5 - Fan Unit ........................................................................................9 Figure 3-6 - Fire Enclosure.............................................................................10 Figure 3-7 - Connection and Conversion Field...............................................11 Figure 4-1 - Hole pattern for short rails ..........................................................13 Figure 4-2 - Setting Operations ......................................................................15 Figure 4-3 - Setting operations.......................................................................16 Figure 4-4 - Testing of torque.........................................................................16 Figure 4-5 - Alignment of short rails ...............................................................17 Figure 5-1 - Base unit and covers ..................................................................19 Figure 5-2 - Positioning of assembly bolt and its correct position ..................19 Figure 5-3 - Assembly bolt seen from the back..............................................20 Figure 5-4 - Wall mounted base unit seen from above ..................................20 Figure 5-5 - Locking the assembly bolts in the rails .......................................21 Figure 5-6 - Locking the base unit..................................................................21 Figure 6-1 - Removal of pre-punched plate....................................................22 Figure 6-2 - Grounding of base unit ...............................................................22 Figure 6-3 - ESD connection ..........................................................................23 Figure 7-1 - Position numbering for SNAR.....................................................24 Figure 7-2 - Grounding of subrack to the cabinet...........................................24 Figure 7-3 - SIS Subrack allocation...............................................................25 Figure 7-4 - Installation of CCF with 4/BMF 90410/1 .....................................26 Figure 8-1 - Board connectors........................................................................27 Figure 8-3 - External test access cabling .......................................................35 Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 4 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 1 Introduction The Small node cabinet can be installed in the 400 mm deep BYB 502 module. This installation instruction describes the installation procedure related to the wall mounting option. If reference is given to Installation Engineering (IE) documents, this means that the required information is specific for a certain configuration or installation site and will be found in specific documents. 1.1 Target Group This document is intended for using by trained personnel familiar with Ericsson Telecom equipment. All Ericsson standard safety methods should be understood and practised. 1.2 Prerequisites It is assumed that the reader/user of this Installation instruction: • • Is familiar with Ericsson Telecom equipment Has understanding of all Ericsson standard safety methods and is able to practice these methods. 1.3 Precautions 1.3.1 Grounding Check that the equipment is connected to the system ground of the building. Be sure to adhere to local regulations when grounding the system to earth. 1.3.2 Electrical Power Make sure that the correct system voltage is supplied (-48V) for all equipment before applying power. 1.3.3 Electrostatic Discharge Sensitive Devices Precautions for handling Electrostatic Discharge Sensitive (ESDS) devices should be observed. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 5 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File This means that a grounded wrist strap or approved shoes, used on a semiconductor floor surface, must be used. A wrist strap can be connected in each cabinet. If not properly handled, the electronic components can be severely damaged. 1.3.4 CE Marking The equipment, when installed according to the installation procedures specified in this document, is in compliance with the EMC directive 89/336/EEC and 92/331/EEC with amendments, and the low voltage directive 73/23/EEC and 93/68/EEC with amendments. Other subrack configurations may be used, but have to be approved by Ericsson. This is a product intended for installation in telecom centres, commercial or light industry environment. It may also be installed in locations other than telecom centres or equivalent. