NAME: KATLEGO GAOALAFE STUDENT ID: 202000271 LAB SLOT: MONDAY 2-4 MMB323 LAB 1 REPORT – DERTERMINATION OF DRYNESS FRACTION OF THE STEAM SUPPLY ABSTRACT Steam calorimeters are commonly used to determine the quality of steam in process industries, power plants and other industries. Performance of steam processes depend on the quality of. Separating or throttling or combined separating and throttling calorimeters are being used for this purpose. This experiment a combined calorimeter was used to determine the dryness fraction of steam. Finding of the separating and throttling calorimeters individually and then multiplying them together helped find the final value of steam. Experimental errors were found during the process however the objectives of the experiment were completed. INTRODUCTION This experiment was conducted to determine the dryness fraction of the steam supply using the combined separating and throttling calorimeters. The following shall fully explain the processes undergone. AIMS The aims of the experiments is to find out: ο· ο· Measurement of Dryness fraction of steam by using : 1. The separating calorimeter 2. The throttling calorimeter 3. Both separating and throttling calorimeter together Understanding various methods of measurement of Dryness fraction THEORY 1. Separating calorimeter: Separating calorimeter is used when the steam is very wet, the quality of wet steam is shown by its dryness fraction. When the dryness fraction, pressure and temperature of the steam are known, then the state of wet steam is fully defined. Figure 1: Separating calorimeter The steam is collected out of the main steam supply and enters the separator from the top. The steam is forced to make a sharp turn when it hits the perforated cup (or any other mechanism that produces the same effect). This results in a vortex motion in the steam, and water separates out by the centrifugal action. The droplets then remain inside the separator and are collected at the bottom, where the level can be recorded from the water glass. The dry steam will pass out of the calorimeter into a small condenser for the collection of the condensate. However, not all the water droplets remain in the collector tank. Some water droplets pass through to the condenser, and hence this calorimeter only gives a close approximation of the dryness fraction of the steam. From the results obtained from the two collectors, the dryness fraction may then be found from Dryness fraction = This can be expressed as: x= M is the mass of dry steam and m is the mass of suspended water separated in the calorimeter in the same time. 2. Throttling calorimeter: It is used when steam is nearly dry. This calorimeter is operated by first opening the stop valve completely so that the steam is not partially throttled as it flows through the apparatus for a while to allow the pressure and temperature to stabilize. If the pressure is very near to atmospheric pressure, the saturation should be 100°C, it may be assumed that the steam is superheated. When the conditions have become steady, the gauge pressure before throttling is read from the pressure gauge. After throttling, the temperature and gauge pressure are read from the thermometer and manometer. The barometric pressure is also recorded. From the equation h1=h2 .We have: β2 p1=hsup at p2 βπ1 + π ∗ βππ1 = βπ2 + πΆπ (ππ π’π − ππ ππ‘ ) π= Figure 2: Throttling calorimeter βπ2 + πΆπ (ππ π’π − ππ ππ‘ ) − βπ1 βππ1 3. Separating and throttling calorimeter: If the steam dryness fraction is to be determined is very wet then throttling to atmospheric pressure may not be suitable to ensure superheated steam at exit. In this case it is necessary to dry the steam partially, before throttling. Done by passing the steam from the main through a separating calorimeter as shown in figure 3. The steam changes direction suddenly, and the water being denser than the dry steam is separated out. The quantity of water which is separated out (mw) is measured at the separator, the steam remaining which now has a higher dryness fraction, is passed through the throttling calorimeter. With the combined separating and throttling calorimeter it is necessary to condense the steam after throttling and measure the amount of condensate (ms). If a throttling calorimeter only is sufficient, there is no need to measure condensate, the pressure and temperature measurements at exit being sufficient. Figure 3: Separating and throttling calorimeter APPARATUS USED ο· ο· ο· ο· Mini steam power pant Separating calorimeter Throttling calorimeter Measuring cylinder PROCEDURE The isolating valves (V1) were checked to see if it was closed for both the separating and throttling calorimeter. Steam flow along the steam header was arranged furthermore the steam trap pipe in the closure unit, P7682 was not isolated. Moreover the steam header was allowed to