F E A T U R E A R T I C L E Diagnosing Transformer Faults Using Frequency Response Analysis Key Words: Frequency response analysis, diagnostics, transformer faults, correlation coefficient, loose turns, winding damage F requency response analysis, generally known within the industry as FRA, is a powerful diagnostic test technique. It consists of measuring the impedance of a transformer winding over a wide range of frequencies and comparing the results with a reference set. Differences may indicate damage to the transformer, which can be investigated further using other techniques or by an internal examination. Fundamentals As already mentioned, FRA essentially consists of measuring the impedance of transformer windings over a wide range of frequencies and comparing the results with a reference set. There are two ways of injecting the wide range of frequencies necessary, either by injecting an impulse into the winding or by making a frequency sweep using a sinusoidal signal. The former method is sometimes known as the impulse response method and the latter as the swept frequency method. A detailed evaluation of the relative merits of the two methods can be found in [1]. Briefly, the main advantage of the impulse response method over the swept frequency method is a shorter measurement time. The main advantages of the swept frequency method over the impulse response method are as follows: ● better signal to noise ratio ● equal, or nearly equal, accuracy and precision across the whole measurement range ● a wider range of frequencies are injected ● less measuring equipment is required. The author (and most others) uses the swept frequency method. All of the results shown in this article were obtained using the swept frequency method. So far as is known to the author, the swept frequency method was invented by Dick and Erven of Ontario Hydro Research Laboratories (now Kinectrics) between 16 S.A. Ryder Alstom Transformer Research Centre Saint-Ouen, France Frequency response analysis consists of measuring the impedance of a transformer winding over a wide range of frequencies and comparing the results with a reference set. 1975 and 1977, and the first description of the method to appear in the literature is [2]. An introduction to the method for the nonspecialist may be found in [3]. Measurement Method The swept frequency method for FRA requires the use of a network analyzer to generate the signal, make the measurements, and manipulate the results. A number of suitable network analyzers are presently commercially available. Figure 1 shows engineers making measurements on a test transformer as part of a research program. The author is on the right. The basic measurement circuit is shown in Figure 2. The tested impedance, in this case the transformer winding, is ZT. The standardized test impedance, in this case the impedance of the measurement cables is ZS. The injected signal is S, the reference measurement is R and the test measurement is T. A number of different methods are used for presenting the results. Following the lead of Dick and Erven [2], the author uses the modulus-argument form. The modulus is defined as: 0883-7554/03/$17.00©2003IEEE IEEE Electrical Insulation Magazine k = 20 log 10 (T / R ), (1) using the same notation as Figure 2, which is equivalent to ZS k = 20 log 10 , ZS + ZT (2) also using the same notation as Figure 2. The modulus is variously called the amplitude, the voltage ratio, the voltage gain, the impedance, and the admittance. The author prefers amplitude, which is used throughout this article. Voltage ratio and voltage gain can be seen to be descriptive. Impedance and admittance can also be seen to be descriptive, but can also be slightly misleading, as k is the ratio of two admittances or impedances. The argument is defined by φ = ∠(T / R ), (3) again using the same notation as Figure 2. The argument is usually called the “phase.” The measured frequency range is usually rather large (5 Hz to 20 MHz in the tests reported here) and so the results are usually presented on a graph of amplitude or phase against frequency. The phase-frequency graph does not contain as much useful information as the amplitude-frequency graph does, so it is often not plotted or analyzed. It is possible to use either a linear scale or a logarithmic scale for frequency in the graphs. A logarithmic scale has the advantage of allowing all of the information to be presented on a single graph (with linear scales it is often necessary to use a separate plot for each decade examined). nance. The first resonant frequencies can vary with the state of residual magnetization of the core. They will also be different on sister transformers, where manufacturing differences in the core joints will give different reluctances. At medium frequency there is a group of resonances, corresponding to the interaction of the shunt capacitance and air-cored inductance of the windings. These are generally the most repeatable. Slight differences may exist between sister transformers, owing to the effect of manufacturing differences in the windings. More significant differences may be found between windings on different phases of three-phase transformers, owing