Bühler AG CH-9240 Uzwil, Switzerland Phone +41 71 955 11 11 Fax +41 71 955 33 79 www.buhlergroup.com Operating instructions Moisture controller For spare parts see spare parts catalog 7952 MYFC-MOZF-66542-1-en-0803 2 Moisture controller Preface These operating instructions document the moisture controller MYFC-MOZF. The operating instructions have to be handed over to those persons who are responsible for the operation and the supervision of these devices. These operating instructions contain the information required for the user regarding installation, operation and maintenance. Description of activities that do not require any special knowledge have been omitted. Repair instructions that exceed the normal maintenance work are not provided. The machine meets all acknowledged safety regulations. However, improper use can involve physical danger for the user. Highest priority, therefore, has been given to safety. The corresponding safety instructions are marked as follows: Danger! Risk of injury to persons. Caution! Warning of material damage. Note: Important information or instructions. Important information • Procedures upon receipt Inspect the equipment visually in accordance with the delivery contract as soon as it has been received. • Storage Equipment that is not installed immediately must be stored protected against weather and other influences. • Installation The assembly and installation of the machine and machine equipment must only be carried out by observing all installation instructions supplied. • Design versions If different designs are described in the documentation provided, only the information concerning the version supplied will apply. We reserve the right to make modifications due to technical progress up to the time of delivery. • Duty of instruction Commissioning and maintenance must only be done by trained specialists. Prior to the initial start-up the operating personnel must familiarize themselves with the documentation provided. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Table of contents 3 Table of contents 1 Safety................................................................................................................6 1.1 1.2 1.3 1.4 1.5 2 3 Technical data .................................................................................................8 Description of the dampening system.........................................................10 3.1 3.2 3.3 4 Handling with a crane ......................................................................................................21 Transport weights and volumes .......................................................................................21 Installation .....................................................................................................22 5.1 6 Structure and application possibilities of the dampening system ....................................10 3.1.1 Functional description.......................................................................................10 3.1.2 Control of the moisture .....................................................................................11 3.1.3 Percent dampening ..........................................................................................11 3.1.4 Litre dosing .......................................................................................................13 3.1.5 Manual operation..............................................................................................13 3.1.6 Formulas...........................................................................................................13 Electrical connections ......................................................................................................14 3.2.1 Moisture controller MYFC/MOZF (Standard wiring) .........................................14 3.2.2 Moisture controller MYFC-MOZF (supplementary wiring)................................15 3.2.3 Percent dampening with MOZF........................................................................16 3.2.4 Litre dosing with MOZF ....................................................................................17 3.2.5 Moisture control MYFC with MOZE (special application).................................18 Remote control.................................................................................................................19 3.3.1 Built-in version ..................................................................................................19 3.3.2 Table/wall version.............................................................................................19 3.3.3 Remote control connection to MYFC ...............................................................20 3.3.4 Remote control connection to MOZF (Litre dosing or with MYFC) ..................20 3.3.5 Remote control connection to MOZF (Percent dampening).............................20 Transport........................................................................................................21 4.1 4.2 5 Safety of persons ...............................................................................................................6 Instructions for the safe use in hazardous areas ...............................................................6 1.2.1 Designated use...................................................................................................6 Installation / commissioning ...............................................................................................6 1.3.1 Installation instructions / assembly.....................................................................7 1.3.2 Special conditions for safe operation .................................................................7 Service / Maintenance .......................................................................................................7 Safety concept ...................................................................................................................7 Location............................................................................................................................22 Commissioning .............................................................................................23 6.1 6.2 Checklist for verifying EU conformity ...............................................................................23 Initial start-up MYFC ........................................................................................................23 6.2.1 Setting the parameters .....................................................................................23 6.2.2 Alignment of the measuring container..............................................................25 6.2.3 Alignment of the level measurement ................................................................26 6.2.4 Alignment of the Flowbalancer MZAH..............................................................26 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 4 Table of contents 6.3 7 7.2 7.3 Display operation............................................................................................................. 31 7.1.1 Changing parameters ...................................................................................... 32 7.1.2 Selecting parameters....................................................................................... 32 Display and status messages (MYFC and MOZF) ......................................................... 33 Offset and nominal value adjustment of the moisture..................................................... 34 7.3.1 Adjusting the offset value................................................................................. 34 7.3.2 Adjusting the moisture nominal value .............................................................. 34 Description of the MYFC Moisture Control................................................. 35 8.1 8.2 8.3 8.4 8.5 8.6 9 6.2.5 Alignment of the temperatures......................................................................... 27 6.2.6 Alignment of the microwave unit...................................................................... 28 Initial start-up MOZF........................................................................................................ 29 6.3.1 Venting the system .......................................................................................... 29 6.3.2 Checking the release and product probe......................................................... 29 6.3.3 MOZF as percent dampening .......................................................................... 29 6.3.4 Alignment of the water meter........................................................................... 30 Operation....................................................................................................... 31 7.1 8 Moisture controller Mechanics ....................................................................................................................... 35 Schematic diagram.......................................................................................................... 36 Control............................................................................................................................. 37 8.3.1 Overview .......................................................................................................... 37 8.3.2 Control unit MEAF with MYFC auxiliary board EBD1293 variant.................... 38 8.3.3 Auxiliary board EBD1293................................................................................. 39 Electrical connections ..................................................................................................... 40 Parameters...................................................................................................................... 41 8.5.1 Overview of main menu ................................................................................... 41 8.5.2 Overview of general parameters...................................................................... 42 8.5.3 Parameter group REC ..................................................................................... 43 8.5.4 Parameter group TCON................................................................................... 45 8.5.5 Parameter group SYS...................................................................................... 47 8.5.6 Parameter group ADC ..................................................................................... 49 8.5.7 Parameter group HOST................................................................................... 50 8.5.8 Parameter group SVV...................................................................................... 50 8.5.9 Parameter group PROD .................................................................................. 51 Flowbalancer MZAH........................................................................................................ 52 8.6.1 Design features................................................................................................ 52 Description of the Liquids Flow Controller MOZF ..................................... 53 9.1 9.2 9.3 Mechanism and design variations................................................................................... 53 Control............................................................................................................................. 55 9.2.1 Control unit MEAF with IO-Extension EBD1270.............................................. 55 9.2.2 Electrical connections ...................................................................................... 56 Parameters...................................................................................................................... 57 9.3.1 Main menu overview........................................................................................ 57 9.3.2 General parameter overview ........................................................................... 57 9.3.3 Parameter group TCON................................................................................... 58 9.3.4 Parameter group HOST................................................................................... 59 9.3.5 Parameter group SYS...................................................................................... 60 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 10 Alarm messages ..............................................................................................................61 Locking the product probe MOZL (ERR63 FLOWD) .......................................................67 External 24 V alarm acknowledgement ...........................................................................67 Parameter group SERV ...................................................................................................68 Maintenance...................................................................................................71 11.1 MYFC 11.1.1 11.1.2 11.1.3 11.1.4 11.1.5 11.1.6 11.1.7 11.1.8 11.1.9 11.1.10 11.2 MOZF 11.2.1 11.2.2 11.2.3 11.2.4 11.2.5 12 5 Alarms and warnings MYFC and MOZF.......................................................61 10.1 10.2 10.3 10.4 11 Table of contents 71 Removing the measuring container..................................................................71 Sensor tongue ..................................................................................................72 Single-point force transducer ...........................................................................73 Force transducer ..............................................................................................74 Diaphragm drive ...............................................................................................75 Inlet spout .........................................................................................................76 Metering slide gate ...........................................................................................77 Baffle plate........................................................................................................78 Protective bellows.............................................................................................78 Force transducer ..............................................................................................78 79 Water filter ........................................................................................................79 Shut-off valve....................................................................................................79 Control valve.....................................................................................................80 Water meter......................................................................................................81 One-way light scanner for 10…30 V DC (Telco probe)....................................82 After-sales service.........................................................................................83 12.1 Spare parts.......................................................................................................................83 12.2 Address 85 13 Appendix ........................................................................................................86 13.1 13.2 13.3 13.4 13.5 13.6 13.7 13.8 13.9 13.10 Parameter list MYFC........................................................................................................86 Recipe list MYFC .............................................................................................................87 Parameter list MOZF........................................................................................................88 MYFC-65005 overview ....................................................................................................89 MYFC-65000 dimensional drawing..................................................................................90 MOZF-65000 dimensional drawing standard and hot water version ...............................91 MOZF-65007 dimensional drawing chlorine version .......................................................92 Wiring diagram MOZF......................................................................................................93 Sample taking ..................................................................................................................94 Moisture determination in the laboratory .........................................................................94 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 6 Safety Moisture controller 1 Safety 1.1 Safety of persons • • • 1.2 Safety covers must always be installed and locked. Open or removed safety covers are danger spots for crushing and cutting injuries. Always keep safety devices in good working condition. Safety devices must not be bridged over or put out of operation. Maintenance work at the machine or parts thereof must only take place with the installation at a standstill! Ensure that all power sources such as: – electricity – pneumatics – water are switched off and interrupted. Set service or local switches to «0» and secure with lock against being switched on again. Instructions for the safe use in hazardous areas Operating instructions (section relevant for explosion protection) for MYFC Moisture control unit MOZF Liquids flow controller according to EU guideline 94/9/EG Group II, category 3D 1.2.1 Designated use Use in hazardous areas according to classification II 3D group II, category 3D, operating material for dust atmosphere zone 22 The requirements of standards EN50014 and EN50281-1-1 are fulfilled Marking (see device) II 3D IP55 T=70°C Ta<=55°C Permitted temperature max. 55°C 1.3 Installation / commissioning • • The devices may only be installed, connected and commissioned by qualified personnel. The qualified personnel must have knowledge of types of protection, rules and regulations for operating materials in Ex areas. Check whether the classification (see marking on the device) is appropriate for the application. