Al-Balqa Applied University 1 Dr.Audih In previous lectures have covered how to calculate the parameters inductance, capacitance and resistance of transmission lines. In this section we will use these parameters to develop the transmission line models used in power system analysis. Transmission line take power from generators, transmit it to location where it will be used ( loads center). The power capability of a transmission line is proportional to the square of the voltage on the line. Dr.Audih 2 Therefore, very high voltage levels are used to transmit power over long distances. Once the power reaches the area where it will be used, it is stepped down to a lower voltages in distribution substations, and then delivered to customers through distribution lines. An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of the power system. The conductors are usually aluminum cable steel reinforced (ACSR), which are steel core (for strength) and aluminum wires . Dr.Audih 3 1-Short length model : Overhead transmission lines(OHL) shorter than 80 km can be modeled as a series resistance and inductance, since the shunt capacitance can be neglected over short distances. 2- Medium length model: OHL between (80-240 km), can be modeled as shunt capacitance should be considered by two capacitors of a half at both ends of the line. 3- Long length model: OHL longer than 240 km are long transmission lines and will be discussed later , Dr.Audih 4 In the single line equivalent circuit of a short line ,the current sending IS and current received IR are : IS IR Neglected the shunt admittance and using KVL , the relation between sending end voltage VS and receiving end voltages VR is: VS VR ZI VR R jX L I VR VS R j L I which is very similar to the equation derived for a synchronous generator. Dr.Audih 5 1- Phasors Diagrams of TL: Load with lagging power factor. Load with unity power factor. Load with leading power factor. Dr.Audih 6 2- Voltage regulation of a transmission line: It’s define as the percentage change in voltage at the receiving end of the transmission line in case of loads and no loads. VR% VNL VFL VFL VS VR A 100% 100= VR where :VNL and VFL are the no-load and full-load voltages at the line output and constant A=1 for short module( will discuss later). If the load at terminals of the line is lagging (inductive) , the voltage at the end of the transmission line decreases ( large positive VR). If unity-PF (resistive) loads, the voltage at the end of the transmission line decreases slightly (small positive VR). If the load at terminals of the line is leading (capacitive) , the voltage at the end of the transmission line increases (negative VR). Dr.Audih 7 3. Power flow in a transmission line: The real ,reactive and apparent power input and output of a 3-phase transmission line can be computed as: Psending 3VLL , S I S cos S Precived 3VLL , R I R cos R Qsending 3VLL , S I S sin S QRecived 3VLL , R I R sin R S sending 3VLL , S I S 4. Transmission line efficiency: Srecived 3VLL, R I R Pout Pout 100% 100% Pin Pout P Dr.Audih 