Uploaded by n70v2n70

1531-COA BFE30813 EN A PDFV1R2 Кабели EAR

advertisement
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
1 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Installation and cabling of Small Node Access Ramp,
MUS/MUA - COA/BFE 30813
Abstract
This instruction describes methods for wiring, handling and installation of
Small Node Access Ramp cabinet, BFE 30813/n, supporting both PSTN and
ISDN accesses.
Keywords
EAR, NB, BYB502
Contents
1
1.1
1.2
1.3
2
3
3.1
3.2
3.3
3.4
3.5
3.6
4
4.1
4.2
4.3
4.4
4.5
5
5.1
5.2
5.3
6
6.1
6.2
6.3
6.4
Introduction..........................................................................................4
Target Group .......................................................................................4
Prerequisites .......................................................................................4
Precautions .........................................................................................4
Installation Document Overview ..........................................................6
Equipment Overview ...........................................................................7
Cabinet base .......................................................................................7
SIS Subrack ........................................................................................8
Cable Shelf..........................................................................................8
Fan Unit...............................................................................................9
Fire Enclosure ...................................................................................10
Connection and Conversion Field, CCF ............................................11
Cabinet Installation............................................................................12
Validation...........................................................................................12
Mounting of rails ................................................................................13
Settings operations............................................................................15
Alignments.........................................................................................17
Tightening torque ..............................................................................17
Rail mounting of the base unit...........................................................19
Preparation of cabinet base ..............................................................19
Assembly bolt preparation .................................................................19
Positioning of the cabinet ..................................................................20
Accessories and covers ....................................................................22
Cable access .....................................................................................22
Grounding the base unit ....................................................................22
Connecting the ESD strap .................................................................23
Mounting the covers ..........................................................................23
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
2 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
7
7.1
7.2
7.3
7.4
7.5
8
8.1
8.2
8.3
9
10
Equipment Installation .......................................................................24
Subrack .............................................................................................24
Fan Unit.............................................................................................25
Cable Shelf........................................................................................25
Fire Enclosure ...................................................................................25
CCF ...................................................................................................26
Electrical Connections of Units..........................................................27
Board connectors ..............................................................................27
Internal cabling ..................................................................................27
External cabling.................................................................................31
Glossary ............................................................................................36
References ........................................................................................36
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
3 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Table of Figures
Figure 3-1 - Cabinet base dimensions .............................................................7
Figure 3-2 - SIS subrack ..................................................................................8
Figure 3-3 - Cable Shelf ...................................................................................9
Figure 3-4 - Parallel cooling .............................................................................9
Figure 3-5 - Fan Unit ........................................................................................9
Figure 3-6 - Fire Enclosure.............................................................................10
Figure 3-7 - Connection and Conversion Field...............................................11
Figure 4-1 - Hole pattern for short rails ..........................................................13
Figure 4-2 - Setting Operations ......................................................................15
Figure 4-3 - Setting operations.......................................................................16
Figure 4-4 - Testing of torque.........................................................................16
Figure 4-5 - Alignment of short rails ...............................................................17
Figure 5-1 - Base unit and covers ..................................................................19
Figure 5-2 - Positioning of assembly bolt and its correct position ..................19
Figure 5-3 - Assembly bolt seen from the back..............................................20
Figure 5-4 - Wall mounted base unit seen from above ..................................20
Figure 5-5 - Locking the assembly bolts in the rails .......................................21
Figure 5-6 - Locking the base unit..................................................................21
Figure 6-1 - Removal of pre-punched plate....................................................22
Figure 6-2 - Grounding of base unit ...............................................................22
Figure 6-3 - ESD connection ..........................................................................23
Figure 7-1 - Position numbering for SNAR.....................................................24
Figure 7-2 - Grounding of subrack to the cabinet...........................................24
Figure 7-3 - SIS Subrack allocation...............................................................25
Figure 7-4 - Installation of CCF with 4/BMF 90410/1 .....................................26
Figure 8-1 - Board connectors........................................................................27
Figure 8-3 - External test access cabling .......................................................35
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
4 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
1
Introduction
The Small node cabinet can be installed in the 400 mm deep BYB 502
module.
This installation instruction describes the installation procedure related to the
wall mounting option. If reference is given to Installation Engineering (IE)
documents, this means that the required information is specific for a certain
configuration or installation site and will be found in specific documents.
1.1
Target Group
This document is intended for using by trained personnel familiar with
Ericsson Telecom equipment. All Ericsson standard safety methods should be
understood and practised.