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Safety 7 1.3.1 Installation instructions / assembly • Avoid static charges on plastic devices and cables. • To avoid static charges, only clean the device with a damp cloth. • Do not install the device in the dust flow. • Avoid dust accumulation on the devices. • Protect devices and cables effectively against damage (e.g. no installation in or near transport routes or crane travel routes). • For connection allocation and electrical parameters, see marking on the device or operating instructions. • Only remove any sealing plugs of cable screw connections or plugs immediately before inserting lines or screwing on socket in order to prevent dirt entering. • Avoid dust deposits in the switch cabinets by keeping them closed wherever possible. If dust has accumulated, clean the cabinets with a suitable vacuum cleaner (EX area). 1.3.2 Special conditions for safe operation • Devices with connection room (cable screw connections) have reduced control cable relief. Sufficient cable relief must be ensured or the cable must be permanently laid. • For devices with connection room, do not disconnect connection leads when energized. • For plug connections, a warning sign must be fitted near the plug connection switch the warning «Do not separate when energized». If available, use the sticker supplied. 1.4 Service / Maintenance No modifications may be made to the device. This also applies to repairs (e.g. no replacement of components with other products). If in doubt, please contact the manufacturer. 1.5 Safety concept The moisture controller MYFC/MOZF is normally part of an installation and therefore integrated into the safety concept of the installation. If the moisture controller MYFC/MOZF is not used within this safety concept, the user has to redefine the risk estimation of the dangers involved and has to take suitable measures. After the initial startup and safety inspection, the CE sign can be mounted and the EC Declaration of Conformity issued (see chapter 6.1). © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 8 Technical data 2 Technical data Moisture controller Housing Protection type IP65 Ambient conditions Temperature (in operation) Temperature (device turned off) Humidity –10…+50 °C –10…+75 °C max. 95 % no condensation Power supply MYFC voltage range MYFC power input 115 V AC / 230 V AC (+10 % / –15 %) 50/60 Hz max. 70 VA MOZF voltage range MOZF power input Compressed air MYFC 85...264 V AC 50/60 Hz max. 70 VA 4...10 bar Air quality: Free of dust, oil and water, dried according to Pneurop 6611 (see also UAS-10030/-10031) Air consumption: 10 l/h Data backup Min. 20 years (battery-buffered RAM) 24 V inputs Power input max. 15 mA 24 V outputs Max. load 200 mA short-circuit-proof. The entire load of the 24 V from external consumers must not exceed 700 mA. Analog output 0/4…20 mA Maximal load resistance 500 Ω (Resolution 800 parts) Analog input 0/4…20 mA Input resistance 150 Ω (Resolution 500 parts) Serial interface RS-485 Bühler Standard Scales Protocol to control system (according to Handbook 66435) or remote control according to Appendix Interference emission EN 50081-1 Class B fulfilled Interference immunity EN 50082-2 Industrial sector fulfilled MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Accuracy MYFC Technical data 9 The MYFC does not replace laboratory measurements. The device measures online the product moisture and reacts to fluctuations in raw moisture. The raw moisture has to be checked periodically. In addition please note that the B1 moisture has to be checked as well. Losses that can occur due to transport or in the silo cannot be corrected by the MYFC. Please note that differences may occur with different product. These differences can be corrected via the recipe parameters. Humidity measurement MYFC At the operation point (AP) the accuracy is ±0.2 %. AP 0.4 % 4 % Flowbalancer After referencing with a check weigher, the accuracy is 2…20 t/h ±0.5 t/h 20…100 t/h ±2.5 % It is to be noted that the reproduceability, which is very important for dampening, is somewhat more accurate. Accuracy MOZF The accuracy of the MOZF depends on the size of the device and the flow line. The device can be calibrated if more accurate dosing is required. (TCON.WCNT) MOZF 315 MOZF 1000 MOZF 2250 MOZF 4500 ± 6 l/h ±20 l/h ±45 l/h ±45 l/h Water quality Water pressure MOZF standard version Hot water version MOZF chlorine version (PVC) © Copyright 2008 Bühler AG See section 9 Chlorine addition max. 50 ppm Water temperature max. 50 °C Chlorine addition max. 50 ppm Water temperature max. 90 °C Chlorine addition max. 600 ppm Water temperature max. 50 °C With very dirty water the optional filter assembly MOZF 82004-81 is to be used. MYFC-MOZF-66542-1-en-0803 10 Description of the dampening system Moisture controller 3 Description of the dampening system 3.1 Structure and application possibilities of the dampening system 3.1.1 Functional description The MYFC/MOZF moisture controller is used to determine the product moisture of wheat. Here it is possible to determine the natural moisture as well as the moisture of tempered wheat (Note standing times). The moisture control system requires no external data in order to be able to calculate the correct amount of water. All necessary parameters are determined by the moisture control unit MYFC. The system can therefore be integrated into any cleaning process. The system basically consists of two machines: The moisture control unit MYFC and the liquids flow controller MOZF. The moisture control unit MYFC continually measures the moisture of the wheat. The measurements are made with the use of microwave measuring technology. The product flows through a bypass (approx. 2 t/h), which is equipped with various sensors. The current moisture of the product is calculated from the microwave signal, the weight in the container and the product temperature. Based upon this current moisture, the pre-set nominal moisture and the current product flow, the MYFC calculates the required water volume, which is transmitted to the water dosing unit. The MOZF then controls the calculated water volume. Wheat MYFC Moisture control unit Nominal value for water l Release MOZF Wheat Dampener (e.g. MOZL) Wheat Liquids flow controller Alarm Water Two MOZF and two dampeners can be connected if required. TCON.MODE = MOIST2 Fig. 3.1 Moisture controller MYFC-MOZF MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Description of the dampening system 11 3.1.2 Control of the moisture This is the normal operation of the moisture control. The user enters a moisture nominal value and the system doses the required water volume to achieve this nominal value. 3.1.3 Percent dampening Only the current product flow and a nominal water value in percent are needed for percent dampening. The system calculates the required water value on the basis of the product flow. This mode of operation is used as a pre- or after-dampening when a defined percentage of water should be added. This mode of operation can be implemented in different ways: • Percent dampening with MYFC • Percent dampening without MYFC Percent dampening with MYFC This mode of operation is used in the following situations. 1. The user would like to add a certain percentage of moisture. This is not recommended, however, since the operation mode of the MYFC must be switched over. 2. There is a problem with the moisture measurement. The level control and the metering slide gate work perfectly. This mode of operation can be switched on temporarily until the problem with the moisture measurement is rectified. The advantage is that the water volume is calculated correctly even when the product flow varies. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 12 Description of the dampening system Moisture controller Percent dampening without MYFC (only MOZF) The percent dampening can be implemented without MYFC, since the moisture determination of the wheat is not required. The MOZF calculates the required water volume. For this the current product flow must be known, however; i.e. one or more dosing elements must be connected to the MOZF. The MOZF then independently totals the sum over all connected dosing or scale elements. This mode should only be used with relay controls. If a control system is available, the MOZF should be operated as a litre dosing device, as the capacity of the check weigher is known to the control system. Functional description MOZF Configuration is very simple. The parameter TCON.CTRL determines how many dosing elements were connected to the MOZF. The MOZF now automatically tests which and how many check weighers are connected to the bus. For percent dampening, only the current flow capacity of the check weighers is relevant. Error messages of the check weighers are not processed. The following faults result in an alarm message: • The number of check weighers is <> TCON.CTRL • The sum of dosing capacities is > TCON.FMAX Wheat Bühler Scale controller or Flowbalancer Product capacity kg/h maximum 32 Dosing or Scale elements Wheat MOZF Liquids flow controller Water Dampener (e.g. MOZL) Wheat Fig. 3.2 Percent dampening with MOZF MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 3.1.4 Description of the dampening system 13 Litre dosing This mode of operation is always switched on at the MOZF. The litre dosing mode is used in the following situations: 1. Only a MOZF is used to pre-set a water volume. No moisture control unit MYFC is available. The water volume is pre-set via an interface or locally at the device. Example: Dampening 1. break flour or B1 2. The product flow measurement of the MYFC does not function, or the connection between MYFC and MOZF is interrupted. In this case the MOZF must be switched over to litre dosing or manual operation. 3.1.5 Manual operation This mode of operation is only necessary when the MOZF does not function. The water volume is set via a tap and can be read at the sight glass. The water flow is stopped as soon as the product detection probe of the dampener is no longer covered or the release is interrupted. In case of a malfunction in the MYFC, the MOZF should be switched over to litre dosing (3.1.4). This allows the MOZF to continue regulating and controlling the water flow. 3.1.6 Formulas QH2O = Qproduct ∗ Qproduct 100% – fnominal = QH2O ∗ fnominal – fraw fraw = fnominal – fnominal = © Copyright 2008 Bühler AG fnominal – fraw 100% – fnominal Legend: QH2O = Dosing rate in l/h Qproduct = Product rate in kg/h fraw = Raw moisture in % fnominal = Nominal moisture in % QH2O ∗ (100% – fnominal ) Q product Qproduct ∗ fraw + QH2O ∗ 100% Q product + QH2O MYFC-MOZF-66542-1-en-0803 14 Description of the dampening system Moisture controller 3.2 Electrical connections 3.2.1 Moisture controller MYFC/MOZF (Standard wiring) MYFC Moisture measuring unit 0 lb kg MEAF F 115 / 230 V AC 70 VA X11 L1 N PE 1 2 3 4 on off Compressed air 4...10 bar X53 SIO2+ X53 SIO2– X53 Shield S6 MOZF Water dosing unit 0 Interface cable RS-485 twisted and shielded lb kg MEAF F 1 2 3 4 on off 85...264 V AC X7 SIO+ X7 SIO– S3 X101:L X101:N X101:PE X101:7 Alarm X101:6 0V 24 V Alarm signal 0 V = Alarm Release 24 V 0.5 A Water dosing unit X101:9 Release 24 V X101:8 0V X101:11 Valve Flow-Detect-Probe MOZL X101:4 24V X101:5 Signal X101:6 0V X101:10 0 V Water shut-off valve MOZL (24 V / 3 W) Fig. 3.3 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 3.2.2 Description of the dampening system 15 Moisture controller MYFC-MOZF (supplementary wiring) MYFC Moisture measuring unit 0 lb kg MEAF F 0/4…20 mA input nominal moisture X54 AI+ X54 AIShield HOST interface RS-485 X7 SIO+ X7 SIO– Shield Profibus interface X20 X2 DO4 X2 0V 24 V weight pulse X8 AO+ X8 AOShield 0/4…20 mA output configurable Actual moisture or product rate t/h X52 24V X52 0V X52 SIO3+ X52SIO3– Shield Remote control built-in or cabinet version 0 lb kg MEAF F MOZF Water dosing unit 0 MEAF lb kg F 0/4…20 mA input nominal value water flow rate (only when MOZF used without MYFC) X19 AI+ X19 AI– Shield X2 DO4 X2 0V 24 V water pulse X19 AO2+ X19 AO2– Shield 0/4…20 mA output water flow rate l/h X17 24V X17 0V X17 SIO2+ X17 SIO2– Shield Remote control built-in or cabinet version 0 MEAF lb kg F Fig. 3.4 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 16 Description of the dampening system 3.2.3 Percent dampening with MOZF Moisture controller MOZF Water dosing unit 0 MEAF lb kg F 0/4…20 mA input nominal value percent (optional) Profibus interface (optional) HOST interface RS-485 (optional) or remote control (optional) 0 MEAF lb kg X19 AI+ X19 AI– Shield X20 X2 DO4 X2 0V 24 V weight pulse X19 AO2+ X19 AO2– Shield 0/4…20 mA output water flow rate l/h 1 2 3 4 on off X7 SIO+ X7 SIO– Shield S4 X17 SIO2+ X17 SIO2– Shield X6 24 V X6 0 V Maximum 32 control units Bühler dosing or scale elements F It is not possible to use a remote control if the HOST-interface is used! The addresses may be defined at will! X101:L1 85...264 V AC 70VA X101:N X101:PE Release 24 V 0.5 A Water dosing Flow-DetectProbe MOZL X101:7 Alarm X101:6 0 V 24 V alarm signal 0 V = alarm X101:9 Release 24 V X101:8 0 V X101:11 Valve Water shut-off valve MOZL (24 V / 3 W) X101:4 24 V X101:5 Signal X101:6 0 V X101:10 0 V Fig. 3.5 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 3.2.4 Description of the dampening system 17 Litre dosing with MOZF MOZF Water dosing unit 0 MEAF lb kg F 0/4…20 mA input nominal value water (optional) X19 AI+ X19 AI– Shield Profibus interface (optional) X20 HOST interface RS-485 (optional) X7 SIO+ X7 SIO– Shield X2 DO4 X2 0 V 24 V weight pulse X19 AO2+ X19 AO2– Shield 0/4…20 mA output water flow rate l/h X17 24 V X17 0 V X17 SIO2+ X17 SIO2– Shield Remote control built-in or cabinet version 0 MEAF lb kg F X101:L1 85...264 V AC 70 VA X101:N X101:PE Release 24 V 0.5 A Water dosing Flow-DetectProbe MOZL X101:7 Alarm X101:6 0 V 24 V alarm signal 0 V = alarm X101:9 Release 24 V X101:8 0 V X101:11 Valve Water shut-off valve MOZL (24 V / 3 W) X101:4 24 V X101:5 Signal X101:6 0 V X101:10 0 V Fig. 3.6 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 18 Description of the dampening system Moisture controller 3.2.5 Moisture control MYFC with MOZE (special application) The MYFC can also be operated with a liquid flow control MOZE. Differences exist only in the lock. The product probe of the dampener must be linked in the system control directly with the release function. The supplementary functions of the MYFC are all present. See 3.2.2 Moisture controller MYFC-MOZF (supplementary wiring) MYFC 115/230 V / 70 VA X11 L1 0 lb kg MEAF F N PE Alarm X2: DO 1 X2: 0 V 1 2 3 4 Compressed air 4…10 bar 24 V alarm signal 0 V = alarm on off S6 X53 SIO2+ X53 SIO2– X53 Shield Interface cable RS-485 twisted and shielded 115/230 V / 70 VA X12 = B X13 = B X14 = B L N PE Release 24 V Water dosing Comp. air 4…8 bar I = 300 mA 24 V / 9 W X4:1 +RS-485 X4:2 –RS-485 MOZE Water dosing unit X9:2 Release 24 V X9:3 0 V Water shut-off valve Fig. 3.7 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 3.3 Description of the dampening system 19 Remote control The remote control can be connected at any time. The remote control allows all functions and displays present on the device. The remote control can be connected to the MYFC and the MOZF. If there is an MYFC with remote control, no remote control is needed for the MOZF since the current water flow and error messages of the MOZF are already displayed on the MYFC. If the MOZF is used for percent dampening or litre dosing, a remote control is useful. 