Laboratory report 2 MECE-608: Power System Analysis Department: Electrical and Computer Engineering By: Mohammad Jawid Ahmadi ID: 202115365 Objectives The purpose of this lab is to investigate how changing transmission line characteristics affects power flow in a distribution grid. The research will be carried out using the PowerWorld Simulation system. Section I Procedure PowerWorld was used to construct a circuit with two generators, three buses, transmission lines, two loads, and one shunt capacitor as the first step in the lab exercise. All transmission lines had their "per unit impedance parameters" adjusted to 0 as recommended by the Laboratory Manual. All lines have 250,000 MWA ratings applied to them. After that, we simulated this power grid using the predefined settings and monitored the resulting power flow and losses. Figure 1. PowerWorld network created using default settings. As can be seen, all transmission lines have zero power losses, with the exception of the line connecting buses 4 and 5, where a reactive power loss of 0.0002 Mvar exists. The per-unit impedances of all transmission lines were all set to 0, but the series reactance was always set by the tool to 0.000010. This is why. Hence, some neglectable Mvar losses (which may be approximated to zero) can be detected at this line. Because the per-unit parameters are 0, the transmission lines’ losses are likewise 0. The top generator's numbers started out at 60 MW and 20 Mvar, but during the run, they dropped to 20 MW and 16 Mvar, while the bottom generator showed 40 MW and 5 Mvar. The 40 MW, 20 Mvar, 20 MW, and 10 Mvar loads as well as the 9.3 Mvar shunt capacitor are to blame. In response to the load consumption, both generators provided a total of 60 MW and 21 Mvar, which is the same as the load consumption. The shunt capacitor reduces the reactive power that the top generator produces. Figure 2. The concise list of power flow for the first circuit. Section II Procedure To ascertain the impact of increasing load consumption on the power flow and losses, the identical circuit utilized in the first section of the laboratory study was employed in the second section. According to Table 1, the load consumption values for the two loads were set to various levels. The simulation of this power network was then conducted using both the default and modified settings, and the power flow and power losses were recorded. Figure 3. Power network with the increased load consumption: 30MW and 50 MW. Figure 4. The circuit's rapid power flow list with the higher load consumption. Figure 5. Increased load demand on the power network: 40 MW and 60 MW. Figure 6. The circuit's rapid power flow chart with the rising load consumption. Test Table 1. The transmission line losses according to the increased load consumption. The load 1 values The load 2 values Transmission line losses for 1-2, 2-3 Transmission line losses for 1-5 Transmission line losses for line 45 MW Mvar MW Mvar ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) Total network losses 1 20 10 40 20 0.000 0.000 0.000 0.000 0.000 0.0002 0.000 0.0003 2 30 10 50 20 0.000 0.000 0.000 0.000 0.000 0.0002 0.000 0.0003 3 40 10 60 20 0.000 0.000 0.000 0.000 0.000 0.0002 0.000 0.0004 4 50 10 70 20 0.000 0.0001 0.000 0.000 0.000 0.0002 0.000 0.0005 5 60 10 80 20 0.000 0.0001 0.000 0.000 0.000 0.0002 0.000 0.0006 As can be seen, all transmission lines have zero power losses, with the exception of lines 1-2 and 2-3 and the line connecting buses 4-5, which occasionally have reactive power losses of 0.0002 Mvar and 0.0001 Mvar, respectively. Again, this is because all of the transmission lines' per-unit impedances were set to 0, but the tool itself always sets the series reactance to 0.000010. As a result, along this line, there are some Mvar losses that may be neglected and are about equal to zero. Since the per-unit parameters are zero, the losses on the transmission lines are also zero. While the reactive power and real and reactive powers of the bottom generator remained constant throughout the simulation, the top generator's real power values changed: 1๐ ๐ก ๐๐ก๐๐๐๐ก๐๐๐: 40 MW, 5 Mvar for bottom generator; 20 MW, 16 Mvar for top generator; 2๐๐ ๐๐ก๐๐๐๐ก๐๐๐: 40 MW, 5 Mvar for bottom generator; 40 MW, 16 Mvar for top generator; 3๐๐ ๐๐ก๐๐๐๐ก๐๐๐: 