1.2
Prerequisites
It is assumed that the reader/user of this Installation instruction:
•
•
Is familiar with Ericsson Telecom equipment
Has understanding of all Ericsson standard safety methods and is able to
practice these methods.
1.3
Precautions
1.3.1
Grounding
Check that the equipment is connected to the system ground of the building.
Be sure to adhere to local regulations when grounding the system to earth.
1.3.2
Electrical Power
Make sure that the correct system voltage is supplied (-48V) for all equipment
before applying power.
1.3.3
Electrostatic Discharge Sensitive Devices
Precautions for handling Electrostatic Discharge Sensitive (ESDS) devices
should be observed.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
5 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
This means that a grounded wrist strap or approved shoes, used on a
semiconductor floor surface, must be used. A wrist strap can be connected in
each cabinet. If not properly handled, the electronic components can be
severely damaged.
1.3.4
CE Marking
The equipment, when installed according to the installation procedures
specified in this document, is in compliance with the EMC directive
89/336/EEC and 92/331/EEC with amendments, and the low voltage directive
73/23/EEC and 93/68/EEC with amendments.
Other subrack configurations may be used, but have to be approved by
Ericsson.
This is a product intended for installation in telecom centres, commercial or
light industry environment. It may also be installed in locations other than
telecom centres or equivalent.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
6 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
2
Installation Document Overview
In addition to this installation instruction, the documents included in
the following list should be used :
1. Final assembly of cabinet 1/BYB 502140/200
1531-1/BYB 502 140/200
This Installation instruction describes the required method for
the handling and installation for wall mounting of cabinet BYB
502.
2. Wall Mounting Set 18/BYB502
1531-18/BYB502 Uen.
This Installation instruction describes the handling and
installation of wall mounting set 18/BYB 502.
3. Handling of Printed Board Assemblies ROJ,
1531-FCM 101 1804 Uen.
This document contains general information about handling of
printed board assemblies.
Also the following instruction should be used to support the work:
4. Installation instruction for CCF, BMF 904 10.
1531-BMF 904 10 Uen.
This document describes the method for installation of the CCF.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
7 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
3
Equipment Overview
This section provides information about the cabinet base, subrack
and additional equipment that can be mounted in the cabinet.
3.1
Cabinet base
The cabinet base complies with standard ETS 300 119-2 and has
the following dimensions:
Cabinet base
1/BYB 502 140/200
Hc
[mm]
Hc1
[mm]
Wc
[mm]
Wc3
[mm]
Dc
[mm]
A
[mm]
400
400
600
465
400
100
The weight of unequipped cabinet base is ∪12,5 kg.
The cabinet base is available with a subrack mounting pitch
according to the metric standard IEC 917-2.
The cabinet base, together with different mounting sets (doors,
side plates, coverings, and wall mounting set) creates the different
cabinet versions.
1.
Figure 3-1 - Cabinet base dimensions
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
8 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
3.2
SIS Subrack
The Single Switch Subrack (SIS) contains both the switching part
of the EAR (one AUS/AUS-C boards) and the access units (AUs).
The subrack has the following dimensions:
SIS Subrack
BFD 518 004/1
Hs
[mm]
Ws3
[mm]
Ws
[mm]
D
[mm]
Dc1
[mm]
300
465
450
250
280
Ws
Hs
Ws3
Figure 3-2 - SIS subrack
3.3
Cable Shelf
The cable shelf, SXK 123 122/1, is designed for a cabinet depth of
300 mm or 400 mm. The cable shelf is always mounted below the
SIS subrack.
The cable shelf has the following dimensions:
Cable shelf
SXK 123 122/1
Hs
[mm]
Ws3
[mm]
Ws
[mm]
D
[mm]
Dc2
[mm]
50
465
434
238
280
80 mm (max) is the available space for front cables.
1
2
Including cables
Including cables
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
9 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Cable Area
Figure 3-3 - Cable Shelf
3.4
Fan Unit
The fan unit BFD 509 13/1 is used, in order to implement the
principle of parallel cooling. That is in the cabinet the cooling air is
taken in at the front and is exhausted in the reserved air chimney
area at the back of the cabinet. The nominal depth of the air
chimney is ~ 100 mm.
Figure 3-4 - Parallel cooling
A rear plate is mounted 100 mm from the back of the cabinet to
secure a chimney so that pressure rise in the chimney can’t cause
heated air to be forced in to the above or below equipment the
wrong way.