3.3.1 Built-in version 246 216 Order No. see spare parts catalog 7952 Protection type Foil IP65 Depth 40 mm 165 75.5 135 Mains supply 24 V DC from MEAF max. 100 mA 75.5 8 holes 6 mm Front cut-out 116 116 Fig. 3.8 3.3.2 Table/wall version 49 310 200 2 slots in the rear wall for wall mounting Order No. spare parts catalog 7952 Protection type IP65 244 Weight approx. 4 kg Height upper rear approx. 65 mm Height lower front approx. 45 mm Mains supply 24 V DC from MEAF max. 100 mA Fig. 3.9 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 20 Description of the dampening system Moisture controller 3.3.3 Remote control connection to MYFC MYFC EBD1293 Remote control 1234 S5 S5:1=ON S5:2=ON S5:3=ON S5:4=OFF Shield SIO+ SIOCOM 24 V 0V X52:1 X52:2 X52:3 X52:4 X52:5 X52:6 RS485 green yellow brown white X2:1 Shield X2:2 X2:3 X2:4 X2:5 + X2:6 – X1:1 X1:2 0 V X1:3 +24 V Cable UXE-30605-302 max. length 1000 m X61 RS232 SYS.DISP see description 12345678 S9 S9:1 = OFF S9:2 = ON S9:3 = OFF S9:4 = OFF S9:5 = OFF S9:6 = OFF S9:7 = ON S9:8 = OFF Fig. 3.10 3.3.4 Remote control connection to MOZF (Litre dosing or with MYFC) MEAF IO-Extension Remote control 1234 S4 S4:1 = ON S4:2 = ON S4:3 = ON S4:4 = OFF Shield SIO2+ SIO2COM +24 V 0V X17:1 X17:2 X17:3 X17:4 X17:5 X17:6 green yellow brown white X2:1 Shield X2:2 X2:3 X2:4 X2:5 + X2:6 – X1:1 X1:2 0 V X1:3 +24 V Cable UXE-30605-302 max. length 1000 m SYS.DISP see description 12345678 S9 S9:1 = OFF S9:2 = ON S9:3 = OFF S9:4 = OFF S9:5 = OFF S9:6 = OFF S9:7 = ON S9:8 = OFF Fig. 3.11 3.3.5 Remote control connection to MOZF (Percent dampening) MEAF Base PCB Remote control 1234 S3 S3:1 = ON S3:2 = ON S3:3 = ON S3:4 = OFF Shield SIO+ SIOCOM X7:1 X7:2 X7:3 X7:4 24 V X6:1 X6:2 X6:3 X6:4 0V SYS.DISP see description green yellow brown white Cable UXE-30605-302 max. length 1000 m X2:1 Shield X2:2 X2:3 X2:4 X2:5 + X2:6 – X1:1 X1:2 0 V X1:3 +24 V 12345678 S9 S9:1 = OFF S9:2 = ON S9:3 = OFF S9:4 = OFF S9:5 = OFF S9:6 = OFF S9:7 = ON S9:8 = OFF Fig. 3.12 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 4 Transport 21 Transport Note: The transport must only be handled by persons who are familiar with and trained for this task. 4.1 Handling with a crane A crane can be used to unload and transport the equipment. Caution: The hoisting gear has to be checked for the required design and the permissible load capacity. The moisture control unit must only be lifted with the transportation safety device installed by Bühler. Attach the ropes only at the eyebolts provided for this purpose. Fig. 4.1 4.2 Transport weights and volumes Note: Generally the transport weights in the shipping papers apply and have to be observed! © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 22 Installation Moisture controller 5 Installation 5.1 Location Note: When adjusting the height of the device, be sure that the overflow container does not rest on the Flowbalancer, but rather hangs at the upper table board (otherwise the metering slide gate scrapes on the inlet spout in the Flowbalancer). • • • • First tighten the transport safety screws by hand. Then screw the eyebolts into the upper table board and hang the MYFC on a crane. Now the lateral screws on both table boards (upper and lower boards) can be loosened. The machine can now be moved down by lowering the crane. The control unit must be mounted free from vibration on a solid floor or on the ceiling. Supply and discharge elements/machines may not be screwed to the control unit. Select the place of installation for the unit so that the electronics are not exposed to direct sunlight. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Commissioning 6 Commissioning 6.1 Checklist for verifying EU conformity 23 The following items must be checked prior to commissioning of the machine: 1. The operator has been informed that the operating instructions must always be accessible to the personnel and that is he is responsible for instructing the personnel. 2. Assembly and installation have been carried out according to the operating instructions. 3. If erected in an Ex-zone, the machine must be earthed properly. 6.2 Initial start-up MYFC 6.2.1 Setting the parameters The following points must be checked before start-up: 1. Remove the transportation safety device of the measuring container (yellow-headed screws). 2. TCON.FMAX The maximum cleaning capacity + approx. 20 % must be set. This value should not be too large, since the level control reacts differently at a setting of 2 tons than at 60 tons. 3. TCON.T1 This time determines the maximum delay between the release and the detection of the product in the MYFC. See 10.2 4. TCON.T2 This determines the maximum time the product needs from the MYFC to the dampener. Set the time with adequate tolerance (+100 %). If there is no flow detection probe, deactivate the monitoring with 0. See 10.2 5. Settings only when a control system is present. Set the parameter SYS correctly according to the wiring. See 8.5.5 Set the parameter HOST correctly. See 8.5.7 6. Settings only when a MEAF remote control is available. Set the parameter SYS.DISP correctly. See 8.5.5 7. Settings of the recipes with valid starting values Load at least Recipe 0 with valid values. See 8.5.3 8. Checking the mechanics The following points must be checked: – The measuring container must be center-mounted and hang freely. – The level measuring rod must turn freely. – The MZAH slide may not touch even when completely open. 9. Checking the sensors The sensors are aligned during manufacture. A brief check of the values and zero points is recommended, however. A new alignment need not be made. ADC.ZFLO Zero point of the MZAH ADC.ZNIV Zero point of the level control ADC.ZWT Zero point of the measuring container ADC.EXT Ambient temperature © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 24 Commissioning Moisture controller The following settings must be checked when the product is dosed: 1. The throttle flap for the measuring container must be set correctly. At the normal rate the product should need approx. 10 seconds to flow through the sight glass. This amounts to a flow rate of approx. 1.5 t/h. For very low flow rates < 3 t/h a flow time of approx. 15 seconds should be selected. The adjustment is made with the two adjusting screws. Upper screw clockwise => product quantity is decreased Lower screw clockwise => product quantity is increased ca. 10 10 approx. Sekunden seconds Fig. 6.1 2. Check the inlet aspiration. The inlet aspiration should be approx. 3…5 m³/min. 3. Check the outlet aspiration. The outlet aspiration may be a maximum of 2 m³/min. Check for secondary air at the dampener. This can otherwise lead to major measurement errors. 4. Take a product sample and adjust the moisture offset in the corresponding recipe. REC.OFFS 5. Check the flow capacity of the MZAH (reference check weigher or capacity measurement). If large deviations occur, the alignment and the mechanics of the baffle plate must be checked. The output can be adapted with parameter TCON.FCOR. Note: The inlet and outlet aspiration values must be strictly adhered to. Incorrect air volumes can influence the measurement. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 6.2.2 Commissioning 25 Alignment of the measuring container 1. Ensure that the measuring container is empty. If necessary, open the metering slide gate with the pneumatic push button. 2. Set the calibration switch to the CAL position. 3. For the zero adjustment change to the ADC.ZWT menu and press the F-key. SET appears during the weight acceptance and after the adjustment 0 is displayed. Fluctuations of ±50 grams are normal. 4. Attach one of the supplied 3 kg reference weights to the hook of the measuring container. Fig. 6.2 5. Change to the parameter ADC.CWT and press the F-key. SET appears and after the adjustment 3.000 is displayed. 6. Change to the parameter ADC.WT and check the display. With the reference weight 3.000 kg and without the reference weight 0 must be displayed. Fluctuations of ±50 grams are normal. 7. Set the calibration switch to the RUN position. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 26 Commissioning Moisture controller 6.2.3 Alignment of the level measurement 1. Set the calibration switch to the CAL position. 2. Check the following points: Open the metering slide gate with the pneumatic push button if necessary. – Ensure that the product measuring rod is not covered with product – The rod must be able to turn freely – The rod is not to be jammed 3. Change to the parameter ADC.ZNIV and push the F-key. SET appears during the weight acceptance and after the adjustment 0 is displayed. 4. Set the calibration switch to the RUN position. 6.2.4 Alignment of the Flowbalancer MZAH 1. Set the calibration switch to the CAL position. 2. Change to the parameter ADC.ZFLO and push the F-key. SET appears during the weight acceptance and after the adjustment 0 is displayed. 3. Place both supplied 3 kg reference weights on the baffle plate left and right at the indicated mounting points. Fig. 6.3 4. Change to the parameter ADC.CFLO and push the F-key. SET appears during the weight acceptance and after the adjustment 6.000 is displayed. 5. Change to the parameter ADC.ZFLO and check the display with and without reference weights. 6. Set the calibration switch to the RUN position. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 6.2.5 Commissioning 27 Alignment of the temperatures Alignment of the internal cabinet temperature measurement CINT 1. Set the calibration switch to CAL position. 2. Set Jumper X60 to CAL position (see 8.3.3 Auxiliary board EBD1293). 3. Change to parameter ADC.CINT and press the F-key; SET appears now on the display. 4. Re-set Jumper X60 to RUN position. 5. Change to parameter ADC.INTT. The correct temperature (± approx. 3 °C) must be displayed. 6. Set the calibration switch to RUN position. Alignment of the external product temperature measurement CEXT 1. Set the calibration switch to CAL position. 2. Set Jumper X62 to CAL position (see 8.3.3 Auxiliary board EBD1293). 3. Change to parameter ADC.CEXT and press the F-key; SET appears now on the display. 4. Re-set Jumper X62 to RUN position. 5. Change to parameter ADC.EXTT. The correct temperature (± ca. 3 °C) must be displayed. 6. Set the calibration switch to RUN position. Note: It is possible to adjust the temperature more precisely. However, this does not have any effect on the accuracy of the measurement, as only temperature changes are relevant. For this the temperature must be measured with a temperature gauge. The measured value can now be entered for the corresponding parameter CINT or CEXT. Then press the F-key (X62 / X60 remain on RUN) and the temperature now corresponds to the measured value. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 28 Commissioning Moisture controller 6.2.6 Alignment of the microwave unit 1. Set the calibration switch to the CAL position. 2. Be sure that the internal temperature measurement is adjusted. CAL INTT appears on the display if the temperature is outside of the tolerance. Check the parameter ADC.INTT. The cabinet temperature must be displayed (± approx. 3 °C). If the display is not correct, make alignment 6.2.5. 3. Check SVV parameter. The settings must correspond to the data on the microwave module. 4. Connect the supplied reference resistor. Fig. 6.4 5. Change to parameter ADC.CHF and press the F-key. SET appears and after adjustment 10.00 dB is displayed. 6. Remove the reference resistor and fasten the plugs again correctly. No force is to be exerted on the measuring container. The cable must be connected horizontally. Fig. 6.5 7. Change to parameter ADC.ZWT and check the zero point. If necessary, repeat alignment 6.2.2. 8. Set the calibration switch to the RUN position. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Commissioning 29 6.3 Initial start-up MOZF 6.3.1 Venting the system To guarantee the function of the MOZF from the beginning, the system must be vented and the pressure reduction valve correctly adjusted. See section 9.1 1. Turn the Manual / Automatic selector to vertical position so that the water can flow through the sight glass. 2. Lay the test and service connection so that the water can be drained through the hose connection into a container. 3. Open the water tap completely. 4. The MOZF can be tested with the parameter SERV.VA. As soon as a litre value is stipulated there, water dosing starts immediately. Independently of the release, the product probe and serial nominal values. 5. Vent the water filter and activate the relay manually again. 6. After venting, return the Manual / Automatic selector to the horizontal position so that the water can flow through the control valve and water meter. Set the test and service connection to the original position. The MOZF is now ready to dose water. 6.3.2 Checking the release and product probe The MOZF is locked via the signals of the release and the product probe. The signals must be checked so that the unit can start correctly. 6.3.3 MOZF as percent dampening 1. Set the parameter SYS.REM. See 9.3.5. 2. If there is a serial HOST-connectivity, set the parameter HOST correctly. See 9.3.4. 3. Set the parameter TCON.CTRL to the correct number of connected dosing elements. If no addresses have been defined for the dosing elements, then each device must be set with a different address. If the number is entered incorrectly, ERR 17 HSTI appears. 4. Set the parameter TCON.FMAX correctly. This parameter defines the limit value of the sum of all dosing elements. If the sum exceeds this value, an ERR 63 FMAX is given. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 30 Commissioning Moisture controller 6.3.4 Alignment of the water meter If the water volume must be corrected, the parameter TCON.WCNT must be adjusted. The measurement must be made at the operating point. Fluctuations occur with very small dosing volumes. Note: Do not use the water feed rate for the correction; work instead with the total sum counter (see SERV.VA from Version 26A onwards or Σ3). This prevents temporary control deviations from leading to a miscalculation! The following calculation can be used for the correction. TCON.WCNTnew = nominal value ∗ TCON.WCNT Value _ measured Example: A water volume of 95 litres instead of 100 litres was measured. The new value can be calculated as follows: TCON.WCNTnew = MYFC-MOZF-66542-1-en-0803 100 ∗ 105.7 = 111.3 95 © Copyright 2008 Bühler AG Moisture controller Operation 7 Operation 7.1 Display operation 31 The devices MYFC and MOZF have an identical operation. This chapter addresses the elements which are present in both devices and which are relevant for the operation of the moisture control system MYFC/MOZF. Joint flashing: calibration switch = CAL 1 2 3 4 5 6 7 0 FLO lb kg 123.456 F 14 13 12 11 10 9 8 Fig. 7.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 © Copyright 2008 Bühler AG Operation mode, Local / Remote (LED ON) Operation Metering slide gate opens Metering slide gate closes Zero alignment Tolerance reached Weight unit in lb or kg Display of the parameters with code and value «Minus» key previous parameter «Plus» key next parameter «Enter» key data entry «Arrow» key next parameter group «F» key special function depending on parameter Lamp test key and clear alarm MYFC-MOZF-66542-1-en-0803 32 Operation Moisture controller 7.1.1 Changing parameters longer than 1 sec. (until decimal point is flashing) 1. Press 2. , increases or decreases the value, or select the decimal place to be changed with 3. Press 7.1.2 briefly (until decimal point is not flashing anymore) Selecting parameters Operating parameters ↑ ↓ >1s + >1s 1 2 ) ) Parameter groups (configuration) REC TCON SYS ADC HOST SERV SVV PROD ↑ ↓ 1 Operating parameter → Parameter groups Press and together for more than 1 second 2 Parameter groups → Operating parameter Press for more than 1 second ) Change ) Change MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 7.2 Operation 33 Display and status messages (MYFC and MOZF) In order of importance the most important statuses are displayed. These displays are only active when the MYFC has been stopped or there is no product flow. Status text Condition for display No display. Only the decimal point on the right side is flashing The device has been inactive for 30 min. The display reappears as soon as – the device is activated – a key is pressed • MYFC The dosing release is available but no product flow is measured. • MOZF No dosing release is available. * STOP * There is no water dosing release * WAIT * • MYFC Dosing release available, but no product in the MYFC detected. • MOZF as litre dosing The dosing release is available, but no set point given. • MOZF as percent dampening The dosing release is available, but no product has been detected. * MANUAL * The local switch of the MOZF was switched to manual operation. EMPTY MYFC as dosing device → no product in the MYFC WAIT FLOWD Wait until the flow detect probe has reacted LOW SETPOINT The nominal moisture value is lower than the actual value DISCHARGE The rest discharge was activated. (Input DI 2) * LOCAL * Display MOZF The MOZF was switched to LOCAL! * LOCAL MOZF * Display MYFC Standard display MYFC If no key is pressed for more than 5 minutes, the display changes automatically to the standard display selected by the user. For the possibilities of this standard display, see parameter SYS.SD chapter 8.5.5 Standard display MOZF If no key is pressed for more than 5 minutes, the display changes automatically to the display of the current water dosing rate. For the possibilities of this standard display, see parameter SYS.SD chapter 9.3.5 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 34 Operation Moisture controller 7.3 Offset and nominal value adjustment of the moisture The correct setting of the nominal moisture and the moisture offset is essential for the operation of the device. The B1 moisture is of great significance for optimal grinding. With the MYFC the moisture is regulated in a storage cell before filling. Various influences can change the moisture of the wheat after dampening: • Temperature and relative humidity • Long transport distances to the storage cell • Conveyance by means of suction pneumatics • etc. These influences can change daily. Thus it is essential that the B1 moisture be checked. There are basically two possibilities for calibrating the MYFC: 1. The moisture of the dry wheat is measured and if there are deviations from the display of the MYFC, the offset value is corrected. 2. The moisture of the stored wheat is determined and if there are deviations, the moisture nominal value is adjusted. 7.3.1 Adjusting the offset value This adjustment must be made at the commissioning. The moisture of the dry wheat is measured and compared with the actual moisture value of the sample taken. If there are differences, the offset value is corrected accordingly. REC.OFFS = Lab value – MOIST at the sample-taking The adjustment of the offset value corrects only the errors at the moisture measurement. Water losses which occur after dampening must be corrected with the moisture nominal value. 7.3.2 Adjusting the moisture nominal value This value determines which value is used for dampening by the dampener. Losses through transport etc. must be adjusted by changing the nominal value. The setting can be made in the main menu parameter MOIST, or when recipes are used, in the menu REC.MOIS. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Description of the MYFC Moisture Control 8 Description of the MYFC Moisture Control 8.1 Mechanics 35 The product stream is divided in the inlet. The main stream goes into the product surge and approx. 2 t are fed directly into the microwave measuring channel. There must always be some product in the product surge so that the Flowbalancer MZAH can measure precisely. The level control ensures that the upper surge is always half full. Inlet 2…60 t/h Inlet aspiration Operation and display Microwave measurement Product depot with level control Control MEAF Product volume setting in measuring container Button for emergency opening of the metering slide gate Electrical connections Flowbalancer MZAH Compressed air connection Outlet with hopper Fig. 8.1 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 36 Description of the MYFC Moisture Control 8.2 Schematic diagram Moisture controller The product is divided in the inlet. The main stream flows to the left into the upper product surge bin. The bypass stream (approx. 2 t/h) flows through the measuring container, where the moisture is determined by means of microwaves. The product surge bin is needed for the flow measurement. The Flowbalancer MZAH must always be fully supplied for a precise measurement. This is achieved with a level control, which ensures that the product surge bin is always half filled with product. Aspiration Product Fig. 8.2 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 8.3 Control 8.3.1 Overview Description of the MYFC Moisture Control 37 The control takes over all measuring, checking and control functions. The MEAF standard control serves as the basis. Reference resistor Microwave module Display board MEAF Torque key Auxiliary board MYFC Motherboard (MEAF) Fig. 8.3 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 38 Description of the MYFC Moisture Control Moisture controller 8.3.2 Control unit MEAF with MYFC auxiliary board EBD1293 variant Basic print RAM/BATTERY EPROM S2 a 24 V DC 100…240 V AC { RUN CAL } MYFC auxiliary board EBD1293 1 2 3 4 S6 X60 A B S5 X50 X51 X52 X53 X54 X55 X56 F3 b } A B A B X11 S3 X1 1 2 3 4 X42 X41 X9 X2 X3 X4 X5 X6 X7 X8 Fig. 8.4 a b EPROM S2 S3, S5 S6 X41, X42 X60, X62 X61 F3 Mains supply (AC/DC converter) Mains voltage connection 100…240 V AC to X11 See Appendix on mains supply for wiring details Program component: To change the program, the EPROM must be lifted carefully with a screwdriver out of the socket. Caution: The notch must face to the left! Calibration switch: RUN = released for operation / CAL = calibration mode Settings for RS-485 host interface: (Detail see operating instructions «Description of the serial interface RS-485») Settings for RS-485 interface to the MOZF (all switches are activated) X41, X42 Position A Alignment for temperature measurement Position B = RUN Setting Position B = RS-485, Position A = RS-232 only for service purposes Miniature fuse 1.25 A slow-blow as 24 V input fuse Note: There are two design variants of supply units. The new version illustrated above and the version for MYFC delivered before October 2004. The old versions are equipped with the supply unit EBD1269 (Printed circuit board with black transformer)! A conversion set is available (UVV 00031624). The advantage of the conversion is simplified stockkeeping of spare parts. The MOZF uses the same supply unit as the MYFC. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 8.3.3 Description of the MYFC Moisture Control 39 Auxiliary board EBD1293 This auxiliary board converts all relevant signals for the operation of the MYFC. X62 Temperaturabgleich External temperatureExtern alignment S6 Busabschlusseinstellungen Bus terminator settings SIO2SIO2 S5 Busabschlusseinstellungen Bus terminator settings SIO3SIO3 LED 15V I.O. X61 Umschaltung RS232 / RS485 SIO3 Switchover RS232 / RS485 forfür SIO3 X60 Temperaturabgleich internal temperature Intern alignment Fig. 8.5 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 40 Description of the MYFC Moisture Control 8.4 Electrical connections Connection Terminals X11 +24 V AC 85...264 V L1 N PE Moisture controller DC 24 V Highfrequency circuit 0V EBD 1231 3 2 1 0V 0V 15V X58 X1 24V 0V 1 2 3 X59 DO 1 DO 2 DO 3 DO 4 DO 5 0V 1 2 3 4 5 6 DO 6 0V DO 7 0V DO 8 0V 1 2 3 4 5 6 Valve 3 X4 24V DI 1 DI 2 DI 3 DI 4 0V 1 2 3 4 5 6 24 V 24 V = Release TCON.MODE = DOSING 24 V = Rest discharge n.u. n.u. 0V X7 Shield SIO+ SIOCOM 1 2 3 4 X8 Shield 1 2 AO+ 3 AO- X2 X3 Shield Sense+ OUT+ X9 IN+ INOUTSense- 1 2 3 4 5 6 7 Alarm 24 V = Release for water dosing n.u. 24 V Volume pulse X57 X50 Valve 1 Valve 2 +15V 0V 0V n.u. n.u. Shield Serial interface RS-485 to Host Analog output 0/4…20 mA Actual capacity/actual moisture or nominal value water SYS.AO transparent DMS baffle plate MZAH 4-line DMS EBD 1268 MEAF DO = Digital Output (24 V output) n.u. = not used X59 X58 1 2 3 4 5 6 9-Pol SUB-D RS-232 Service interface Jumper X61=RS-232 Use zero-modem cable (crossed) TXD 3 X51 RXD 2 GND 5 Valve 4 green white red black X57 X52 Shield SIO3+ SIO3COM 24V 0V 1 2 3 4 5 6 X53 Shield SIO2+ SIO2COM 24V 0V 1 2 3 4 5 6 X54 AI+ AIShield T2+ T2Shield 1 2 3 4 5 6 Serial interface for remote display X61=RS-485 Serial interface to MOZF 0/4…20 mA SYS.AI 0V PT 100 + brown PT 100 – white Shield OUT+ IN+ X55 INCOM 1 2 3 4 5 blue/green white red black/grey DMS measuring container Shield OUT+ X56 IN+ INCOM 1 2 3 4 5 brown green yellow white DMS level measurement EBD 1293 MYFC-Extension Fig. 8.6 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Description of the MYFC Moisture Control 8.5 Parameters 8.5.1 Overview of main menu User defined This display can be defined by the user. The device switches after 5 minutes automatically to the selected parameter. See SYS.SD 8.5.5 Parameter group SYS MOIST 12.3 % MOISTS 12.3 % Nominal moisture or actual moisture. As soon as the Enter key is pressed, the nominal moisture can be entered. H2O 123 l/h Actual water volume of the water dosing element FLO 1.442 t/h Actual product throughput in tons per hour ∑1 123456 Erasable total volume of product in kg With the F-key the meter can be deleted ∑2 123456 Non-erasable total volume of product in kg ∑3 123456 Erasable total volume of water in litres or m³ With the F-key the meter can be deleted. ∑4 123456 Non-erasable total volume of water in litres or m³ LOAD 0 Load current recipe and new recipe. 41 Examples: *1* > 0 Recipe 1 is active (*). Recipe 1 was loaded into work recipe 0 and both recipes are identical. 1 > *0* Recipe 0 is active (*). Recipe 1 was loaded but adaptations were made in recipe 1 or recipe 0. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 42 Description of the MYFC Moisture Control 8.5.2 Overview of general parameters Moisture controller REC Recipes TCON Type-specific configuration SYS System configuration ADC AD converter HOST Ser./ Profibus host interface SVV Current predistortion PROD Product group REC Recipe number MODE REM ADR Address FMAX Max. flow FBAL DISP Remote control FCOR Capacity correction MZAH T1 Monitoring time Release T2 Monitoring time MOZL QMIN Minimum dosing rate QMAX Maximum dosing rate AINV Alarm output A1 Actual curve parameter B1 Actual curve parameter C1 Actual curve parameter A2 Actual curve parameter B2 Actual curve parameter C2 Actual curve parameter P Phase PROD Product group MOIS Nominal value moisture PROD Product group FLO Actual product flow ZFLO Zero Alignment FBAL CFLO Ref. Alignment FBAL NIV/NIVS 20 Actual value level ZNIV 12 Zero Alignment Level WT Actual weight OFFS Offset moisture DMAX Maximum dosing rate IMP Weight pulse AO Analog output AI Analog input SD StandardDisplaySelection INIT Basic initialization BAUD Baud rate TOUT Timeout ZWT Zero alignment container CWT Ref. alignment container INTT Internal temperature CINT Ref. alignment Internal temperature EXTT External temperature CEXT Ref. alignment External temperature HF Actual attenuation CHF Ref. alignment attenuation CAL0 Calibration value CAL1 Calibration value CAL4 Calibration value CAL5 Calibration value CALT Temperature coefficient Note: The menu SERV can be found on page 68. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 8.5.3 Description of the MYFC Moisture Control 43 Parameter group REC Code Parameter group REC (Recipe) Input range REC Recipe number This setting determines which recipe can be edited. This setting has no influence on the LOAD parameter in the main menu. MOIS Nominal value moisture This is the current nominal value for the moisture. 0…25 % [0] PROD Product group This value allows the use of various calibrations. This can be very useful for special applications. The correction values for the corresponding product number can be found in MENU PROD. (CAL0,CAL1,CAL4,CAL5). For wheat use the calibration 0! OFFS 0…20 [0] Offset moisture This is the offset value of the moisture. Here a correction can be made if the actual moisture MOIST deviates from the laboratory determination. DMAX Maximum dosing rate The maximum dosing rate limits the water flow. This is a monitoring and safety function. If the calculated water flow increases excessively, an alarm 66 DMAX is triggered and the water flow is stopped. 0…9 [0] –99.99…99.99 % [0] 0…TCON.QMAX litre [4500] Note: Recipes are necessary when the MYFC is used as the first and second dampening or the product variety changes extensively. (Hard and soft wheat) Note: When recipes are changed, the change is not effected until the recipe is loaded in the main menu with LOAD! © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 44 Description of the MYFC Moisture Control Moisture controller Recipe 0 Recipe 0 has a special significance. This recipe is called an operating recipe because it is always active. Changes made in the main menu are always integrated into Recipe 0. When the nominal moisture is adjusted in the main menu, the value REC.MOIS[0] is changed accordingly. Recipe 0 is thus used in two cases: 1. The user is working without recipe settings 2. The user would like to change the settings only temporarily and not store these changes. Recipe 1…20 These recipes are needed to optimize the moisture measurement. When very different products should be dampened, e.g. hard and soft wheat, the accuracy can be improved with the recipe settings. Note that the MYFC works very accurately to a point of ±2 % moisture with the same product; therefore no recipes are required. In addition, the safety of the dampening can be improved because an alarm is triggered with the limit value DMAX as soon as the required water volume becomes too large. This can have various causes: • There was no first dampening • The product rate is too high • The nominal value was set too high • The MYFC is measuring incorrectly Recipe administration if the MYFC is connected to a control system If the device is connected to a control system, the administration of the recipe data should take place at the level of the control system. In this case the recipes are only displayed and cannot be changed! It is only possible to change the recipes when the parameter SYS.REM is set on LOC or REMA. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 8.5.4 Description of the MYFC Moisture Control 45 Parameter group TCON Code Parameter group TCON (Type-specific configuration) Input range MODE The operational mode of the moisture control MOIST…%-DOS [MOIST] MOIST = Moisture control on the entered nominal value %-DOS = Percent dampening based on product flow rate Special case when two dampeners and therefore also two liquids flow controllers MOZF are connected. The water capacity is divided 50 % \ 50 % between the two devices. MOIST2 = Moisture control to the set nominal value %-DOS2 = Percentage dampening due to product flow rate DOSING = The MYFC operates as a dosing device with a full inlet. Input DI 1 is used as a release input. The flow rate can be set with the parameter TCON.FMAX CALC = The MYFC operates as a moisture control unit without MOZF The nominal value can still be set and the water quantity is calculated and can be issued at the analog output AO. This setting determines the operational mode of the control. For normal operation the MOIST setting is always used. The %-DOS setting is only selected when the moisture measurement is not functioning properly. FMAX Maximum flow of the Flowbalancer This value must be adapted to the cleaning rate so that downstream devices are not overloaded. Standard value: Maximum cleaning value +20 % FCOR Output correction factor (100.0 = no correction) Correction factor FCOR = Reference / MZAH FLO x 100 T1 T2 QMIN 1.000…999.999 t [60.000] 70.0…130 % [100 %] Monitoring time of the release The setting of T1 determines how much time is allowed between the dosing release and the arrival of the product at the MYFC. See 10.2 Locking the product probe MOZL (ERR63 FLOWD) 0…9999 seconds [3600] Monitoring time of the product probe of the dampener. The setting of T2 determines how much time is allowed until the product probe at the dampener detects the product dosed from the MYFC. This guarantees that the product probe is adjusted correctly and ensures that the product does not remain dry. This value must be adjusted in the system, since delays between the MYFC and the moisture unit can vary from cleaning process to cleaning process. See 10.2 Locking the product probe MOZL (ERR63 FLOWD) 0…9999 seconds [300] Minimum permissible dosing rate With this value the minimum water rate is determined. If the actual value is lower than this setting, the water is stopped. This setting serves to monitor the system. If the actual water value is too low, this can have various causes. The product moisture is being measured incorrectly or the product flow meter is measuring incorrectly. See (ERR65 QMIN) © Copyright 2008 Bühler AG 0 = monitoring deactivated 0 = no product probe connected to the MOZF X1:5 0…QMAX [0] MYFC-MOZF-66542-1-en-0803 46 Description of the MYFC Moisture Control Code Parameter group TCON (Type-specific configuration) QMAX Maximum permissible dosing rate (device limit) This value determines the editing limits of the maximum water dosing rate. The setting should be adjusted to the liquids flow controller. 315 for MOZF315 1000 for MOZF1000 etc. Moisture controller Input range [QMIN…6500] litres [4500] With this the value set at the parameter REC.DMAX is limited to the QMAX value. Note that the (ERR66 DMAX) is not related to this QMAX but to the parameter REC.DMAX, which can be set according to the recipe. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 8.5.5 Description of the MYFC Moisture Control 47 Parameter group SYS Code Parameter group SYS (System configuration) Input range REM LOC REMS REMA REMP = The nominal values are set locally = The nominal values are serially (RS-485) adjusted = The nominal value is adjusted by a 0…20 mA signal = The nominal values are serially (Profibus) adjusted LOC…REMP [LOC] DISP OFF LOC REM BOTH = The remote control is turned off = Local control (remote control displays only) = Remote control = Both local and remote control LOC…BOTH [OFF] AINV Invert alarm output DO 1 ON = 0 V is an alarm (fail-safe in case of wire breakage) OFF = 24 V is an alarm ON…OFF [ON] IMP Weight pulse The setting determines the size in [kg] of the 24 V weight pulse of the output (DO 4). Note that the setting must be made correctly. A pulse always lasts 0.5 s. Then a pause of at least 0.5 s follows. 0.5 s >= 0.5 s 0.5 s TCON.FMAX/3600 …65000 [100] >= 0.5 s This results in a maximum of 60 pulses per minute and 3600 pulses per hour. Example: If the maximum product flow is 30 tons, the IMP can be calculated as follows: IMP >= 30’000 kg / 3600 = 8.333 Thus the pulse must be set greater than 8.33. In this case the setting is limited by the software to 9! => Selection 10 kg / pulse If the pulse output is used to determine the current product flow rate, this must be calculated over at least 5 pulses or over approx. 1 minute. Note: If the TCON.FMAX rate is later dramatically increased, the pulse size may need to be adjusted. All of the pulses are always emitted. If the rate is too high, the missing pulses continue to be emitted after shutdown. AO Function of the analog output AO OFF = The output is deactivated H2OS = Nominal water value for dampener MOIST = Actual moisture value FLO = Current product flow H2OS 4 = Nominal water value for dampener MOIS 4 = Actual moisture value FLO 4 = Current product flow © Copyright 2008 Bühler AG OFF…FLO [OFF] 0…20.0 mA = TCON.QMAX 0…20.0 mA = 20.0 % 0…20.0 mA = TCON.FMAX 4…20.0 mA = TCON.QMAX 4…20.0 mA = 20.0 % 4…20.0 mA = TCON.FMAX MYFC-MOZF-66542-1-en-0803 48 Description of the MYFC Moisture Control Code AI Moisture controller Parameter group SYS (System configuration) Function of the analog input AI OFF = The input is deactivated H2O IN = Actual water value MOISTS = Nominal moisture value H2O 4 = Actual water value MOIS 4 = Nominal moisture value Input range OFF…MOISTS [OFF] 0…20.0 mA = TCON.QMAX 0…20.0 mA = 20.0 % 4…20.0 mA = TCON.QMAX 4…20.0 mA = 20.0 % The setting H2O IN is needed if no MOZF or MOZE is connected. This allows any liquids flow controller to be connected. The input current is displayed in the main group (H2O). This input is displayed only. No check is made whether the nominal value AO.H2OS is being reached! SD Standard-Display-Selection With this setting the standard display can be selected which appears every five minutes on the display. No. 0 1 2 3 4 5 6 7 Value left Nominal moisture Nominal moisture Nominal moisture Nominal moisture Water throughput Actual moisture Actual moisture Actual moisture 0…7 [0] Value right Actual moisture Product flow FLO Water throughput ∑1 erasable product quantity Product throughput FLO Product throughput FLO Water flow ∑1 erasable product quantity The user can also choose any parameter as a standard display. The lamp test button is pressed on the desired parameter for 10 seconds and then the parameter is displayed. Example SERV.TIME INIT Basic initialization All parameters are reset to the standard settings. Note: Only possible when the calibration switch is activated! MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 8.5.6 Description of the MYFC Moisture Control 49 Parameter group ADC Code Parameter group ADC (Analog-Digital-Converter) FLO Display of the current Flowbalancer flow – ZFLO With the F-key a null balance of the Flowbalancer can be made. See 6.2.4 Alignment of the Flowbalancer MZAH – CFLO Reference alignment of the Flowbalancer. This value is identical with the weight of the supplied weights. See 6.2.4 Alignment of the Flowbalancer MZAH 0.100…99.999 kg [6.000] NIV /NIVS The current level in the bypass is displayed. The product level should be in the middle of the sight glass. A correction can be made with the input key. The arrow indicates whether the current level is too high or too low. 20…300 [60] ZNIV With the F-key a null balance of the level-DMS can be made. Be sure that the bypass is empty and the product detection rod turns freely. See 6.2.3 Alignment of the level measurement WT Input range – Displays the current weight of the measuring container. ZWT With the F-key a null balance of the measuring container can be made. Be sure that both cables for the microwave measurement are connected and the measuring container is empty. See 6.2.2 Alignment of the measuring container CWT Reference alignment of the measuring container. This value is identical to the weight of one weight. Be sure that both cables for the microwave measurement are connected and the measuring container is empty. See 6.2.2 Alignment of the measuring container INTT The internal cabinet temperature is displayed. CINT Reference alignment of the internal cabinet temperature. Be sure that the Jumper X60 is switched to CAL! The alignment is made with the F-key. See 6.2.5 Alignment of the temperatures EXTT The product temperature is displayed. CEXT Reference alignment of the product temperature. Be sure that the Jumper X62 is switched to CAL! The alignment is made with the F-key. See 6.2.5 Alignment of the temperatures 0…20.000 kg [3.000] – –500.0…+500.0 °C [–258.2] – –500.0…+500.0 °C [–258.2] HF Actual attenuation The value of the attenuation of the microwave measuring segment is displayed. If product is in the measuring container, a value of 7..14 dB is displayed. – CHF Reference alignment attenuation With the F-key the attenuation of the microwave measuring segment can be aligned. For this the reference resistor (10 dB) must be connected in place of the microwave measuring line. The alignment can only be made if ADC.INTT was aligned correctly. If the alignment is not possible, CAL INTT appears. See 6.2.6 Alignment of the microwave unit 0…99.99 dB [10 dB] Note: Alignments can be made only when the calibration switch is activated! © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 50 Description of the MYFC Moisture Control 8.5.7 Parameter group HOST Code Parameter group HOST (Serial Interface 1 and Profibus DP) ADR Address Moisture controller Input range 0…255 [0] BAUD Setting of the baud rate for the HOST and service interface TOUT If the host does not communicate with this device for longer than the preset time, an error ERR 12 HOST is triggered. The monitoring is only active if the SYS.REM parameter is set on REMS or REMP. If the parameter is set on LOC or REMA, the error monitoring is not active. 8.5.8 4800 / 9600 / 19200 [4800] 0…99 seconds [60] Parameter group SVV Code Parameter group SVV (Current pre-distortion) Input range A1 Current curve parameter (see table on the microwave module) 0.01…5.00 [0.40] B1 Current curve parameter (see table on the microwave module) 0.01…1000.00 [400.00] C1 Current curve parameter (see table on the microwave module) 0.01…5.00 [0.75] A2 Current curve parameter (see table on the microwave module) 0.01…5.00 [0.50] B2 Current curve parameter (see table on the microwave module) 0.01…1000.00 [280.00] C2 Current curve parameter (see table on the microwave module) 0.01…5.00 [0.75] P Phase current curve parameter (see table on the microwave module) 0…360.0 degree [80.0] CALT Temperature correction value for the microwave circuit in dB / °C (to be changed by Bühler personnel only!) –999.999…+9999.999 [0.050] Note: These parameters determine the modulation of the microwave circuit. These parameters can be read off the microwave unit and must be entered. If the microwave circuit is replaced, these parameters must be re-entered and the adjustment of the microwave unit must be repeated (see 6.2.6 Alignment of the microwave unit). MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 8.5.9 Description of the MYFC Moisture Control 51 Parameter group PROD Code Parameter group PROD (Product group) Input range PROD Product group CAL0 Calibration constant 0 Offset of the calibration [15.781] CAL1 Calibration constant 1 Attenuation (S21) [+1.245] CAL4 Calibration constant 4 Product quantity in measuring container (bulk density) [-1.638] CAL5 Calibration constant 5 Product temperature [-0.100] Note: These parameters determine the moisture calculation. A change may be made only with information from Bühler. Incorrect settings lead to an incorrect moisture calculation. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 52 Description of the MYFC Moisture Control 8.6 Flowbalancer MZAH 8.6.1 Design features Moisture controller Fig. 8.7 The automatic Flowbalancer is used to meter a pre-selected volume of free-flowing product from a full product stream. The product is supplied at the inlet (1). A pneumatically operated slide gate (2) meters the product flow which, after a short drop, strikes an inclined plate (3) and is thus deflected from the original direction of flow. The resulting deflection force is proportional to the weight-related flow volume. This force is measured by a force transducer (4). The MEAF electronic control unit (5) monitors and controls the balance with the help of the control valves (6) via the diaphragm drive (7), by opening and closing the slide gate (2). This will result in a constant flow capacity. MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Description of the Liquids Flow Controller MOZF 9 Description of the Liquids Flow Controller MOZF 9.1 Mechanism and design variations Control unit 53 Test and service connection Hand switch Manual / Automatic Setting the water quantity in manual operation Water meter Shut-off valve Water filter Sight glass for manual operation Pressure reducing valve Control valve Shut-off valve Change-over switch Manual / Automatic Fig. 9.1 Design variations: standard version (maximum water temperature 50 °C and maximum chlorine addition 50 ppm) Type designation Dosing range automatic operation [l/h] Sight glass for manual operation [l/h] Minimum inlet water pressure [bar] Setting of internal pressure reduction valve [bar] MOZF 315 20…1000 31.5…315 1.5 1 MOZF 1000 20…1000 100…1000 2 1.5 MOZF 2250 180…2250 250…2500 2.5 2 MOZF 4500 180…4500 650…6500 4 3.5 Note: Setting of the internal pressure reduction valve. The value in the table corresponds to the setting if no height difference has to be overcome on the outlet. The pressure drop after the MOZF must be added to the setting of the pressure reduction valve and to the inlet water pressure (approximate value: 0.1 bar per meter if the water has to be transported upwards). Only correct setting and sufficient inlet pressure ensure faultless operation! If the inlet pressure is set too high, this can lead to fluctuations in the water dosing rate! © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 54 Description of the Liquids Flow Controller MOZF Moisture controller Special version for hot water applications (maximum water temperature 90 °C and maximum chlorine addition 50 ppm) Type designation Dosing range automatic operation [l/h] Sight glass for manual operation [l/h] Minimum inlet water pressure [bar] Setting of internal pressure reduction valve [bar] MOZF 315 H 20…1000 31.5…315 1.5 1 MOZF 1000 H 20…1000 100…1000 2 1.5 Design version for chlorine addition (Maximum water temperature 50 °C and maximum chlorine addition 600 ppm) Type designation Dosing range automatic operation [l/h] Sight glass for manual operation [l/h] Minimum inlet water pressure MOZF 315 C 20…1000 31.5…315 1.5 MOZF 1000 C 20…1000 100…1000 2 MOZF 2250 C 180…2250 250…2500 2.5 MOZF 4500 C 180…4500 650…6500 4 [bar] Note: The design