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 6 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 2 Installation Document Overview In addition to this installation instruction, the documents included in the following list should be used : 1. Final assembly of cabinet 1/BYB 502140/200 1531-1/BYB 502 140/200 This Installation instruction describes the required method for the handling and installation for wall mounting of cabinet BYB 502. 2. Wall Mounting Set 18/BYB502 1531-18/BYB502 Uen. This Installation instruction describes the handling and installation of wall mounting set 18/BYB 502. 3. Handling of Printed Board Assemblies ROJ, 1531-FCM 101 1804 Uen. This document contains general information about handling of printed board assemblies. Also the following instruction should be used to support the work: 4. Installation instruction for CCF, BMF 904 10. 1531-BMF 904 10 Uen. This document describes the method for installation of the CCF. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 7 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 3 Equipment Overview This section provides information about the cabinet base, subrack and additional equipment that can be mounted in the cabinet. 3.1 Cabinet base The cabinet base complies with standard ETS 300 119-2 and has the following dimensions: Cabinet base 1/BYB 502 140/200 Hc [mm] Hc1 [mm] Wc [mm] Wc3 [mm] Dc [mm] A [mm] 400 400 600 465 400 100 The weight of unequipped cabinet base is ∪12,5 kg. The cabinet base is available with a subrack mounting pitch according to the metric standard IEC 917-2. The cabinet base, together with different mounting sets (doors, side plates, coverings, and wall mounting set) creates the different cabinet versions. 1. Figure 3-1 - Cabinet base dimensions Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 8 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 3.2 SIS Subrack The Single Switch Subrack (SIS) contains both the switching part of the EAR (one AUS/AUS-C boards) and the access units (AUs). The subrack has the following dimensions: SIS Subrack BFD 518 004/1 Hs [mm] Ws3 [mm] Ws [mm] D [mm] Dc1 [mm] 300 465 450 250 280 Ws Hs Ws3 Figure 3-2 - SIS subrack 3.3 Cable Shelf The cable shelf, SXK 123 122/1, is designed for a cabinet depth of 300 mm or 400 mm. The cable shelf is always mounted below the SIS subrack. The cable shelf has the following dimensions: Cable shelf SXK 123 122/1 Hs [mm] Ws3 [mm] Ws [mm] D [mm] Dc2 [mm] 50 465 434 238 280 80 mm (max) is the available space for front cables. 1 2 Including cables Including cables Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 9 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Cable Area Figure 3-3 - Cable Shelf 3.4 Fan Unit The fan unit BFD 509 13/1 is used, in order to implement the principle of parallel cooling. That is in the cabinet the cooling air is taken in at the front and is exhausted in the reserved air chimney area at the back of the cabinet. The nominal depth of the air chimney is ~ 100 mm. Figure 3-4 - Parallel cooling A rear plate is mounted 100 mm from the back of the cabinet to secure a chimney so that pressure rise in the chimney can’t cause heated air to be forced in to the above or below equipment the wrong way. The Fan unit has the following dimensions: Fan Unit BFD 50913/1 Hs [mm] Ws3 [mm] Ws [mm] D [mm] 50 465 435 240 FAN UNIT Connector 1 Connector 2 Power Alarm Figure 3-5 - Fan Unit Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 10 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 3.5 Fire Enclosure The fire enclosure, SXK 123 124/1 must be used beneath the lowest installed equipment in the cabinet. The fire enclosure bottom must be clean to allow free airflow. Check the fire enclosure bottom regularly. The fire enclosure bottom can be extracted to facilitate cleaning. The fire enclosure has the following dimensions: Fire enclosure SXK 123 124/1 Hs [mm] Ws [mm] D [mm] 16,2 427 250 The Fire Enclosure is shown in Figure 3-6. Figure 3-6 - Fire Enclosure Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 