Do not scale from this drawing. All dimensions are to be
checked and verified on site and all discrepancies reported to
5PA Architects Ltd prior to any construction work taking
place. This drawing is the property and copyright of 5PA
Architects Ltd and cannot be reproduced without permission.
The contractor shall allow for all materials and work
necessary to complete the works as intended whether
indicated or not on specifications or drawings.
DRAWING TO BE PRINTED IN COLOUR
This drawing may incorporate information from other professionals. 5PA
cannot accept responsibility to the integrity and accuracy of such
information. Any clarification and/or additions that are required appertaining
to such information should be sought from the relevant profession or their
appointment.
160mm (100mm + 60mm) Rockwool Duoslab or similar approved insulation fastened
back to substrate using Ejot JT3 D6H 5.5/6.3 self drilling screws and DMT 85/7E washers
or similar approved, setting out to comply with Rockwool's requirements
- NBS Section F30, Clause 155A
59.5
12.5
160
100
Vedex Zedex Non-Combustible DPC cavity tray installed strictly in accordance with
manufactures/warranty providers guidance. Secure Visqueen Joint Support at lap joint
location, apply Visqueen Mastic along substrate to adherer Visqueen Zedex Non-Combustible
DPC cavity tray and then install Visqueen Non-Combustible fixing strip using s/s mechanical
fixings suitable for substrate. For additional guidelines refer to manufacturers / warranty
providers requirements for Building Control approval
- NBS Section F30, Clause 320
Allow for brick reveal support plates to all 215mm window jamb reveals. For
brick reveals greater than 215mm refer to drawing XXX for ancon masonry
support.
Fire sealant only required to gaps / joints greater than 5mm.
Waterproofing and insulation to be installed to manufacturers
recommendations. Drawings to be read in conjunction with IKO's specialists
details.
Rainscreen cladding to be water tested by independent UKAS accredited
body.
Any apertures in cladding, soffit boards, reveals and jambs greater than
10mm should have insect mesh applied whether shown on the drawings or
not. Insect mesh generally indicated as
2 No. layers of 12.5mm Siniat GTEC dB Board, tape and staggered joint
finish. Each layer to be independently fixed to SFS to limit effects of
flanking sound transmission
All products to be fully compatible with each other and to be installed in
accordance with the products own BBA certification.
All brickwork/cladding structural fixings must be fixed directly to structure.
TYPICAL COLUMN
EXTENT, SHOWN IN
DISTANCE
165
150 MIN
Blockwork coursing shown indicatively. Specialist sub-contractor to ensure
blockwork courses throughout and within BS guidelines.
All cavity trays and DPC's to be installed in accordance with BS
8215:1991 whether shown on the drawings or not and compliant to the
current ADB.
Membranes used as part of the external wall construction should achieve a
minimum classification of European Class B-s3, d0.
Slip sheet to be applied on top of waterproofing and under brickwork and to
extend a minimum 200mm from face of brickwork, to manufacturers details.
Blockwork behind waterproofed upstand, cut blocks as required to suit
coursing - NBS Section F10, Clause 355C
Any metalwork within façade that sits outside the VCL/EPDM line to be
stainless steel, any metalwork behind the VCL/EPDM line to be GMS.
All EPDM's to be Obex Cortex or similar approved and achieve a
minimum classification of European Class B-s3, d0. See NBS Section P10,
clause 315
152.5
IKO PermaGUARD M
protection layer
62.5
90
Rockwool Hardrock Multi-Fix angle fillet with adhesive fixing to horizontal
slab edge, prior to EPDM seal between sheathing and concrete
82
Fire Barrier rating/spec may vary dependant on location. Refer to 67 Series
Fire Strategy Elevations
Polyester Powder Coated to be AkzoNobel Interpon D2000 series Class
A2,s1-d0 in accordance with BS EN 13501-1. See NBS Section Z31
SFS stud channel fixed securely to concrete, resin bonded or similar to
create watertight junction with waterproof membrane, all to specialists
details
Siderise Cavity barriers as NBS Section P12, Clauses 360
PRECISE WINDOW AND DOOR SETTING OUT TBC ONCE WINDOW
SYSTEM/MANUFACTURER IS CONFIRMED
DPC laid across top of upstand under SFS track and turned down inside
face of upstand by minimum 150mm. DPC to link to VCL
150
DETAIL SHOWN IS A TYPICAL SCENARIO THAT OCCURS ACROSS THE
SCHEME, THEREFORE THERE MAY BE VARIANCES OF THIS DETAIL. PLEASE
REFER TO 04 SERIES GA PLANS, 05 SERIES ELEVATIONS & 06 SERIES
SECTIONS.
PLEASE NOTE THAT THIS DRAWING IS TO BE USED FOR TENDER PURPOSES
ONLY. THIS DRAWING HAS NOT BEEN COORDINATED WITH RELEVANT
SPECIALISTS.
