Faculty of Engineering and Technology, University of Buea EEF480: Control of Electrical Machines Lecture No. 1: Traditional Starting Methods Outline: Introduction Direct On-line Starter Stator Resistance Starter Autotransformer Starter Star-Delta Starter Rotor Resistance Starter Motor Protection 3-point starter 4-point starter 2-point starter I. Introduction When a motor is switched on, there is a high inrush current from the mains which may, especially if the power line section is inadequate, cause a drop in voltage likely to affect receptor operation. This drop may be severe enough to be noticeable in lighting equipment. An induction motor is similar to a poly-phase transformer whose secondary is short circuited. Thus, at normal supply voltage, like in transformers, the initial current taken by the primary is very large for a short while. Unlike in DC motors, large current at starting is due to the absence of back emf. If an induction motor is directly switched on from the supply, it takes 4 to 8 times its full load current and develops a torque which is only 1.5 to 2.5 times the full load torque which put the mechanical elements under considerable strain. This large starting current produces a large voltage drop in the line, which may affect the operation of other devices connected to the same line. Hence, it is not advisable to start induction motors of higher ratings (generally above 25kW) directly from the mains supply. Some sector rules prohibit the use of motors with direct on-line starting systems beyond a given power. This exclusive starting current has to be prevented because: • It causes sudden depression of voltage of supply (large voltage drop occurs) system causing disturbances to other loads connected in the system. • It would cause heavy sparking at the brushes which may destroy the commutator and brush gear. • Due to heavy inrush of current at start there is possibility of damage of the motor winding. There are several starting systems which differ according to the motor and load specifications. The choice is governed by electrical, mechanical and economic factors. The kind of load driven is also important in the choice of starting system. At starting the motor takes large amount of current which is nearly 25 x full load current. This large amount of current cannot be allowed to flow in a motor even for a short period of time. This exclusive starting current has to be prevented because Various starting methods of electrical motors based on Manual Starting, Across the Line Starting Reduced Voltage Starting, used to reduce currents and torque are described below. Fotso Raoul, PhD 1 Faculty of Engineering and Technology, University of Buea II. AC Starters 1. Manual Starter A manual motor starter is package consisting of a horsepower rated switch with one set of contacts for each phase and corresponding thermal overload devices to provide motor overload protection. • The main advantage of a manual motor starter is lower cost than a magnetic motor starter with equivalent motor protection but less motor control capability. • Manual motor starters are often used for smaller motors-typically fractional horsepower motors but the National Electrical Code allows their use up to 10 Horsepower. • Since the switch contacts remain closed if power is removed from the circuit without operating the switch, the motor restarts when power is reapplied which can be a safety concern. • They do not allow the use of remote control or auxiliary control equipment like a magnetic starter does. 2. Across the Line Starter Also, called magnetic starter, it is a package consisting of a contactor capable of opening and closing a set of contacts that energize and de-energize the circuit to the motor along with additional motor overload protection equipment. Magnetic starters are used with larger motors (required above 10 horsepower) or where greater motor control is desired. The main element of the magnetic motor starter is the contactor, a set of contacts operated by an electromagnetic coil. a. Direct On-line (DOL) Starter This is the simplest mode, where the stator is directly connected to the mains supply (See Fig.1). The motor starts with its own characteristics. In spite of its advantages (simple equipment, high starting torque, fast start, low cost), direct on-line starting is only suitable when: β the power of the motor is low compared to that of the mains, which limits interference from inrush current, β the machine to drive does not need to speed up gradually or has a damping device to limit the shock of starting, β the starting torque can be high without affecting machine operation or the load that is driven. Its drawback is the high overcurrent. L1 and L2 are indicating lights to show the presence of supply and the running of motor, respectively. Fotso Raoul, PhD 2 Faculty of Engineering and Technology, University of Buea Figure 1: DOL-Power Circuit Figure 2: DOL-Control Circuit b. Direct On-line Starter with Forward and Reverse Directions Figure 3: DOL-FR-Power Circuit Fotso