1.1.1. Medium voltage switchgear
1.1.1.1.
MV switchboard – General datas (SM6-MV24.16-06.common)
Type
Component
Manufacturer
Type
Nominal voltage
Nominal short-time withstand current
Nominal busbar current
Nominal frequency
Intermal ARC distance A-FLR
Altitude
Temperature
Temperature average over 24h
24
16
630
50
16
1000
-5..+40
35
MV switchgear
SM6-MV24.16-06.common
Schneider Electric
SM6
kV
kA (1sec)
A
Hz
kA (1 sec)
m
°C
°C
Description:
The Medium voltage cubicles are modular units designed as type-tested, metal-enclosed
and air insulated SF6 switchgear for indoor installation.
Standards:
Recommendations IEC:
60694: Common specifications for high-voltage switchgear and control gear standards.
62271-200: A.C. metal-enclosed switchgear and control gear for rated voltage above 1 kV and up to including 52
kV.
60265: High voltage switches for rated voltages of 52 kV and above.
62271-105: High voltage alternating current switch-fuse combinations.
60255: Electrical relays.
62271-100: High-voltage alternating current circuit breakers.
62271-102: High-voltage alternating current disconnectors and earthing switches.
UTE standards:
NFC 13.100: Consumer substation installed inside a building and fed by a second category voltage public
distribution system.
NFC 13.200: High voltage electrical installations requirements.
NFC 64.130: High voltage switches for rated voltage above 1 kV and less than 52 kV.
NFC 64.160: Alternating current disconnectors and earthing switches.
EDF specifications:
HN 64-S-41: A.C. metal-enclosed switchgear and control gear for rated voltages above 1 kV and up to and
including 24 kV.
HN 64-S-43: Electrical independent-operating mechanism for switch 24 kV - 400 A.
Scope of delivery:
Medium voltage switchgear incl. engineering, planning and protection settings for delivered
scope and related cabling.
Accessories: (included if needed for delivered items)
1set Unigear single end cover
1pc Operating lever for earthing switch
1pc Operating lever for load breaker / disconnector switch
Not included:
The offer does not include a pressure shock calculation. The client is responsible for the
adequate design of the MV switchyard room in order to have relevant openings for pressure
equalization in case of short circuit failure.
1.1.1.2.
MV circuit breaker feeder (SM6-MV24.16-06.CB06)
Type
Component
Manufacturer
Type
Nominal voltage
Schort circuit current
Nominal busbar current
Nominal outgoing current
24
16
630
630
MV CB feeder
SM6-MV24.16-06.CB06
Schneider
SM6
kV
kA (1s)
A
A
Description:
Circuitbreaker feeder with fix installed CB, cable side
earther, current and voltage transformers according to
the detailed technical description.
Hardware description:
Circuit breaker
Actuator
Auxiliary contacts
Local-Remote-control
Load breaker and earthing switch
Actuator
Auxiliary contacts
Cable earthing switch
Actuator
Auxiliary contacts
Current transformer
Core 1:
Core 2:
Voltage transformer
Winding 1:
Winding 2:
Additional
Capacitive voltage detector
Bus bar
Low voltage department
Heating
Design if used for generator feeder
Under voltage coil
Synchronizeable
Local-Remote-Control
1
Yes
Yes
Yes
1
Manual
Yes
1
Manual
Yes
3
3
pc
pc
pc
xx/1/1A
1 A / 0,5FS 5 / 10 VA
1 A / 5P20 / 10 VA
xx/V3 / 0,1/V3 / 0,1/3 kV
Cl. 0,5 / 15 VA
Cl. 3P / 15 VA
Yes
3pole
Yes
Yes
Yes
Yes
No
(only remote, synchronizer)
1.1.1.3.
Generator protection relay (MV.EnergyG32)
Type
Component
Manufacturer
Model
Type
Description
Generatorprotectionrelay designed for door mounting,
useable for generator- or block differential protection.
Technical datas:
Supply voltage
I/O Card
Communication interface
Current measurement
Protection functions:
Under-impedance
Overfluxing
Synchrocheck
Undervoltage
Reverse power
Loss of field
Negative sequence overcurrent
Incorrect phase sequence
Phase overcurrent
Earth fault overcurrent
Breaker failure
Over voltage
Stator earth fault
Directional phase overcurrent
Pole Slip
Frequency
Machine differential
80-265
1/5
21G
24
25
27
32
40
46
47
50/51
50N/51N
50BF
59
64S
67
78PS
81
87M
MV protection
MV.EasergyG32
Schneider Electric
Easergy (or equal)
P3G32 (or equal)
VAC/DC
6DI+4DO
IEC61850
A
Generator- or Blockdifferential protection
1.1.1.4.
MV own use feeder (SM6-MV24-06.AuxTrafo)
Type
Component
Manufacturer
Type
Nominal Voltage
Nominal busbar current
Nominal outgoing current
24
630
MV own use feeder
SM6-MV24-06. AuxTrafo
Schneider Electric
SM6
kV
A
Fuses acc. nominal current of the
transformer
Functional description:
To be used for supplying the auxiliary transformer.
Hardware description:
MV fuses
Type
Spare fuses
Load breaker and earthing switch
Actuator
Auxiliary contacts
Working release
Cable earthing switch
Actuator
Auxiliary contacts
Additional
Capacitive voltage detector
Bus bar
Low voltage department
Heating
3
Yes
1
Manual
Yes
Yes
1
Manual
Yes
pc
DIN
pc
pc
Yes
3pole
Yes
Yes
1.1.1.5.
MV voltage measurement feeder (SM6-MV24-06.BB.Meas)
Type
Component
Manufacturer
Type
Nominal voltage
Busbar current
24
630
MV voltage measurement
feeder
SM6-MV24-06.BB.Meas
Schneider Electric
SM6
kV
A
Functional description:
To be used for measuring the bus bar voltage, this is
necessary for synchronisation.
Hardware description:
MV Fuses
Type
Spare fuses
Load breaker and earthing switch
Actuator
Auxiliary contacts
Working release
Cable earthing switch
Actuator
Auxiliary contacts
Additional
Capacitive voltage detector
Bus bar
Low voltage department
Heating
Voltage transformer
Winding 1:
Winding 2:
3
NO
1
Manual
Yes
No
1
Manual
Yes
pc
DIN
pc
pc
Yes
3pole
Yes
Yes
3
xx/V3 / 0,1/V3 / 0,1/3 kV
Cl. 0,5 / 15 VA
Cl. 3P / 15 VA
1.1.1.6.
Protection relay for grid connection (MV.EasergyU30)
Type
Component
Manufacturer
Model
Type
Description
Protection relay for usage in a simple grid feeder.
Technical datas:
Supply voltage
I/O Card
Communication interface
Current measurement
Protection functions:
Fault locator
Undervoltage
Underpower
Phase undercurrent
Thermal overload
Phase overcurrent
Earth fault overcurrent
Breaker failure
Overvoltage
Neutral voltage displacement
Directional phase overcurrent
Frequency
Rate of change of frequency
MV protection
MV.EasergyU30
Schneider Electric
Easergy (or equal)
P3U30 (or equal)
80-265
1/5
21FL
27
32
37
49
50/51
50N/51N
50BF
59
59N
67
81/81U
81R
VAC/DC
6DI+4DO
IEC61850
A
Download