Foamglas T4+ or similar approved non combustible insulation in wet areas, taped and
sealed against concrete upstand to manufacturers recommendations
- NBS Section F30, Clause 150B
1mm gauge 40x14x40mm 'Z' galvanized mild steel angle to fix
plasterboard to upstand at 600mm vertical centres
300
15
15mm floor finish zone
55mm 'Gyvlon' or similar anhydrate screed
system, incorporating underfloor heating
pipework, on 1200 gauge polythene sheet
tucked up to top of screed - NBS Section M13,
Clause 120
80
55
FOR UPSTAND HEIGHTS
SEE DRAWING
9615-A-C-11-27-200
25mm Kingspan TF70 Thermafloor high
performance rigid thermoset insulation NBS Section M13, Clause 260E
25
150
177
Where materials are being fixed and mixed i.e aluminium with stainless steel;
please use isolating washers or good quality butyl tape to avoid bi-metallic
corrosion. All galvanised items to have a micron coating of no less than
60μm.
EPDM dressed over waterproofing layer up to
cavity tray level
300
First install of IKO permatec waterproofing
system up to top of upstand level.
PermaGuard-M additional layer applied to
take brickwork leaf
A row of brickwork ties to be installed at 450mm horizontal centres within
four courses of masonry support angles. Please refer to SE drgs for further
info
All external walls below DPC to be engineered brickwork with class i mortar
with sulphate resisting cement unless specified otherwise by Structural
Engineer.
Rytons Rytweep A1 metal fire-rated cavity weep vent or
similar approved Part B of the Building Regulations
compliant weep vent, at 900mm horizontal centres
- NBS Section F30, Clause 132A
FALLS STRATEGY SHOWN INDICATIVELY,
FOR DESIGN INTENT/PRINCIPLE SEE
DRAWING 9615-A-C-11-27-200
Masonry ties to be allowed for in accordance with British Standards and
Building Regulations, whether shown on this drawing or not.
Procheck FR 200 Vapour Control Layer (VCL) to be sealed at all laps,
junctions and penetrations using tape recommended by manufacturer.
Appropriate manufacturer recommended tape to fix to concrete / block /
brick. VCL to approved by Building Control / LABC - NBS Section P10,
Clause 310
100 MIN
Ibstock Bradgate multi-cream brickwork with natural mortar
- NBS Section F10, Clause 110
Permaflash D-150 reinforcement where
minor movement or change in in
materials occur
7.5mm overall of two coats of IKO
Anti-Root incorporating PermaFLASH F
reinforcement fleece and IKO
PermaGUARD F protection layer. See 27
Series for further details
For levels, refer to 05 Series Elevations and 06 Series Sections.
25
219.5
ROOF TYPE RF-01 / RF-02
FOR EXACT LOCATION REFER TO ROOF
REFERENCE 9615-A-Z-RF-27-001
FOR PRECISE ROOF BUILD-UP, SEE ROOF
& PODIUM BUILD-UP
DRG. 9615-A-Z-M-27-001
12.5mm Siniat Weather Defence board or similar non
combustible board with appropriate mastic jointing
covered with 100mm wide EPDM bonded to surface
All materials used within the facade to be Class A rated. If in doubt ask.
100mm EOS or similar approved SFS with studs at nominal 600mm
centres to specialists details with 100mm Rockwool RWA45 or similar
approved mineral fibre insulation within metal frame
459.5
102.5
Finish varies
The sub-contractor (tenderer) to allow for all details & products to be
constructed & installed strictly in accordance with the manufacturers details,
specifications and relevant British Standards.
This drawing is subject to final BC/ warranty provider approval.
Ancon 25/14 brickwork restraint system or similar approved, comprising 25/14 channel
fixed back to SFS studs at 600(h)x225(v)mm centres using HTSS-240-2PT-W self drill self
tap fixings. SD25 ties x 150mm long at 300mm vertical centres on each stud
NBS Section F30, Clause 245
2mm PPC flashing keyed into brickwork coursing and
under DPC cavity tray to protect waterproof
membrane as shown. Colour to match windows
Tyvek Firecurb House wrap breather
membrane blockwork, dressed over cavity
tray - NBS Section P10, Clause 320
Foamglas Perinsul Block HL (A1
rated/non-combustible) with protection
layer to protect from freeze thaw from
wet zone where heated space below or
similar approved thermal block to prevent
cold bridging - NBS Section F30, Clause
185
C06 DPC membrane added as per LABC
comments
14.11.22
Revisions
5PA
CHARTERED
ARCHITECTS
5PA Architects Ltd, 3 Southwark St, London, SE1 1RQ
10mm Yelofon E-Strip or similar acoustic
flanking strip - NBS Section M10, Clause 295
Cavity backfilled with splayed top lean mix
concrete
Project
TELFORD HOMES &
CATALYST BY DESIGN
CIW - BRENTFORD
Title
BLOCK C 11TH FLOOR ROOF
WALL BASE DETAIL
BRICK FACADE
Revision
Drawn by
C06
5PA
Drawing Status
19.07.22
C04
C03
C02
C01
01.07.22
11.04.22
01.04.22
24.01.22
C2 WATERPROOFING ISSUE
C2 SFS ISSUE
C2 BRICK & BLOCKWORK ISSUE
General coordination
Date
5PA
JUL 20
Scale
C2 ISSUE
C05 amended to JWA and client comments
Checked
1:5 @A3
Drawing Number
9615-A-Z-M-21-107