8 5-Maximum power transfer: Consider the following diagram IR IS + VS Ssend - + Transmission Line with Impedance Z - * VR * V VS VR * S sen d V S I S V S VS Z Z w ith V S V S , V R V R 0 o , Z Z Z o S sen d * VS VR 0 VS Z Z VS Z 2 VS VR Z 0o Z Dr.Audih Z 9 S send VS 2 Z VS VR Z Z If w e assum e a line im pedance is jX L Z and just interested in real pow er transfer then = 90 0 ,thuse : Psend jQ send 2 VS X 90 L VS VR X o 90 L M athm atically ,w e get : 2 VS P sending X cos 90 L VS VR X cos( o 90 ) L Dr.Audih V S X V R sin o L 10 Hence the maximum power transfer is meet when 90 o , then : Psend Max VS V R XL and for 3 system Psend Max 3 VS V R XL The power supplied by a transmission line depends on the angle(δ) between the phasors (input and output voltages). The maximum power is called steady-state stability limit of the transmission line. The maximum power of a transmission line is inversely proportional to its series reactance, which may be a serious problem for long transmission lines. Some very long lines include series capacitors to reduce the total series reactance and thus increase the total power capability of the line. *Note: The angle controls the power flowing through the line. It is possible to control power flow by placing a phase-shifting transformer at one end of the line and varying voltage phase. Dr.Audih 11 6. Transmission line limits: a) Power losses : Is the main limiting factors in transmission line operation (since its resistivity). The maximum steady-state current must be limited to prevent the overheating of the transmission line. Ploss 3I L2 R b) Voltage drop: Its the ratio of the magnitude of the receiving end voltage to the magnitude of the sending end voltage ,should be limited to approximately 5%, VR VS 0.95 c) Stability limits: The angle in a transmission line should typically be 300 to the static stability limit . Dr.Audih 12 Example: An over-head 3-phase transmission line delivers 5 MW at 22 kV at 0·8 p.f. lagging. The resistance and reactance of each conductor is 4Ω and 6Ω respectively. Determine : (i)sending end voltage (ii)percentage regulation (iii)transmission efficiency. Solution Load power factor cos 0.8 lagging 36.869o Receiving end voltage per phase VR1 22 103 12.7 kV 3 impedance per phase Z R jX 4 j6 7.21156.3o 5 106 o Line current I 164 36.86 A 3 3 22 10 0.8 Taking VR0o of single phase as the reference phasor VR = 12.70o kV Dr.Audih 13 (i) Sending end voltage per phase is VS (1 ) VR(1 ) + I.Z=127000o + 164 36.86o 7.21156.3o = =13.8211.63o kV VS (3 ) 3 13.821 23.938 kV (ii) % age Regulation = ** VS VR VR 13.821 12.700 100= 100 8.83 % 12.700 note : the %VR equation here is valid for short module only since A 1 . (iii) Line losses = 3R.I2 = 3 4 (164)2 322 752kW 5000 Transmission efficiency = 100 93.94% 5000 322 752 . Dr.Audih 14 Example: A 3-phase line delivers 3600 kW at a p.f. 0·8 lagging to a load. If the sending end voltage is 33 kV, determine (i) the receiving end voltage (ii) line current (iii) transmission efficiency. The resistance and reactance of each