Uploaded by ingeniero.shadai

505377-UEN TM D670I 2p2-153-240

advertisement
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Section 7
7.1
7.1.1
Differential protection
High impedance differential protection, single phase
HZPDIF
Identification
IP14239-1 v4
M14813-1 v4
IEC 61850
identification
Function description
High impedance differential protection,
single phase
IEC 60617
identification
Id
HZPDIF
ANSI/IEEE C37.2
device number
87
SYMBOL-CC V2 EN-US
7.1.2
Functionality
M13071-3 v13
High impedance differential protection, single phase (HZPDIF) functions can be used when the
involved CT cores have the same turns ratio and similar magnetizing characteristics. It utilizes an
external CT secondary current summation by wiring. Actually all CT secondary circuits which are
involved in the differential scheme are connected in parallel. External series resistor, and a voltage
dependent resistor which are both mounted externally to the IED, are also required.
The external resistor unit shall be ordered under IED accessories in the Product Guide.
HZPDIF can be used to protect tee-feeders or busbars, reactors, motors, auto-transformers,
capacitor banks and so on. One such function block is used for a high-impedance restricted earth
fault protection. Three such function blocks are used to form three-phase, phase-segregated
differential protection.
7.1.3
Function block
M13737-3 v3
HZPDIF
ISI*
BLOCK
BLKTR
TRIP
ALARM
MEASVOLT
IEC05000363-2-en.vsd
IEC05000363 V2 EN-US
Figure 39:
7.1.4
HZPDIF function block
Signals
IP14244-1 v2
PID-6990-INPUTSIGNALS v1
Table 83:
HZPDIF Input signals
Name
Type
Default
Description
ISI
GROUP
SIGNAL
-
Single phase current input
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Block of trip
Line differential protection RED670
Technical manual
147
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
PID-6990-OUTPUTSIGNALS v1
Table 84:
HZPDIF Output signals
Name
7.1.5
Type
Description
TRIP
BOOLEAN
Trip signal
ALARM
BOOLEAN
Alarm signal
MEASVOLT
REAL
Measured RMS voltage on CT secondary side
Settings
IP14245-1 v2
PID-6990-SETTINGS v1
Table 85:
HZPDIF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
U>Alarm
5 - 500
V
1
10
Alarm voltage level in volts on CT
secondary side
tAlarm
0.000 - 60.000
s
0.001
5.000
Time delay to activate alarm
U>Trip
10 - 900
V
1
100
Operate voltage level in volts on CT
secondary side
SeriesResistor
50 - 20000
Ohm
1
250
Value of series resistor in Ohms
7.1.6
Monitored data
PID-6990-MONITOREDDATA v1
Table 86:
HZPDIF Monitored data
Name
MEASVOLT
7.1.7
Type
REAL
Values (Range)
-
Unit
kV
Operation principle
Description
Measured RMS voltage on CT
secondary side
IP14242-1 v2
M13075-3 v11
High impedance protection system is a simple technique which requires that all CTs, used in the
protection scheme, have relatively high knee point voltage, similar magnetizing characteristic and the
same ratio. These CTs are installed in all ends of the protected object. In order to make a scheme all
CT secondary circuits belonging to one phase are connected in parallel. From the CT junction points
a measuring branch is connected. The measuring branch is a series connection of one variable
setting resistor (or series resistor) RS with high ohmic value and an over-current element. Thus, the
high impedance differential protection responds to the current flowing through the measuring branch.
However, this current is result of a differential voltage caused by this parallel CT connection across
the measuring branch. Non-linear resistor (that is, metrosil) is used in order to protect entire scheme
from high peak voltages which may appear during internal faults. Typical high impedance differential
scheme is shown in Figure 40. Note that only one phase is shown in this figure.
148
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
RS
3
I
U
1
I> (50)
5
4
2
GUID-5CEAF088-D92B-45E5-B98F-3083894A694C V1 EN-US
Figure 40:
HZPDIF scheme
Where in the Figure:
1.
2.
shows one main CT secondary winding connected in parallel with all other CTs, from the same
phase, connected to this scheme.
shows the scheme earthing point.
It is of utmost importance to insure that only one earthing point exists in such
protection scheme.
3.
4.
shows the setting (stabilizing) resistor RS.
shows the over-current measuring element.
The series connection of stabilizing resistor and over-current element is
designated as measuring branch.
5.
6.
7.
shows the non-linear resistor (that is, metrosil).
U is the voltage across the CT paralleling point (for example, across the measuring branch).
I is the current flowing through the measuring branch.
U and I are interrelated in accordance with the following formula U=RS × I.
Due to the parallel CT connections the high impedance differential relay can only measure one
current and that is the relay operating quantity. That means that there is no any stabilizing quantity
(that is, bias) in high-impedance differential protection schemes. Therefore in order to guaranty the
stability of the differential relay during external faults the operating quantity must not exceed the set
pickup value. Thus, for external faults, even with severe saturation of some of the current
transformers, the voltage across the measuring branch shall not rise above the relay set pickup
value. To achieve that a suitable value for setting resistor RS is selected in such a way that the
saturated CT secondary winding provides a much lower impedance path for the false differential
current than the measuring branch. In case of an external fault causing current transformer
saturation, the non-saturated current transformers drive most of the spill differential current through
the secondary winding of the saturated current transformer and not through the measuring brunch of
the relay. The voltage drop across the saturated current transformer secondary winding appears also
across the measuring brunch, however it will typically be relatively small. Therefore, the pick-up value
of the relay has to be set above this false operating voltage.
See the application manual for operating voltage and sensitivity calculation.