reach full working pressure and temperature. The cooling water supply valve (V4) was then turned on, furthermore the condensate collecting valves were placed under the condenser outlet. Afterwards the drain valves (V2) and the small valves (V3) were closed and the digital manometer of throttling calorimeter was isolated. Moreover water flowing through the condenser was checked to ensure it being sufficient to condense the steam. The steam valves (V1) were then open allowing steam to flow, followed by the partial opening of the drain valve (V2) the steam flowed through the separating chamber to warm up the system. During this process the drain vessel collects water. Afterwards the drain valve (V2) were closed followed by the opening of valve (V3) to the manometer. The separating condensate level was allowed to build up and can be seen in the calorimeter level tube. Furthermore the main condensate collecting vessel was drained and put back. The following measurements were then taken, the initial value of fluid level in the separating calorimeter, the initial value of the condensate level in the collecting vessel, the steam pressure, the steam pressure after throttling and the main steam temperature. The values of the last four quantities were recorded every 10 minutes for about six times during the experiment, followed by the recording of the barometric pressure. Furthermore a reasonable amount of condensate was allowed to collect then measured and the value of fluid level in the separating calorimeter was also noted .Afterwards the steam supply (V1) was turned off once the experiment ended, followed by the closing of valve (V3) to isolate the manometer. Moreover everything was allowed to cool and the condenser cooling water valve (V4) was turned off .Draining of the separating calorimeter and the condensate collecting vessel was done. RESULTS Table 1: Showing results found in the experiment DATA Steam pressure in P1(bar) Temperature in main before throttling T1(deg) Steam pressure after throttling P2(bar) Temperature in main after throttling T2(deg) 1 7 2 6.5 3 7 4 7 5 6.75 6 6.5 Average 6.792 172 170 172 172 172 171 171.5 73 72 71 72 72 72 72 116 120 121 121 122 124 121 Table 2:Showing the values of separated water, condensate and the barometric pressure DATA Quantity of separated water(ml) Quantity of condensate water(ml) Barometric pressure(bar) VALUE 415 11590 1.5 Figure 4: Separating and throttling calorimeter Calculating the dryness fraction of the steam supply by using a) Separating calorimeter: ππ ππ + ππ€ 11590 = 11590 + 415 = π. πππ π₯1 = b) Throttling calorimeter βπ + πΆππ (ππ π’π − ππ ππ‘ ) − βπ βππ (β2− β1 )(π − π1 ) βπ = π1 − π2 (2722 − 2766)(72 − 70) = + 2722 75 − 70 = 2754.4 ππ½/ππ (β2− β1 )(π − π1 ) βπ = π1 − π2 (697 − 670)(6.792 − 6) = + 691.384 7−6 691.384ππ½ = ππ (β2− β1 )(π − π1 ) βππ = π1 − π2 π₯2 = (2067 − 2087)(6.792 − 6) + 2087 7−6 π2 − π1 ππ ππ‘ = × (π − π1 ) + π1 π2 − π1 290.5 − 285.8 = × (72 − 70) + 285.8 75 − 70 = πππ. πβ = Therefore: 2754.4 + 2.1(121 − 287.5) − 691.384 2075.16 = 0.256 c) Combined throttling and separating calorimeter π = π₯1 × π₯2 = 0.826 × 0.996 = π. πππ π₯2 = DISCUSSION The dryness fraction of the combined separating and throttling calorimeter was calculated using the individual dryness fractions from separating calorimeter is 0.996 followed by 0.826 from throttling and then multiplying them together, the value obtained was 0.822. This shows that the steam was wet but because the value is close to 1, this means it contained few particles of water. The value of the dryness fraction calculated with the throttling calorimeter is not realistic as when we compare it with that of a similar experiment conducted by,( Sagar G. Mushan et al, 2020), the value is always above 0.95. this error may have been caused by experimental errors including but not limited to: incorrect calibration of the steam calorimetry, incorrect reading of the temperature and pressure on the system and human error when taking the water level readings with respect to the sight glass reference work. it would be recommended to maintain the laboratory apparatus to reduce risk of more experimental error. CONCLUSION In conclusion, the purpose of this experiment was to estimate the quality of steam using a combined throttling and separating calorimeter and the objective of the experiment was completed. The dryness fraction of steam at the separating and throttling calorimeter was 0.996 and 0.822 respectively. when combined the overall value was 0.822. REFERENCES 5.2 calorimetry - chemistry 2E. OpenStax. (n.d.). Retrieved March 17, 2023, from https://openstax.org/books/chemistry-2e/pages/5-2-calorimetry Moran, M. J., & Shapiro, H. N. (2004). Fundamentals of Engineering Thermodynamics. John Wiley & Sons. Sumeet Salunkhe: “Performance improvement of throttling calorimeter”, M.Tech Report, 2017