40 MW, 5 Mvar for bottom generator; 60 MW, 16 Mvar for top generator; 4๐กโ ๐๐ก๐๐๐๐ก๐๐๐: 40 MW, 5 Mvar for bottom generator; 80 MW, 16 Mvar for top generator; 5๐กโ ๐๐ก๐๐๐๐ก๐๐๐: 40 MW, 5 Mvar for bottom generator; 100 MW, 16 Mvar for top generator; It can be observed that both generators’ supply is controlled according to the load consumption: for example in the 2nd iteration, the total power supply by both generators were 80 MW (40 MW for top and 40 MW for bottom generator) and 21 Mvar (16 Mvar and 5 Mvar) Despite the fact that the overall load consumption parameters were 80 MW (30 MW for the first load and 50 MW for the second load) and 30 Mvar (10 Mvar and 20 Mvar), the shunt capacitor itself led to a decrease in the reactive power provided by a top generator for 9.3 Mvar. Section III Procedure In the third part of the laboratory work, the same circuit was used to determine how increased perunit impedances affected power flow and losses. Table 2 shows all transmission lines' "per unit impedance parameters" adjusted to various values. After that, this power network was simulated with default and changed parameters to record power flow and power losses. Figure 7. Power network with the increased per-unit impedances: iteration 2. Figure 8. Power network with the increased per-unit impedances: iteration 4. Table 2. losses on the transmission lines due to higher per-unit impedances. Test Pui values for 1-2 Pui values for 2-3, 1-5, 4-5 Transmissio n line losses for 1-2, 2-3 Transmission line losses for 1-5 Transmission line losses for line 4-5 Total network losses R X R X ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar ) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) 1 0 10−5 0 10−5 0.000 0.000 0.000 0.000 0.000 0.0002 0.000 0.0003 2 0.1 0.01 0.01 0.1 0.000 0.000 0.0468 0.4681 0.1611 1.6112 0.2079 2.0795 3 0.2 0.02 0.02 0.2 0.000 0.000 0.0947 0.9471 0.3244 3.2441 0.4191 4.1914 4 0.3 0.03 0.03 0.3 0.000 0.000 0.1441 1.4413 0.4911 4.9111 0.6352 6.3525 5 0.4 0.04 0.04 0.4 0.000 0.000 0.1956 1.9557 0.6626 6.6258 0.8582 8.5817 Except for two lines connecting buses 1 and 2, and 2 and 3, transmission lines lose power. Transmission line losses rise with per-unit impedance. Hence, per-unit impedance values affect transmission line power losses: if they are 0, power losses are 0, but if they are nonzero but elevated, power losses are likewise raised. The top generator's actual and reactive power values changed during the simulation, however the bottom generator's reactive power values remained constant: 1๐ ๐ก ๐๐ก๐๐๐๐ก๐๐๐: 20 MW, 16 Mvar for top generator; 40 MW, 5 Mvar for bottom generator; 2๐๐ ๐๐ก๐๐๐๐ก๐๐๐: 20 MW, 19 Mvar for top generator; 40 MW, 3 Mvar for bottom generator; 3๐๐ ๐๐ก๐๐๐๐ก๐๐๐: 20 MW, 20 Mvar for top generator; 40 MW, 5 Mvar for bottom generator; 4๐กโ ๐๐ก๐๐๐๐ก๐๐๐: 21 MW, 21 Mvar for top generator; 40 MW, 6 Mvar for bottom generator; 5๐กโ ๐๐ก๐๐๐๐ก๐๐๐: 21 MW, 22 Mvar for top generator; 40 MW, 8 Mvar for bottom generator; Section IV Procedure In order to assess the impact of increased active power provided by the bottom generator on the power flow and on the performance of the other generator, the identical circuit utilized in the earlier stages of the laboratory work was employed for the final portion of the study. Just the true power levels produced by the bottom generator were raised by 5 MW in each cycle, and the "per unit impedance parameters" of all transmission lines were once again set to 0. The power flow and power losses were then recorded as the simulation of this power network was run with the default parameters as well as with changed values. Figure 9. Electricity network with bottom generator's higher actual power: iteration 4. Figure 10. Power network with enhanced actual power from the generator at the bottom: iteration 5. Test Table 3. The increased real power supplied by the bottom generator and power flows. Bottom generator Top generator Overall network losses Transmission line losses for 1-2, 2-3 Transmission line losses for 15 Transmission line losses for line 4-5 MW Mvar MW Mvar ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) ๐๐๐๐ ๐ (MW) ๐๐๐๐ ๐ (Mvar) 1 40 5 20 16 0.000 0.0003 0.000 0.000 0.000 0.000 0.000 0.0002 2 45 5 15 16 0.000 0.0004 0.000 0.000 0.000 0.0001 0.000 0.0002 3 50 5 10 16 0.000 