to different lead configurations or different winding external clearances. At high frequency there is a more confused group of resonances, corresponding to the interaction of the shunt and series capacitances and air-cored inductances of parts of the windings. The high-frequency response is affected by manufacturing differences, lead configuration, and winding external clearances in much the same way as is the medium-frequency response. At the highest frequencies the influence of the measurement cables can become important, especially on large transformers. Grounding Characteristics of Figure 1. Making measurements on a test transformer. Winding Frequency Response Results of FRA measurements made on the LV winding of a 60 MVA trackside ZS transformer made before and after a short-circuit withstand test are shown in Figure 3. The transformer withstood the applied short-circuits without damage, which is why there are no significant differences between the results. R S The low-frequency response is typically characterized by decreasing amplitude reaching a minimum in a resonance at or below 1 kHz. This resonance is caused by the interaction of the shunt capacitance of the windings with the magnetizing inductance. If there are two flux paths in the core of different lengths, then it will be a double resoFigure 2. Measurement circuit. March/April 2003 — Vol. 19, No. 2 ZT ZS T ZS 17 low-frequency response. Circulating currents loops, if they are sufficiently 0 large, redirect leakage flux into the core −10 and also change the low-frequency response. An ungrounded core changes the −20 shunt capacitance of the winding closest to the core and also the low-frequency −30 response. The medium-frequency response is −40 sensitive to faults that cause a change in the properties of the whole winding. A −50 significant increase in the medium-frequency resonances normally indicates −60 axial movement of a winding. A signifiBefore Test −70 cant decrease normally indicates radial After Test movement of the inner winding (hoop −80 buckling). Slight differences are often acFrequency (Hz) cepted as being a result of “windings settling into place.” Figure 3. Frequency response of LV winding. The high-frequency response is sensitive to faults that cause changes in the properties of parts of the winding. Localized winding damage causes seemingly random changes in the high-frequency response, often leading to the creation of new resonant frequencies. The high-frequency response may also be affected by the tank or cable grounding. Poor tank grounding is easy to spot, as it affects all windings, whereas damage is usually confined to one winding or at worst one phase. Poor cable grounds are more difficult to detect, as they may cause changes to just one winding, but are unlikely to lead to the creation of new resonant frequencies. The comparison is best made using measurements made earlier on the same winding. Where appropriate, both sets of measurements should be made on the same Figure 4. Loosened turns on 100 kVA distribution transformer. tap position and with the same accessories, such as bushings, fitted. If the transformer is oil filled, then the oil of the transformer and the cable screens can also have an should have the same relative permittivity as previously. important influence. The upper limit of the reproducible Relative permittivity is influenced by the type of oil, the range is likely to be at least 1 MHz, probably rather more relative humidity (itself a function of temperature and the for small transformers. For more details on factors absolute humidity) and so-called “normal aging.” If it is limiting the repeatable range, see [4]. suspected that the oil has been changed since the baseline measurement was made or that there has been a signifiDiagnosing Faults cant change in the relative humidity, then caution is necAs has been stated above, FRA consists of measuring essary and it may be advisable to make inter-phase the impedance of transformer windings over a wide range comparison to supplement the comparisons with the of frequencies and comparing the results with a reference baseline measurement. set. To be detectable a fault must cause either the inducInter-phase comparison is possible with three-phase tance or the capacitance of a significant part of the windtransformers. Owing to differences in the magnetizing ining to change by a significant amount. Faults that do not ductance between the three phases, there will be differcause such changes (partial discharge is probably the best ences between the FRA results at low frequencies. At example) are not detectable. Such faults may become demedium and high frequencies, the results usually agree tectable if they become sufficiently severe to cause detectable secondary damage (short-circuited turns, severe quite well, although not so well as different results from local winding damage, etc.). the same winding. For some designs the agreement is not as good, owing either to differences in the lead configuraFaults, such as short-circuited turns, change the magtions or in the winding external clearances. See [5] for an netizing characteristics of the transformer and, hence, the 10 100 1000 10,000 