Line differential protection RED670
Technical manual
149
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
7.1.7.1
1MRK 505 377-UEN Rev. P
Logic diagram
M13075-9 v5
The logic diagram shows the operation principles for the 1Ph High impedance differential protection
function HZPDIF, see Figure 41.
The function utilizes the raw samples from the single phase current input connected to it. Thus the
twenty samples per fundamental power system cycle are available to the HZPDIF function. These
current samples are first multiplied with the set value for the used stabilizing resistor in order to get
voltage waveform across the measuring branch. The voltage waveform is then filtered in order to get
its RMS value. Note that used filtering is designed in such a way that it ensures complete removal of
the DC current component which may be present in the primary fault current. The voltage RMS value
is then compared with set Alarm and Trip thresholds. Note that the TRIP signal is intentionally
delayed on drop off for 30 ms within the function. The measured RMS voltage is available as a
service value from the function. The function has block and trip block inputs available as well.
IEC05000301 V1 EN-US
Figure 41:
7.1.8
Logic diagram for 1Ph High impedance differential protection HZPDIF
Technical data
IP14246-1 v1
M13081-1 v13
Table 87:
HZPDIF technical data
Function
Range or value
Accuracy
Operate voltage
(10-900) V
I=U/R
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio
>95% at (30-900) V
-
Maximum continuous power
See1)
-
Operate time at 0 to 10 x Ud
Min. = 5 ms
Max. = 15 ms
Reset time at 10 x Ud to 0
Min. = 75 ms
Max. = 95 ms
Critical impulse time
2 ms typically at 0 to 10 x Ud
-
Table continues on next page
150
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Function
Range or value
Accuracy
Operate time at 0 to 2 x Ud
Min. = 25 ms
Max. = 35 ms
Reset time at 2 x Ud to 0
Min. = 50 ms
Max. = 70 ms
Critical impulse time
15 ms typically at 0 to 2 x Ud
-
1) The value U2Trip/ R should always be lower than Stabilizing resistor thermal rating to allow continuous activation
during testing. If this value is exceeded, testing should be done with a transient faults. Typical value for the thermal
rating of the resistor is 100W.
7.2
7.2.1
Low impedance restricted earth fault protection
REFPDIF
Function revision history
Document
revision
7.2.2
Product
revision
IP14640-1 v6
GUID-BFAA47D8-C2B6-4EC2-9129-B031333BAD19 v2
History
A
2.2.1
-
B
2.2.1
-
C
2.2.1
-
D
2.2.2
-
E
2.2.2
-
F
2.2.2
-
G
2.2.3
-
H
2.2.3
-
J
2.2.3
-
K
2.2.3
-
L
2.2.4
-
M
2.2.4
The upper limit of ROA setting range is changed from 90 degrees to 119
degrees.
N
2.2.5
-
Identification
M14843-1 v6
Function description
Restricted earth fault protection, low
impedance
IEC 61850
identification
IEC 60617
identification
REFPDIF
ANSI/IEEE C37.2
device number
87N
IdN/I
SYMBOL-AA V1 EN-US
Line differential protection RED670
Technical manual
151
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
7.2.3
1MRK 505 377-UEN Rev. P
Functionality
IP12418-1 v2
M13047-3 v20
Restricted earth-fault protection, low-impedance function (REFPDIF) can be used on all directly or
low-impedance earthed windings. The REFPDIF function provides high sensitivity and high speed
tripping as it protects each winding separately and thus does not need inrush stabilization.
The REFPDIF function is a percentage biased function with an additional zero sequence current
directional comparison criterion. This gives excellent sensitivity and stability during through faults.
REFPDIF can also protect autotransformers. Five currents are measured at the most complicated
configuration as shown in Figure 42.
CT
YNdx
CT
CT
CB
CB
d
Y
CB
CB
Autotransformer
CT
IED
The most typical
application
CT
CB
CB
CT
The most complicated
application - autotransformer
IEC05000058-2-en.vsd
IEC05000058-2 V1 EN-US
Figure 42:
7.2.4
Examples of applications of the REFPDIF
Function block
M13736-3 v9
REFPDI F
I3P*
I3PW1CT1*
I3PW1CT2*
I3PW2CT1*
I3PW2CT2*
BLOCK
TRIP
START
DIROK
BLK2H
IRES
IN
IBIAS
IDIFF
ANGLE
I2RATIO
IEC06000251-3-en.vsdx
IEC06000251 V3 EN-US
Figure 43:
REFPDIF function block
152
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
7.2.5
Section 7
Differential protection
Signals
IP12658-1 v2
PID-7411-INPUTSIGNALS v1
Table 88:
REFPDIF Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for neutral current input
I3PW1CT1
GROUP
SIGNAL
-
Group signal for primary CT1 current input
I3PW1CT2
GROUP
SIGNAL
-
Group signal for primary CT2 current input
I3PW2CT1
GROUP
SIGNAL
-
Group signal for secondary CT1 current input
I3PW2CT2
GROUP
SIGNAL
-
Group signal for secondary CT2 current input
BLOCK
BOOLEAN
0
Block of function
PID-7411-OUTPUTSIGNALS v1
Table 89:
REFPDIF Output signals
Name
7.2.6
Type
Description
TRIP
BOOLEAN
Trip by restricted earth fault protection function
START
BOOLEAN
Start by restricted earth fault protection function
DIROK
BOOLEAN
Directional Criteria has operated for internal fault
BLK2H
BOOLEAN
Block due to 2-nd harmonic
IRES
REAL
Magnitude of fund. freq. residual current
IN
REAL
Magnitude of fund. freq. neutral current
IBIAS
REAL
Magnitude of the bias current
IDIFF
REAL
Magnitude of fund. freq. differential current
ANGLE
REAL