Raoul, PhD Figure 4: DOL-FR-Power Circuit 3 Faculty of Engineering and Technology, University of Buea H1, H2, H3 and H4 are indicating lights to show the presence of supply, the fault, the running of motor in forward and in reverse directions, respectively. (a) Figure 5: (a) T vs N and (b) I vs N ππ = 0.6 π‘π 1.5 ππ πππ (b) πΌπ = 4 π‘π 8 πΌπ 3. Reduced Voltage Starters Reduced Voltage Starting connects the motor windings/terminals at lower-than-normal line voltage during the initial starting period to reduce the inrush current when the motor starts. β’ Reduced voltage starting may be required when: - The current in-rush form the motor starting adversely affects the voltage drop on the electrical system. - needed to reduce the mechanical “starting shock” on drive-lines and equipment when the motor starts. β’ Reducing the voltage reduces the current inrush to the motor and also reduces the starting torque available when the motor starts. β’ All NEMA induction motors can will accept reduced voltage starting however it may not provide enough starting torque in some situations to drive certain specific loads. If the driven load or the power distribution system cannot accept a full voltage start, some type of reduced voltage starting scheme or solid state (electronic) starters must be used. Reduced voltage starters can only be used where low starting torque is acceptable or a means exists to remove the load from the motor or application before it is stopped. Here, the voltage applied to the motor is reduced by ballast chokes or resistors, as is the starting current. The starting torque is reduced by the square of the current reduction. a. Stator Resistance Starter In this case, cost-efficient resistors are used instead of the chokes. This method is less helpful in reducing the starting current for the same torque requirement, because the motor torque reduces as a value of the square of the voltage and the voltage applied to the motor increases only due to the motor’s reduced current consumption during increasing speed. It is better to reduce the ballast resistor step by step during start. But this requires considerably more switchgear. Fotso Raoul, PhD 4 Faculty of Engineering and Technology, University of Buea Another possibility is the use of encapsulated wet (electrolytic) resistors. For these resistors, the ohmic resistance reduces in line with the temperature increase caused by the starting current’s heating capability. With this system (Fig. 6), the motor starts at reduced voltage because resistors are inserted in series with the windings. When the speed stabilizes, the resistors are eliminated and the motor is connected directly to the mains. This process is usually controlled by a timer. This starting method does not alter the connection of the motor windings so the ends of each winding do not need outputs on a terminal board. The resistance value is calculated according to the maximum current peak on starting or the minimum starting torque required for the resistance torque of the machine to drive. The starting current and torque values are generally: ππ πΌπ = 0.6 π‘π 0.85 πππ = 4.5 ππ πΌπ During the acceleration stage with the resistors, the voltage applied to the motor terminals is not constant but equals the mains voltage minus the voltage drop in the starting resistance. The voltage drop is proportional to the current absorbed by the motor. As the current weakens with the acceleration of the motor, the same happens to the voltage drop in the resistance. The voltage applied to the motor terminals is therefore at its lowest on starting and then gradually increases. As the torque is proportional to the square of the voltage at the motor terminals, it increases faster than in star-delta starting where the voltage remains constant throughout the star connection. This starting system is therefore suited to machines with a resistive torque that increases with the speed, such as fans and centrifugal pumps. It has the drawback of a rather high current peak on starting. This could be lowered by increasing the resistance value but that would cause the voltage to drop further at the motor terminals and thus a steep drop in the starting torque. On the other hand, resistance is eliminated at the end of starting without any break in power supply to the motor, so there are no transient phenomena. The characteristics of the motor is illustrated in Fig. 7. An alternative to the stator resistance starter power circuit diagram is shown in Fig. 8. Fotso Raoul, PhD 5 Faculty of Engineering and Technology, University of Buea Figure 6: Stator Resistance Starting- Power and Control circuits Figure 7: Characteristics of the inductor motor Fotso Raoul, PhD Figure 8: Alternative power circuit diagram 6 Faculty of Engineering and Technology, University of Buea b. Stator Choke Starter During the off state, the motor resistance is low. A large percentage of the mains voltage is reduced at the ballast chokes. Therefore, the motor’s starting torque is considerably reduced. As the torque increases, the