conductor are 5·31Ω and 5·54 Ω respectively. Solution. Resistance of each conductor, R 5·31 Reactance of each conductor, X L 5·54 Load power factor, cos 0·8 (lagging) Sending end voltage per phase, VS 33/ 3 19.052 kV Let VR be the phase voltage at the receiving end. P3 3600 power delivered per phase 1200 kW 3 3 Dr.Audih 15 I per phase 1200 103 15 105 VR(1 ) .cos VR 0.8 VR P(1 ) (i) Using approximation expression for VS , we get; 15 105 15 105 VS =VR IR cos IX L sin VR 5.31 0.8 5.54 0.6 VR VR VR2 19,052VR 1,13,58,000 0 VR 18.435kV VS ( LL ) 3 18.435 31.93kV 15 105 (ii)line current I 81.36 A 18, 435 (iii)line losses 3RI 2 3 5.31 (81.36)2 105.447kW Pout 3600 The efficiency 100 100 97% Pout Plosses 3600 105.447 Dr.Audih 16 Example: 220kV ,60 Hz ,three phase transmission line with 40km long and R=0.15Ω/km/phase , L=1.3263mH/km/phase, if C is negligible ,find voltage sending ,voltage regulation and efficiency when supplying a load of: a) 381MVA at 0.8 lagging at 220kV. b) 381MVA at 0.8 leading at 220kV. Solution: The total impedance per km length is : Z z.l (r j L).l (0.15 j 2 60 1.3263 103 ) 40 6 j 20 VR (3 ) 2200o VR (1 ) 1270o kV 3 3 S R 381 cos1 (0.8) 38136.87o 304.8 j 228.6 MVA * S R 381106 36.87o o IR 1 36.87 kA 3 o 3 127 10 0 Dr.Audih 3VR 17 VS (1 ) VR Z .I R 1270o (20.8873.3o 1 36.87o ) 144.334.93o kV (note is greater than VR ) VS (3 ) 3 VS (1 ) 3 144.33 250 kVLL SS (3 ) 3.Ss (1 ) 3.Vs I s* 3 144.334.93o 136.87o 322.8MW j 288.6MVAr 43341.8o MVA VR% VSLL VRLL VRLL 100 250 220 220 100 13.6% Pout PR 304.8 100% 100% 100% 94.4% Pinp PS 322.8 Dr.Audih 18 b) for leading P.F . I 136.87 o kA VS (1 ) VR Z .I R 1270o (20.8873.3o 136.87 o ) 121.399.29o kV (note is less than VR ) VS (3 ) 3 VS (1 ) 3 121.39 210.26 kV S S (3 ) 3.S s (1 ) 3.Vs I s* 3 121.399.29o 1 36.87 o 322.8MW j168.6 MVAr 364.17 27.58o MVA 210.26 220 VR % 100 4.43% 220 (negative) PR 304.8 100% 100% 94.4% PS 322.8 Dr.Audih 19 A transmission line can be represented by a two-port as shown. If the network is linear, the relationship between the sending and receiving end voltages and currents are: VS AVR BI R I S CVR DI R Vs A B VR as matrix . Is C D IR ABCD constants are sometimes called TL constants . - A represents the effect of a change in the sending end voltage per the receiving end voltage. - B represents the effect of a change in the sending end Dr.Audih voltage per the receiving end current 20 - C denotes the effect of a change in the sending end current per the receiving end voltage. D is the effect of a change in the sending end current per the receiving end current. VS VR A VR % 100 VR For short model IS = IR = I, and the ABCD constants are A=1 B=Z VS VR ZI AVR BI R I S I R CVR DI R C=0 D=1 Where: A and D are dimensionless, B has units of , and C is measured in Siemens. Dr.Audih 21 Considering medium-length lines (80 to 240km long), the shunt admittance must be included in calculations. However, the total admittance is usually modeled ( model) as two capacitors of equal values (each is a half of total admittance) placed at the sending and receiving