Direction angle from zerosequence feature
I2RATIO
REAL
Second harmonic ratio
Settings
IP12660-1 v2
PID-7411-SETTINGS v1
Table 90:
REFPDIF Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
Table 91:
1 - 12
Unit
-
Step
1
Default
1
Description
Selection of one of the Global Base
Value groups
REFPDIF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IdMin
4.0 - 100.0
%IB
0.1
10.0
Maximum sensitivity in % of IBase
CTFactorPri1
1.0 - 10.0
-
0.1
1.0
CT factor for HV side CT1 (CT1rated/
HVrated current)
Table continues on next page
Line differential protection RED670
Technical manual
153
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Name
Values (Range)
Unit
Step
Default
Description
CTFactorPri2
1.0 - 10.0
-
0.1
1.0
CT factor for HV side CT2 (CT2rated/
HVrated current)
CTFactorSec1
1.0 - 10.0
-
0.1
1.0
CT factor for MV side CT1 (CT1rated/
MVrated current)
CTFactorSec2
1.0 - 10.0
-
0.1
1.0
CT factor for MV side CT2 (CT2rated/
MVrated current)
Table 92:
REFPDIF Group settings (advanced)
Name
Values (Range)
Unit
ROA
60 - 119
7.2.7
Monitored data
Step
Deg
1
Default
60
Description
Relay operate angle for zero sequence
directional feature if protected winding
neutral point is grounded via resistor
increase ROA to 115 degrees
PID-7411-MONITOREDDATA v1
Table 93:
Name
REFPDIF Monitored data
Type
Values (Range)
Unit
Description
IRES
REAL
-
A
Magnitude of fund. freq. residual current
IN
REAL
-
A
Magnitude of fund. freq. neutral current
IBIAS
REAL
-
A
Magnitude of the bias current
IDIFF
REAL
-
A
Magnitude of fund. freq. differential
current
ANGLE
REAL
-
deg
Direction angle from zerosequence
feature
I2RATIO
REAL
-
-
Second harmonic ratio
7.2.8
Operation principle
7.2.8.1
Fundamental principles of the restricted earth fault protection
IP16290-1 v2
M5447-3 v16
Restricted earth fault protection, low impedance function (REFPDIF) detects earth faults on earthed
power transformer windings, most often an earthed star winding. REFPDIF is a unit protection of the
differential type. Since REFPDIF is based on the zero sequence current, which theoretically only
exists in case of an earth fault, REFPDIF can be made very sensitive regardless of normal load
currents. It is the fastest protection a power transformer winding can have. The high sensitivity and
the high speed tend to make such a protection unstable. Special measures must be taken to make it
insensitive to conditions for which it should not operate, for example, heavy through faults of phaseto-phase type or heavy external earth faults.
REFPDIF is a differential protection of the low impedance type. All three-phase currents, and the
neutral point current, must be fed separately to REFPDIF. The fundamental frequency components of
all currents are extracted from all input currents, while other eventual zero sequence components,
such as the 3rd harmonic currents, are fully suppressed. Then the residual current phasor is
calculated from the three line current phasors. This zero sequence current phasor is added to the
neutral current vectorially, in order to obtain differential current.
The following facts may be observed from Figure 44 and Figure 45, where the three line CTs are
shown as connected together in order to measure the residual 3Io current, for the sake of simplicity.
154
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
These three
zero-sequence
currents are not measured
zone of protection
Izs1
L1
Power
system
L1
Izs1
L2
L2
Izs1
L3
L3
3Izs1
Uzs
IL1+ IL2+IL3 = 3I0
3I0 = 3Izs1
Ifault
Current in the neutral
(measured as IN ) serves
as a directional reference
because it has the same
direction for both internal
and external faults.
IN = -3Izs1
(Summation in the IED)
Return path through
transformer
Return path via
power system
External
fault
region
block
operate
Zero-sequence differential
current for external fault
Idiff = abs(3I0 + IN )
Idiff = 3Izs1 - 3Izs1 = 0
IN
3I0
block
ROA
External
fault
region
Internal
fault
region
block
ROA = Relay Operate Angle
IEC09000107-3-en.vsd
IEC09000107-3 V1 EN-US
Figure 44:
Zero sequence currents at an external earth fault
zone of protection
L1
Power
system
L2
L3
Izs2
Izs1
Izs2
Izs1
Izs2
Izs1
L1
L2
L3
3Izs1
Uzs
IL1+ IL2+IL3 = 3I0
3I0 = -3Izs2
IN = -3Izs1
Ifault
(Summation in the IED)
Current in the neutral
(measured as IN ) serves
as a directional reference
because it has the same
direction for both internal
and external faults.
Return path
through transformer
Return path via
power system
External
fault
region
block
3I0
block
External
fault
region
operate
ROA
block
IN (reference)
Zero-sequence differential
current for internal fault
Idiff = abs(3I0 + IN )
Idiff = 3Izs2 + 3Izs1 > 0
Idiff = Ifault
Internal
fault
region
ROA = Relay Operate Angle
IEC09000108-3-en.vsd
IEC09000108-3 V1 EN-US
Figure 45:
1.
2.
Zero sequence currents at an internal earth fault
For an external earth fault (Figure 44), the residual current 3Io and the neutral current IN have
equal magnitude, but they are seen within the IED as 180 degrees out-of-phase if the current
transformers are connected as in Figure 44, which is the Hitachi Power grids recommended
connection. The differential current becomes zero as both CTs ideally measure exactly the same
component of the earth fault current.