version for chlorine addition is supplied without pressure reducing valve. Make sure to install the correct inlet water pressure (provide chlorineresistant pressure reducing valve) MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller 9.2 Description of the Liquids Flow Controller MOZF 55 Control Motherboard MEAF IO-board MEAF Power supply 24 V Relay for shut-off valve Connection terminals Display board MEAF Local switch AUT / MAN Fig. 9.2 9.2.1 Control unit MEAF with IO-Extension EBD1270 Motherboard RAM/BATTERY EPROM S2 MEAF MOZF RUN IO-Extension X104 X14 X15 A B 1 2 3 4 S4 X49 DI12 DI13 DI14 X13 CAL X16 X17 X18 X19 F3 A B A B S3 X1 1 2 3 4 X42 X41 X9 X2 X3 X4 X5 X6 X7 X8 Fig. 9.3 S2 S3 S4 F3 DI12 X104 Calibration switch: RUN = released for operation / CAL = calibration mode If there is an MYFC, turn S3.3 to «On». Settings for RS-485-Host-Interface: (For details see operating instructions «Description of the serial interface RS-485»). Miniature fuse 1.25 A slow-blow as 24 V input fuse Bridge for water meter must be removed Switch over output DO20 to pulse width modulation (Position MOZF!) © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 56 Description of the Liquids Flow Controller MOZF 9.2.2 Electrical connections Connection Terminals X101 L1 N PE +24 V AC 85...264 V DC 24 V X1 1 2 3 X2 DO 1 DO 2 DO 3 DO 4 DO 5 0V 1 2 3 4 5 6 Alarm Water valve n.u. Volume pulse n.u. n.u X3 DO 6 0V DO 7 0V DO 8 0V 1 2 3 4 5 6 n.u. n.u. n.u. n.u. n.u. n.u X4 24V DI 1 DI 2 DI 3 DI 4 0V 1 2 3 4 5 6 24 V Release =>(X101:9) Manual operation Product probe =>(X101:5) Relay test n.u X5 24V DI 5 DI 6 0V 1 2 3 4 n.u. n.u. n.u. n.u. X6 24V DI 7 DI 8 0V 1 2 3 4 n.u. Clear alarm (pulse) Clear alarm (release) n.u. X7 Shield SIO+ SIOCOM 1 2 3 4 X8 Shield 1 2 AO+ AO3 1 2 3 4 5 6 7 DI = Digital Input (24 V Input) DO = Digital Output (24 V Output) n.u. = not used 0V 24V 0V Shield Sensor+ X9 OUT+ IN+ INOUTSensor- Moisture controller X13 DO 9 DO 10 DO 11 DO 12 DO 13 0V 1 2 3 4 5 6 n.u. n.u. n.u. n.u. n.u. n.u. X14 DO 14 DO 15 DO 16 DO 17 DO 18 0V 1 2 3 4 5 6 n.u. n.u. n.u. n.u. n.u. X15 DO 19 DO 20 +24V DI 9 DI 10 0V 1 2 3 4 5 6 n.u. Control valve + n.u. n.u. n.u. Control valve – X16 +24V DI 11 DI 12 DI 13 DI 14 0V 1 2 3 4 5 6 Water meter +24 V n.u. Signal water meter n.u. n.u. Water meter 0V X17 Shield SIO2+ SIO2COM +24V 0V 1 2 3 4 5 6 X18 Shield T+ TR+ RCOM 1 2 3 4 5 6 X19 Shield AO2+ AO2Shield AI+ AI- 1 2 3 4 5 6 =>(X101:7) Serial interface RS-485 to MYFC or Host Analog output 0/4...20 mA current water flow rate n.u. Serial interface 2 RS-485 to Remote control n.u. Analog output 0/4…20 mA current water flow rate (electrically isolated) Analog input 0/4...20 mA Nominal water value l OPTION IO-Extension Fig. 9.4 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Description of the Liquids Flow Controller MOZF 9.3 Parameters 9.3.1 Main menu overview H2O H2OS 9.3.2 123 l/h 123 l/h 57 Current water flow H2OS appears as soon as the «Enter» key is pressed. The nominal value can be set here if the device is operated locally (SYS.REM = LOC). MOISTS + 1.2 % Nominal value if the MOZF is used as percent dampening. This parameter is normally hidden. ∑3 123456 Erasable total volume of water in litres or m³ ∑4 123456 Non-erasable total volume of water in litres or m³ 15.0 % 10.2 % Nominal moisture % and actual moisture % (The nominal moisture cannot be changed; these data are conveyed from the MYFC) FLO 12.345 t/h Current product flow in tons / hour (These data are conveyed from the MYFC) General parameter overview TCON Type-specific configuration SYS System configuration HOST Serial / Profibus Host interface MODE MYFC / %-DOS / LDOS FMAX Max. product flow rate T1 Monitoring time release WDLY Water dosing time delay QMIN Minimum dosing rate REM Local/ Serial/ Analog / Profibus DISP Remote control AINV Alarm output inv. ADR Address QMAX Maximum dosing rate WCNT Water meter constant CTRL Number of devices © Copyright 2008 Bühler AG SERV See page 68 BAUD Baud rate TOUT Time-out IMP Flow quantity pulse AO Analog output 0/4…20 mA AI Analog input 0/4…20 mA SD Standard-DisplaySelection INIT Basic initialization MYFC-MOZF-66542-1-en-0803 58 Description of the Liquids Flow Controller MOZF 9.3.3 Parameter group TCON Code Moisture controller Parameter group TCON (Type-specific configuration) Input range MODE The operational mode of the liquids flow controller MOZF MYFC … L-DOS [MYFC] MYFC = The MOZF is connected to an MYFC %-DOS = Percent dampening based on product flow rate L-DOS = Litre dosing based on a nominal value This setting determines the operational mode of the control. For standard operation the MYFC setting is always used. The %-DOS setting is only selected when the device is involved in a dampening process in which no MYFC is present but the product rate can be obtained from Bühler dosing elements. L-DOS is used when a constant volume of water dosage is desired. This volume can be set locally or pre-set via an interface. FMAX 2) T1 1) Maximum permissible total of the product dosage rate of all connected devices when the MOZF is used for percent dampening. If this setting is exceeded, an ERR 42 LIMIT is triggered. Monitoring time of the release The setting of T1 determines how much time is allowed between the dosing release and its detection by the product detection probe at the dampener. See 10.2 Locking the product probe MOZL (ERR63 FLOWD) 0…9999 seconds [3600] 0 = monitoring deactivated 0…9999 seconds [0] WDLY Water dosing time delay Waiting time until water dosing starts. As soon as all of the following conditions are met, the time begins to elapse. QMIN 1) – Release must be present – Nominal value > 0 must be available – Product probe must be covered – No Alarm Minimum permissible dosing rate With this value the minimum water rate is determined. If the actual value is lower than this setting, the water is stopped. This setting serves to monitor the system. See (ERR65 QMIN) QMAX Maximum permissible dosing rate (device limit) This value determines the editing limits of the maximum water dosing rate. The setting must be adjusted to the type of liquid flow control. 315 1000 1…500’000 kg [100’000] 0…QMAX [0] QMIN…6500 litres [4500] for MOZF315 for MOZF1000 etc. Note that the (ERR66 DMAX) is not active when TCON.MODE = MYFC is set. In this mode the maximum water dosage rate is set at the MYFC according to the recipe MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Code Description of the Liquids Flow Controller MOZF Parameter group TCON (Type-specific configuration) 59 Input range WCNT Correction value of the water meter. This value defines the number of pulses per litre. Thus any water meter can be connected, or the flow can be corrected with this factor if deviations occur. 0.1…6500.0 [105.7] Standard values MOZF 315 680 MOZF1000 709.5 MOZF 2250 105.7 MOZF 4500 105.7 CTRL 2) Number of connected dosing elements when the MOZF is used for percent dampening. If the sum of the detected devices is not identical to this number an ERR 17 HSTI is triggered. 1…32 [1] 1) These parameters are only displayed when TCON.MODE is set at %-DOS or L-DOS. When TCON.MODE = MYFC is set, then these parameters are not necessary and serve no function. 2) These parameters are only displayed when TCON.MODE is set at %-DOS. 9.3.4 Parameter group HOST Code Parameter group HOST (Serial Interface 1 and Profibus DP) ADR Address Input range 0…255 [1] BAUD Setting of the baud rate for the HOST and service interface TOUT Time-out time of the host interface. If the host does not communicate with this device for longer than the preset time, an error ERR 12 HOST is triggered. The monitoring is only active if the SYS.REM parameter is set to REMS or REMP. If the parameter is set to LOC or REMA, the error monitoring is not active. © Copyright 2008 Bühler AG 4800 / 9600 / 19200 [4800] 0…99 seconds [60] MYFC-MOZF-66542-1-en-0803 60 Description of the Liquids Flow Controller MOZF 9.3.5 Parameter group SYS Moisture controller Code Parameter group SYS (System configuration) Input Range REM LOC REMS REMA REMP = The nominal values are set locally = The nominal values are serially (RS-485) adjusted = The nominal value is adjusted by a 0…20 mA signal = The nominal values are serially (Profibus) adjusted LOC…REMP [REMS] DISP OFF LOC REM BOTH = The remote control is turned off = Local control (remote control only displays) = Remote control = Both local and remote control LOC…BOTH [OFF] AINV Invert alarm output DO 1 ON = 0 V is an alarm (fail-safe in case of wire breakage) OFF = 24 V is an alarm ON…OFF [ON] IMP Water pulse The setting determines the volume in litres of the 24 V water pulse of the output (DO 4) Note that the setting must be made correctly. A pulse always lasts for 0.5 s. Then a pause of at least 0.5 s follows. 0.5 s >= 0.5 s 0.5 s 0.1…6500.0 [10.0] >= 0.5 s This results in a maximum of 60 pulses per minute and 3600 pulses per hour. Example: If the maximum water rate is 2000 litres, the IMP can be calculated as follows: IMP >= 1000 l/ 3600 = 0.556 Thus the pulse must be set to a value greater than 0.55. If the pulse output is used to determine the current product flow rate, this must be calculated over at least 5 pulses or over approx. 1 minute. Note: If the rate is later highly increased, the pulse size may need to be adjusted. All of the pulses are always emitted. If the rate is too high, the missing pulses continue to be emitted after shutdown. AO Analog output change-over 0/4…20 mA The setting is valid for both outputs AO and AO2! 0MA/4MA [0MA] AI Analog input change-over 0/4…20 mA 0MA/4MA [0MA] SD Standard display At the MOZF, the standard display after a time-out of 5 minutes is always the actual water flow quantity. The user can, however, choose any parameter as a standard display. The lamp test button is pressed on the desired parameter for 10 seconds and then the parameter is displayed. Example SERV.TIME INIT Basic initialization All parameters are reset to the standard settings. Note: Only possible when the calibration switch is activated! MYFC-MOZF-66542-1-en-0803 [USER.H2O] © Copyright 2008 Bühler AG Moisture controller 10 Alarms and warnings MYFC and MOZF 61 Alarms and warnings MYFC and MOZF 10.1 Alarm messages The MYFC and MOZF have alarm and warning messages. Alarms are triggered in serious situations. The 24 V alarm output is set. Warnings are given when the basic functions of the device are not influenced, e.g. interruption of the connection to the remote control. The error is displayed on both the MYFC and the MOZF. The errors can be acknowledged with the alarm acknowledgement key. The errors can also be acknowledged at the MYFC or at the MOZF. Example 1: The MYFC reports the error 26 TOL. The error also appears on the MOZF display with the message that the MYFC has detected an error. Display MYFC Display MOZF ERR 26 TOL ERR 26 *MYFC Example 2: The MOZF reports the error 67 QTOL. The error also appears on the MYFC display with the message that the MOZF has detected an error. Display MYFC Display MOZF ERR 67 *MOZF ERR 67 QTOL © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 62 Alarms and warnings MYFC and MOZF Number Meaning Moisture controller O A Standard M ERR 1 EPROM EPROM Error detected in program storage during start-up Acknowledgement by switching off and on again Automatic acknowledgement when the cause of the alarm has been eliminated Manual acknowledgement with key Turn the MEAF off and on again. If the alarm reoccurs, the EPROM must be replaced. M ERR 2 RAM RAM Turn the MEAF off and on again. M Error detected in data storage If the alarm reoccurs, the motherboard must be replaced. during start-up ERR 3 RTIME Running time error software During program execution, data have assumed incorrect values If the alarm reoccurs, the EPROM must be replaced. Contact Bühler-Service and give the system address (Parameter SERV.SADR) and the program version (SERV.VER). ERR 4 WDOG Watch-Dog Timeout during a program cycle Turn the MEAF off and on again. M If the alarm reoccurs, the EPROM or the electronics must be replaced. Contact Bühler-Service. ERR 5 NO24V 24 V voltage too low Check 24 V A ERR 6 MLOST Data loss Incorrect data detected in data storage (RAM) during start-up. The data are automatically initialized to the original values. Change the battery over the storage component (RAM). The data must then be re-entered. M AD-converter sector The measuring range is exceeded or fallen short of. • Make new alignment • Eliminate outside influence on baffle plate • Check force transducer cable • Replace force transducer or motherboard • Make new alignment • Eliminate outside influence on baffle plate • Check installation position of force transducer ERR 7 RANGE ERR 8 ADCAL AD-converter calibration Too few AD-values are available for the calibration M Caution: The error can only be acknowledged if an expansion board is mounted on the motherboard. A complete commissioning must be carried out. A A ERR 9 ADFCT AD-converter function Converter component delivers no AD-values • Replace motherboard A ERR 10 AD10V AD-converter sensor supply The sensor supply is outside of the permissible tolerance • Check jumpers X41, X42 (Sense-signals) A • Replace force transducer • Replace motherboard • Measure current • Set counter-device to 4…20 mA also • Correct line interruption • Replace Option IO-Extension ERR 11 <4MA Nominal value lower 4 mA For analog nominal value selection 4…20 mA (Remote-Mode-Analog) MYFC-MOZF-66542-1-en-0803 A © Copyright 2008 Bühler AG Moisture controller Number Meaning Alarms and warnings MYFC and MOZF O A M Acknowledgement by switching off and on again Automatic acknowledgement when the cause of the alarm has been eliminated Manual acknowledgement with key • Put host in operation • Interface cable interrupted or incorrectly connected • Enlarge HOST.TOUT • HOST.TOUT = 0 (switch off) WRN 13 Remote control DISP Serial communication to remote control disturbed (not on alarm-output) • Check wiring • Set the remote control board switch correctly • Remote control connected to correct terminals according to SYS.SIO or SYS.SIO2 ERR 14 P-DP Profibus Profibus warning or communication has been interrupted (Timeout) • Is the Profibus master active? • Check Profibus wiring and address HOST.ADR Internal communication MYFC The serial communication between MYFC and MOZE/F is disturbed for longer than 5 s. • Check serial interface cable between MYFC and MOZE/F • Are the bus terminators set correctly? • It is possible that the interface SIO2 of the MYFC is defective. Connect cable to SIO3 and wait for 30 s (from version V24A) • If there is no MOZF/E, switch TCON.MODE to CALC. • Check that all the addresses of the dosing elements were set correctly and that all dosing elements work properly. If necessary adjust the TCON.CTRL parameter. ERR 12 HOST ERR 17 HSTI Timeout on Host-interface The host system no longer communicates with the MEAFelectronics MOZF for percent dampening. The number of detected dosing elements is not identical with the number in TCON.CTRL parameter Flowbalancer 63 A A A Note: This warning can only be issued if a Profibus DP extension board is installed. The exact cause of the fault can be read off from the parameter SERV.P-DP (Profibus diagnosis). A The baud rate of the dosing elements must be 4800 bauds. If new devices are connected, the error can exist for 4 minutes until the device is found. WRN 18 Battery Low BAT The buffer battery has inadequate voltage (not on alarm-output) • Check contacts of buffer battery • Replace battery ERR 26 TOL Tolerance The control continually works outside of the coarse tolerance (e.g. with strongly inhomogeneous product) • Increase coarse tolerance if necessary • Decrease regulation correction RCOR if necessary ERR 29 PTIME Dosing time exceeded • After starting, no product is found on the baffle plate. M ERR 30 ZERO Error during zero set Weight deviation too large during zero set. • Clean