ends. The current of the receiving end capacitor (IC2) is: The current of the series impedance elements is I ser I C 2 I R V R Y IR Dr.Audih 2 22 From the Kirchhoff’s voltage law, the sending end voltage is VS V VR ZIser VR Z IC2 IR VR ZY Y YZ Z VR IR VR VR ZIR VR 1VR ZIR 2 2 2 The source of current will be Y Y IS IC1 Iser IC1 IC2 IR VS VR IR 2 2 YZ Y Y YZ Y Y Y Y 1VR ZIR VR IR VR . VR. ZIR. VR IR 2 2 2 2 2 2 2 2 Y 2Z Y Y Y ZY ZY VR. VR ZIR. IR Y 1VR 1 IR VR 4 2 2 2 4 2 Dr.Audih 23 Therefore, the ABCD constants of a medium-length π of transmission line are: ZY A D 1 2 B Z ZY C Y 1 4 VS AVR BIR IS CVR DIR ZY 1 Vs 2 I ZY s Y 1 4 Z VR . ZY IR 1 2 If the shunt capacitance of the line is ignored (Y=0) , the ABCD constants are the constants for a short transmission line. Dr.Audih 24 Example 1: (general case of TL) The ABCD constant of a three phase short length of TL are: A D 0.936 j0.016 0.9360.98o o B 33.5 j138 14276.4 6 C (5.18 j914) 10 S The load at the receiving end is 50MW at 220kV with a power factor of 0.9 lagging. Find the magnitude of the sending end voltage and the voltage regulation. Assume the magnitude of the sending end voltage remains constant. 25 Dr.Audih Solution: P 3.V LL .cos IR 50 10 6 145.8 [A] 3 3 220 10 0.9 cos 1 (0.9) 25.84 o and since its lagging then the angle is negative,thus; I R 145.8 25.84 o [ A] V LL 220 127 0 o kV and 3 3 AV R (1 ) BI R (1 ) (0.936 0.98 o (127 10 3 0 o ) V R (1 ) V s (1 ) (142 76.4 o 145.8 25.84 o ) 133.23 7.77 o k V V S LL V R ( nL ) 3 133.23 230.8 kV V S LL A 230.8 246.5 kV LL 0.9361 (% ) regulation V R ( nL ) V R (FL) V R (FL ) 100% 246.5 220 100% 12% 220 26 Dr.Audih Example 2: Find the ABCD constants of a π circuit having a 600Ω resistor for shunt branch al sending end, a 1kΩ resistor for the shunt branch at the receiving end and an 80Ω resistor for series branch. Solution: V s V R V V R (80 I L ) from KCL I L I R I (1000 ) VR IR ( ) 1000 27 Dr.Audih V s V R (80 I L ) V R (80 ( I R ( V R 80 I R VR )) 1000 80V R V R 80 I R 0.08V R 1.08V R 80 I R 1000 V s 1.08V R 80 I R and since A 1.08 and V s AV R BI R then ; B 80 And for C and D from KCL Is IL I 600 VR Vs VR 1.08VR 80IR Is IL I600 (IR ) ( ) (I R ) ( ) 1000 600 1000 600 IR 0.001VR 0.0018VR 0.133IR (0.001 0.0018)VR (1 0.133)IR And since Is CVR DIR 0.0028VR 1.133IR C 0.0028 and D1.133 28 Dr.Audih Example 3: Determine the voltage regulation of 3-phase,150km long,50Hz transmission line delivering 20MW at p.f. of 0.8 lagging and 66kV to at balance load. Resistance of the line is 0.075Ω/km,1.5cm outside diameter, placed equilaterally 2 meters between center. Use normal π method. Solution : R r .l 0.075 150 11.25 d 1.5 0.75 cm 2 2 D 2 10 2 200 cm radius of the condctor is r D istance D T he inductance is L 2 10 7 . ln l r 200 cm 7 3 2 10 . ln (150 10 ) m 0.1675 H enry 0.75 cm X L 2 f . L 2 50 0.1675 52 .62 Dr.Audih 29 2 o 2 8.854 1012 F / m Now Cphase .l (150 103 )m 1.49 F D 200 cm ln ln r 0.75 cm Y jC j 2 fC j 2 50 1.49 106 j 468.1106 mho Y 234 106 90o mho 2 Z R jX L 11.25 j52.62 53.80977.9o ZY Now 0.01259167.9o (0.0123 