11 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 3.6 Connection and Conversion Field, CCF The CCF, BMF 904 10, is a cabinet mounted filter intended for connection of external 2Mb/s E1 links with 75 ohms or 120 ohms impedance. The CCF is connected to the AUS-C by means of 100 ohms pair cable, supplied with 10-pin Metral connector. The external side of CCF is connected to DDF by means of 75 ohms coax cables or 120 ohms pair cables, supplied with 24 pin Sofix connectors. The CCF includes parallel connection of dedicated pins between in– and output connections, for testing of analogue subscriber lines. Several nodes can therefore be connected in parallel to one test unit without damping and impedance conversion of the test signal. The CCF has the following dimensions: CCF BMF 904 10 Hs [mm] Ws [mm] D [mm] 286 25 75 The CCF is shown in the Figure 3-7. Figure 3-7 - Connection and Conversion Field Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 12 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 4 Cabinet Installation This instruction for wall mounting of cabinet BYB 502, defines what steps have to be taken to ensure secure mounting of fully equipped cabinet modules to a wall structure. The initial wall strength testing operations are required to accurately obtain the wall strength value. This value is converted in table 2 to the recommended rail mounting torque. A drilling template is included with the cabinet packing, and shall be used to achieve correct positioning of the mounting holes. Wall mounting kits, 18/BYB 502/1 includes all the parts required for mounting one cabinet on a wall. Additional plugs & screws and expanders are included for wall strength testing. General wall mounting applications require the plug &screw solution for mounting of rails. The supplied expanders should only be used when seismic compliance is required. All dimensions and tolerances are given in mm. All tightening torques are given in Nm. 4.1 Validation To ensure that wall mounted support assemblies for BYB 502 will securely maintain accurate suspension of fully equipped cabinet units, the installation application must comply with the following sections: 1. All operation activities in the mounting instruction 1531-1/BYB 502 140/200 must be followed, and fulfils defined acceptance criteria. 2. Wall mounting kits 18/BYB 502/1 must be used. None of the supplied parts may be replaced by other similar products. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 13 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 4.2 Mounting of rails 4.2.1 Marking of mounting holes Marking of the hole patterns on the wall may be performed manually, or by using the supplied drilling template. Brick wall: Nail the template to the wall by using small nails. Concrete wall: Fix the template to the wall by using strong adhesive cello tape. Check alignment with horizontal and vertical levels, by using a water level or a plummet. Figure 4-1 - Hole pattern for short rails Drill guide holes with a 3-6 mm drill-bit through the markings 1, 3, 7 and 9. The guide holes should be drilled to a depth of 10-20 mm. 4.2.2 Choice of fasteners The use of correct fasteners for fixing of rails on various wall structures is crucial. Information regarding fasteners and wall structures is available in table1. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 14 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Information Concrete and brick walls Seismic compliance The plug & screw should be used in concrete and brick walls. The expander is only to be used in unfractured concrete walls with the wall strength values C20/25 or higher. The expander will withstand earth quakes according to Bellcore zone 4. Drilling diameter 10 mm 12 mm Drilling depth 85 mm 100 mm Mounting torque 5 Nm-18 Nm 25 Nm IMPORTANT It is vital to achieve the correct mounting torque, in order to obtain the load handling of 100 kg on short rails alternatively 200 kg on long rails. Fasteners It is vital to achieve the correct mounting torque in order to obtain seismic compliance and the load handling of 100 kg on short rails alternatively 200 kg on long rails. Table 4-1- Choice of fasteners IMPORTANT. ! ! ! When the drill hits un-penetrable reinforcing iron in the concrete wall, move the template at least 100 mm and drill new holes. All holes intended for supports have to be spaced minimum 200 mm apart. Holes intended for supports shall not be drilled closer than 150 mm from any corner. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 15 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 4.3 Settings operations 4.3.1 Wall strength testing Operation 1 Plug & screw/ expander: Drill the hole with a drill bit. Operation 2 Plug & screw/ expander: Blow out dust and fragments. Operation 3 Plug & screw/ expander: Install and tap in the plug. Operation 1 Operation 2 Operation 3 Figure 4-2 - Setting Operations Operation 4 Plug & screw/ expander: Position the rail. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 16 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Operation 5 Plug & screw: Mount the rail; apply the washer before tightening the screw lightly. Expander: Mount the rail, tap in the expander and tighten the bolt lightly. Operation 4 Operation 5 Figure 4-3 - Setting operations Operation 6 Plug & screw: Tighten the screw to 5 Nm. Check that the rail is securely tightened against the wall. No vertical movements are allowed. If this is achieved the testing is completed and approved. If vertical movements of the rail is still obtained, continue tightening the screw one Nm at a time, until the plug starts rotating in the wall. Take a note of the last torque reading, and convert this to a mounting torque value in table 2 on page14. Figure 4-4 - Testing of torque Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 17 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Operation 6.2 Expander (Seismic compliance): Tighten the bolt of the expander to 25 Nm. Check that the rail is securely tightened against the wall. No vertical movements are allowed. If this is achieved the testing is completed and approved. If the expander starts rotating in the wall before 25 Nm is achieved, it is not recommended to use expanders for mounting of the rails. Revert to the instruction for plug & screw. See operation 1 on page 12. 4.4 Alignments Make sure the short rails are aligned with the given tolerance before tightening the fasteners. See Figure 4-5. Adjust if necessary. Insert the clevis pins in the two upper holes. Figure 4-5 - Alignment of short rails 4.5 Tightening torque Convert the previously established testing torque value to the recommended mounting torque in table 2. The lowest of the stated values in the mounting torque column is the recommended mounting torque value. If vertical movements can still be applied to the rail, tighten the fasteners one Nm at a time, until the rails are securely fixed. The tightening torque must not exceed the higher of the stated mounting torque values for each level. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 18 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Denomination Plug & screw Expander Testing torque (Nm) Mounting torque (Nm) 7 5-6 8 5-6 9 6-7 10 6-8 11 6-9 12 7-10 13 7-10 14 8-11 15 9-12 16 9-12 17 10-13 18 10-14 19 12-15 20 13-16 21 15-17 22 16-18 25 25 Information Concrete and brick walls Concrete walls Table 4-2 - Conversion table from testing torque to mounting torque values. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 19 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 5 Rail mounting of the base unit 5.1 Preparation of cabinet base Lift off the front cover and remove top, bottom and side covers for necessary access. The top and bottom covers are mounted with four screws each. 1 Loosen the front of the side cover by unscrewing the two mounting screws a couple of turns. 2 Pull the side cover outwards. 3 Unhook the back of the side cover by moving it backwards. Figure 5-1 - Base unit and covers 5.2 Assembly bolt preparation Position the four assembly bolts in their dedicated holes at the rear of the cabinet base. Push the centre screw through the base until an audible click is heard. 