The Fan unit has the following dimensions:
Fan Unit
BFD 50913/1
Hs
[mm]
Ws3
[mm]
Ws
[mm]
D
[mm]
50
465
435
240
FAN UNIT
Connector 1
Connector 2
Power
Alarm
Figure 3-5 - Fan Unit
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
10 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
3.5
Fire Enclosure
The fire enclosure, SXK 123 124/1 must be used beneath the
lowest installed equipment in the cabinet.
The fire enclosure bottom must be clean to allow free airflow.
Check the fire enclosure bottom regularly. The fire enclosure
bottom can be extracted to facilitate cleaning.
The fire enclosure has the following dimensions:
Fire enclosure
SXK 123 124/1
Hs
[mm]
Ws
[mm]
D
[mm]
16,2
427
250
The Fire Enclosure is shown in Figure 3-6.
Figure 3-6 - Fire Enclosure
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
11 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
3.6
Connection and Conversion Field, CCF
The CCF, BMF 904 10, is a cabinet mounted filter intended for
connection of external 2Mb/s E1 links with 75 ohms or 120 ohms
impedance.
The CCF is connected to the AUS-C by means of 100 ohms pair
cable, supplied with 10-pin Metral connector. The external side of
CCF is connected to DDF by means of 75 ohms coax cables or
120 ohms pair cables, supplied with 24 pin Sofix connectors.
The CCF includes parallel connection of dedicated pins between
in– and output connections, for testing of analogue subscriber
lines. Several nodes can therefore be connected in parallel to one
test unit without damping and impedance conversion of the test
signal.
The CCF has the following dimensions:
CCF
BMF 904 10
Hs
[mm]
Ws
[mm]
D
[mm]
286
25
75
The CCF is shown in the Figure 3-7.
Figure 3-7 - Connection and Conversion Field
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
12 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
4
Cabinet Installation
This instruction for wall mounting of cabinet BYB 502, defines what
steps have to be taken to ensure secure mounting of fully equipped
cabinet modules to a wall structure. The initial wall strength testing
operations are required to accurately obtain the wall strength value.
This value is converted in table 2 to the recommended rail
mounting torque. A drilling template is included with the cabinet
packing, and shall be used to achieve correct positioning of the
mounting holes.
Wall mounting kits, 18/BYB 502/1 includes all the parts required for
mounting one cabinet on a wall. Additional plugs & screws and
expanders are included for wall strength testing. General wall
mounting applications require the plug &screw solution for
mounting of rails. The supplied expanders should only be used
when seismic compliance is required.
All dimensions and tolerances are given in mm.
All tightening torques are given in Nm.
4.1
Validation
To ensure that wall mounted support assemblies for BYB 502 will
securely maintain accurate suspension of fully equipped cabinet
units, the installation application must comply with the following
sections:
1. All operation activities in the mounting instruction 1531-1/BYB
502 140/200 must be followed, and fulfils defined acceptance
criteria.
2. Wall mounting kits 18/BYB 502/1 must be used. None of the
supplied parts may be replaced by other similar products.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
13 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
4.2
Mounting of rails
4.2.1
Marking of mounting holes
Marking of the hole patterns on the wall may be performed
manually, or by using the supplied drilling template.
Brick wall:
Nail the template to the wall by using small nails.
Concrete wall:
Fix the template to the wall by using strong adhesive cello tape.
Check alignment with horizontal and vertical levels, by using a
water level or a plummet.
Figure 4-1 - Hole pattern for short rails
Drill guide holes with a 3-6 mm drill-bit through the markings 1, 3, 7
and 9. The guide holes should be drilled to a depth of 10-20 mm.
4.2.2
Choice of fasteners
The use of correct fasteners for fixing of rails on various wall
structures is crucial.
Information regarding fasteners and wall structures is available in
table1.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
14 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Information
Concrete and brick walls
Seismic compliance
The plug & screw should be
used in concrete and brick
walls.
The expander is only to be used
in unfractured concrete walls
with the wall strength values
C20/25 or higher.
The expander will withstand
earth quakes according to
Bellcore zone 4.
Drilling diameter
10 mm
12 mm
Drilling depth
85 mm
100 mm
Mounting torque
5 Nm-18 Nm
25 Nm
IMPORTANT
It is vital to achieve the
correct mounting torque, in
order to obtain the load
handling of 100 kg on short
rails alternatively 200 kg on
long rails.
Fasteners
It is vital to achieve the correct
mounting torque in order to obtain
seismic compliance and the load
handling of 100 kg on short rails
alternatively 200 kg on long rails.
Table 4-1- Choice of fasteners
IMPORTANT.
!
!
!
When the drill hits un-penetrable reinforcing iron in the concrete wall, move
the template at least 100 mm and drill new holes.
