Project : Ujung Pangkah Development Offshore Phase II ( CPP & AUP EPCC ) Location : CPP HVAC Tech Building Document No. : UPD-W4-11523-602-1039 Document Title : Instrument List / Index Revision : 01 Sr.No UPD-W4-11523-602-1039-01 Tag No Old Tag No Service Instrument Type Set Point Unit Signal Type IO Type IP Rating Ex Catergory Mounting AHU Casing 1 567-PDT-001 567-PDT-001 Differential Air Pressure ( Main Filter ) Transmitter 300 Pa 4-20 mA AI IP 67 Required. Zone 2 2 567-PDT-002 567-PDT-002 Differential Air Pressure ( Pre Filter ) Transmitter 150 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing 3 567-PDT-003 567-PDT-003 Differential Air Pressure ( FA Filter ) Transmitter 100 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing 4 567-PDT-004 567-PDT-004 Differential Air Pressure ( Blower ) Transmitter 450 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing 5 567-PDT-005 567-PDT-005 Differential Air Pressure ( Blower ) Transmitter 450 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing 6 567-PT-001 567-PT-001 Differential Air Pressure ( Exhaust Fan ) Transmitter 100 Pa 4-20 mA AI IP 67 Zone 2 Duct Mounted 7 567-PDT-431 567-PDT-431 Differential Air Pressure ( Room ) Transmitter 35 Pa 4-20 mA AI IP 67 Safe Wall 8 567-PDT-432 567-PDT-432 Differential Air Pressure ( Room ) Transmitter 35 Pa 4-20 mA AI IP 67 Safe Wall 9 567-PDT-433 567-PDT-433 Differential Air Pressure (Battery Room) Transmitter 20 Pa 4-20 mA AI IP 67 Zone 1 Wall 10 567-MTT-101 Humidity / Temperature ( Return Air ) Transmitter 24 / 50 o C/% 4-20 mA AI IP 65 Safe Duct Mounted 11 567-MTT-201 Humidity / Temperature ( Return Air ) Transmitter 24 / 50 o C/% 4-20 mA AI IP 65 Safe Duct Mounted Refrigerant Suction Pressure Transmitter 1 bar (g) 4-20 mA AI IP 67 Zone 2 Refrigeration Line Refrigerant Suction Pressure Switch 0.6 bar (g) - - IP 65 Zone 2 Refrigeration Line 10 ~ 12 bar (g) 4-20 mA AI IP 66 Zone 2 Refrigeration Line 567-PT-001A 12 567-PT-001A 13 567-PSL-001A 14 567-PT-002A 567-PT-002A Refrigerant Discharge Pressure Transmitter 15 567-PT-001B 567-PT-001B Refrigerant Suction Pressure Transmitter 1 bar (g) 4-20 mA AI IP 67 Zone 2 Refrigeration Line 16 567-PSL-001B Refrigerant Suction Pressure Switch 0.6 bar (g) - - IP 65 Zone 2 Refrigeration Line 17 567-PT-002B Transmitter 10 ~ 12 bar (g) 4-20 mA AI IP 66 Zone 2 Refrigeration Line 18 567-XY-021A Shut Off Damper - Unit A Solenoid Valve - - - - IP 67 Eex'd' Shut Off Damper 19 567-ZSO-021A Shut Off Damper - Unit A Limit Switch Open - - - IP 67 Ex'd' Shut Off Damper 20 567-ZSC-021A Shut Off Damper - Unit A Limit Switch Close - - - IP 67 Ex'd' Shut Off Damper 21 567-XY-021B Shut Off Damper - Unit B Solenoid Valve - - - - IP 67 Eex'd' Shut Off Damper 22 567-ZSO-021B Shut Off Damper - Unit B Limit Switch Open - - - IP 67 Ex'd' Shut Off Damper 23 567-ZSC-021B Shut Off Damper - Unit B Limit Switch Close - - - IP 67 Ex'd' Shut Off Damper 24 557-RY-022 Shut Off Damper - FA Solenoid Valve - - - - IP 67 Eex'd' Shut Off Damper 25 557-ZSO-022 Shut Off Damper - FA Limit Switch Open - - - IP 67 Ex'd' Shut Off Damper 26 557-ZSC-022 Shut Off Damper - FA Limit Switch Close - - - IP 67 Ex'd' Shut Off Damper 27 557-RY-101 F & G Damper - 557-RV-101 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 28 557-ZSO-101 F & G Damper - 557-RV-101 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 29 557-ZSC-101 F & G Damper - 557-RV-101 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 30 557-RY-102 F & G Damper - 557-RV-102 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 31 557-ZSO-102 F & G Damper - 557-RV-102 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 32 557-ZSC-102 F & G Damper - 557-RV-102 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 33 557-RY-103 F & G Damper - 557-RV-103 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 34 557-ZSO-103 F & G Damper - 557-RV-103 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 35 557-ZSC-103 F & G Damper - 557-RV-103 Close - - - IP 67 Ex'd' F & G Damper 36 557-RY-104 F & G Damper - 557-RV-104 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 37 557-ZSO-104 F & G Damper - 557-RV-104 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 38 557-ZSC-104 F & G Damper - 557-RV-104 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 39 557-RY-201 F & G Damper - 557-RV-201 