1. Figure 5-2 - Positioning of assembly bolt and its correct position Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 20 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Figure 5-3 shows the protrusion of the assembly bolt at the back of the base unit when inserted correctly. Figure 5-3 - Assembly bolt seen from the back 5.3 Positioning of the cabinet Support the weight of the cabinet base and carefully position protruding ends of the assembly bolts in the rail openings. Hold the cabinet base firmly against the rails while continuing with the following steps: IMPORTANT: Clevis pins are not intended to provide support until the assembly bolts have been engaged in the rails. INFORMATION: Access to the assembly bolts in equipped cabinets (supplied with subrack), is only possible from the top and bottom at the rear of the base unit. Figure 5-4 - Wall mounted base unit seen from above 1. Carefully unscrew the centre screw of the assembly bolt to its end position. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 21 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 2. Position the base unit against the rails, slightly push the screw and rotate the large washer a quarter of a turn in order to engage the rear flange in the rail. See Figure 5-5 Figure 5-5 - Locking the assembly bolts in the rails 3. Make sure the flanges of the large washer fit into the dedicated cutouts of the base unit when turned correctly. 4. Pressing the centre screw of each assembly bolt can perform vertical adjustments of the base unit. (This requires simultaneous pressing of two or four centre screws) 5. Tighten the centre screw of each assembly bolt. This will prevent the base unit to slide downwards. 6. Avoid using the Clevis pins as additional supports when mounting a fully equipped cabinet. This may cause damage to the assembly bolts. 7. Align the base unit with the top of the rails. 8. Tighten the four bolts with a torque of 40 Nm. See Figure 5-6 Figure 5-6 - Locking the base unit 9. Mount the end plugs to all rails for protection Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 22 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 6 Accessories and covers 6.1 Cable access Remove the pre-punched plate by hand from the top or bottom cover, to achieve desired cable access to the cabinet. Figure 6-1 - Removal of pre-punched plate 6.2 Grounding the base unit The base unit is supplied with four grounding points. Two are positioned on the left hand side, and two on the right hand side of the frame. Attach the cable lug to dedicated grounding positions in the base unit. Note the positioning of washers between base unit and lug. See fig. Figure 6-2 - Grounding of base unit Tighten bolts with torque 12 Nm. Cable lug assembly in Figure 6-2 shows the right hand grounding position. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 23 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 6.3 Connecting the ESD strap The ESD strap may be connected to one of four positions in each base unit. See figure 43. Figure 6-3 - ESD connection 6.4 Mounting the covers 1. Mount the bottom cover with four screws. 2. Mount the top cover with four screws. 3. Mount the side covers individually by first hooking the back end into the slot of the base unit, and slide it forwards. Push in the front end against base unit and lock in position by tightening the two screws. Recommended tightening torque 2 Nm. 4. Mount the front cover by positioning the guide pins in the base unit slots. Lock the cover by pressing the two handles downwards until an audible click is heard. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 24 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 7 Equipment Installation 7.1 Subrack The SIS subrack is mounted according to the Figure 7-1. FAN P0314 CCF 01 P2102 CCF 00 P0102 SIS P0302 FEB P0400 CABLE SHELF P0300 Figure 7-1 - Position numbering for SNAR 7.1.1 Ground connection of subrack When the subrack is mounted, make sure that enough torque is used to get good ground connection to the cabinet (10 Nm). Use tool Torx T30. 10 Nm Figure 7-2 - Grounding of subrack to the cabinet 7.1.2 Subrack ID The subrack identity, SUBID, is the subrack number in the configuration file of the system node. There is a DIP-switch on the back-plane where the number is set. Normal binary coding of the number is used and the 4 least significant bits are decoded by the back-plane. The Dip-switch must be set before the boards are inserted in the subrack. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 25 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 7.1.3 Subrack Allocation TAU TAU-C AUS-C AU AUS AU AU AU AU AU AU AU AU AU AU DU-3 AU DU-3 The SIS subrack has 18 slots, numbered 1-16, 29,30. Two of these, slots 29 and 30, are half-height slots reserved for DU-3 boards. The rightmost slot, number 16, always contains a TAU-C, while the slot number 15 always contains a TAU. Figure 7-3 - SIS Subrack allocation One AUS/ AUS-C pair is always located in slots 14 and 13. The remaining 12 slots are used for AU boards. For any partially equipped subrack, the following rules apply: 1. Place AU boards from right to left, starting at slot #12. 2. Dummy panels must cover unused slots. First, 100 mm covers must be used as far as possible to cover four slots at a time. Then, 25 mm covers must be used to cover any remaining empty slots. 7.2 Fan Unit The fan unit is always mounted above the subrack, according to Figure 7-1. Put the Fan Unit on the guiding bars and push it in position. Put the screws in the positions on the sides of the front. Tighten all screws. 7.3 Cable Shelf The cable shelf is always mounted below the subrack, according to Figure 7-1. 7.4 Fire Enclosure The fire enclosure is always used below the cable shelf. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 26 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File The fire enclosure bottom must be clean to allow free airflow. Check the fire enclosure bottom regularly. The fire enclosure can be extracted to facilitate cleaning. 7.5 CCF The CCF is vertically mounted in the right and left ducts of the cabinet, according to the picture below. The following mounting kits are used: 4/BMF90410/1 (right side) and 4/BMF90410/2 (left side). They include a mounting support with spring locking of CCF. Figure 7-4 - Installation of CCF with 4/BMF 90410/1 Generic instructions for the installation and positioning of CCF in the cabinet can be found in [4]. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 27 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 8 Electrical Connections of Units 8.1 Board connectors The figure below shows the front connectors for EAR boards. M DU-3 I A AUS-EP MIA X104 X106 OS OS IS 27 IS 27 26 26 25 25 24 23 24 23 22 22 21 21 20 19 20 19 18 18 X110 17 17 16 15 16 15 X111 14 14 13 12 13 12 X112 11 11 10 10 09 09 08 07 08 07 06 06 X115 05 05 04 03 04 03 X116 02 02 01 01 00 X107 X108 X114 MIA TAU-C MIA MIA I N T E R C . I N I N T E R C . O U T S U B S C R I B E R C2 C1 C0 A5 A4 A3 A2 A1 A0 00 ET SYNC-RING EMRP- EMRP- X118 AUS F A N LED.TEST S U B S C R I B E R ET AUS-EP TAU AU-ISDN MIA PWR COM SYN CSR TL1 TL2 RX -TX AUS-C AU-PSTN MIA AUS AUS-C MIA EXT.TEST 1 0 1 0 ET ET AU-PSTN AU-ISDN TAU X107 P W R X106 0 X108 X110 X111 X112 X114 X115 X116 NB-ALARM X118 00 ET X106 X104 BB-ALARM TAU-C DU-3 Figure 8-1 - Board connectors 8.2 Internal cabling Internal cables for SNAR cabinet are normally arranged in NTM kits and are included in the cabinet structure. Two NTM kits exist: ! NTM 180 20/142 SIS cable set ! NTM 180 20/143 SIS PRA cable set Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 28 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 8.2.1 SIS Cable set, NTM 180 20/142 8.2.1.1 AUS Synch On AUS there is a connector to be used for clock synchronization (Sync-Ring). The Sync-Ring is built -up in a ring structure from one AUS to the next and back again with communication possible in two directions as the redundancy principle. In case of SNAR, one AUS is used and to close the ring, a loop cable has to be implemented on AUS board itself. The cable to be used is TSR 910 2006/300. The cable must be connected between the AUS board outlets called “RX” (X116-1) and “TX” (X116-5). 