For an internal fault, the total earth fault current is composed generally of two zero sequence
currents. One zero sequence current (3IZS1) flows towards the power transformer neutral point
and into the earth, while the other zero sequence current (3IZS2) flows into the connected power
system. These two primary currents can be expected to have approximately opposite directions
(about the same zero sequence impedance angle is assumed on both sides of the earth fault).
Line differential protection RED670
Technical manual
155
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
3.
4.
However, on the secondary CT sides of the current transformers, they will be approximately in
phase if the current transformers are oriented as in Figure 42, which is the orientation
recommended by Hitachi Power grids. The magnitudes of the two currents may be different,
dependent on the magnitudes of zero sequence impedances on both sides. No current can flow
towards the power system, if the only point where the system is earthed, is at the protected
power transformer. Likewise, no current can flow into the power system, if the winding is not
connected to the power system (circuit breaker open and power transformer energized from the
other side).
For both internal and external earth faults, the current in the neutral connection IN always has
the same direction, which is towards the earth (except in case of autotransformers where the
direction can vary).
The two internally processed zero sequence currents are 3Io and IN. The vectorial sum is the
REFPDIF differential current, which is equal to Idiff = IN +3Io .
The line zero sequence (residual) current is calculated from 3 line (terminal) currents. A bias quantity
must give stability against false operations due to high through fault currents. To stabilize REFPDIF
at external faults, an operate-bias characteristic is used.
REFPDIF should also be stable against heavy phase-to-phase internal faults, not including earth.
These faults may also give false zero sequence currents due to saturated line CTs. Such faults,
however are without neutral current, and can thus be eliminated as a source of danger.
As an additional measure against unwanted operation, a directional check is made in agreement with
the above points 1 and 2. Operation is only allowed if the currents 3Io and IN (as shown in Figure 44
and Figure 45) are both within the operating region. By taking a smaller ROA, REFPDIF can be
made more stable under heavy external fault conditions, as well as under the complex conditions,
when external faults are cleared by other protections.
7.2.8.2
Restricted earth fault protection, low impedance differential protection
M5447-20 v14
Restricted earth fault protection, (REFPDIF) is a protection of low impedance differential type, a unit
protection, whose settings are independent of any other protection. It has some advantages
compared to the transformer differential protection. It is less complicated, as no current phase
correction or magnitude correction is needed, not even in the case of an eventual on-load tap
changer (OLTC). REFPDIF is not sensitive to inrush and overexcitation currents. The thing to take
into account is an eventual current transformer saturation.
The differential protection REFPDIF calculates a differential current and a bias current. In case of
internal earth faults, the differential current is theoretically equal to the total earth fault current. The
bias to give stability to REFPDIF. The bias current is a measure of how high the currents are and how
difficult the conditions are under which the CTs operate. With a high bias, difficult conditions can be
suspected, and it will be more likely that the calculated differential current has a component of a false
current, primarily due to CT saturation. This “law” is formulated by the operate-bias characteristic.
This characteristic divides the Idiff - Ibias plane in two areas. The area above the operate-bias
characteristic is the operate area (trip), while the one below is the restrain (block) area, see Figure
47.
Calculation of operate bias characteristic
End of zone 1:
Endzone1 = 125%
End of zone 2:
Endzone2 =
156
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
EndZone2 = 125 +
(100 − IdMin)
0.7
(Equation 2)
IECEQUATION20201 V1 EN-US
SlopeSection2:
The slope in section 2 (see Figure 47) of operate-restrain characteristic is fixed to 70%. The slope
section 2, starts at end of zone 1, continues until end of zone 2.
SlopeSection3:
The slope in section 3 (see Figure 47) of operate-restrain characteristic is fixed to 100%. The slope
section 3, starts at end of zone 2 and continues.
REFPDIF uses an operate-bias characteristic shown in Figure 47, using a setting IdMin see Table 7.
Table 95:
Setting range of IdMin, end zones and slopes
IdMin default
(zone 1)
% of IBase
IdMin min (zone
1)
% of IBase
10
4
IdMin max (zone
1)
% of IBase
100
End of zone 1
(fixed)
% of IBase
125
Slope section 2
(fixed)
% of IBase
70
Slope section 3
(fixed)
% of IBase
100
IEC20000410-1-en.vsdx
IEC20000410 V1 EN-US
Figure 47:
Representation of Operate-bias characteristics at different IdMin setting values
Figure 47 represents the Operate-bias characteristics at different IdMin setting values
The highest individual current contribution is taken as a common bias (restrain) current among all
phase currents or neutral current. This "maximum principle" makes the differential protection more
secure, with less risk to operate for external faults and in the same time brings more meaning to the
breakpoint settings of the operate-restrain characteristic.
7.2.8.3
Calculation of differential current and bias current
M5447-47 v13
The differential current (operate current), as a fundamental frequency phasor, is calculated as (with
designations as in Figure 44 and Figure 45):
Line differential protection RED670
Technical manual
157
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Idiff = IN + 3 Io
(Equation 3)
EQUATION1533 V1 EN-US
where:
IN is current in the power transformer neutral as a fundamental frequency phasor.
3Io is residual current of the power transformer terminal currents as a phasor.
If there are two three-phase CT inputs, as in breaker-and-a-half configurations, then their respective
residual currents are added within the REFPDIF function so that:
I3PW1 = I3PW1CT1 + I3PW1CT2
where the signals are defined in the input and output signal tables for REFPDIF.
The bias current is a measure (expressed internally as a true fundamental frequency current in
Amperes) of how difficult the conditions are under which the instrument current transformers operate.
Dependent on the magnitude of the bias current, the corresponding zone (section) of the operatebias characteristic is applied, when deciding whether to trip, or not to trip. In general, the higher the
bias current, the higher the differential current required to produce a trip.