All holes intended for supports have to be spaced minimum 200 mm apart.
Holes intended for supports shall not be drilled closer than 150 mm from any
corner.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
15 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
4.3
Settings operations
4.3.1
Wall strength testing
Operation 1
Plug & screw/ expander: Drill the hole with a drill bit.
Operation 2
Plug & screw/ expander: Blow out dust and fragments.
Operation 3
Plug & screw/ expander: Install and tap in the plug.
Operation 1
Operation 2
Operation 3
Figure 4-2 - Setting Operations
Operation 4
Plug & screw/ expander: Position the rail.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
16 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Operation 5
Plug & screw: Mount the rail; apply the washer before tightening
the screw lightly.
Expander: Mount the rail, tap in the expander and tighten the bolt
lightly.
Operation 4
Operation 5
Figure 4-3 - Setting operations
Operation 6
Plug & screw:
Tighten the screw to 5 Nm. Check that the rail is securely tightened
against the wall. No vertical movements are allowed.
If this is achieved the testing is completed and approved.
If vertical movements of the rail is still obtained, continue tightening
the screw one Nm at a time, until the plug starts rotating in the wall.
Take a note of the last torque reading, and convert this to a
mounting torque value in table 2 on page14.
Figure 4-4 - Testing of torque
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
17 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Operation 6.2
Expander (Seismic compliance):
Tighten the bolt of the expander to 25 Nm. Check that the rail is
securely tightened against the wall. No vertical movements are
allowed. If this is achieved the testing is completed and approved.
If the expander starts rotating in the wall before 25 Nm is achieved,
it is not recommended to use expanders for mounting of the rails.
Revert to the instruction for plug & screw. See operation 1 on page
12.
4.4
Alignments
Make sure the short rails are aligned with the given tolerance
before tightening the fasteners. See Figure 4-5. Adjust if
necessary.
Insert the clevis pins in the two upper holes.
Figure 4-5 - Alignment of short rails
4.5
Tightening torque
Convert the previously established testing torque value to the
recommended mounting torque in table 2.
The lowest of the stated values in the mounting torque column is
the recommended mounting torque value. If vertical movements
can still be applied to the rail, tighten the fasteners one Nm at a
time, until the rails are securely fixed. The tightening torque must
not exceed the higher of the stated mounting torque values for
each level.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
18 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Denomination
Plug & screw
Expander
Testing
torque (Nm)
Mounting
torque (Nm)
7
5-6
8
5-6
9
6-7
10
6-8
11
6-9
12
7-10
13
7-10
14
8-11
15
9-12
16
9-12
17
10-13
18
10-14
19
12-15
20
13-16
21
15-17
22
16-18
25
25
Information
Concrete and
brick walls
Concrete walls
Table 4-2 - Conversion table from testing torque to mounting torque
values.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
19 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
5
Rail mounting of the base unit
5.1
Preparation of cabinet base
Lift off the front cover and remove top, bottom and side covers for
necessary access. The top and bottom covers are mounted with
four screws each.
1
Loosen the front of the side cover by unscrewing the two
mounting screws a couple of turns.
2
Pull the side cover outwards.
3
Unhook the back of the side cover by moving it backwards.
Figure 5-1 - Base unit and covers
5.2
Assembly bolt preparation
Position the four assembly bolts in their dedicated holes at the rear
of the cabinet base. Push the centre screw through the base until
an audible click is heard.
1.
Figure 5-2 - Positioning of assembly bolt and its correct position
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
20 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Figure 5-3 shows the protrusion of the assembly bolt at the back of
the base unit when inserted correctly.
Figure 5-3 - Assembly bolt seen from the back
5.3
Positioning of the cabinet
Support the weight of the cabinet base and carefully position
protruding ends of the assembly bolts in the rail openings. Hold the
cabinet base firmly against the rails while continuing with the
following steps:
IMPORTANT:
Clevis pins are not intended to provide support until the assembly
bolts have been engaged in the rails.
INFORMATION:
Access to the assembly bolts in equipped cabinets (supplied with
subrack), is only possible from the top and bottom at the rear of the
base unit.
Figure 5-4 - Wall mounted base unit seen from above
1.
Carefully unscrew the centre screw of the assembly bolt to its
end position.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
21 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
2.
Position the base unit against the rails, slightly push the screw
and rotate the large washer a quarter of a turn in order to
engage the rear flange in the rail. See Figure 5-5
Figure 5-5 - Locking the assembly bolts in the rails
3.
Make sure the flanges of the large washer fit into the dedicated
cutouts of the base unit when turned correctly.