8.2.1.2 AUS-C - AUs cabling The connection between AUS-C board and the AUs is performed with unscreened balanced two pair cables with 10 poles connector, TSR 910 2006/500. The table below shows the ET ports allocation of AUS-C board and the corresponding AU slot. AUS-C AU Connector PIU Front Marking To Slot / Connector X116-1 ET02 Slot 1 X115-5 ET03 X115-3 Cable/ length TSR 910 2006/600 Slot 2 X118-5 X118-5 ET04 Slot 3 X118-5 TSR 910 2006/500 X115-1 ET05 Slot 4 X118-5 TSR 910 2006/500 X114-5 ET06 Slot 5 X118-5 TSR 910 2006/500 X114-3 ET07 Slot 6 X118-5 TSR 910 2006/500 X114-1 ET08 Slot 7 X118-5 TSR 910 2006/500 X112-5 ET09 Slot 8 X118-5 TSR 910 2006/400 X112-3 ET10 Slot 9 X118-5 TSR 910 2006/400 X112-1 ET11 Slot 10 X118-5 TSR 910 2006/400 X111-5 ET12 Slot 11 X118-5 TSR 910 2006/400 X111-3 ET13 Slot 12 X118-5 TSR 910 2006/400 TSR 910 2006/600 Table 8-1 – ET ports allocation for AUS-C/AU connection Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 29 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 8.2.1.3 AUS-C/TAU cabling The connection between TAU board and AUS-C is performed with an unscreened balanced two pair cable with 10 poles connector, TSR 910 2006/ 400. The cable is connected from the TAU board outlet called “ET 00” (X118-5) to the AUS-C 0 outlet called “ET 21” (X107-5). 8.2.1.4 TAU-C strap Not used. 8.2.1.5 AUS-C/ CCF connections The cable TSR 910 2006/500 is connected from the AUS-C board to the CCF 01 (right side) according to the following rules: AUS-C 8.2.1.6 CCF-01 Comments Connector PIU Front Marking Connector X104-5 ET 27 X121-1 0 X106-1 ET 26 X120-5 1 X106-3 ET 25 X120-3 2 X106-5 ET 24 X120-1 3 High traffic X107-1 ET 23 X119-5 4 High traffic Fan Cables The fan unit is supplied from the DU-3 boards in the subrack through two cables TSR 491 0225/400 and TSR 491 0225/500. These cables also transmit alarm signals from the fan unit to the system. The fan cable is connected to the DU board outlet called “FAN” and at the fan unit to outlet called “Connector 1" and “Connector 2". Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 30 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 8.2.2 PRA cable set, NTM 180 20/143 8.2.2.1 AUS-C/ CCF (PRA connections) The connection between AUS-C board and the CCF (PRA connections) is performed with unscreened balanced two pair cables with 10 poles connector, TSR 910 2006/700 The table below shows the ET ports allocation of AUS-C board and the corresponding CCF port. AUS-C CCF-00 Connector PIU Front Marking Connector/ Port X111-1 ET14 X119-1 6 TSR 910 2006/700 X110-5 ET15 X119-3 5 TSR 910 2006/700 X110-3 ET16 X119-5 4 TSR 910 2006/700 X110-1 ET17 X120-1 3 TSR 910 2006/700 X108-3 ET19 X120-3 2 TSR 910 2006/700 X108-1 ET20 X120-5 1 TSR 910 2006/700 X107-3 ET22 X121-1 0 TSR 910 2006/700 Cable/ length Table 8-2 – ET ports allocation for AUS-C/CCF connection Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 31 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 8.3 External cabling 8.3.1 Power cables The subrack has dual power feeding connection with redundancy. The cable is connected to the DU board connector called “PWR” and the other end to the power source. The power source shall be compliant with the Ericsson TS-HOD 500 distribution scheme. Location of the cabinets determines the required power distribution cable length. Depending on the required length the appropriate cross section area for the cable can be selected: • • 8.3.2 2 x 06 mm2 2 x 10 mm2 TSR 490 0106/ 30M TSR 490 0107/ 50M. Subscriber cables The Subscriber cable is connected to the AU board outlet called “Subscriber”, (X110-X112). The subscriber cables from MDF to SIS come in different lengths. DISTANCE TO MDF PRODUCT NUMBER 0 – 10 m TSR 910 1030/10M 10 – 15 m TSR 910 1030/15M 15 – 30 m TSR 910 1030/30M 30 – 50 m TSR 910 1030/50M 50 – 70 m TSR 910 1030/70M 70 – 150 m TSR 910 1030/150M The cables should be distributed between the two cables ducts of the cabinet with the first 6 AU cables routed to the left and the other AU cables routed to the right. The colour coding of the pairs is shown in Table 8-3. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 32 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Subscriber line number Pair number in cable Connector pin a/b wire Colour code a/b wire 1 1 A17/B17 white/blue 2 2 A16/B16 white/orange 3 3 A15/B15 white/green 4 4 A14/B14 white/brown 5 5 D13/C13 white/grey 6 6 D14/C14 red/blue 7 7 D15/C15 red/orange 8 8 D16/C16 red/green 9 9 D17/C17 red/brown 10 10 D18/C18 red/grey 11 11 A11/B11 black/blue 12 12 A10/B10 black/orange 13 13 A09/B09 black/green 14 14 A08/B08 black/brown 15 15 D07/C07 black/grey 16 16 D08/C08 yellow/blue 17 17 D09/C09 yellow/orange 18 18 D10/C10 yellow/green 19 19 D11/C11 yellow/brown 20 20 D12/C12 yellow/grey 21 21 A05/B05 white/blue 22 22 A04/B04 white/orange 23 23 A03/B03 white/green 24 24 A02/B02 white/brown 25 25 D01/C01 white/grey 26 26 D02/C02 red/blue 27 27 D03/C03 red/orange 28 28 D04/C04 red/green 29 29 D05/C05 red/brown 30 30 D06/C06 red/grey Colour of cable unit marker Table 8-3 - The colour coding of the pairs in Subscriber cable blue blue orange Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 33 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 8.3.3 PRA/V5.1 Subscriber cables The subscriber cables for PRA/V5.1 come in different lengths (see below) and there is also the possibility to choose 75 ohms coax or 120 ohms balanced pair cable. 