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 40 557-ZSO-201 F & G Damper - 557-RV-201 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 41 557-ZSC-201 F & G Damper - 557-RV-201 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 567-PT-002B Refrigerant Discharge Pressure CPP HVAC Tech Building - Instrument List / Index 1 Project : Ujung Pangkah Development Offshore Phase II ( CPP & AUP EPCC ) Location : CPP HVAC Tech Building Document No. : UPD-W4-11523-602-1039 Document Title : Instrument List / Index Revision : 01 Sr.No Tag No Old Tag No Service Instrument Type Set Point Unit Signal Type IO Type IP Rating Ex Catergory Mounting F & G Damper 42 557-RY-202 F & G Damper - 557-RV-202 Solenoid Valve - - - - IP 67 Required. Eex'd' 43 557-ZSO-202 F & G Damper - 557-RV-202 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 44 557-ZSC-202 F & G Damper - 557-RV-202 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 45 557-RY-203 F & G Damper - 557-RV-203 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 46 557-ZSO-203 F & G Damper - 557-RV-203 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 47 557-ZSC-203 F & G Damper - 557-RV-203 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 48 557-RY-204 F & G Damper - 557-RV-204 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 49 557-ZSO-204 F & G Damper - 557-RV-204 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 50 557-ZSC-204 F & G Damper - 557-RV-204 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 51 557-RY-205 F & G Damper - 557-RV-205 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 52 557-ZSO-205 F & G Damper - 557-RV-205 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 53 557-ZSC-205 F & G Damper - 557-RV-205 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 54 557-RY-206 F & G Damper - 557-RV-206 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 55 557-ZSO-206 F & G Damper - 557-RV-206 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 56 557-ZSC-206 F & G Damper - 557-RV-206 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 57 557-RY-207 F & G Damper - 557-RV-207 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper 58 557-ZSO-207 F & G Damper - 557-RV-207 Limit Switch Open - - - IP 67 Ex'd' F & G Damper 59 557-ZSC-207 F & G Damper - 557-RV-207 Limit Switch Close - - - IP 67 Ex'd' F & G Damper 60 567-SOV-001A Refrigerant Liquid Line Solenoid Valve - - - - IP 67 Eex nA Refrigeration Line 61 567-SOV-002A Compressor Oil Injection Solenoid Valve - - - - - - Compressor 62 567-SOV-003A Capacity Control Valve - A Solenoid Valve - - - - - - Compressor 63 567-SOV-004A Capacity Control Valve - B Solenoid Valve - - - - - - Compressor 64 567-TS-001A Refrigerant Discharge Temperature Sensor - - - - - - Compressor 65 567-TS-002A Lube Oil Temperature Temp. Switch - - - - - - Compressor 66 567-LOL-001A Lube Oil Level - 1 Level Switch - - - - - - Compressor 67 567-LOL-002A Lube Oil Level - 2 Level Switch - - - - - - Compressor 68 567-FS-001A Lube Oil Flow Flow Switch - - - - - - Compressor 69 567-SOV-001B Refrigerant Liquid Line Solenoid Valve - - - - IP 67 Eex nA Refrigeration Line 70 567-SOV-002B Compressor Oil Injection Solenoid Valve - - - - - - Compressor 71 567-SOV-003B Capacity Control Valve - A Solenoid Valve - - - - - - Compressor 72 567-SOV-004B Capacity Control Valve - B Solenoid Valve - - - - - - Compressor 73 567-TS-001B Refrigerant Discharge Temperature Sensor - - - - - - Compressor 74 567-TS-002B Lube Oil Temperature Temp. Switch - - - - - - Compressor 75 567-LOL-001B Lube Oil Level - 1 Level Switch - - - - - - Compressor 76 567-LOL-002B Lube Oil Level - 2 Level Switch - - - - - - Compressor 77 567-FS-001B Lube Oil Flow Flow Switch - - - - - - Compressor 75 N.A Instrument Air Pressure Reducer c/w gauge Pressure Regulating 8 bar (g) - - - - Instrument Air Line System - A System - B Note : 1. The item indicated is part of compressor. It is supplied by Bitzer manufacturer and certified the compressor as explosion proof.. 2. Ex-proof junction box will be provided as necessary to suite project requirement ( For refrigerant pressure transmitters, etc,. ) 3. These items will be supplied as loose and shall be installed by other.( Maximim Inlet Pressure : 17 bar & Regulating Pressure 0.5 ~ 8 bar ) UPD-W4-11523-602-1039-01 CPP HVAC Tech Building - Instrument List / Index 2