Uploaded by tassnim.mohammed

blowdown savings

advertisement
Incontrollable blowdown TDS
Manual TDS monitoring results in losing sensible heat energy generated inside the boiler thus
consuming more fuel, also more water and chemicals
Boiler 1
Make
StandardKessel
Capacity (t/h)
2
Design p (barg)
13
Operating p (barg)
9
Blowdown TDS range
750 - 2250
Feedwater TDS
180
Manual valve size (inch) 1
Boiler 2
Homani
3.2
15
9
1780 - 2360
180
1.5
Steam demand for bar hall = 485 100 kg/year
Existing blow down
Required blow down
𝐹𝑒𝑒𝑑 𝑤𝑎𝑡𝑒𝑟 𝑇𝐷𝑆 ∗ 𝑠𝑡𝑒𝑎𝑚 𝑙𝑜𝑎𝑑
𝐵𝑙𝑜𝑤𝑑𝑜𝑤𝑛 𝑇𝐷𝑆−𝐹𝑒𝑒𝑑 𝑤𝑎𝑡𝑒𝑟 𝑇𝐷𝑆
=
𝐹𝑒𝑒𝑑 𝑤𝑎𝑡𝑒𝑟 𝑇𝐷𝑆 ∗ 𝑠𝑡𝑒𝑎𝑚 𝑙𝑜𝑎𝑑
𝐵𝑙𝑜𝑤𝑑𝑜𝑤𝑛 𝑇𝐷𝑆−𝐹𝑒𝑒𝑑 𝑤𝑎𝑡𝑒𝑟 𝑇𝐷𝑆
180 ∗ 485100
2360−180
=
= 40 054 kg/y
180 ∗ 485100
3500−180
= 26 300.6 kg/y
∴ Excess blowdown = 13 753.4 kg/y
Savings = 13 753.4 kg/Y * 182.54 kcal/kg = 2 510 545.6 kcal/year
= 257.5 kg fuel/year
-__-
Download