4.
Pressing the centre screw of each assembly bolt can perform
vertical adjustments of the base unit. (This requires
simultaneous pressing of two or four centre screws)
5.
Tighten the centre screw of each assembly bolt. This will
prevent the base unit to slide downwards.
6.
Avoid using the Clevis pins as additional supports when
mounting a fully equipped cabinet. This may cause damage to
the assembly bolts.
7.
Align the base unit with the top of the rails.
8.
Tighten the four bolts with a torque of 40 Nm. See Figure 5-6
Figure 5-6 - Locking the base unit
9.
Mount the end plugs to all rails for protection
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
22 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
6
Accessories and covers
6.1
Cable access
Remove the pre-punched plate by hand from the top or bottom
cover, to achieve desired cable access to the cabinet.
Figure 6-1 - Removal of pre-punched plate
6.2
Grounding the base unit
The base unit is supplied with four grounding points. Two are
positioned on the left hand side, and two on the right hand side of
the frame. Attach the cable lug to dedicated grounding positions in
the base unit. Note the positioning of washers between base unit
and lug. See fig.
Figure 6-2 - Grounding of base unit
Tighten bolts with torque 12 Nm. Cable lug assembly in Figure 6-2
shows the right hand grounding position.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
23 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
6.3
Connecting the ESD strap
The ESD strap may be connected to one of four positions in each
base unit. See figure 43.
Figure 6-3 - ESD connection
6.4
Mounting the covers
1. Mount the bottom cover with four screws.
2. Mount the top cover with four screws.
3. Mount the side covers individually by first hooking the back end
into the slot of the base unit, and slide it forwards. Push in the
front end against base unit and lock in position by tightening the
two screws. Recommended tightening torque 2 Nm.
4. Mount the front cover by positioning the guide pins in the base
unit slots. Lock the cover by pressing the two handles
downwards until an audible click is heard.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
24 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
7
Equipment Installation
7.1
Subrack
The SIS subrack is mounted according to the Figure 7-1.
FAN
P0314
CCF 01
P2102
CCF 00
P0102
SIS
P0302
FEB
P0400
CABLE SHELF
P0300
Figure 7-1 - Position numbering for SNAR
7.1.1
Ground connection of subrack
When the subrack is mounted, make sure that enough torque is
used to get good ground connection to the cabinet (10 Nm). Use
tool Torx T30.
10 Nm
Figure 7-2 - Grounding of subrack to the cabinet
7.1.2
Subrack ID
The subrack identity, SUBID, is the subrack number in the
configuration file of the system node. There is a DIP-switch on the
back-plane where the number is set. Normal binary coding of the
number is used and the 4 least significant bits are decoded by the
back-plane. The Dip-switch must be set before the boards are
inserted in the subrack.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
25 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
7.1.3
Subrack Allocation
TAU
TAU-C
AUS-C
AU
AUS
AU
AU
AU
AU
AU
AU
AU
AU
AU
AU
DU-3
AU
DU-3
The SIS subrack has 18 slots, numbered 1-16, 29,30. Two of
these, slots 29 and 30, are half-height slots reserved for DU-3
boards. The rightmost slot, number 16, always contains a TAU-C,
while the slot number 15 always contains a TAU.
Figure 7-3 - SIS Subrack allocation
One AUS/ AUS-C pair is always located in slots 14 and 13.
The remaining 12 slots are used for AU boards.
For any partially equipped subrack, the following rules apply:
1. Place AU boards from right to left, starting at slot #12.
2. Dummy panels must cover unused slots. First, 100 mm
covers must be used as far as possible to cover four slots at
a time. Then, 25 mm covers must be used to cover any
remaining empty slots.
7.2
Fan Unit
The fan unit is always mounted above the subrack, according to
Figure 7-1. Put the Fan Unit on the guiding bars and push it in
position. Put the screws in the positions on the sides of the front.
Tighten all screws.
7.3
Cable Shelf
The cable shelf is always mounted below the subrack, according to
Figure 7-1.
7.4
Fire Enclosure
The fire enclosure is always used below the cable shelf.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
26 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
The fire enclosure bottom must be clean to allow free airflow.
Check the fire enclosure bottom regularly. The fire enclosure can
be extracted to facilitate cleaning.
7.5
CCF
The CCF is vertically mounted in the right and left ducts of the
cabinet, according to the picture below.
The following mounting kits are used: 4/BMF90410/1 (right side)
and 4/BMF90410/2 (left side). They include a mounting support
with spring locking of CCF.
