Mechanical Smoke Ventilation Calculations For ………………………………… Mechanical Ventilation system for ……………………… Mf = Q g L2 p Cp T0 0.58 p 1/3 2 + 1+ 0.22 Z +2 L WHERE :Q p Cp g T0 L Z = = = = = = = Heat Flux = 5000 Density of smoke 1.2 Kg/m3 Specific Heat 1.01 Kj/KgK Gravity Accel. 9.81m/sec2 KW FOR Shoping Araes = = = = = = = = = = = Abs.Temp - Amb.Temp. 303 K Length of void edge past which gases spill Width of void 3 m Hight of rise of thermal plume above void edge H - d2 = 4.0 - 0.8 3.2 m Emprical hight of virtual source below void edge 0.3 H = 0.3 x 4 1.2 m THEN :- Mf = 0.58 p Mf = 5193.05 Q g L2 p Cp T0 1/3 3 2 + 1.2 1+ 0.22 Z + 2 1.2 3 2/3 2/3 Mechanical Smoke Ventilation Calculations For ………………………………… Mechanical Ventilation system for ……………………… # Assumptions:Fire Area = 3x3 = Smoke Plume High (Y) = Total height (H) = Smoke layer thickness (db) = H - Y = Floor Area = 9 2.5 3.5 1 sq.m M M M sq.m # Determining the heat release Q = q x A …………………………(1) where q = 93 KW/sq.M (for vehicles) Refference :- BS7436 tables with aid of NFBA 204M tables . From equation (1) Qs = 837 HEAT RELEASE = 93 KW/M2 FOR FURNATURE 310 KW/M2 FOR CELLULOSICS ()ورقكققارتونلققلتعبئه واققلتغليفو م نتجاتقققطنية 260 KW/M2 FOR VIHICLES(car park) kw # Determining smoke mass flow rate Ms Ms = 0.188 PY 3/2 ………………… (2) where P = Fire Perimeter = Y = Clear height of smoke plume = From equation (2) Ms = 0.188 x12 x 2.53/2 Ms = 8.9 kg/s. 12 M 2.5 M # Determining plume temperature rise : Qs dT = ………….(3) Ms x Cps dT = 93 K And Ts = To + DT …………………….(4) Where : Ts = Smoke temp. To =Ambient temp. = 303 K Ts = 396 K # Determining the required air flow rate : V = Ms Ts To ps ……………….(5) Where :V = Required air volumetric flow rate ps = Smoke density = 1.2 Kg/m3 V = = 9.7 M3/Sec. 20,584 CFM ~~= 21,000 CFM # Determining duct size and fan static pressure :V = A X v ………………………….(8) Where v = volumetric flow rate for one fan = OR. v = volumetric flow rate for one fan = A = duct cross sec. Area V = desired air velocity in the duct = 21,000 cfm 9.7 M3/Sec. 6 M/Sec. A = 1.62 M2 Static pressure ( in.wg) = 0.5 + duct friction loss where duct friction loss = 0.5 in.wg Total Static pressure ( in.wg) = 1 in.wg. Conclusion : System Discription : Exhaust Smoke Fans : Nunmers: 2 Nos. Fans/Zone Capacity: 10,500 cfm (each) Type : Tubilar ducted Location : …………………………………………. # Determining fresh air intake area : No. of entrances and doors = Average door size (m) = = Total fresh air intake area = V = AXv 2 2.2 4.4 8.8 input the sugested fans numbers here . If u put it as one it gives the total flow required . doors (width) , m2 m2 EDIT THE ACTUAL NO. AS PER ARCH. DRAWINGS . 2 (height) ………………………….(8) Where V = The required fresh air supply = 21,000 CFM = 9.7 M3/Sec. Assuming average air velocity through doors to be 2m/s ( to allow door opening for occupants evacuation ) in case if the enterances area A= 4.86 m2 is less than the required The required area is less than doors and enterance areas area , so, the fresh air fans SO, Enterance area is sufficient as fresh air supply openings . are required . Fresh Air Fans: Fresh Air Fans capacity shall be half of exhaust air capacity depending on the doors and park ramp opening to deliver adequate fresh air amount for the other half of the floor area . Fresh Air properties shall be : Nunmers: 2 Nos. Fans Capacity: 5,250 cfm (each) Type : Tubilar ducted Location : …………………………………………. Total Static pressure ( in.wg) = 1 in.wg. GENERAL - All fans used in smoke management and exhaust system ( exhaust and fresh air fans ) shall be capable to withstand 200 oC temp.for 30 min. - All fans shall be interconnected with fire allarm panel for automatic operation also, shall be provided with ON /OFF switch near enterances for manual operation by occupants. Mechanical Ventilation Calculations For Car Park ( Basement ) inter the floor area here 1-Mechanical Ventilation system inter the floor hight here Location Floor Area Floor Hiegh Floor Volume : : : = 690 Sq.M 3.5 M 2415 Cu.M follow the regulation for the area application , for basement 4times/hr. No. of air change per hour = 6 times Total air volume = = 14490 Cu.M 512014.1 Cu.Ft Total flow rate (cfm) = 8533.569 cfm <=> 9000 cfm Fan selection Fan Capacity No. of fans = = 1800 cfm 5 nos. fans CONCLUSION System Discription : Exhaust Smoke Fans : Nunmers: 5 Nos. Fans Capacity: 1,800 cfm (each) Type : Tubilar ducted Location : …………………………………………. according to plane (or the posibility to install many nos. of fans to reduce the cap. Of the fan . Stair Case Pressurization For Internal Stairs . No. Of Floors = No. Of Doors = Qe Gr. + (Gr.) Floors + + Roof = (Typical Floors) 2 Floors + (Roof ) = 0 Doors = KAe (P)1/2 Where : Ae = 0.003 x (( 2.2 + 0.8 ) x 2 ) x 0 = 0 M2 K = 0.839 P = 50 Pascal. Qe = 0.839 x Ae x (50)1/2 Qe = 0 M3/Sec. = 0 CFM Incase One Door Opened : Qo = VA 0.6 = 0.75 x 2.2 x 0.8 0.6 = 2.2 M3/Sec. = 4659.6 M3/Sec.