100,000 1,000,000 10,000,000 Amplitude (dBm) 1 18 IEEE Electrical Insulation Magazine nances and relies on there being sufficient resonances to give useful information but not so many as to cause confusion. This method can be difficult for computers to apply, because they tend to confuse noise for resonances, especially at the edges of the reproducible range. An alternative, which the author has been involved in promoting, is to calculate statistical indicators of the amount of agreement or disagreement between the two sets of measurements. This amounts to a more objective and transparent way of performing the first part of the graphical comparison described above (and if the changes are large enough, the other two as well). This extracts information from the results across the whole of the repeatable range and is easily applied by computers. 10 100 1000 10,000 100,000 Amplitude (dBm) example of differences in medium- and high-frequency FRA results between the phases of a new transformer. Comparison between sister transformers is also possible. It can be particularly useful for single-phase transformers forming three-phase banks. There may be quite large normal differences in the low-frequency results, but at higher frequencies the results tend to agree quite well, although not so well as different results from the same winding. See [4] for an example of normal differences between FRA results from sister transformers. The faults causing changes to the low-frequency response can all be reliably detected using other means: short-circuited turns by magnetizing current or turns ratio measurements, circulating currents by DGA or a thermal scan, and no core earth by capacitance measurement. The faults causing changes at medium and at high 1 frequency are difficult to detect using 0 other means: turns ratio, capacitance measurement, and leakage impedance −20 measurement are effective in some cases but not all. For a detailed evaluation of −40 FRA for fault diagnosis see [6]. For a particularly spectacular example of FRA succeeding where other methods fail see −60 [7]. The rest of this article, and the practi−80 cal examples presented, will concentrate on the detection of winding damage. March/April 2003 — Vol. 19, No. 2 Baseline Loosened Loosened, Moved Down −100 Loosened, Moved to Ends −120 Frequency (Hz) Figure 5. Frequency response for HV A-B – 10 Hz to 10 MHz. 100,000 −10 1,000,000 10,000,000 −15 Amplitude (dBm) Comparison Methods The comparison of results is usually made by plotting a graph of the amplitude against frequency for both sets of measurements. An experienced observer then examines the two curves for any significant differences. Significant differences are usually understood to be: ● changes to the shape of the curve ● the creation of new resonant frequencies or the elimination of existing resonant frequencies ● large shifts in existing resonant frequencies. The main problem with this method of comparison is that the expert’s opinion may lack both objectivity and transparency. One way of addressing both problems is to note down all of the resonant frequencies. This gives objective and transparent information on the number of resonances that have been created or eliminated, and how far any resonances may have shifted. However, it can only extract information from the results at the reso- 1,000,000 10,000,000 100,000,000 −20 −25 −30 −35 Baseline Loosened Loosened, Moved Down Loosened, Moved to Ends −40 Frequency (Hz) Figure 6. Frequency response for HV A-B – 100 kHz to 10 MHz. 19 Table I. Correlation coefficients for 100 kVA distribution transformer. Decade Band 10 Hz-100 Hz 100 Hz-1 kHz 1 kHz-10 kHz 10 kHz-100 kHz 100 kHz-1 MHz Loosened 0.9999 0.9652 1.0000 0.9991 0.9827 Correlation Coefficient Between Baseline Results and: Loosened, Moved Down Loosened, Moved to Ends 0.9998 0.9998 0.9893 0.9737 1.0000 1.0000 0.9994 0.9996 0.9886 0.9908 Trials by the author indicate that the correlation coefficient is the most reliable statistical indicator. Full results of an evaluation may be found in [8]. The mathematical definition of the correlation coefficient is given in the Appendix. Case Studies A small number of case studies are presented to show the application of different comparison methods to the diagnosis of real and simulated faults on transformers. Case Study 1—Loosened Turns on 100 kVA Distribution Transformer (Simulated) This case study concerns a fault that was simulated on the 100 kVA distribution transformer, shown in Figure 1. The fault was simulated by cutting away the cotton tape holding the outside of the A phase HV winding in place and manually displacing turns from the outer layers of the winding. This is intended to simulate localized winding damage that might result from a through fault. Figure 4 shows the damage created (the damaged phase is on the right, the visible damage on the other phases was part of another experimental program not described here). The frequency response of the A-B phase of the HV winding, before, during, and after the fault simulations, which were made in three stages, is shown in Figure 5. The double-decade band from 100 kHz to 10 MHz, where the changes caused by the damage are most apparent, is shown in Figure 6. Figure 7. Damage to LV winding of 440 MVA generator transformer. 