4 PRA connections are possible. 8.3.3.1 8.3.3.2 8.3.4 Shielded Pair Cable, 120 ohm with DC Barrier DISTANCE TO DDF PRODUCT TO ORDER 0 – 15 m TSR 491 0289/15M 15 – 30 m TSR 491 0289/30M 30 – 70 m TSR 491 0289/70M 70 – 150 m TSR 491 0289/150M Coax cables 75 ohms DISTANCE TO DDF PRODUCT TO ORDER 0 – 15 m TSR 492 0211/15M 15 – 30 m TSR 492 0211/30M 30 – 70 m TSR 492 0211/70M 70 – 150 m TSR 492 0211/150M Transmission cables Transmission cables are E1 cables towards the (AXE) host. The cables come in different lengths. There is also a possibility to choose 75 ohms coax, TSR 492 0211, or 120 ohm pair cables, TSR 491 0289, supplied with 24-pin Soffix connectors. There are 5 positions to be used for 2Mb/s connections. The positions are used according to the table below. Empty (not used) positions can be used for PRA. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 34 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File Table 8-4 – CCF ports allocation 8.3.5 Port Position CCF 01 19 54 18 49 ISI 17 44 OSI 16 39 High traffic 15 34 Normal Traffic 14 29 Normal Traffic 13 24 Normal Traffic 12 19 Normal Traffic External alarm cable External alarms can be connected to SIS subrack via TAU-C. Six ports are available for each TAU-C. The cable used is TSR 910 2007.The cables come in different lengths. DISTANCE TO TAU-C PRODUCT TO ORDER 0 – 30 m TSR 910 2007/30M 30 – 80 m TSR 910 2007/80M 80 – 150 m TSR 910 2007/150M The connection position is at TAU-C board outlet marked “NBALARM”, (X114-X116). 8.3.6 V24/ typewriter cable A PC can be connected to EAR via RS232 interface. One cable is available TSR 910 2018/15M. The cable must be connected at AUS connector X115-5. 8.3.7 External Synchronization cable For 2,048 Mb/s incoming external synchronization (ISI) of the node or/and 2,048 Mb/s outgoing external synchronization signal (OSI), the following cable, TSR 910 2006/500, can be used. The cable is connected at CCF 01, according to the Table 8-4. Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 35 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 8.3.8 External test access The TAU board outlet, called “Ext. Test” is used for connection of external line and circuit test instruments. The cable to be used is the TSR 491 381. 8.3.9 Extension of test bus between cabinets To enable access at one point at a site with an external line and circuit test instrument to several cabinets at a the same site, the cabinets have to be interconnected with each other as in Figure 8-3. Up to 8 nodes can be cascaded. DESCRIPTION External Test Equip. LENGHT PRODUCT TO ORDER 0 – 30 m TSR 491 367/15M 30 – 75 m TSR 491 367/75M 75 – 100 m TSR 491 367/100M 0– 5m TSR 491 368/5000 5 – 20 m TSR 491 368/20M 0,3 m TSR 910 2034/300 SNAR cascading CCF-TAU cabling TSR 491 368 SIS Test Head TAU TAU-C TAU TAU-C TAU TAU-C TSR 491 367 SIS SIS TSR 910 2034 TSR 910 2034 TSR 910 2034 Node 0 Node 1 Node 2 CCF Figure 8-3 - External test access cabling Information Limited Internal INSTRUCTION Prepared (also subject responsible if other) 36 (36) No. ERI/YS A. Olivieri 1531-COA/BFE 30813 Uen Approved Checked Date Rev Reference ERI/YS (M. Palaia) PC-SSS 07/09/2004 A File 9 Glossary AU BB DDF DSUB DU DU-3 EMC IE ISDN MDF NBA POTS 10 Access Unit Broad Band Digital Distribution Frame D-sub Connector Distribution Unit Distribution Unit, type 3 Electromagnetic Compatibility Installation Engineering Integrated Services Digital Network Main Distribution Frame Narrowband Access subrack Plain Old Telephone Service References 1. 1531-18/BYB502 Uen, Wall Mounting Set 18/BYB502 2. 1531-1/BYB 502 140/200, Final assembly of cabinet 1/BYB 502140/200 3. 1531-FCM 101 1804 Uen, Handling of PBA ROJ 4. 1531-BMF 904 10 Uen, Installation instruction for CCF, BMF 904 10.