voltage applied to the motor increases due to a reduction in current consumption and the vectoral voltage division between motor and the ballast reactance. This leads to an increased motor torque. After a successful run-up, the chokes are short-circuited. The starting current is reduced depending on the required starting torque. Figure 9: Stator choke starting power circuit diagram c. Autotransformer Starter An autotransformer starter enables the start of squirrel-cage motors using a reduced starting current, since the voltage is reduced during start. Contrary to a star-delta connection, only three wires to the motor and 3 motor connections are required. This connection is particularly widely used in English-speaking countries. The motor is powered at reduced voltage via an autotransformer which is bypassed when the starting process is completed (Fig. 10). The starting process is in three steps: • in the first place, the autotransformer is star-connected, then the motor is connected to the mains via part of the autotransformer windings. The process is run at a reduced voltage which depends on the transformation ratio. The autotransformer is usually tapped to select this ratio to find the most suitable voltage reduction value. In order to adapt the motor start characteristics to the torque requirement, autotransformers are usually equipped with three selectable tappings (e.g. 80%, 65%, 50%), • the star connection is opened before going onto full voltage (motor almost reaches its rated torque). The fraction of coil (transformer’s partial windings) connected to the mains then acts as an inductance (chokes) in series with the motor windings. This operation takes place when the speed balances out at the end of the first step, • full voltage connection is made after the second step which usually only lasts a fraction of a second. The piece of autotransformer winding in series with the motor is shortcircuited and the autotransformer is switched off. The values obtained are: ππ πΌπ = 1.7 π‘π 4 πππ = 0.5 π‘π 0.85 ππ πΌπ The starting process runs with no break in the current in the motor, so transient phenomena due to breaks do not occur. However, if a number of precautions are not taken, similar transient phenomena can appear on full voltage connection because the value of the inductance in series with the motor is high compared to the motor after the star arrangement is open. This leads to a steep drop in voltage which causes a high transient current peak on Fotso Raoul, PhD 7 Faculty of Engineering and Technology, University of Buea full voltage connection. To overcome this drawback, the magnetic circuit in the autotransformer has an air gap which helps to lower the inductance value. This value is calculated to prevent any voltage variation at the motor terminals when the star arrangement opens in the second step. The air gap causes an increase in the magnetizing current in the autotransformer. This current increases the inrush current in the mains supply when the autotransformer is energized. This starting system is usually used in LV for motors powered at over 150kW. It does however make equipment rather expensive because of the high cost of the autotransformer. Note: There is an interlock between KM1 and KM2. Figure 10: Autotransformer starter-power circuit diagram Fotso Raoul, PhD Figure 11: Characteristics of induction motor - T vs N and I vs N 8 Faculty of Engineering and Technology, University of Buea 4. Star-Delta Starter This starting system (Fig. 12) can only be used with a motor where both ends of its three stator windings are fitted to a terminal board. Furthermore, the winding must be done so that the delta connection matches the mains voltage: e.g. a 380V, 3-phase supply will need a motor with 380V delta and 660V star coiling. The principle is to start the motor by connecting the star windings at mains voltage, which divides the motor’s rated star voltage by √3 (in the example above, the mains voltage at 380V = 660V / √3). The starting current peak (SC) is divided by 3: SC = 1.5 to 2.6 RC (RC rated Current). A 380V / 660V motor star-connected at its rated voltage of 660V absorbs a current √3 times less than a delta connection at 380V. With the star connection at 380V, the current is divided by √3 again, so by a total of 3. As the starting torque (ST) is proportional to the square of the supply voltage, it is also divided by 3: ST = 0.2 to 0.5 RT (RT Rated Torque). The motor speed stabilizes when the motor and resistive torques balance out, usually at 75-85% of the rated speed. The windings are then delta connected and the motor recovers its own characteristics. The change from star connection to delta connection is controlled by a timer. The delta contactor closes 30 to 50 milliseconds after the star contactor opens, which prevents shortcircuiting between phases as the two contactors cannot close simultaneously (interlock). The current through the windings is broken when the star contactor opens and is restored when the delta contactor closes. There is a brief