Tugas Perancangan Bangunan Sipil 4 BAB VII PERENCANAAN DIMENSI BATANG KOLOM A. Diketahui fy = 250 MPa fr = 70 MPa E = 200.000 MPa U = 0,3 B. Data profil baja pakai ( Profil WF. 175 . 175 . 5,5 . 8 ) tf tw h h2 r h1 bf ht ht = 170 mm bf = 125 mm tw = 5,5 mm tf = 8 mm r = 12 mm A = 29,65 cm2 = 2965 mm2 lx = 1530 cm4 = 15300000 mm4 ly = 261 cm4 = 2610000 mm4 rx = 7,18 cm = 718 mm ry = 2,97 cm = 297 mm Sx = 181 cm3 = 181000 mm3 Sy = 41,8 cm3 = 41800 mm3 C. Data Balok Kolom Lx =6m = 6000 mm Ly =3m = 3000 mm a = 0,5 m = 500 mm ts = 6 mm Mu = 1292,58 kgm 1 Ma = x Mu 4 Mb = Mc = 1 2 3 4 = 12925800 N.mm = 3231500 N.mm x Mu = 6462900 N.mm x Mu = 9694400 N.mm Nu = 4309,34 kgf = 43093,4 N Vu = 235,01 kgf = 2350,1 N Φn = 0,85 Φb = 0,9 Φf = 0,75 202510079 - 202510089 Tugas Perancangan Bangunan Sipil 4 D. Section Properties G = = E 2 × (1+U) 200000 2 × (1+0,3) = 76923,0769 MPa h1 = tf + r = 8 + 12 = 20 mm h2 = ht – (2 x h1) = 175 – (2 x 20) = 135 mm h = ht – tf = 175 – 8 = 167 mm J 1 1 3 3 = 2 x x bf x tf3 + x (ht – 2 x tf) x tw3 1 1 3 3 = 2 x x 175 x 83 + x (175 – 2 x 8) x 5,53 = 51484,5417 mm4 Iw = Iy × h2 4 = 2610000 × 1352 4 = 18197572500,000 mm6 X1 = = π Sx ×√ π 219000 ExGxJxA 2 ×√ 200000 × 76923,0769 × 51484,5417 × 2965 2 = 18808,3369 MPa X2 = 4 x ( Sx GxJ =4×( )2 x lw ly 181000 76923,0769 × 51484,5417 )2 × 18197572500,000 2610000 = 0,00005825 mm2/N2 Zx = = tw x ht2 4 + ( bf – tw) x ( ht – tf ) x tf 5,5 × 1752 4 + ( 175 – 5,5 ) x ( 175 – 8 ) x 8 = 201761,3750 mm3 Zy = tf x bf2 2 202510079 - 202510089 + ( ht – 2 x tf ) x tw2 4 Tugas Perancangan Bangunan Sipil 4 = 8 × 1752 2 + (175 – 2 x 8) x 5,5 4 = 63702,4375 mm3 E. Perhitungan Kekuatan Syarat yang harus dipenuhi untuk balok dengan pengaku : a h 500 167 ≤ 3 ≤ 3 2,9940 ≤ 3 (OKE) Ketebalan plat badan dengan pengaku vertical tanpa pengaku memanjang harus memenuhi : h tw 167 5,5 ≤ 7,07 x √ ≤ 7,07 x √ 30,3636 E fy 200000 250 ≤ 199,9698 (OKE) 1. Momen Nominal Pengaruh Tekuk Lokal (Lokal Buckling) a. Pengaruh tekuk lokal sayap Kelangsingan penampang sayap λ = bf tf = 175 8 = 15,6250 Batas kelangsingan maksimum penampang compact λp = 500 √fy = 500 √250 = 31,6228 Batas kelangsingan maksimum penampang non compact λr = 625 √fy = 625 √250 = 39,5285 Momen plastis Mp = fy x Zx = 250 x 201761,3750 = 50440343,7500 N.mm Momen batas tekuk Mr = Sx x (fy – fr) = 181000 x ( 250 – 70 ) = 32580000 N.mm Didapat λ < λp dan λ < λr, maka berdasarkan nilai kelangsingan sayap termasuk penampang compact. Momen nominal untuk penampang compact Mn = Mp = 50440343.7500 N.mm 202510079 - 202510089 Tugas Perancangan Bangunan Sipil 4 b. Pengaruh Tekuk Lokal Badan Kelangsingan penampang badan λ = h 167 = tw 5,5 = 30,3636 Batas kelangsingan maksimum penampang compact λp = 1680 = √fy 1680 √250 = 106,2525 Batas kelangsingan maksimum penampang