baffle plate A • Make new alignment • Check force transducer (may be defective) © Copyright 2008 Bühler AG A M MYFC-MOZF-66542-1-en-0803 64 Alarms and warnings MYFC and MOZF Number Meaning Moisture controller O A M ERR 38 FGATE MYFC / MOZF ERR 39 LEAK ERR 42 LIMIT ERR 54 REL ERR 55 MOIST ERR 56 INTT ERR 57 EXTT Acknowledgement by switching off and on again Automatic acknowledgement when the cause of the alarm has been eliminated Manual acknowledgement with key Slide The metering slide gate cannot be correctly closed after being opened and closed 3 times • Check slide mechanism • Slide scrapes on inlet spout • Slide mechanically jammed, e.g. foreign objects Leak Excessive air loss in the pneumatic control system during operation with product. • Check for leakage • Check the air hoses • Check valves 1…4 • Air filter MYFC The maximum dosage rate TCON.FMAX was reached for 1 minute; now the product is clogged • Check whether the selected TCON.FMAX value was large enough. Reference value: cleaning rate + 20 % • Check whether the level control is functioning correctly MOZF (percent dampen.) The sum of all connected dosing elements has exceeded the TCON.FMAX value • Check whether TCON.FMAX is set correctly • Check the nominal value for the dosing elements Relay MOZF Relay does not work correctly. The response at input D14 did not occur within 5 seconds. • Check relay position • Tighten all screws on the hand switch (also the unused contacts!) • Replace relay • Replace main board Moisture Calculated moisture is outside of the tolerance range for more than 60 s. < 5.0 %…> 25.0 % • Check all measurements • Check the offset value (can also be changed by HOST) • Check the PROD.CAL parameter Internal temperature Measured internal temperature outside of the tolerance range. < –10 °C…> 70 °C • Check wiring between X50 and temperature sensor A • Jumper X60 on RUN-position? • Make new alignment External temperature Measured external temperature outside of the tolerance range. < –5 °C…> +70 °C • Check wiring between X54 and temperature sensor A • Jumper X62 on RUN-position? • Make new alignment MYFC-MOZF-66542-1-en-0803 M When a foreign object blocks the measuring section, the metering slide gate can be opened with the key at the device (MZAH). A M M M M © Copyright 2008 Bühler AG Moisture controller Number Meaning Alarms and warnings MYFC and MOZF O A M ERR 58 HF ERR 59 WT ERR 60 NIV 65 Acknowledgement by switching off and on again Automatic acknowledgement when the cause of the alarm has been eliminated Manual acknowledgement with key Attenuation measurement The measured attenuation lies outside of the tolerance for more than 60 s. < 5…> 20 dB <= version 27A < 3…> 20 dB >= version 27B • Check wiring between MYFC auxiliary board and microwave unit • Check wiring between microwave unit and microwave tongue • Are the SVV parameters set correctly? The monitoring occurs as soon as the MZAH-actual flow and the MZAH-set flow are greater than 0. • Make new alignment Bulk density measurement The measured bulk density lies outside of the tolerance. < –1.0 kg …> 10 kg • Check wiring between X55 and load cell • Can the measuring container move freely? – Transport safety device removed – No objects attached to the measuring container • Make new alignment • Replace load cell • Check wiring between X56 and load cell • Can the force measuring rod move freely? – Not covered with dirt • Make new alignment • Replace load cell Level The measured level lies outside of the tolerance. < –5...> 500 M A A ERR 61 Software SWERR The internal security monitoring has reacted Bühler customer service must be contacted immediately. ERR 62 BOARD Extension board There is an error on the extension board. The exact cause can be found under parameter SERV.ST2. • Is an extension board present? • Re-start the control Unplug X1, wait a few seconds and plug in again • Replace extension board Product probe MOZL product probe has recognized an error. • Check position and condition of MOZL M product probe. Does the probe react only when product is present? • Check the times TCON.T1 and TCON.T2 and increase if necessary. ERR 63 FLOWD ERR 64 *MOZE MOZE alarm A MOZE alarm has occurred. MOZE alarms must be handled directly at the MOZE; see also MOZE operating instructions ERR 65 QMIN Minimum permissible water dosing rate Minimum dosing rate fallen short of for more than 60 s. • Increase nominal moisture or switch on dry dampening • Check TCON.QMIN © Copyright 2008 Bühler AG M O M M MYFC-MOZF-66542-1-en-0803 66 Alarms and warnings MYFC and MOZF Number Meaning Moisture controller O A M ERR 66 DMAX ERR 67 Q TOL Acknowledgement by switching off and on again Automatic acknowledgement when the cause of the alarm has been eliminated Manual acknowledgement with key Maximum water dosing rate The calculated water dosing rate exceeds the recipestipulated rate for more than 60 s. • Reduce nominal moisture • Check REC.DMAX • Increase pre-dampening if necessary • Reduce product flow if necessary Water dosing value The water dosing value lies outside of the control tolerance ±10 % for more than 120 s or the valves are not closing properly any more. The alarm is also triggered when the control valve is at the high or low limit position. See parameter SERV.PWM • Check water supply M Is the water pressure correct? Could the lines and/or filters be clogged? Can the desired water quantity be dosed in manual operation? • Check shut-off valves Do the shut-off valves at the MOZF and at the dampener (MOZL) open correctly? • Check water meter Is the measurement value of the water meter correct (calibrate)? • Check control valve Standard values approx. 30…50 %. If the display shows 10 % or 90 %, the control valve is completely closed or fully open. MYFC-MOZF-66542-1-en-0803 M © Copyright 2008 Bühler AG Moisture controller Alarms and warnings MYFC and MOZF 67 10.2 Locking the product probe MOZL (ERR63 FLOWD) This error message checks the product flow in the system and guarantees that the product probe also functions dynamically. This increases safety dramatically because the product probe is tested at each start and stop. The parameter TCON.T2 is to be set for this monitoring. The setting must be made according to the cleaning conditions. The time setting is dependent on the flow time the product needs from the MYFC to the dampener. If no product probe is used, the parameter TCON.T2 is to be set on 0. This deactivates the monitoring. In addition, the product flow from the silo cell to the MYFC can be monitored with the release signal. When the dosing release is on, the MYFC expects product to be detected at the MYFC within the TCON.T1 time. If this is not the case, a malfunction may be present in the transport or in the dosing element of the silo cell. If the release signal is not used or this monitoring should not take place, then TCON.T1 must be set on 0. This deactivates the monitoring. Release 24 V MYFC product detected < T1 < T1 Probe MOZL product detected < T2 3s < T2 Fig. 10.1 If T1 or T2 are exceeded then ERR 63 is triggered and the water dosing is stopped. The water is not stopped if the probe does not signal any product for < 3 seconds. It is also possible to fill in a dry state. In this case the release signal must be set on 0 V, or the moisture nominal value must be 0 %. 10.3 External 24 V alarm acknowledgement It is possible to acknowledge alarms automatically. The signals are present on the base PCB of the MOZF. No parameters have to be changed. There are two versions available: 1. Clear alarm (pulse) DI7 The current alarm is cleared as soon as a positive side of 0 V to 24 V has occurred on this input. 2. Clear alarm (release) DI8 The current alarm is cleared as soon as the release DI1 is no longer active. To activate this function, the input must be wired to 24 V. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 68 Alarms and warnings MYFC and MOZF Moisture controller 10.4 Parameter group SERV MYFC VER MOZF Parameter group SERV (Service information) VER Input range Program version (left) and data version (right) – DATE DATE Date 1-1-00…31-12-99 TIME TIME Time (seconds = 80 -> clock stopped) Normally the clock is turned on. A battery test is made every 24 h only when the clock is turned on. 0-0-0…23-59-59 ERR ERR The 3 most actual alarms. On the left the newest, on the right the oldest alarm. – Expanded alarm display: Press the F-key to turn on the expanded alarm display. With the Fand plus-keys or the F- and minus-keys, the last 9 alarms can be displayed. On each alarm the date and time of the alarm can be displayed with the enter-key. After the 9th alarm «CLEAR ALARM» is displayed. Here all alarms can be erased with the enter key. CPU CPU Computer workload in % – SADR SADR System address for a program error – PCNT PCNT Meter number voltage losses – DMS1 – Voltage of the DMS input X9 on the motherboard (Baffle plate MZAH) – DMS2 – Voltage of the DMS input X55 on the MYFC auxiliary board EBD1293 (Weight measuring container) – DMS3 – Voltage of the DMS input X56 on the MYFC auxiliary board EBD1293 (Force level-measuring rod) – +10V – DMS sensor supply in V (is refreshed in Step 1 only) – AOUT AOUT Analog output (actual current) in mA Current can be set for tests when the calibration switch = CAL – – AOU2 Analog output 2 (actual current) in mA Current can be set for tests when the calibration switch = CAL – AIN AIN Analog input (actual current) in mA – DIN DIN Digital inputs 1…8 on motherboard (left DI1, right DI8) – – DIN9 Digital inputs 9…14 on Option IO-extension (left DI9, right DI14) – DO DO Digital outputs 1…8 on motherboard (left DO1, right DO8) – DO9 Digital outputs 9…16 on Option IO-extension (left DO9, right DO16) – – DO17 Digital outputs 17…20 on Option IO-extension (left DO17, right DO20) MYFC-MOZF-66542-1-en-0803 – © Copyright 2008 Bühler AG Moisture controller MYFC Alarms and warnings MYFC and MOZF MOZF Parameter group SERV (Service information) SIO SIO SIO2 SIO2 69 Input range Serial interface RS-485 to host (communication meter, command, error number) Communication meter: Increases by 1 after each communication to the correct address. Command: Actual command Error number: Error number of the communication (see 66435-1) – Serial interface RS-485 (as in SIO) The number at the left indicates the actual status of the internal communication at the MYFC. The number at the right is the error number. – 0. = Internal communication turned off 1. = Water dosing device not found 2. = MOZE found as water dosing device 3. = MOZF found as water dosing device 4. = Two water dosing devices configurated SIO3 – Serial interface RS-485 (as in SIO) – ST1 – Status of measurements and program step – Measurements: 0. = Measured values invalid 1. = Measured values valid 2. = Measured values stored Program step Flowbalancer 0. = Calibrate 1. = Starting position 2. = Dosing stop / zero-set 3. = Dosing 4. = Standing time 5. = Measuring time 6. = Calculations 7. = Leakage test 8. = Valve test ST2 – Status of water dosing rate and extension board – W-XX: Status water dosing 0. = Water stopped 1. = Limit water dosing rate DMAX 2. = Limit water dosing rate QMAX 3. = Minimum water dosing rate QMIN fallen short of 4. = Normal operation (water can be dosed normally) B-XX: Extension board status A decimal value is displayed in which the bits display the individual states (errors). Bit 0: = No extension board found Bit 1: = AD converter defective Bit 2: = Error in SVV-RAM-Test Bit 3: = Auxiliary voltage 15 V outside of the tolerance Bit 4: = Auxiliary voltage 5 VA outside of the tolerance © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 70 Alarms and warnings MYFC and MOZF MYFC MOZF Parameter group SERV (Service information) P-DP P-DP Moisture controller Input range Profibus DP-Status display (only displayed when the Profibus board is present) – 0 = Timeout / communication interrupted 1 = Error when initializing 2 = No error +15V – Display of the 15 V voltage of the MYFC extension board – +5VA – Display of the 5 V analog voltage of the MYFC extension board – HFIN – Display of the high-frequency input of the MYFC extension board In normal operation approx. 1..3 volts should be displayed (approx. 10 dB) – VA VA FO…WAIT SO…WAIT SC…WAIT…FC MYFC Function test of the valve group (Drive control of the metering slide gate) Pressing the F-key will start the sequence: FO WAIT SO WAIT SC WAIT FC fast open metering slide gate stops for approx. 3 seconds slow open metering slide gate stops for approx. 3 seconds slow close metering slide gate stops for approx. 3 seconds fast close MOZF Functional test of the valves. No nominal water value can be entered. The water is then dosed immediately, irrespective of release signals and settings! The water is stopped again after 10 minutes or by the F-key (in parameter SERV.VA). From Version 26A onwards: At the left a total sum counter is displayed 0.01l and at the right the current actual rate. The total sum counter can be deleted by pressing the lamp test key. This is necessary for checking the accuracy of the water counter. When the input key is pressed, the nominal value can be entered. LK – – CNT Frequency of the water meter DI12 – – PWM Pulse width modulation value of the proportional valve – PARP Leakage test with simulator (special test for factory setting ) Test result visible on display (no alarm messages) Start/Stop with F-key PARP Activate parameter printout with F key P SIO P SIO2 P SIO3 R SIO R SIO2 R SIO3 SUP RUN NOWT ERR– / OK / ERR+ SUP [P SIO3] Parameter output on SIO Parameter output on SIO2 Parameter output on SIO3 Recipe output on SIO Recipe output on SIO2 Recipe output on SIO3 ON The super-user parameters are displayed OFF The super-user parameters are not displayed After a Power-On the parameter is always automatically set to OFF MYFC-MOZF-66542-1-en-0803 ON/OFF [OFF] © Copyright 2008 Bühler AG Moisture controller 11 Maintenance 71 Maintenance 11.1 MYFC 11.1.1 Removing the measuring container 1. Empty the MYFC completely 2. Remove the inlet connection by undoing the upper screws (1) 3. Remove the inlet housing by undoing the six lateral screws (2) 4. Undo the knurled nut of the cable (3) on both sides of the shaft 5. Remove the three nuts (4) on both sides 6. Undo the two screws (5) on one side and remove support 7. Pull out the measuring container sideways 5 1 2 4 Fig. 11.1: Inlet box 3 Fig. 11.2: Removing the measuring container To assemble, follow the steps above in reverse order Note: After assembly a weight alignment must be made. See 6.2.2 Alignment of the measuring container. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 72 Maintenance Moisture controller 11.1.2 Sensor tongue Removing the sensor tongue 1. Remove the measuring container (see 11.1.1) 2. Undo the slotted bolt (1) of the shaft on both sides (e.g. with pitch gauge) 3. Undo the fillister screws (2) on one side and remove the adapter cone (3) 4. Carefully pull out the sensor tongue (4) with the disk (5) 5. Separate the disk from the tongue 4 5 2 3 1 1 Fig. 11.3 Measuring container 6 Fig. 11.4 Sensor tongue Assembling the sensor tongue 1. First put sealing compound into the milled slot (6) of the disk (5) (the use of Permabond Acryl 500 is compulsory). Scrape the sealing compound towards the edge to stop water from entering after assembly. 2. Insert the sensor tongue carefully (Caution: O-ring in disk; tongue must be vertical in the milled slot of the disk) 3. Put sealing compound into the milled slot of the second disk also (the use of Permabond Acryl 500 is compulsory). 4. Insert the disk (5) over the tongue (4) until it stops at the measuring container (the tongue must be in the milled slot of the disk) 5. Mount adapter cone (3) 6. On both sides carefully screw the bolt (1) in the shaft of the tongue. 