Figure 7-4 - Installation of CCF with 4/BMF 90410/1
Generic instructions for the installation and positioning of CCF in
the cabinet can be found in [4].
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
27 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
8
Electrical Connections of Units
8.1
Board connectors
The figure below shows the front connectors for EAR boards.
M
DU-3 I
A
AUS-EP
MIA
X104
X106
OS
OS
IS
27
IS
27
26
26
25
25
24
23
24
23
22
22
21
21
20
19
20
19
18
18
X110
17
17
16
15
16
15
X111
14
14
13
12
13
12
X112
11
11
10
10
09
09
08
07
08
07
06
06
X115
05
05
04
03
04
03
X116
02
02
01
01
00
X107
X108
X114
MIA
TAU-C
MIA
MIA
I
N
T
E
R
C
.
I
N
I
N
T
E
R
C
.
O
U
T
S
U
B
S
C
R
I
B
E
R
C2
C1
C0
A5
A4
A3
A2
A1
A0
00
ET
SYNC-RING
EMRP-
EMRP-
X118
AUS
F
A
N
LED.TEST
S
U
B
S
C
R
I
B
E
R
ET
AUS-EP
TAU
AU-ISDN
MIA
PWR
COM
SYN
CSR
TL1
TL2
RX
-TX
AUS-C
AU-PSTN
MIA
AUS
AUS-C
MIA
EXT.TEST
1
0
1
0
ET
ET
AU-PSTN
AU-ISDN
TAU
X107
P
W
R
X106
0
X108
X110
X111
X112
X114
X115
X116
NB-ALARM
X118
00
ET
X106
X104
BB-ALARM
TAU-C
DU-3
Figure 8-1 - Board connectors
8.2
Internal cabling
Internal cables for SNAR cabinet are normally arranged in NTM
kits and are included in the cabinet structure.
Two NTM kits exist:
!
NTM 180 20/142
SIS cable set
!
NTM 180 20/143
SIS PRA cable set
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
28 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
8.2.1
SIS Cable set, NTM 180 20/142
8.2.1.1
AUS Synch
On AUS there is a connector to be used for clock synchronization
(Sync-Ring). The Sync-Ring is built -up in a ring structure from one
AUS to the next and back again with communication possible in
two directions as the redundancy principle.
In case of SNAR, one AUS is used and to close the ring, a loop
cable has to be implemented on AUS board itself. The cable to be
used is TSR 910 2006/300.
The cable must be connected between the AUS board outlets
called “RX” (X116-1) and “TX” (X116-5).
8.2.1.2
AUS-C - AUs cabling
The connection between AUS-C board and the AUs is performed
with unscreened balanced two pair cables with 10 poles connector,
TSR 910 2006/500.
The table below shows the ET ports allocation of AUS-C board and
the corresponding AU slot.
AUS-C
AU
Connector
PIU Front
Marking
To Slot /
Connector
X116-1
ET02
Slot 1
X115-5
ET03
X115-3
Cable/ length
TSR 910 2006/600
Slot 2
X118-5
X118-5
ET04
Slot 3
X118-5
TSR 910 2006/500
X115-1
ET05
Slot 4
X118-5
TSR 910 2006/500
X114-5
ET06
Slot 5
X118-5
TSR 910 2006/500
X114-3
ET07
Slot 6
X118-5
TSR 910 2006/500
X114-1
ET08
Slot 7
X118-5
TSR 910 2006/500
X112-5
ET09
Slot 8
X118-5
TSR 910 2006/400
X112-3
ET10
Slot 9
X118-5
TSR 910 2006/400
X112-1
ET11
Slot 10
X118-5
TSR 910 2006/400
X111-5
ET12
Slot 11
X118-5
TSR 910 2006/400
X111-3
ET13
Slot 12
X118-5
TSR 910 2006/400
TSR 910 2006/600
Table 8-1 – ET ports allocation for AUS-C/AU connection
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
29 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
8.2.1.3
AUS-C/TAU cabling
The connection between TAU board and AUS-C is performed with
an unscreened balanced two pair cable with 10 poles connector,
TSR 910 2006/ 400.
The cable is connected from the TAU board outlet called “ET 00”
(X118-5) to the AUS-C 0 outlet called “ET 21” (X107-5).
8.2.1.4
TAU-C strap
Not used.