non compact λr = 2550 = √fy 2550 √250 = 161,2762 Didapat λ < λp dan λ < λr, maka berdasarkan nilai kelangsingan sayap termasuk penampang compact. Momen nominal untuk penampang compact Mn = Mp = 50440343,7500 N.mm 2. Momen Nominal Untuk Balok Plat Berdinding Penuh Kelangsingan penampang badan λ= h tw = 167 5,5 = 30,3636 Untuk penampang yang mempunyai ukuran : h tw < λp 30,3636 < 39,5285 (OKE) Koefisien momen tekuk torsi lateral Cb = = 12,5 × Mu (2,5 × Mu + 3 × Ma + 4 × Mb + 3 × Mc) 12,5 × 12925800 (2,5 × 12925800 + 3 × 3231500 + 4 × 6462900 + 3 × 9694400) = 1,6667 < 2,3 (OKE) Maka diambil Cb = 1,7 Perbandingan luas plat badan terhadap luas plat sayap ar = = h × tw bf × tf 167 × 5,5 175 × 8 = 0,9185 Momen inersia I1 = = Iy 2 - 1 12 x tw3 x 2610000 2 - 1 12 h2 3 x 5,53 x = 1304376,0938 mm4 Luas penampang A1 202510079 - 202510089 = A 2 1 - x tw x h2 3 135 3 Tugas Perancangan Bangunan Sipil 4 = 2965 1 − x 5,5 x 135 2 3 = 1235 mm2 Jari – jari girasi daerah plat sayap ditambah sepertiga bagaian plat badan yang memgalami tekan r1 =√ l1 A1 =√ 1304376,0938 1235 = 32,4988 mm a. Momen Nominal Berdasarkan Tekuk Torsi Lateral Jarak antar pengekang lateral L = Ly = 3000 mm Angka kelangsingan λg = = L r1 3000 32,4988 = 92,3111 Batas kelangsingan maksimum untuk penampang compact λp = 1,76 x √ = 1,76 x √ E fy 200000 250 = 49,7803 Batas kelangsingan maksimum untuk penampang non compact λr = 4,40 x √ = 4,40 x √ E fy 200000 250 = 124,4508 Tegangan acuan untuk momen kritis tekuk torsi lateral fc = Cb x = 1,7 x fy 2 250 2 = 212,5 MPa Karena fc < fy, maka diambil fc = 212,5 MPa Sedangkan λg < λr, maka tegangan kritis penampang dihitung sebagai : fcr = Cb x fy x (1 − λg− λp ) 2 x (λr− λp) = 1,7 x 250 x (1 − 92,3111 − 49,7803 2 x (124,4508 − 49,7803) = 303,9643 MPa Karena fcr > fy, maka diambil fcr = 250 MPa 202510079 - 202510089 ) Tugas Perancangan Bangunan Sipil 4 Modulus penampang elastis S = Sx = 181000 mm3 Koefisien balaok plat berdinding penuh Kg =1–( =1-( ar (1200+300)× ar )x( 0,9185 h tw − 2550 √ fcr 167 (1200+300) × 0,9185 )x( 5,5 − ) 2550 √ 250 ) = 1,0815 Momen nominal penampang Mn = kg x Sx x fcr = 1,0815 x 181000 x 250 = 48937875.0000 N.mm b. Momen Nominal Berdasarkan Tekuk Lokal Pada Sayap Kelangsingan penampang sayap λg = = bf 2 × tf 175 2×8 = 7,81 faktor kelangsingan pada plat badan Ke 4 = √ = h tw 4 167 √ 5,5 = 0,726 > 0,763 Maka diambil 0,726 Batas kelangsingan maksimum untuk penampang kompak λp = 0,38 x √ = 0,38 x √ E fy 200000 250 = 10,7480 Batas kelangsingan maksimum untuk penampang non kompak λr E = 1,35 x √k e × fy = 1,35 x √0,726 × = 32,5347 202510079 - 202510089 200000 250 Tugas Perancangan Bangunan Sipil 4 Tegangan acuan untuk momenkritis tekuk lokal fc = = fy 2 250 2 = 125 MPa karena λG ≤ λr, maka tegangan kritis penampang dihitung sebagai : fcr = fy = 250 MPa modulus penampang elastis S = Sx = 181000 mm3 Kg =1–( =1–( ar )x( (1200+300).ar h tw 0,9185 2550 − √ fcr 167 )x( (1200+300) × 0,9185 5,5 ) − 2550 √ 250 ) = 1,0815 Momen nominal penampang Mn = kg x S x fcr = 1,0815 x 181000 x 250 = 48937875 N.mm 3. Momen Nominal Pengaruh Tekuk Lokal Panjang batang maksimum balok yang mampu menahan momen plastis Lp = 1,76 x ry x √ E fy = 1,76 x 297 x √ 200000 250 = 14784,7543 mm fL = fy – fr = 250 – 70 = 180 MPa Panjang bentang minimum balok yang tahananya ditentukan oleh momen kritis tekuk torsi lateral Lr ry × x1 = √ 1+ √ 1+(x2 × fL2 ) 297 × 18808,3369 = √ 1+ √ 1 + (0,00005825 × 1802 ) = 50986,1631 mm Koefisien momen tekuk torsi lateral Cb = = 12,5 × Mu (2,5 × Mu + 3 × Ma + 4 × Mb + 3 × Mc) 12,5 × 12925800 (2,5 × 12925800 + 3 × 3231500 + 4 × 6462900 + 3 × 9694400) = 1,7 202510079 - 202510089 Tugas Perancangan Bangunan Sipil 4 Momen plastis Mp = fy x Zx = 250 x 201761,3750 = 50440343,8 N.mm Momen batas tekuk Mr = Sx x (fy - fr) = 181000 x (250 -70) = 32580000 N.mm Panjang bentang terhadap sumbu y (jarak dukungan lateral) L = Ly = 3000 mm Maka didapat L < Lr, sehingga termasuk kategori bentang pendek, sehingga momen nominal dihitung sebagai berikut : Mn = Mp = fy x Zx = 250 x 201761,3750 = 50440344N.mm 4. Momen Nominal Pengaruh Tekuk Lokal Badan Kelangsingan penampang badan λ = = h tw 167 5,5 = 30,364 Gaya aksial leleh Ny = A x fy = 2965 x 250 = 741250 N Nu / ( Φb x Ny ) 43093,4 / 0,9 x 1741250 = 0,065 N Maka λp = = 1680 √fy 1680 √250 2,75 × Nu x (1- Φb × Ny x (1- ) 2,75 × 43093,4 0,9 × 1741250 ) = 87,260 Batas kelangsingan maksimum untuk penampang compact λp = 87,260 Penampang non compact λr = = 2550 √fy 2550 √250 x (1x (1- = 153.5188 202510079 - 202510089 0,74 × Nu Φb × Ny ) 0,74 × 43093,4 0.9 × 1741250 ) Tugas Perancangan Bangunan Sipil 4 Didapat λ < λp dan λ < λr, maka berdasarkan nilai nilai kelangsingan sayap termasuk penampang compact Momen nominal untukpenampang Mn = Mp Mp = fy x Zx = 250 x 201761,3750 = 50440344 N.mm 5. Tahanan momen lentur a. Momen normal pengaruh local bucking Momen nominal pengaruh local bucking pada sayap Mn = 50440343,75 Nmm Momen nominal pengaruh local bucking pada badan Mn = 50440343,75 Nmm b. Momen normal balok plat berbanding penuh Momen nominal pengaruh tekuk torsi lateral Mn = 48937875 Nmm Momen nominal pengaruh local bucking pada sayap Mn = 48937875 Nmm c. Momen nominal pengaruh lateral bucking Mn = 50440343,75 Nmm d. Momen nominal pengaruh local bucking pada badan Momen nominal ( terkecil ) yang menentukan Mn = 48937875 Nmm Tahanan momen lentur Ɵb Mn = 0,9 x 48937875 = 44044087,50 Nmm 6. Tahanan aksial tekan Tumpuan jepit sendi k = 0,8 Panjang batang Lx = 6000 mm, Ly Panjang batang efektif Lkx = k x Lx = 0,8 x 6000 = 4800 mm Panjang batang efektif