20 The changes to the FRA results take the form of seemingly random changes in the amplitude, which are highly characteristic of this type of fault. The existing resonances are shifted around, but there is no creation of new resonances. Creation of new resonances is a common symptom of winding damage on large transformers, but not on small distribution transformers such as this. The correlation coefficients between the baseline measurement and the three measurements made during the damage simulation, calculated in decade bands, are shown in Table I. For most windings the correlation coefficients between results from undamaged transformers are very close to unity from 1 kHz up to 1 MHz. The author considers that a correlation coefficient of less than 0.9950 in this range, between different measurements on the same winding, merits further investigation. In this case study the correlation coefficient for the 100 kHz-1 MHz decade band is low enough to merit further investigation in all three cases. Case Study 2—Hoop Buckling Failure of LV Winding in 440 MVA Generator Transformer This case study concerns a 440 MVA 21/245 kV generator transformer. The transformer was originally installed at a generating station in Germany in 1969. It was damaged by a through fault and was rewound in 2000. The frequency response of the three phases of the LV winding is shown in Figure 8. The measurements were made after the windings had been removed from the core; the low-frequency response was largely absent and was therefore cropped from the graph. The changes to the FRA results take the form of decreases in the first two resonant frequencies (from about 62 kHz to 56 kHz and from about 222 kHz to about 207 kHz) and the creation of two new resonant frequencies (at about 370 kHz and at about 700 kHz). These changes are quite typical of what can be expected from hoop buckling associated with winding damage, i.e., decreases in the medium-frequency resonances and the creation of new resonances at high frequencies. The correlation coefficients between the measurements, calculated in decade bands, are shown in Table II. In this case study the correlation coefficients between the undamaged phases 1 and 3 may be used as a baseline. It can be seen that the correlation coefficients with the damIEEE Electrical Insulation Magazine 20 10 1,000 0 Amplitude (dBm) aged phase 2 are very much lower than those between the undamaged phases in both the 10 kHz-100 kHz and 100 kHz-1 MHz decade bands. This is a good indication of abnormal differences, which merit further investigation. Note that the correlation coefficients between the two undamaged phases are rather lower than in Case Study 1, partly owing to manufacturing differences between the two phases and partly owing to the less than ideal measurement conditions. See [9] for another example of a hoop buckling failure. 1,000,000 −10 −20 −30 −40 Case Study 3—Axial Collapse of Series Winding in 300 MVA Autotransformer (Suspected) 100,000 −50 Phase 1 Phase 2 (Damaged) Phase 3 −60 Amplitude (dBm) This case study concerns a 300 MVA Frequency (Hz) 400/220 kV autotransformer. The transformer was originally installed at a substation in France in 1980. It remained in Figure 8. Frequency response for LV winding. service there until 1998, when it was replaced by a higher-capacity transformer 1,000 10,000 100,000 1,000,000 10 100 and transferred to the reserve. The HV 0 and LV bushings were removed and the −10 transformer was stored under dry nitrogen. In 2000, the transformer was moved −20 to a different substation, where it was reassembled and the bushings refitted. −30 Shortly after its return to service the transformer was tripped by various pro−40 tective relays. FRA measurements were made to see whether the windings had −50 been damaged. The incident is described A⋅a in more detail in [10]. −60 C⋅c The frequency response of A-a and −70 C-c phases of the series winding is shown in Figure 9. Earlier measurements (deFrequency (Hz) scribed in [10]) had identified the C phase as damaged and had eliminated the Figure 9. Frequency response for series winding. possibility of damage to the common winding. The correlation coefficient reaches very low values in The differences in the FRA results take the form of an the 1 kHz-10 kHz decade band, where the changes increase in the frequency of the main medium-frequency caused by the axial displacement are most apparent, and resonance on C-c winding with respect to A-a winding in the 100 kHz-1 MHz decade band, where the changes (1640 Hz on A-a winding, 1830 Hz on C-c winding) and caused by the consequent winding damage are most apthe creation of several new resonant frequencies above parent. The correlation coefficient in the 10 kHz-100 100 kHz on C-c winding (175 kHz, 190 kHz, 443 kHz, kHz decade band is close to normal. See [5], [9], and [11] 637 kHz, 679 kHz, and 843 kHz). These changes are for further examples of axial collapse of windings. quite typical of what can be expected from axial displacement associated with winding damage, i.e., increases in Conclusions the medium-frequency resonances