j0.00264) 2 and B Z then; Dr.Audih 30 P 20106 cos1(0.8) o I 218.7 36.87 A 3 3V.cos 3 6610 0.8 66000 And VR 38104 V 3 ZY VS AVR BIR 1 VR ZIR 2 1 0.01259167.9o 381050o 53.80977.9o 218.7 36.87o 47.1679.554o kV or VS (3 ) 3 47.15 81.696kV VR% VR(nL) VR(FL) VR(FL) .100 VS VR A VR 81.696 66 0.9877 66 % 25.3% Dr.Audih 31 Example 4: A three-phase,60-Hz,completely transposed 345-kV,200-km ,and the following .positive-sequence line constants: z 0.032 j 0.35 / km y j 4.2 10 6 S / km Full load at the receiving end of the line is 700 MW at 0.99 p.f. leading and at 95% of rated voltage. Assuming a medium-length line, determine the following: a. ABCD parameters of the nominal π circuit b. Sending-end voltage VS, current IS, and real power PS c. Percent voltage regulation d. Transmission-line efficiency at full load Dr.Audih 32 Solution : a)The total series impedance and shunt admittance values are: Z = z.l (0.032 j0.35) (200) 70.2984.78o Y y.l j4.2 106 200 8.4 104 90o S 70.2984.78o 8.4 104 90o ZY A D 1 1 2 2 0.97060.159o B Z 70.2984.78o 4 o o 8.4 10 90 70.29 84.78 ZY 4 o C Y 1 8.4 10 90 1 4 4 8.277 104 90.08o Dr.Audih 33 b ) sending end voltage : V R 345 95%(from rated voltage) 327.8kV LL V R (3 ) 327.8 V R (1 ) 189.20o kV Ln 3 3 3 P 700 10 IR . cos1 cos1 (0.99) 3.V LL .cos 3 327.8 0.99 1.245 8.110 kA (leading ) The sending quantities are o o V S (1 ) AV R BI R 0.97060.159 189.20 70.2984.78o 1.2458.110 199.526.15o kV Ln V S (3 ) 3 199.5 345.5 kV LL Dr.Audih 34 I S CVR DI R (8.277 10 4 90.08 o 189.2 0 o ) (0.9706 0.159 o 1.2458.110 ) 1.240 o 15.447 o kA and the real power delivered to the sending end is : Ps 3VLL , S I S cos( v i ) i v 0 o 3 345.5 1.240 cos(26.15 o 15.447 o ) 729.77MW Dr.Audih 35 (c) voltage regulation VR % VR ( nl ) VR ( Fl ) V R ( Fl ) VS VR ( Fl ) A 100 100 VR ( Fl ) 345.8 327.8 0.9706 100 8.6% 327.8 (d ) Pout 700 100% 100% 96% Pin 729.77 Plosses Pin Pout 729.77 700 30MW Dr.Audih 36 inverse matrix : If we need to find VR and IR 1 VR A B then inverse matrix is used IR C D D AD CB C AD CB Vs . Is B V AD CB s D B Vs . . A Is C A Is AD CB Dr.Audih 37 It’s longer than 240 km. The single-line diagram of a long transmission line is shown in Fig. . ΔI The length of the line is l . Let us consider a small strip Δx that is at a distance x from the receiving end Dr.Audih 38 V = value of voltage just before entering the element Δx. I = value of current just before entering the element Δx. V+ΔV = voltage leaving the element Δx. I+ΔI = current leaving the element Δx. ΔV = voltage drop across element Δx. zΔx = series impedance of element Δx yΔx = shunt admittance of element Δx The voltage drop across the infinitely small element Δx is given by: V V zx.I I.z x or dV I.z dx 1 Now to determine the current ΔI through the capacitor branch, from A to B we apply KCL to node A. Dr.Audih 39 I (V V ) yx Vyx Vyx Since the term Vyx is the product of 2 infinitely small values, we ignore it for making easier calculation. 2 I I Vyx Vy x or dI yV . dx 3 Now derivate both sides of eq (1)by d/dx d dV d I .z . . dx dx dx d 2V dI z. 2 dx dx Dr.Audih 4 40 Now substituting 3 in 4 we get: 2 dV z .y V . or 2 dx 2 dV z .y V . 