The bias current is the highest current of all separate input currents to REFPDIF, that is, of current in
phase L1, phase L2, phase L3, and the current in the neutral point (designated as IN in Figure and
in Figure Figure).
If there are two feeders included in the zone of protection of REFPDIF, as in case of an autotransformer with two feeders included on both sides, then the respective bias current is found as the
relatively highest of the following currents:
current 1 = max( I 3PW 1CT1) 
1
CTFactor Pr i1
(Equation 4)
EQUATION1526 V2 EN-US
current  2 = max( I 3PW 1CT 2) 
1
CTFactor Pr i 2
(Equation 5)
EQUATION1527 V2 EN-US
current 3 = max( I 3PW 2CT1) 
1
CTFactorSec1
(Equation 6)
EQUATION1528 V2 EN-US
current  4 = max( I 3PW 2CT 2) 
1
CTFactorSec2
(Equation 7)
EQUATION1529 V2 EN-US
current 5 = IN
(Equation 8)
EQUATION1530 V2 EN-US
The bias current is thus generally equal to none of the input currents. If all primary ratings of the CTs
were equal to IBase, then the bias current would be equal to the highest current in Amperes. IBase
shall be set equal to the rated current of the protected winding where REFPDIF function is applied.
7.2.8.4
Detection of external earth faults
M5447-75 v12
External faults are more common than internal earth faults for which the restricted earth fault
protection should operate. It is important that the restricted earth fault protection remains stable
158
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
during heavy external earth and phase-to-phase faults, and also when such a heavy external fault is
cleared by some other protection such as overcurrent, or earth fault protection. The conditions during
a heavy external fault, and particularly immediately after the clearing of such a fault may be complex.
The circuit breaker’s poles may not open exactly at the same moment, some of the CTs may still be
highly saturated, and so on.
The detection of external earth faults is based on the fact that for such a fault a high neutral current
appears first, while a false differential current only appears if one or more current transformers
saturate.
An external earth fault is thus assumed to have occurred when a high neutral current suddenly
appears, while at the same time the differential current Idiff remains low, at least for a while. This
condition must be detected before a trip request is placed within REFPDIF. Any search for external
fault is aborted if a trip request has been placed. A condition for a successful detection is that it takes
not less than 4ms for the first CT to saturate.
For an internal earth fault, a true differential current develops immediately, while for an external fault
it only develops if a CT saturates. If a trip request comes first, before an external fault could be
positively detected, then it must be an internal fault.
If an external earth fault has been detected, then the REFPDIF is temporarily desensitized.
Directional criterion
M5447-110 v13
The directional criterion is applied in order to positively distinguish between internal and external
earth faults. This check is an additional criterion, which should prevent malfunctions at heavy
external earth faults, and during the disconnection of such faults by other protections. Earth faults on
lines connecting the power transformer occur much more often than earth faults on a power
transformer winding. It is important that the Restricted earth fault protection, low impedance
(REFPDIF) must remain stable during an external fault, and immediately after the fault has been
cleared by some other protection.
For an external earth faults with no CT saturation, the residual current in the lines (3Io) and the
neutral current (IN in Figure 44) are theoretically equal in magnitude and are 180 degrees out-ofphase. The current in the neutral (IN) serves as a directional reference because it has the same
direction for both internal and external earth faults. The directional criterion in REFPDIF protection
makes it a current-polarized protection.
However, if one or more CTs saturate under external fault conditions, then the measured currents 3Io
and IN may no longer be equal, nor will their positions in the complex plane be exactly 180 degrees
apart. There is a risk that the resulting false differential current Idiff enters the operate area of the
operate-restrain characteristic under external fault conditions. If this happens, a directional test may
prevent a malfunction.
A directional check is only executed if:
1.
2.
a trip request signal has been issued (REFPDIF function START signal set to 1)
the residual current in lines (3Io) is at least 3% of the IBase current.
If a directional check is either unreliable or not possible to do, due to too small currents, then the
direction is cancelled as a condition for an eventual trip.
If a directional check is executed, the REFPDIF protection operation is only allowed if currents 3Io
and IN (as seen in Figure 44 and Figure 45) are both within the operating region determined by the
set value of ROA, in degrees.
ROA = 60 to 119 deg; where ROA stands for Relay Operate Angle.
Second harmonic analysis
M5447-106 v13
When energizing a transformer a false differential current may appear in earth fault protection, low
impedance function (REFPDIF). The phase CTs may saturate due to a high DC component with a
Line differential protection RED670
Technical manual
159
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
long duration, but the current through the neutral CT does not have either the same DC component
or the same amplitude and the risk for saturation of this CT is not as high. As a result, the differential
current due to the saturation may be so high that it reaches the operate characteristic. A calculation
of the content of 2nd harmonic in the neutral current is made when the neutral current, residual
current and bias current are within some windows and some timing criteria are fulfilled. If the ratio
between second and fundamental harmonic exceeds the preset value of 40% 40%, REFPDIF is
blocked.
7.2.8.5
Algorithm of the restricted earth fault protection
M5447-95 v14
1.
Check if current in the neutral Ineutral (IN) is less than 50% of the base sensitivity Idmin. If yes,
only service values are calculated, and rest of the REFPDIF algorithm is not executed.
2. If current in the Ineutral (IN) is more than 50% of Idmin, then determine the bias current Ibias.
3. Determine the differential (operate) current Idiff as a phasor, and calculate its magnitude.
4. Check if the point P(Ibias, Idiff) is above the operate-bias characteristic. If yes, increment the trip
request counter by 1. If the point P(Ibias, Idiff) is found to be below the operate-bias
characteristic, then the trip request counter is reset to zero.