and the creation of Frequency response analysis is a proven and effective new resonances at high frequencies. This diagnosis has means of detecting faults in transformers. The main interyet to be confirmed by an internal inspection. est of the method lies in its ability to find faults, princiThe correlation coefficients between the measurepally mechanical damage to the windings, which cannot ments, calculated in decade bands, are shown in Table III. always be detected using other means. Results can be March/April 2003 — Vol. 19, No. 2 21 Table II. Correlation coefficients for 440 MVA generator transformer. Decade Band 10 kHz-100 kHz 100 kHz-1 MHz Phase 1 – Phase 2 0.8618 0.7761 Correlation Coefficient Between Results Phase1 – Phase 3 Phase 2 – Phase 3 0.9953 0.8923 0.9626 0.7779 Table III. Correlation coefficients for 300 MVA autotransformer. Decade Band Correlation Coefficient 10 Hz-100 Hz 0.9908 100 Hz-1 kHz 0.9918 1 kHz-10 kHz 0.7483 10 kHz-100 kHz 0.9797 100 kHz-1 MHz 0.8577 compared by eye, by noting down the resonant frequencies, or by using statistical indicators. Statistical indicators are particularly useful as they add objectivity and transparency. Acknowledgments This article is published with the permission of Alstom Transformer Research Centre and Electricité de France Recherche. The author gratefully acknowledges the contributions of his colleagues Dominique Lacaze, Michael Rösner, and Stefan Tenbohlen. The fault simulation program on the 100 kVA distribution transformer was undertaken as part of a joint project between Alstom Transformer Research Centre and Electricité de France Recherche. Some of the experiments described in this article were carried out by Vincent Bergaud as part of a final year project while he was a student with IUT Paris Jussieu. Simon A. Ryder (M ’03) was born in England in 1973. He graduated from St. John’s College, Oxford University, with an MEng. in Engineering Science in 1996. He joined Alstom later that year. He is presently working as a research engineer at Alstom Transformer Research Centre. His main areas of interest are frequency response analysis, thermal characteristics of transformers, and winding technology. He is a member of IEEE-PES and of IEE (U.K.), a personal member of CIGRÉ, and a chartered engineer (U.K.). References [1] S. Ryder and S. Tenbohlen, “Comparison of swept frequency and impulse response methods for making FRA measurements,” paper to be presented at 2003 Conference of Doble clients, Boston, 2003. [2] E.P. Dick and C.C. Erven, “Transformer diagnostic testing by frequency response analysis,” IEEE Trans. PAS, vol. 97, pp. 2144-2153, Nov./Dec. 1978. [3] S. Ryder, “Frequency response analysis for diagnostic testing of power transformers,” Electricity Today, vol. 13, no. 6, pp. 14-19, 2001. [4] S. Ryder, “Experimental investigations of the repeatability of [frequency response analysis] measurements,” paper presented at 2002 Conference of Doble clients, Boston, 2002. 22 [5] J.A. Lapworth and T.J. Noonan, “Mechanical condition assessment of power transformers using frequency response analysis,” paper presented at 1995 Conference of Doble clients, Boston, 1995. [6] T.J. Noonan, “Power transformer condition assessment and renewal. Frequency response analysis update,” paper presented at 1997 Conference of Doble clients, Boston, 1997. [7] J.A. Lapworth, “Transformer fails seven years after close-up faults. FRA diagnoses the problem,” paper presented at 2002 Conference of Doble clients, Boston, 2002. [8] S. Ryder, “Methods for comparing frequency response analysis measurements,” in Proc. 2002 IEEE Int. Symp. Electrical Insulation, Boston, MA, 2002, pp. 187-190. [9] J.A. Lapwoth, “Detection of winding movement in power transformers by frequency response analysis (FRA),” presented at the Int. Conf. Power Transformers, Kolobrzeg, Poland, 1999. [10] J.P. Taisne, A. Tanguy, J.P. Patelli, E. Chemin, F. Devaux, and S. Ryder, “French experience with decision making for damaged transformers,” presented at the International Council on Large Electric Systems (CIGRÉ), Paris, France, 2002. [11] M. Stace and S.M. Islam, “Condition monitoring of power transformers in the Australian state of New South Wales using transfer function measurements,” in Proc. 5th ICPADM, Seoul, Korea, 1997, pp. 248-251. [12] S. Ryder, “Diagnosing transformer faults using frequency response analysis: Results from fault simulations,” paper presented at IEEE Power Engineering Society Summer Meeting, Chicago, IL, 2002. [13] D.K. Xu, C.Z. Fu, and Y.M. Li, “Application of the artificial neural network to the detection of the transformer winding deformation,” presented at the International Symposium on High Voltage Engineering, London, U.K., 1999. Appendix: Mathematical Definition of the Correlation Coefficient Consider two sets of n numbers, X {x 1, x 2, x 3, … x n} and Y{y1, y2, y3, … y n}. The correlation coefficient between these two sets of numbers is defined by ρ= n n n x =i x =i x =i ∑ x i y i / ∑ x i2 ∑ y i2 . (A1) The correlation coefficient was first applied to the analysis of FRA results by Xu, Fu, and Li in [13]. A detailed evaluation of its performance may be found in [8]. IEEE Electrical Insulation Magazine