Lky = k x Ly = 0,8 x 3000 = 2400 mm Parameter kelangsingan terhadap sumbu x λcx 202510079 - 202510089 = 1 π x Lkx rx ×√ fy E = 3000 mm Tugas Perancangan Bangunan Sipil 4 = 1 π 4800 x × √ 718 250 200000 = 0,0752 Karena λcx < 0,25, maka ωx =1 Parameter kelangsingan terhadap sumbu y λcy = = 1 π 1 π Lky x ry ×√ 2400 x 297 fy E × √ 250 200000 = 0,0909 Karena λcy < 0,25, maka ωy =1 Tegangan tekuk terhadap sumbu x fcr x = fy ωx = 250 1 = 250 MPa Tegangan tekuk terhadap sumbu y fcr y = = fy ωy 250 1 = 250 MPa Tahanan aksial tekan Nnx = A x fcrx = 2965 x 250 = 741250 N Nny = A x fcry = 2965 x 250 = 741250 N Tekanan aksial tekan nominal terkecil Nn = 741250 N Tekanan aksial tekan = Ɵn x Nn = 0,85 x 655686 = 557333 7. Interaksi aksial tekan dan momen lentur 43595,4 Nu Ɵn × Nn = 43093,4 557333 = 0,0773 < 0,2 maka = Nu Ɵn × Nn 202510079 - 202510089 + 8 9 × Mu Ɵb × Mn Tugas Perancangan Bangunan Sipil 4 = 43093,4 557333 + 8 9 × 12925800 44044088 = 0,3321 < 1 (OKE) 8. Tahanan geser Luas penampang badan Aw = tw x ht = 5,5 x 175 mm2 = 962,5 Kn = 5+5 a ( )2 h = 5+5 500 ( )2 167 = 5,5578 Perbandingan tinggi terhadap tebal badan h = tw 167 5,5 = 30,364 1,10 √Kn × E fy 200000 = 1,10 √5,5578 × 250 = 73.3481 1,37 √Kn × E = 1,37 √5,5578 × fy 200000 250 = 91,3518 Karena h tw < 1,1√kn E fy h dan tw < 1,37√kn E fy maka termasuk tahanan geser plastis Sehingga tahanan geser nominal dihitung sebagai berikut Vn = 0,6 x fy x Aw = 0,6 x 250 x 962,5 = 144375 N Tahanan gaya geser Ɵf x Vn = 0,75 x 144375 = 108281,25 N Gaya geser akibat badan terfaktor Vu = 2350,1 N Syarat yang harus dipenuhi Vu ≤ 2350,1 ≤ Ɵf x Vn 108281,25 9. Interaksi geser dan lentur Syarat yang harus dipenuhi Mu Ɵb × Mn 202510079 - 202510089 + 0,625 + Vu Ɵf × Vn < 1,375 (OKE) Tugas Perancangan Bangunan Sipil 4 12925800 44044088 + 0,625 + 2350,1 < 1,375 108281,25 0,3071 < 1,375 (OKE) 10. Dimensi Pengaku vertikal pada bahan Tebal plat pengaku pada badan (Stiffner), ts = 6 mm Tinggi plat pengaku, hs = ht – (2 x tf) = 175 – (2 x 8) = 159 mm Luas penampang plat pengaku As = hs – ts = 159 x 6 = 954 mm2 Untuk sepasang pengaku, D = 1 Cv = 1,5 x Kn x E fy x = 1,5 x 5,5578 x 1 h ( )2 tw 200000 250 x 1 167 ( )2 5,5 = 7,2340 Luas penampang pengaku plat harus memenuhi syarat sebagai berikut : 0,5 x D x Aw x (1+Cv) x a a 2 ( ) h h ( a √1+(h)2 0,5 x 1 x 962,5 (1 + 7,2340) x ( ≤ As ) 500 500 2 ( ) 167 167 500 2 ) 167 )≤ 954 √1+( 611 ≤ 954 (OKE) Pengaku vertical pada plat badan harus mempunyai momen inersia sebagai berikut Is 2 = x hs x ts3 3 2 = x 159 x 63 3 = 22896 mm4 a h = 500 167 = 2,9940 Untuk a > √2 h 2,9940 > 1,4142 Maka untuk momen inersia minimum di pakai rumus : 1,5 x h3 x tw3 a2 = 1,5 x 1673 x 5,5 5002 = 4649 mm4 Kontrol momen inersia plat pengaku Is > 22896 > 202510079 - 202510089 momen inersia minimum 4649 (OKE)