5. If the trip request counter is still zero, search for an eventual heavy external earth fault. The
search is only made if the neutral current is at least 50% of the Idmin current. If an external earth
fault has been detected, a flag is set which remains set until the external fault has been cleared.
The external fault flag is reset to zero when Ineutral falls below 50% of the base sensitivity
Idmin. Any search for an external fault is aborted if trip request counter is greater than zero.
6. As long as the external fault persists, an additional temporary trip condition is introduced. This
means that REFPDIF is temporarily desensitized.
7. If point P(Ibias, Idiff) is found to be above the operate-bias characteristic), so that trip request
counter is greater than zero, a directional check can be made. The directional check is made
only if Iresidual (3Io) is more than 3% of the IBase current. If the result of the check means
“external fault”, then the internal trip request is reset. If the directional check cannot be
executed, then direction is no longer a condition for a trip.
8. When neutral current, residual current and bias current are within some windows and some
timing criteria are fulfilled, the ratio of 2nd to fundamental harmonic is calculated. If it is found to
be above 40%, the trip request counter is reset and TRIP remains zero.
9. If point P(Ibias, Idiff) is found to be above the operate-bias characteristic), a directional check
can be made. The directional check is made only if Iresidual (3Io) is more than 3% of the IBase
current. If the result of the check means “external fault”, then the internal trip request is reset. If
the directional check cannot be executed, then the direction is no longer a condition for a trip.
10. Finally, the trip request counter is checked. If the trip request counter is greater or equal than 2
and at the same time the actual bias current is at least 50% of the highest bias current Ibiasmax
(Ibiasmax is the highest recording of any of the three phase currents measured during the
disturbance), REFPDIF will set output TRIP to 1. Otherwise, the TRIP signal remains zero.
11. Finally, a check is made if the trip request counter is equal to, or higher than 2. If yes, and at the
same instance of time tREFtrip, the actual bias current at this instance of time tREFtrip is at least
50% of the highest bias current Ibiasmax (Ibiasmax is the highest recording of any of the three
phase currents measured during the disturbance), then REFPDIF sets output TRIP to 1. If the
counter is less than 2, the TRIP signal remains zero.
7.2.9
Technical data
IP12661-1 v1
M13062-1 v23
Table 96:
REFPDIF technical data
Function
Range or value
Accuracy
Operating characteristic
Adaptable
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Reset ratio
> 95%
-
Minimum pickup, IdMin
(4.0-100.0)% of IBase
±1.0% of Ir
Table continues on next page
160
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Function
Range or value
Accuracy
Directional characteristic
Fixed 180 degrees or ±60 to ±119
degrees
±2.0 degrees
Operate time, trip at 0 to 10 x IdMin
Min. = 15 ms
Max. = 30 ms
-
Reset time, trip at 10 x IdMin to 0
Min. = 15 ms
Max. = 30 ms
-
Second harmonic blocking
40.0% of fundamental
±1.0% of Ir
7.3
Line differential protection L4CPDIF
7.3.1
Function revision history
Document
revision
7.3.2
Product
revision
GUID-611723D0-41E1-4F50-B9F6-8E97948D348F v3
History
A
2.2.1
-
B
2.2.1
-
C
2.2.1
-
D
2.2.2
-
E
2.2.2
-
F
2.2.2
-
G
2.2.3
Added charging currents ICL1, ICL2, and ICL3 as service values
H
2.2.3
-
J
2.2.3
-
K
2.2.3
-
L
2.2.4
-
M
2.2.4
-
N
2.2.5
-
Identification
GUID-690568A1-7B01-4FB6-B82E-7A50A886DE9D v2
Function description
High speed line differential protection
for 4 CT sets, 2-3 line ends
IEC 61850
identification
IEC 60617
identification
L4CPDIF
3Id/I>
ANSI/IEEE C37.2
device number
87L
SYMBOL-HH V1 EN-US
7.3.3
Functionality
GUID-57872A74-462D-4513-B75B-A46ADCE03522 v2
High speed line differential protection for 4 CT sets, 2-3 line ends (L4CPDIF) is a unit type protection
system with typical operate time less than one cycle. These types of systems are suitable for the
protection of complex transmission network configurations because they exhibit good performance
during evolving, inter-circuit, and cross-country faults. They are also highly immune to power swings,
mutual coupling and series impedance unbalances. High speed line differential protection requires 2
Mbit/s communication channel to transfer analog signals.
Line differential protection RED670
Technical manual
161
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
The L4CPDIF function applies the Kirchhoff's law, and compares currents entering and leaving the
protected multi-end circuit consisting of overhead power lines and cables. Under normal load
conditions, the sum of currents is small or close to zero. The function is phase-segregated: each
phase has its own differential, bias and incremental currents.
L4CPDIF measures currents at all ends of a protected circuit. At each physical end, currents are
mostly measured by one and sometimes by two three-phase current transformer (CT) groups. The
voltages at all ends are also measured if the exact method is selected for charging current
compensation. The protected zone is determined by the positions of the CTs at all ends of the
protected circuit. L4CPDIF protects all electrical equipment, such as power lines, circuit breakers and
small tap transformers, that are within the protected zone.
The information on all locally measured currents is transmitted via communication channels to
remote IEDs. Then L4CPDIF compares these currents using a classical current differential principle
supplemented by an additional advanced internal fault detector. This results in fast protection with
very high dependability (relay operates correctly with faults it was designed for) and very high
security (relay does not operate with faults it was not designed for).
