c) Standard weight (Kg/km) 432(7/3.15) and 583(7/3.66) d) Location of ground wire One continuous ground wire Wire to run horizontally on the top of the towers for 132 and 220 KV and two ground wire for 400 KV lines. e) Tensile load in each ground wire (to be furnished by the Bidder) i) At min. temp. of 5˚ C and in still air (kgs) ii) At every day temp. of 32˚ C and still air (kgs) iii) At 5˚ C and 2/3rd of full wind (kgs) 1.1.8.1 Towers a) Span lengths in metres i) Ruling design span b) Wind load (kg/sqm) on conductor ACSR Zebra 300 52 ACSR Moose 300 52 ACSR Panthe r 250 52 c) Shielding angle with vertical 20˚ 20˚ 20˚ d) Towers to be designed for heavy V-zone wind zone V-zone v-zone 1.1.8.2 Insulator Strings(Disc)(Antifog type) Sl. Particulars Single No. Suspensi on string 1. No. of standard Discs (nos) 1) 400 KV 1X25 2) 220 kV 1X15 3) 132 Kv 1X10 2. Size of Disc (400kv/220kV/132 kv) 280x145/ 255X145/ 255X145 3. Electromechanical 120/90/9 strength (KN) 0 (400 KV/220 kV/132 VOL-III (TS) Double suspension string 2X25 2X15 2X10 Single Tension string 1X25 1X15 1X10 305x170/ 305x170/ 255X145/ 280x145 280x145/ 255X145 120/90/90 Double Tension string 2X25 2X15 2X10 305x170/3 05x170/28 0x145 160/160/ 160/160/12 120 0 E26-TRANSMISSION LINE- Page 21 of 84