8.2.1.5
AUS-C/ CCF connections
The cable TSR 910 2006/500 is connected from the AUS-C board
to the CCF 01 (right side) according to the following rules:
AUS-C
8.2.1.6
CCF-01
Comments
Connector
PIU Front
Marking
Connector
X104-5
ET 27
X121-1
0
X106-1
ET 26
X120-5
1
X106-3
ET 25
X120-3
2
X106-5
ET 24
X120-1
3
High traffic
X107-1
ET 23
X119-5
4
High traffic
Fan Cables
The fan unit is supplied from the DU-3 boards in the subrack
through two cables TSR 491 0225/400 and TSR 491 0225/500.
These cables also transmit alarm signals from the fan unit to the
system.
The fan cable is connected to the DU board outlet called “FAN” and
at the fan unit to outlet called “Connector 1" and “Connector 2".
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
30 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
8.2.2
PRA cable set, NTM 180 20/143
8.2.2.1
AUS-C/ CCF (PRA connections)
The connection between AUS-C board and the CCF (PRA
connections) is performed with unscreened balanced two pair
cables with 10 poles connector, TSR 910 2006/700
The table below shows the ET ports allocation of AUS-C board and
the corresponding CCF port.
AUS-C
CCF-00
Connector
PIU Front
Marking
Connector/
Port
X111-1
ET14
X119-1
6
TSR 910 2006/700
X110-5
ET15
X119-3
5
TSR 910 2006/700
X110-3
ET16
X119-5
4
TSR 910 2006/700
X110-1
ET17
X120-1
3
TSR 910 2006/700
X108-3
ET19
X120-3
2
TSR 910 2006/700
X108-1
ET20
X120-5
1
TSR 910 2006/700
X107-3
ET22
X121-1
0
TSR 910 2006/700
Cable/ length
Table 8-2 – ET ports allocation for AUS-C/CCF connection
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
31 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
8.3
External cabling
8.3.1
Power cables
The subrack has dual power feeding connection with redundancy.
The cable is connected to the DU board connector called “PWR”
and the other end to the power source. The power source shall be
compliant with the Ericsson TS-HOD 500 distribution scheme.
Location of the cabinets determines the required power distribution
cable length. Depending on the required length the appropriate
cross section area for the cable can be selected:
•
•
8.3.2
2 x 06 mm2
2 x 10 mm2
TSR 490 0106/ 30M
TSR 490 0107/ 50M.
Subscriber cables
The Subscriber cable is connected to the AU board outlet called
“Subscriber”, (X110-X112).
The subscriber cables from MDF to SIS come in different lengths.
DISTANCE TO MDF
PRODUCT NUMBER
0 – 10 m
TSR 910 1030/10M
10 – 15 m
TSR 910 1030/15M
15 – 30 m
TSR 910 1030/30M
30 – 50 m
TSR 910 1030/50M
50 – 70 m
TSR 910 1030/70M
70 – 150 m
TSR 910 1030/150M
The cables should be distributed between the two cables ducts of
the cabinet with the first 6 AU cables routed to the left and the
other AU cables routed to the right.
The colour coding of the pairs is shown in Table 8-3.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
32 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Subscriber
line number
Pair number
in cable
Connector pin
a/b wire
Colour code
a/b wire
1
1
A17/B17
white/blue
2
2
A16/B16
white/orange
3
3
A15/B15
white/green
4
4
A14/B14
white/brown
5
5
D13/C13
white/grey
6
6
D14/C14
red/blue
7
7
D15/C15
red/orange
8
8
D16/C16
red/green
9
9
D17/C17
red/brown
10
10
D18/C18
red/grey
11
11
A11/B11
black/blue
12
12
A10/B10
black/orange
13
13
A09/B09
black/green
14
14
A08/B08
black/brown
15
15
D07/C07
black/grey
16
16
D08/C08
yellow/blue
17
17
D09/C09
yellow/orange
18
18
D10/C10
yellow/green
19
19
D11/C11
yellow/brown
20
20
D12/C12
yellow/grey
21
21
A05/B05
white/blue
22
22
A04/B04
white/orange
23
23
A03/B03
white/green
24
24
A02/B02
white/brown
25
25
D01/C01
white/grey
26
26
D02/C02
red/blue
27
27
D03/C03
red/orange
28
28
D04/C04
red/green
29
29
D05/C05
red/brown
30
30
D06/C06
red/grey
Colour of
cable unit
marker
Table 8-3 - The colour coding of the pairs in Subscriber cable
blue
blue
orange
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
33 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
8.3.3
PRA/V5.1 Subscriber cables
The subscriber cables for PRA/V5.1 come in different lengths (see
below) and there is also the possibility to choose 75 ohms coax or
120 ohms balanced pair cable.