7.3.3.1
Possible configurations
GUID-566BF5F0-3E2D-42D8-9D53-BCAFB7F0BEA9 v3
The simplest and most common configuration is the protection of a conventional two-end power line
(see Figure 48). Circuit breakers (CBs) at both ends can be included in the protected zone
depending on their positions relative to the current transformers (CTs).
Protected zone
IED
IEC05000039 V3 EN-US
Figure 48:
Communication channel
IED
IEC05000039-3-en.vsd
Two-end power line with one CB and one CT group at each end
It is also possible to protect a two-end power line that has two CB and CT groups at one end and one
CB and CT group at the other end (see Figure 49). All currents from the three CTs must be fed
separately to L4CPDIF which processes the measured currents independently from each other.
Summing up the CTs’ secondary currents at the end with two CB and CT groups is not allowed. CBs
at both ends can be included in the protected zone depending on their positions relative to the CTs.
IEC15000459-1-en.vsd
IEC15000459 V1 EN-US
Figure 49:
Two-end power line with two CB and CT groups at one end
If there are two CB and CT groups at both ends of a two-end power line, information on currents
must be fed to all four current inputs of both IEDs. Current values at the remote end are obtained via
a communication channel as shown in Figure 50. Summing up the CTs’ secondary currents at the
end with two CB and CT groups is not allowed. CBs at both ends can be included in the protected
zone depending on their positions relative to the CTs.
162
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
IEC15000460-1-en.vsd
IEC15000460 V1 EN-US
Figure 50:
Two-end power line with two CB and CT groups at each end
Figure 51 shows a three-end power line configuration where one end has two CB and CT groups. All
four current inputs to IEDs are used. Current from each CT is fed to an IED, and currents from
different CTs are processed separately by the protection algorithm. Summing up the CTs’ secondary
currents at the end with two CB and CT groups is not allowed. CBs at all ends can be included in the
protected zone depending on their positions relative to the CTs.
IEC15000461-1-en.vsd
IEC15000461 V1 EN-US
Figure 51:
Three-end power line with two CB and CT groups at one end
The locally measured current samples are exchanged between all IEDs at line ends (in mastermaster mode) or sent for evaluation to one master IED from all slave IEDs (in master-slave mode).
In master-master mode, all IEDs at different ends of a protected zone execute exactly the same
program code with exactly the same information so the same response is expected from all masters.
In master-slave mode, only one IED has access to all currents in the protected zone. It is always
recommended to select the master-master mode if allowed by the number of communication links.
When communication failure occurs, L4CPDIF function will be blocked. Under the blocking period,
COMFBLKD will be set to indicate that L4CPDIF function is blocked by communication failure.
Line differential protection RED670
Technical manual
163
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
7.3.4
1MRK 505 377-UEN Rev. P
Function block
GUID-E2714077-37D7-45A1-991D-03C3DBFB7173 v2
L4CPDIF
I3P1*
I3P2*
I3P3*
I3P4*
U3P1*
U3P2*
U3P3*
U3P4*
BLOCK
LOWSENEN
CCBLK
TRIP
TRL1
TRL2
TRL3
START
STL1
STL2
STL3
STUNR
COMFBLKD
BLKHL1
BLKHL2
BLKHL3
OPENCT
DIFLBLKD
TRLOCAL
TRREMOTE
ALARM
INTFLTL1
INTFLTL2
INTFLTL3
SYNLOSS
CHARGEN
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIASL1
IBIASL2
IBIASL3
IREQSTL1
IREQSTL2
IREQSTL3
IEC15000481‐3‐en.vsdx
IEC15000481 V3 EN-US
Figure 52:
7.3.5
L4CPDIF function block
Signals
PID-7277-INPUTSIGNALS v1
Table 97:
Name
L4CPDIF Input signals
Type
Default
Description
I3P1
GROUP
SIGNAL
-
Three phase current samples, group 1
I3P2
GROUP
SIGNAL
-
Three phase current samples, group 2
I3P3
GROUP
SIGNAL
-
Three phase current samples, group 3
I3P4
GROUP
SIGNAL
-
Three phase current samples, group 4
U3P1
GROUP
SIGNAL
-
Three phase voltage samples, group 1
U3P2
GROUP
SIGNAL
-
Three phase voltage samples, group 2
U3P3
GROUP
SIGNAL
-
Three phase voltage samples, group 3
U3P4
GROUP
SIGNAL
-
Three phase voltage samples, group 4
Table continues on next page
164
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
LOWSENEN
BOOLEAN
0
Input for forcing the function enable low sensitivity
CCBLK
BOOLEAN
0
Block CCC (local)
PID-7277-OUTPUTSIGNALS v1
Table 98:
L4CPDIF Output signals
Name
Type
Description
TRIP
BOOLEAN
Common, main, trip output signal
TRL1
BOOLEAN
Trip signal from phase L1
TRL2
BOOLEAN
Trip signal from phase L2
TRL3
BOOLEAN
Trip signal from phase L3
START
BOOLEAN
Common, main, start output signal
STL1
BOOLEAN
Start signal from phase L1
STL2
BOOLEAN
Start signal from phase L2
STL3
BOOLEAN
Start signal from phase L3
STUNR
BOOLEAN
Start of unrestrained differential protection
COMFBLKD
BOOLEAN
Block due to communication failed
BLKHL1
BOOLEAN
Block signal due to 2nd or 5th harmonic, phase L1
BLKHL2
BOOLEAN
Block signal due to 2nd or 5th harmonic, phase L2
BLKHL3
BOOLEAN