0 2 dx 5 The solution of the above second order differential equation for V is given by. x yz x yz 6 1 2 V ( x ) A .e A .e Taking derivative of (6) with respect to (x) we get dV (x) A1 dx y z .e x yz y z .e x A2 yz 7 Where A1 and A2 are arbitrary constants ,if we combining (1) with (7) we get: 1 dV ( x ) I ( x) z dx A1 .e x z/ y yz A2 .e x z/y Dr.Audih yz 8 41 Let us define the following two quantities z Z C ( ch a ra cteristic im p ed a n ce , ) y yz j 9 ( p ro p a g a tio n co n sta n t ) Substituting 9 into equation 6 and 8, and written in terms of the characteristic impedance and propagation constant we get: V ( X ) A1 .e x A2 .e x A1 x A2 x I(X ) .e .e ZC ZC 10 Dr.Audih 42 assume that x = 0 not (X). Then V (x)= VR and I(x) = IR V ( X ) A1 .e x A 2 .e x A1 x A2 x I(X ) .e .e ZC ZC Note X with R and e0=1 we get: V R A1 A2 and A1 A2 IR ZC ZC 11 Solving (11) we get the following values for A1 and A2 . VR ZC I R A1 2 VR ZC I R and A2 2 Dr.Audih 12 43 Also note that for x = l we have V(x) = Vs and I(x) = IS . Therefore replacing x by l and substituting the values of A1 and A2 in (12) in (10) we get VR ZCIR l VR ZCIR l Vs .e .e 2 2 VR / ZC IR l VR / ZC IR l Is .e .e 2 2 13 14 And noting from hyperbolic equation that e( l ) e( l ) cosh( l ) 2 and e( l ) e( l ) sinh( l ) 2 Dr.Audih 15 44 Then We can rewrite (13) and (14) using hyperbolic equation(15) we get: V S V R c o s h l Z c I R s in h l IS VR s in h l I R c o s h l Zc The ABCD parameters of the long transmission line can be written as: A D cosh l , B Zc sinh( l ) sinh( l ) C Zc , D cosh ( l ) Dr.Audih 45 hyperbolic and exponential equation cosh( x ) cosh( x ) cos( x ) j sinh( x ) sin( x ) sinh( x ) sinh( x ) cos( x ) j cosh( x ) sin( x ) x x j x or as exponential equation e ( x ) e ( x ) 1 x cosh( x ) (e x e x x ) 2 2 e ( x ) e ( x ) 1 x sinh( x ) (e x e x x ) 2 2 e ( x ) e ( x ) .e j ( x ) e ( x ) ( x ) ( radian ) e ( x ) e ( x ) .e j ( x ) e x x ( radian ) Dr.Audih 46 surge impedance loading The term surge impedance loading or SIL is often used to indicate the nominal capacity of the line. The surge impedance is the ratio of voltage and current at any point along an infinitely long line. The term SIL or natural power is a measure of power delivered by a transmission line when terminated by surge impedance and is given by SIL 3V R I R* 3 VR ZC 2 2 3 V R ( 3 ) / 3 ZC If P > SIL then line consumes vars; otherwise line generates vars. Dr.Audih 47 Example 5: Consider a 500 km long line for which the per kilometer line impedance and admittance are given respectively by z = 0.1 + j 0.5145 Ω and y = j 3.1734 x 10 -6 mho. Find A B C D constants of TL. Solution : 79o 90o z 0.52413 o . 