but strong transient current peak during the shift to delta, due to the counter electromotive force of the motor. Star-delta starting is suitable for machines with a low resistive torque or which start with no load (e.g. wood-cutting machines). Variants may be required to limit the transient phenomena above a certain power level. One of these is a 1-2 second delay in the shift from star to delta. Such a delay weakens the counter-electromotive force and hence the transient current peak. This can only be used if the machine has enough inertia to prevent too much speed reduction during the time delay. Another system is 3-step starting: star-delta + resistance-delta. There is still a break, but the resistor in series with the delta-connected windings for about three seconds lowers the transient current. This stops the current from breaking and so prevents the occurrence of transient phenomena. Use of these variants implies additional equipment, which may result in a significant rise in the cost of the installation. Fotso Raoul, PhD 9 Faculty of Engineering and Technology, University of Buea Figure 12: Y-Δ starter power circuit Figure 13: Y-Δ starter control circuit Figure 14: Star-Delta power circuits Fotso Raoul, PhD 10 Faculty of Engineering and Technology, University of Buea 5. Rotor Resistance (or Slip Ring motor) Starter A slip ring motor cannot be started direct on-line with its rotor windings short-circuited, otherwise it would cause unacceptable current peaks. Resistors must therefore be inserted in the rotor circuit (Fig. 15) and then gradually short-circuited, while the stator is powered at full mains voltage. The resistance inserted in each phase is calculated to ascertain the torque-speed curve with strict accuracy. The result is that it has to be fully inserted on starting and that full speed is reached when it is completely short-circuited. The current absorbed is more or less proportional to the torque supplied at the most only a little greater than the theoretical value. Figure 15: Slip ring motor starter-power and control circuits Fotso Raoul, PhD 11 Faculty of Engineering and Technology, University of Buea Figure 16: Rotor resistance starter-power circuit with 3 sets of resistance bank 6. Part winding motor starting This system (Fig. 17), not widely used in Europe, is quite common in the North American market (voltage of 230/460, a ratio of 1:2). This type of motor has a stator winding divided into two parallel windings with six or twelve output terminals. It is equivalent to two “half motors” of equal power. On starting, a single “half motor” is connected directly at full mains voltage strength, which divides the starting current and the torque approximately by two. The torque is however greater than it would be with a squirrel cage motor of equal power with star-delta starting. At the end of the starting process, the second winding is connected to the mains. At this point, the current peak is low and brief, because the motor has not been cut off from the mains supply and only has a little slip. Figure 17: Part winding starting Fotso Raoul, PhD 12 Faculty of Engineering and Technology, University of Buea 7. Summary table of 3-phase motor starting systems This starting system requires the motor to be specifically sized. Figure 18: Comparison of starting methods 8. Motor Protection The summary in the table in figure 19 shows the possible causes of each type of fault, the probable effects and inevitable outcome if no protection is provided. In any event, motors always require two protections: • protection against short circuits, • protection against overload (overheating). Fotso Raoul, PhD 13 Faculty of Engineering and Technology, University of Buea Figure 19: Summary of possible faults in a motor with their causes and effects III. DC Starters Basic operational voltage equation of a DC motor is given as: Vt = Ea + IaRa and hence, Ia = (Vt - Ea)/Ra. Now, when the motor is at rest, obviously, the back emf Ea = 0. Hence, armature current at the moment of starting can be given as Ia = Ea/Ra. In practical DC machines, armature resistance is basically very low, generally about 0.5 β¦. Therefore, a large current flows through the armature during starting. This current is large enough to damage the armature circuit. Due to this excessive starting current: β’ the fuses may blow out and the armature winding and/or commutator brush arrangement may get damaged. β’ very high starting torque will be produced (as torque is directly proportional to the armature current), and this high starting torque may cause huge centrifugal force which may throw off the armature winding. β’ other loads connected to the same source may experience a dip in the terminal voltage. A large DC motor will pick up speed rather slowly due to its large rotor inertia. Hence, building up the back emf slowly causing the level of high starting current maintained for quite some time. This may cause severe damage. To avoid this, a suitable DC motor starter must be used. Very small dc motors, however, may