0.0005 0.000 0.000 0.000 0.0001 0.000 0.0003 4 55 5 5 16 0.000 0.0005 0.000 0.000 0.000 0.0001 0.000 0.0003 5 60 5 0 16 0.000 0.0006 0.000 0.000 0.000 0.0002 0.000 0.0004 As seen in Table 3, increasing the actual power provided by the bottom generator had an impact on the active power of the other generator. With each repetition, the real power of the later generator decreased by 5 MW while the real power of the former generator increased. The reactive powers of both generators remained unaltered. The other generator's power supply was 0 MW at the fifth repetition, even though the bottom generator's true power output was 60 MW. The value of the active power provided by the second generator begins to exhibit negative numbers, such as -5 MW, -10 MW, and so on, when actual power produced by the bottom generator is increased further and exceeds 60 MW. As a result, the top generator serves as a load and consumes energy from the system since it is no longer providing the genuine power. There is a restriction on the iteration process as a result: only a certain number of iterations may be carried out. In this instance, the answer is 5, since the generator begins to function as a load at iteration 6. Since the per-unit impedance values of all transmission lines were set to 0, the power losses on them are approximately 0. Yet, it can be shown that the reactive power losses on transmission lines also grow as the actual power produced by the bottom generator increases. This laboratory study examines how the increased load consumption, per-unit impedance values, and active power produced by one generator affect the network's power flow, transmission line losses, and the active power produced by a different generator. To examine this impact, many simulations were run while the necessary parameters were changed. In Section I, the circuit was formed using components with default characteristics. The transmission lines' power losses were roughly zero since the per-unit impedance values were set to zero. This situation therefore demonstrated the need of lowering the per-unit impedance characteristics of resistance and reactance in order to decrease power losses in transmission lines. Figure. 11: The active and reactive losses in the network The load parameters for both loads were raised by 10 MW in Section II. Once again, the transmission line losses were close to zero, yet the top generator's true power output was rising. This figure was raised by 20 MW at each phase in order to adapt to the load consumption. In this instance, the shunt capacitor had an impact on the reactive power generated by the identical top generator: it reduced it. The transmission lines' per-unit impedance characteristics were raised differently in Section III. Increased power losses were noted during these scenarios because changes in those parameters have an impact on the power losses in transmission lines. Moreover, only the reactive power provided by the other generator was changing, but both the reactive and active powers produced by the top generator were gradually growing. For each test in Section VI, the bottom generator's active power output was raised by 5 MW. The outcomes demonstrated that this modification had an impact on the active power provided by the other one, which reduced by 5 MW throughout each test. Moreover, only a certain number of repetitions may be performed to use both generators; otherwise, the top generator begins to function as a load. That indicates that in order for this generator to continue to run, power must be provided by the bus, which is not ideal. References [1] Laboratory manual [2] Abdelhay A. Sallam; Om P. Malik, "Power Factor Improvement," in Electric Distribution Systems , IEEE, 2019, pp.361-378, doi: 10.1002/9781119509332.ch13. [3] Y. Yao, A. Cosic and C. Sadarangani, "Power Factor Improvement and Dynamic Performance of an Induction Machine with a Novel Concept of a Converter-Fed Rotor," in IEEE Transactions on Energy Conversion, vol. 31, no. 2, pp. 769-775, June 2016, doi: 10.1109/TEC.2015.2505082. [4] R. Kushwaha and B. Singh, "Power Factor Improvement in Modified Bridgeless Landsman Converter Fed EV Battery Charger," in IEEE Transactions on Vehicular Technology, vol. 68, no. 4, pp. 3325-3336, April 2019, doi: 10.1109/TVT.2019.2897118.