4 PRA connections are possible.
8.3.3.1
8.3.3.2
8.3.4
Shielded Pair Cable, 120 ohm with DC Barrier
DISTANCE TO DDF
PRODUCT TO ORDER
0 – 15 m
TSR 491 0289/15M
15 – 30 m
TSR 491 0289/30M
30 – 70 m
TSR 491 0289/70M
70 – 150 m
TSR 491 0289/150M
Coax cables 75 ohms
DISTANCE TO DDF
PRODUCT TO ORDER
0 – 15 m
TSR 492 0211/15M
15 – 30 m
TSR 492 0211/30M
30 – 70 m
TSR 492 0211/70M
70 – 150 m
TSR 492 0211/150M
Transmission cables
Transmission cables are E1 cables towards the (AXE) host. The
cables come in different lengths. There is also a possibility to
choose 75 ohms coax, TSR 492 0211, or 120 ohm pair cables,
TSR 491 0289, supplied with 24-pin Soffix connectors.
There are 5 positions to be used for 2Mb/s connections. The
positions are used according to the table below. Empty (not used)
positions can be used for PRA.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
34 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
Table 8-4 – CCF ports allocation
8.3.5
Port
Position
CCF 01
19
54
18
49
ISI
17
44
OSI
16
39
High traffic
15
34
Normal Traffic
14
29
Normal Traffic
13
24
Normal Traffic
12
19
Normal Traffic
External alarm cable
External alarms can be connected to SIS subrack via TAU-C. Six
ports are available for each TAU-C. The cable used is TSR 910
2007.The cables come in different lengths.
DISTANCE TO TAU-C
PRODUCT TO ORDER
0 – 30 m
TSR 910 2007/30M
30 – 80 m
TSR 910 2007/80M
80 – 150 m
TSR 910 2007/150M
The connection position is at TAU-C board outlet marked “NBALARM”, (X114-X116).
8.3.6
V24/ typewriter cable
A PC can be connected to EAR via RS232 interface. One cable is
available TSR 910 2018/15M. The cable must be connected at
AUS connector X115-5.
8.3.7
External Synchronization cable
For 2,048 Mb/s incoming external synchronization (ISI) of the node
or/and 2,048 Mb/s outgoing external synchronization signal (OSI),
the following cable, TSR 910 2006/500, can be used.
The cable is connected at CCF 01, according to the Table 8-4.
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
35 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
8.3.8
External test access
The TAU board outlet, called “Ext. Test” is used for connection of
external line and circuit test instruments. The cable to be used is
the TSR 491 381.
8.3.9
Extension of test bus between cabinets
To enable access at one point at a site with an external line and
circuit test instrument to several cabinets at a the same site, the
cabinets have to be interconnected with each other as in
Figure 8-3. Up to 8 nodes can be cascaded.
DESCRIPTION
External Test Equip.
LENGHT
PRODUCT TO ORDER
0 – 30 m
TSR 491 367/15M
30 – 75 m
TSR 491 367/75M
75 – 100 m
TSR 491 367/100M
0– 5m
TSR 491 368/5000
5 – 20 m
TSR 491 368/20M
0,3 m
TSR 910 2034/300
SNAR cascading
CCF-TAU cabling
TSR 491 368
SIS
Test Head
TAU
TAU-C
TAU
TAU-C
TAU
TAU-C
TSR 491 367
SIS
SIS
TSR 910 2034
TSR 910 2034
TSR 910 2034
Node 0
Node 1
Node 2
CCF
Figure 8-3 - External test access cabling
Information
Limited Internal
INSTRUCTION
Prepared (also subject responsible if other)
36 (36)
No.
ERI/YS A. Olivieri
1531-COA/BFE 30813 Uen
Approved
Checked
Date
Rev
Reference
ERI/YS (M. Palaia)
PC-SSS
07/09/2004
A
File
9
Glossary
AU
BB
DDF
DSUB
DU
DU-3
EMC
IE
ISDN
MDF
NBA
POTS
10
Access Unit
Broad Band
Digital Distribution Frame
D-sub Connector
Distribution Unit
Distribution Unit, type 3
Electromagnetic Compatibility
Installation Engineering
Integrated Services Digital Network
Main Distribution Frame
Narrowband Access subrack
Plain Old Telephone Service
References
1. 1531-18/BYB502 Uen, Wall Mounting Set 18/BYB502
2. 1531-1/BYB 502 140/200, Final assembly of cabinet 1/BYB 502140/200
3. 1531-FCM 101 1804 Uen, Handling of PBA ROJ
4. 1531-BMF 904 10 Uen, Installation instruction for CCF, BMF 904 10.
Download