406.403 5.5 and 6 y 3.1734 10 2 2 Zc 79o 90o 6 l zy .l 500 0.5241 3.1734 10 2 2 0.644884.5o 0.0618 j 0.6419 l 0.0618 and l j 0.6419 use the following two formulas for evaluating the hyperbolic forms c o s h ( l ) c o s h ( l ) c o s ( l ) o j s in h ( l ) s in ( l ) o s in h ( l ) s in h ( l ) c o s ( l ) o j c o s h ( l ) s in ( l ) o ( l)o 1 8 0 o 0 .6 4 1 9 3 6 .7 8 o Dr.Audih 48 Applied the equations and noting that sin and cos are in degree as well as cosh and sinh in rad co sh l co sh ( l j l ) co sh (0 .0 6 1 8 ) co s(3 6 .7 8 o ) j sin h (0 .0 6 1 8 ) sin (3 6 .7 8 o ) 0 .8 0 2 5 j 0 . 0 3 7 si n h l sin h ( l j l ) sin h (0 .0 6 1 8) co s(3 6 .7 8 o ) j co sh (0 .0 6 1 8) sin (3 6 .7 8 o ) 0 .0 4 9 5 j 0 . 5 9 9 8 Therefore the ABCD parameters of the system can be written as A D c o s h l 0 .8 0 2 5 j 0 .0 3 7 B Z c s in h ( l ) 4 3 .4 j 2 4 0 .7 2 s in h ( l ) C 2 .0 1 1 0 5 j 0 .0 0 1 5 Zc Dr.Audih 49 Example 6: Find Vs for 765 kV transmission line with a receiving end voltage of 765 kV(line to line), a receiving end power SR = 2000+ j1000 MVA and z=0.53587.8 / m and y=7.75106 90.0 m z Solution: zy 2.03688.9 / m ,and c 262.7 -1.1 y VR(1 ) 765 3 441.70 kV * 6 * S (2000 j1000) 10 IR(3 ) 3 441.70103 1688 26.6 A 3.V Vs (x) VR cosh( x) IR Zc sinh( x) 441,7000 cosh(x 2.03688.9) (1688 26.6 262.7 -1.1sinh(x 2.03688.9) where x is the lenght in m Dr.Audih 50 EXAMPLE 7: A three-phase 765-kV, 60-Hz, 300-km, completely transposed line has the following positive-sequence impedance and admittance using exponential method , find ABCD parameters of the line. z 0.0165 j0.3306 0.331087.14o / km y j 4.674 106 S / km Solution: z 0.331087.14o 4 o ZC 7.082 10 2.86 6 o y 4.674 10 90 266.11.43o l zy .l (0.331087.14 o ) (4.674 10 6 90o (300) 1.547 10 6 177.14 o (300) 0.373188.57 o Dr.Audih 51 o l l j l 0.373188.57 0.00931 j 0.3730 (deg.) l l l 0.00931 e e . e j l l e l (radian) j 0.3730 0.00931 e e . e e 0.3730 1.00940.3730 rad . Transfer radian in degree o deg. 180 rad o 180 0.3730 Dr.Audih 21.37 o 52 l e in degree l o e 1.009421.37 0.9400 j 0.3678 same e ( x ) e l e e ( x ) .e 0.00931 in degree e j( x) . e l e j 0.3730 x x (radian) then; 0.9907 0.3730 rad . 0.9226 j 0.3610 l l e e Then ; cosh( l ) 2 (0.9400 j 0.3678) (0.9226 j 0.3610) 2 0.93230.209o Dr.Audih 53 e ( l ) e ( l ) sinh( l ) 2 (0.9400 j 0.3678) (0.9226 j 0.3610) 2 0.3645 88.63 o A = D = cosh( l)=0.9313 0.209 o B Z c sinh( l ) 266.1 1.43 o 0.3645 88.63 o 97.0 87.2 o sinh( l ) 0.3645 88.63 o 3 o C 1.37 10 9 0.06 Zc 266.1 1.43 o Dr.Audih 54 Example 8: Determine the theoretical maximum power in MW and in per unit of SIL,that the line in example 7 can deliver.AssumeVS =VR =765kV S o lu tio n : Z z .l ( 0 . 0 1 6 5 j 0 . 3 3 0 6 ) 3 0 0 9 9 8 7 .1 4 o , th e n ; Z 99 and Z 8 7 .1 4 o a ls o A 0 .9 3 1 3 0 .2 0 9 o th e n ; A 0 .9 3 1 3 a n d Z C 2 6 6 .1 A 0 .2 0 9 o a n d Vs A V S A .V R VR Dr.Audih 55 Using powe r transfer equation we get; V S 2 A.V R2 PR (max) .cos( Z A ) Z Z Z Impedance angle and A is the angle of conta nt A Since V R V S 765 kV then ; 765 2 2 0.9313 765 PR (max) .cos(87.14 o 0.209 o ) 99 99 5911.36 294.74 5616.62 M W Fo r SIL= V 2 ZC 765 2 2199 M W 266.1 PR (max) 5616.62 The max. power in per unit PR(max) 2.55 p .u . SIL 2199 This value is about 4% less than that found in example befor where losses were neglected. Dr.Audih 56 Dr.Audih 57