be started directly by connecting them to the supply with the help of a contactor or a switch. It does not result in any harm because they gather speed quickly due to small rotor inertia. In this case, the large starting current will die down quickly because of the fast rise in the back emf. To avoid the above dangers while starting a DC motor, it is necessary to limit the starting current. So, a DC motor is started by using a starter. A resistance is introduced in series with the armature for very start duration of starting period only, which limits the starting current to a very safe value. This starting resistance is gradually cut out as the motor gains speed and develops the back emf which then regulates the speed of the motor. Fotso Raoul, PhD 14 Faculty of Engineering and Technology, University of Buea There are various types of dc motor starters, such as 3-point starter, 4-point starter, no-load release coil starter, thyristor controller starter, etc. The basic concept behind every DC motor starter is adding external resistance to the armature winding during starting. From the followings, 3-point starters and 4-point starters are used for starting shunt wound motors and compound wound motors. For series motors, 2-point starters are used for starting. 1. 3-Point Starter The internal wiring of a 3-point starter is as shown in the figure. When the connected dc motor is to be started, the lever is turned gradually to the right. When the lever touches point 1, the field winding gets directly connected across the supply, and the armature winding gets connected with resistances R1 to R5 in series. During starting, full resistance is added in series with the armature winding. Then, as the lever is moved further, the resistance is gradually is cut out from the armature circuit. Now, as the lever reaches to position 6, all the resistance is cut out from the armature circuit and armature gets directly connected across the supply. The electromagnet 'E' (no voltage coil) holds the lever at this position. This electromagnet releases the lever when there is no (or low) supply voltage. It can be seen that, when the arm is moved from the position 1 to the last position, the starter resistance gets added in series with the field winding. But, as the value of starter resistance is very small as compared to the shunt resistance, the decrease in shunt field current may be negligible. However, to overcome this drawback a brass or copper arc may be employed within a 3-point starter which makes a connection between the moving arm and the field winding, as shown in the figure of 4-point starter below. When the motor is overloaded beyond a predefined value, 'overcurrent release electromagnet' D gets activated, which short-circuits electromagnet E and, hence, releases the lever and the motor is turned off. 2. 4-Point Starter The main difference between a 3-point starter and a 4-point starter is that the no voltage coil electromagnet (E) is not connected in series with the field coil. The field winding gets directly connected to the supply, as the lever moves touching the brass arc (the arc below the resistance studs). The no voltage coil (or Hold-on coil) is connected with a current limiting resistance Rh. This arrangement ensures that any change of current in the shunt field does not affect the current through hold-on coil at all. This means, electromagnetic pull of the hold-on coil will always be sufficient so that the spring does not unnecessarily restore the lever to the off position. Fotso Raoul, PhD 15 Faculty of Engineering and Technology, University of Buea A 4-point starter is used where field current is to be adjusted by means of a field rheostat for the purpose of operating the motor above rated speed by reducing the field current. 3. 2-Point Starter Construction of DC series motor starters is very basic as shown in the figure. 2-point starter is used in series motors because in case of series motor, the armature winding and field winding are connected in series. Therefore, series motor achieves dangerous high speed. So, series motor should not be started without any load. Two-point starter construction is very much similar to the combination of rheostat with a tap changing. The starting resistance and no-load release coil are connected in series with the armature of a series motor. When a series motor is given a supply, the handle is moved from OFF position stud no.1 ie) full resistance is given at starting. Therefore, inrush of high starting current to the series motor is reduced. Then starting resistance is gradually cut down and the motor gathers speed, which will then develop back emf. The start arm is simply moved towards right to start the motor. Thus, maximum resistance is connected in series with the armature during starting and then gradually decreased as the start arm moves towards right. This starter is sometimes also called as a 2-point starter. The no load release coil holds the start arm to the run position and leaves it when the voltage is lost. Fotso Raoul, PhD 16