7. Re-install the measuring container Note: After assembly the following adjustments must be made: See 6.2.2 Alignment of the measuring container See 6.2.6 Alignment of the microwave unit MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Maintenance 73 11.1.3 Single-point force transducer 1. Empty the MYFC completely 2. Undo the knurled nut (1) on both sides from the shaft 3. Loosen three nuts (2) on one side 4. Undo two screws (3) on both sides and remove support 5. The measuring container can now be placed in the funnel (as an alternative the measuring container can also be removed) 6. Undo four lower screws (4) and pull out the force transducer 7. Remove the holder and distance holder from the transducer 3 2 1 4 Fig. 11.5 Measuring container Fig. 11.6 Single-Point Assembly in reverse order • • • During assembly make sure that the force transducer is in the correct position Torque of the four lower and upper screws (4) to the force transducer: 14 Nm Connection of DMS see 8.4 Note: After assembly the following alignment must be made: See 6.2.2 Alignment of the measuring container © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 74 Maintenance Moisture controller 11.1.4 Force transducer 1. Remove the locking ring (1) on the outer part of the bar 2. Undo cable bracket (2) 3. Remove the force transducer by undoing the two screws (3). During assembly in reverse order note the following: • • • Position the force transducer so that the bar (5) lies on the lower edge of the bore hole (4) in the housing and can be turned easily in the force transducer. Reseal the entry to the insulating tube with new shrinkable tubing or Permabond. Connection of the DMS see 8.4 2 5 1 4 5 3 Fig. 11.7 Force transducer Fig. 11.8 Bore hole for bar Note: After assembly the following alignment must be made: See 6.2.3 Alignment of the level measurement MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Maintenance 75 11.1.5 Diaphragm drive To dismantle, remove the pin from the fork head. The complete diaphragm drive is fastened to the feeder unit with four bolts from the outside. Initially only loosen these four bolts with the head on the outside. • The diaphragm drive is held together by four bolts (8) with the heads countersunk on the inside. The shaft and nut of these bolts protrude on the outside. If these four bolts (8) are loosened equally, all parts of the drive will become detached. • • Observe the following points for reassembling: • • • • Clip the diaphragm plate (4) neatly into the operating diaphragm (3). Place the compression spring (5) in the guide at the top and bottom. Observe the position of the spring support (1) in relation to the top membrane cover (2). Ensure absolutely tight assembly. 2 3 5 4 8 Fig. 11.9 © Copyright 2008 Bühler AG 1 Fig. 11.10 MYFC-MOZF-66542-1-en-0803 76 Maintenance Moisture controller 11.1.6 Inlet spout 1. Remove the pin from the fork head and open the metering slide gate (3) completely. 2. In the case of the MZAH-25, also undo the countersunk screws (7) on both sides. 3. The bottom four flange nuts (34) must be unscrewed during dismantling. 4. The four top flange nuts must remain in position in order to facilitate the installation of the inlet spout (4) later. 5. The inlet spout (4) can be removed from one of the two door openings. Observe when reassembling: There must be a gap «S» of 0.5…1 mm between the metering slide gate (3) and the inlet spout (4). Check with a feeler gauge and by moving the slide gate. Corrections are possible at the flange nuts (34). • • S 34 4 3 7 Fig. 11.11 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Maintenance 77 11.1.7 Metering slide gate 1. Remove the pin from the fork head. 2. Loosen all six screws (three on each side), which are used to fasten the complete metering slide gate (1) in the feeder unit. 3. Open the metering slide gate (1) fully and lift it vertically out of the guides. 4. The metering slide gate can be removed through the side openings. 5. All parts can now be dismantled from the outside towards the inside until the metering slide gate (1) is freed as well. Observe the following points for reassembling: • • • Reassemble in the reverse order. Use sealed ball bearings (6) with permanent lubrication. Check gap («S» = 0.5…1 mm) between the metering slide gate (1) and the inlet spout. 1 6 Fig. 11.12 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 78 Maintenance Moisture controller 11.1.8 Baffle plate See pictures below • To dismount, undo the nuts (36) in order to release the baffle plate (10). • After replacing the baffle plate a weight alignment has to be carried out. 11.1.9 Protective bellows See pictures below 1. Undo fitting screw (12a) (tightening torque Ma = 8 Nm). 2. Draw down baffle plate (10) with protective bellows (7). 3. Undo screws (32) and remove protective bellows (7). 4. Mount spare bellows with due caution. • Reassemble in reverse order. • After replacing the protective bellows a weight alignment has to be carried out. 11.1.10 Force transducer See pictures below 1. Disconnect cable from force transducer. 2. Undo fitting screw (12a) (tightening torque Ma = 8 Nm). 3. Draw down baffle plate. Caution with protective bellows! 4. Undo fitting screws (12b). • Reassemble in reverse order. • Do not shorten the cable of the force transducer. • After replacing the force transducer a weight alignment has to be carried out. 10 12b 36 12a 32 7 Fig. 11.13 Baffle plate MYFC-MOZF-66542-1-en-0803 Fig. 11.14 Valves and force transducer © Copyright 2008 Bühler AG Moisture controller Maintenance 79 11.2 MOZF 11.2.1 Water filter 1. The water filter must be cleaned periodically depending on the water quality. 2. Close shut-off valve 3. Open the drain cock of the water filter and press the air-bleed button at the water filter 4. Open the filter housing and clean or replace the filter cartridge 5. After re-assembly, air-bleed the water filter 11.2.2 Shut-off valve The shut-off valve generally requires no maintenance. In case of contamination or if there is a malfunction, the valve can be cleaned. Remove cover Fig. 11.15 Remove diaphragm and spring Fig. 11.16 Now cleaning can be performed During assembly be sure that the spring is not jammed Fig. 11.17 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 80 Maintenance Moisture controller 11.2.3 Control valve Undo the nuts and remove the coil head Fig. 11.18 Pull off the plastic cover and undo the screws of the base plate. The individual parts can now be cleaned. Fig. 11.19 The piston must be able to be moved freely. Fig. 11.20 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Maintenance 81 11.2.4 Water meter The water meter can be simply disassembled. The sensor head can be lifted off with a slight turning movement after undoing bolt 1. Undo the four bolts 2 and then lift off the top part. The water wheel can now be cleaned and checked. 1 Fig. 11.21 2 Fig. 11.22 © Copyright 2008 Bühler AG Fig. 11.23 MYFC-MOZF-66542-1-en-0803 82 Maintenance Moisture controller 11.2.5 One-way light scanner for 10…30 V DC (Telco probe) Connection diagram Load brown black blue Function Infra-red light beam Operating mode Output-LED yellow Light on Off Light off On Light on On Light off Off Control of water release, e.g. via MOZF control unit Setting without product: 1. Switch on light scanner → LED green shines. 2. Turn potentiometer # 1 all the way to the right limit = light-on 3. Turn potentiometer # 2 from the left (–) to the right (+) until LED yellow shines, then turn back so far until LED yellow goes out again. Light scanner is ready for operation. LED yellow #1 LED green #2 Operation with product: When product flows through the fitting, the light scanner switches and LED yellow shines. LED yellow MYFC-MOZF-66542-1-en-0803 LED green © Copyright 2008 Bühler AG Moisture controller 12 After-sales service 83 After-sales service 12.1 Spare parts When ordering spare parts please use the spare parts catalog 7952 and the relevant illustrations. These parts represent only a small selection of the most important parts. Please note that parts marked «b» should always be available as spare parts at the customer's site, because if this part fails, manual water dosing is no longer possible. a Wear parts b If defective: Automatic and manual mode no longer possible c If defective: Automatic mode no longer possible, manual mode possible MYFC Part name Part number Weighing cell 150 kg 1-PW10D1 UXE –26528-011 c 1 – Force transducer 3 Kg DB-11 UXE –26520-021 c 1 MDDM, MDDO Resistance thermometer UXE –26570-111 c 1 MYFB Inlet spout MZAH-82002-810 a 1 MZAH - 25 Segment slide MZAH-80018-810 a 1 MZAH - 25 Baffle plate complete MZAH-83009-810 a 1 MZAH - 25 MZAH-10002-010 c 1 MZAH UNS-16072-113 c 4 MZAH 2) UXE-26522-142 c 1 MZAH - 25 c 1 MZAH Valve assembly without magnet coil Magnet coil 24 V DC Force transducer Filter complete Qty. Also used for 1) MZAH-95010-810 1) The new valve assembly MZAH-10002-010 is not equipped with magnet coils anymore. A spare parts delivery for the valve assembly requires an additional 4 magnet coils. 2) Due to a change in the make/supplier of the force transducers not only the force transducer but also the spare parts kit MZAH-80007-810 is required for the first spare parts delivery. MOZF Part name Part number Qty. Also used for Filter insert MOZF 315, 1000, 2250 UNS –29015-011 a 1 MOZA, MOZD, MOZE MOZF 4500 UNS –29015-071 a 1 Filter unit MOZF H UNS –29015-085 a 1 – MOZF 315 C, 1000 C, 2250 C UNS –29015-013 a 1 – MOZF 4500C UNS –29015-080 a 1 – Filter unit UNS –29015-071 a 2 MOZF 4500 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 84 After-sales service Part name Moisture controller Part number Qty. Also used for Solenoid valve 2/2-ways MOZF UNS –16014-413 b 1 – MOZF H UNS –16008-261 b 1 – MOZF C UNS –16014-513 b 1 – MOZF 315, 1000, MOZF H UNS –16100-413 c 1 – MOZF 2250, 4500 UNS –16100-113 c 1 – MOZF 315 C, 1000 C UNS –16100-213 c 1 – MOZF 2250 C, 4500 C UNS –16100-313 c 1 – MOZF 315, 1000, MOZF H UNS –43041-001 c 1 – MOZF 2250, 4500 UNS –43041-003 c 1 – MOZF 315 C, 1000 C UNS –43041-011 c 1 – MOZF 2250 C, 4500 C UNS –43041-013 c 1 – Solenoid control valve 2/2-ways Flow meter Control system MYFC & MOZF Part name Part number Qty. Relay 24 V (MOZF) UNE-28040-651 b 1 Base PC-board EBD1268 (EKP-83121-810) c 1 EPROM with the latest program version (MYFC/MOZF) EKP-85228-810 Also used for Bühler check weighers with MEAF – Display unit (MYFC/MOZF) EKP-84172-810 c 1 Bühler check weighers with MEAF EBD1269 Mains / relay module (MYFC up until October 2004 delivery) EKP-84169-810 c 1 Bühler check weighers with MEAF EBD1293 MEAF-extension (MYFC) EKP-84235-810 c 1 – Profibus with connector (MYFC) EKP-83122-930 c 1 Bühler check weighers with MEAF Microwave assembly (MYFC) EKP-84144-810 c 1 MYFB Power pack AC 115/230 V (MOZF and also MYFC from October 2004 delivery onwards) UNE-80206-001 c 1 MYRE I/O-extension EBD1270 (MOZF) EKP-84170-810 c 1 Bühler check weighers with MEAF MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller After-sales service 85 12.2 Address Bühler AG Customer Service Grain Processing CH-9240 Uzwil, Switzerland Phone +41 71 955 30 40 Fax +41 71 955 33 05 service.gp@buhlergroup.com Note: When making any inquiries at Bühler AG use the information on the machine identification plate to identify the machine. © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 86 Appendix 13 Appendix Moisture controller 13.1 Parameter list MYFC Plant:.................................................... Name: ............................................................ Date:........................... Parameter [Default] SYS Set Value Parameter [Default] SVV REM DISP AINV IMP AO AI SD INIT = = = = = = = – A1 B1 C1 A2 B2 C2 P CALT PROD CAL0 CAL1 CAL4 CAL5 [0.40] [400.00] [0.75] [0.50] [280.00] [0.75] [80.0] [+0.05] 0 [+15.781] [+1.245] [-1.638] [-0.100] TCON MODE FMAX FCOR T1 T2 QMIN QMAX [MOIST] [60.000] [100.0] [3600] [300] [0.0] [4500.0] [LOC] [OFF] [ON] [100] [OFF] [OFF] [0] – ADC FLO ZFLO CFLO NIVS ZNIV WT ZWT CWT INTT CINT EXTT CEXT HF CHF – – [6.000] [60] – – – [3.000] – [-258.2] – [-258.2] – [10.00] – – = = – – – = – = – = – = HOST ADR BAUD TOUT [0] [4800] [60] = = = MYFC-MOZF-66542-1-en-0803 Set Value Enter settings from microwave module = = = = = = = = = = = = = = = = = = = © Copyright 2008 Bühler AG Moisture controller Appendix 87 13.2 Recipe list MYFC Plant:.................................................... Name: ............................................................ Date: .......................... No. MOIS [0] PROD OFFS DMAX Notes 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 88 Appendix Moisture controller 13.3 Parameter list MOZF Plant:.................................................... Name: ............................................................ Date:........................... Parameter SYS REM DISP AINV IMP AO AI SD INIT [Default] Set value [REMS] [OFF] [ON] [10.0] [0mA] [0mA] [USER.H2O] – = = = = = = = – HOST ADR BAUD TOUT [1] [4800] [60] = = = TCON MODE FMAX QMAX T1 WDLY QMIN WCNT CTRL [MYFC] [100.000] [4500.0] [3600] [0] [0.0] [105.7] [1] Parameter [Default] Set value = 2) = = 1) = = 1) = = 2) = 1) Only displayed if MODE = L-DOS or %-DOS 2) Only displayed if MODE = %-DOS MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Appendix 89 13.4 MYFC-65005 overview © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 90 Appendix Moisture controller 13.5 MYFC-65000 dimensional drawing MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Appendix 91 13.6 MOZF-65000 dimensional drawing standard and hot water version © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 92 Appendix Moisture controller 13.7 MOZF-65007 dimensional drawing chlorine version MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG Moisture controller Appendix 93 13.8 Wiring diagram MOZF © Copyright 2008 Bühler AG MYFC-MOZF-66542-1-en-0803 94 Appendix Moisture controller 13.9 Sample taking In order to check the MYFC only product before or directly after dampening should be used. Samples from B1 or even flour samples are out of the question, because they have been exposed to different environmental influences since dampening. The samples must be filled into glass jars and closed airtight. Freshly dampened product should frequently shaken for 15 min after extraction to stop the swelling product from sticking together. When taking samples the average current moisture, the current dosing rate and the time of the sample taking have to be noted down. Thus it is possible to check the operation of the automatic moisture control together with the laboratory results. 13.10 Moisture determination in the laboratory Practice has shown that only the carefully applied standard method according to ICC-Standard No. 110/1 provides reliable moisture values. We strongly advise against quick determinations for dampened products. Basic application of the standard method according to ICC-Standard N0. 110/1: (For details please refer to the Standard) Material: • Glass jars with airtight cover • Metal or glass dishes • Laboratory scale with a resolution of 1 mg • Laboratory mill • Drying cabinet (130 °C) • Exsiccator 1. Taking a sample: • Let wheat stand for min. 12 h in airtight closed glass jar. • Shake the glass jar frequently for the first 5…10 min to stop the wheat from sticking together. 2. Pre-drying (only if moisture > 15 %) • Weigh 20…35 g whole kernels of wheat into dish. Æ Weighing 1 • Pre-dry it in the oven for exactly 30 min at 130 °C. • Cooling at room temperature. • Reweighing Æ Reweighing 1 Æ Coarse water = Weighing 1 – Reweighing 1 3. • • • • • • Standard determination: Mill pre-dried wheat. Weigh exactly 10.000 g into dish. Dry it in the oven for exactly 90 min at 130 °C. Cooling in the exsiccator Tare scale with 10.000 g. Reweighing (displayed weight in g * 10 = moisture loss in %) Æ Reweighing 2 Æ Fine water = (Reweighing 2 : 100) x Reweighing 1 Æ Total water = Coarse water + Fine water Æ Moisture = (Total water x 100) : Weighing 1 MYFC-MOZF-66542-1-en-0803 © Copyright 2008 Bühler AG