CT-VT tandelta measurement REV.0 TD5000 - TDX5000 Current and Voltage transformers TanDelta measurement Doc. CT-VT tandelta measurement Rev. 0 Page 2 of 6 Introduction The following document describes the measuring method of Tandelta values for current and voltage transformers. CURRENT TRANSFORMER: 1ST CASE The ground screen can be disconnect from the ground. Connections 1. 2. 3. 4. High voltage cable connected to the primary side IN_A connected to the shield IN_B connected to the bushing using hot collar CT secondary windings short-circuited to the ground Mode The testing mode to use it UST_A Test 1. Voltage sweep at 50Hz, starting from 100V 2. Frequency sweep at 100V, starting from 15Hz to 500Hz Schematic CH Doc. CT-VT tandelta measurement Rev. 0 Page 3 of 6 CURRENT TRANSFORMER: 2ND CASE The ground screen cannot be disconnected from the ground. Connections 1. High voltage cable connected to the primary side 2. IN_B connected to the bushing using hot collar 3. CT secondary windings short-circuited to the ground Mode The testing mode to use it GSTgA+B Test 1. Voltage sweep at 50Hz, starting from 100V 2. Frequency sweep at 100V, starting from 15Hz to 500Hz Schematic CH Doc. CT-VT tandelta measurement Rev. 0 Page 4 of 6 CURRENT TRANSFORMER: 3RD CASE There is no ground shield. Connections 1. High voltage cable connected to the primary side 2. IN_A connected to the CT secondary windings (short-circuited) 3. IN_B connected to the bushing using hot collar Mode The testing mode to use it UST_A Test 1. Voltage sweep at 50Hz, starting from 100V 2. Frequency sweep at 100V, starting from 15Hz to 500Hz Schematic CH Doc. CT-VT tandelta measurement Rev. 0 Page 5 of 6 VOLTAGE TRANSFORMER: 1ST CASE Neutral point of primary side can be disconnected. Connections 1. High voltage cable connected to the primary side 2. IN_A connected to the VT secondary windings (short-circuited) 3. IN_B connected to the bushing using hot collar Mode The testing mode to use it UST_A Schematic N Doc. CT-VT tandelta measurement Rev. 0 Page 6 of 6 VOLTAGE TRANSFORMER: 2ND CASE Neutral point cannot be disconnected. Connections 1. High voltage cable connected to the primary side 2. IN_A connected to the VT secondary windings (short-circuited) 3. IN_B connected to the bushing using hot collar Mode The testing mode to use it UST_A Schematic N