Block signal due to 2nd or 5th harmonic, phase L3
OPENCT
BOOLEAN
An open CT was detected
DIFLBLKD
BOOLEAN
Local line differential function blocked
TRLOCAL
BOOLEAN
Trip from local differential function
TRREMOTE
BOOLEAN
Trip from remote differential function
ALARM
BOOLEAN
Alarm for sustained differential current
INTFLTL1
BOOLEAN
Internal fault has been detected in phase L1
INTFLTL2
BOOLEAN
Internal fault has been detected in phase L2
INTFLTL3
BOOLEAN
Internal fault has been detected in phase L3
SYNLOSS
BOOLEAN
Loss of data synchronism was detected
CHARGEN
BOOLEAN
Charging current compensation is enabled
IDL1
REAL
Instantaneous differential current, phase L1
IDL2
REAL
Instantaneous differential current, phase L2
IDL3
REAL
Instantaneous differential current, phase L3
IDL1MAG
REAL
Magnitude of fund. freq. differential current, phase L1
IDL2MAG
REAL
Magnitude of fund. freq. differential current, phase L2
IDL3MAG
REAL
Magnitude of fund. freq. differential current, phase L3
IBIASL1
REAL
Magnitude of the bias current, L1
IBIASL2
REAL
Magnitude of the bias current, L2
IBIASL3
REAL
Magnitude of the bias current, L3
IREQSTL1
REAL
Required current level to start, phase L1
IREQSTL2
REAL
Required current level to start, phase L2
IREQSTL3
REAL
Required current level to start, phase L3
Line differential protection RED670
Technical manual
165
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
7.3.6
1MRK 505 377-UEN Rev. P
Settings
PID-7277-SETTINGS v1
Table 99:
L4CPDIF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
NoOfUsedCTs
2-4
-
1
2
Total number of 3-Ph CT sets connected
to diff protection
TapTransformer
Off
On
-
-
Off
Small tap transformer included in the
protected zone
DiffMode
Master
Slave
-
-
Master
Differential function mode Master/Slave
ReleaseLocal
Block all
Release local
-
-
Block all
Release of local terminal for trip under
test mode
TestModeSet
Off
On
-
-
Off
Test Mode Off/On
Table 100: L4CPDIF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Mode Off / On
IdMin
0.20 - 2.00
IB
0.01
0.30
Oper - restr charact., section 1
sensitivity, multiple of IBase
IdMinHigh
0.20 - 10.00
IB
0.01
0.80
Initial lower sensitivity, as multiple of
IBase
tIdMinHigh
0.000 - 60.000
s
0.001
1.000
Time interval of initial lower sensitivity, in
s
IdUnre
1.00 - 100.00
IB
0.01
10.00
Unrestrained differential current limit,
multiple of IBase
OpenCTEnable
Off
On
-
-
On
Open CTEnable Off/On
tOCTResetDelay
0.100 - 10.000
s
0.001
0.250
Reset delay in s. After delay, diff.
function is activated
OCTBlockEn
Off
On
-
-
On
Enable Open CT blocking function trip
Off/On
IdiffAlarm
0.05 - 1.00
IB
0.01
0.15
Sustained differential current alarm,
multiple of IBase
tAlarmDelay
0.000 - 60.000
s
0.001
10.000
Delay for alarm due to sustained
differential current, in s
LossSynEn
Off
On
-
-
Off
Loss of data synchronism detection
Off/On
tLossSynReset
0.100 - 60.000
s
0.001
1.000
Loss of data synchronism detection reset
delay in s. After delay, diff. function is
activated
CCCOpMode
Off
U based
IDiff reduction
-
-
Off
Operation mode of charging current
compensation
VTOnLineGrp1
No
Yes
-
-
No
Voltage transformer installed on the line
at the end, the currents of which are
connected to group 1
Table continues on next page
166
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Name
Section 7
Differential protection
Values (Range)
Unit
Step
Default
Description
VTOnLineGrp2
No
Yes
-
-
No
Voltage transformer installed on the line
at the end, the currents of which are
connected to group 2
VTOnLineGrp3
No
Yes
-
-
No
Voltage transformer installed on the line
at the end, the currents of which are
connected to group 3
VTOnLineGrp4
No
Yes
-
-
No
Voltage transformer installed on the line
at the end, the currents of which are
connected to group 4
C0
0.001 - 1000.000
uF
0.001
0.001
Total zero sequence capacitance of the
protected line, in microfarad
C1
0.001 - 1000.000
uF
0.001
0.001
Total positive sequence capacitance of
the protected line, in microfarad
NoOfLineEnds
2-3
-
1
2
Number of physical line ends of the
protected line circuit, 2 ends or 3 ends
NoOfCTSetsGrp1
1-2
-
1
1
Number of 3-ph CTs at line end, the
currents of which are connected to group
1 (1 or 2)
NoOfCTSetsGrp2
1-2
-
1
1
Number of 3-ph CTs at line end, the
currents of which are connected to group
2 (1 or 2)
NoOfCTSetsGrp3
1-2
-
1
1
Number of 3-ph CTs at line end, the
currents of which are connected to group
3 (1 or 2)
NoOfCTSetsGrp4
1-2
-
1
1
Number of 3-ph CTs at line end, the
currents of which are connected to group
4 (1or 2)
tChargCurrDelay
0.010 - 60.000
s
0.001
0.100
Delay for compensation of charging
current due to initial voltage oscillation,
in s
Table 101: L4CPDIF Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
EndSection1
0.20 - 2.00
IB
0.01
1.00
End of section 1, as multiple of reference
current IBase
EndSection2
1.00 - 10.00
IB
0.01
3.00
End of section 2, as multiple of reference
current IBase
SlopeSection2
10.0 - 100.0
%
0.1
50.0
Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3
30.0 - 100.0
%
0.1
100.0
Slope in section 3 of operate-restrain
characteristic, in %
I2/I1Ratio
5.0 - 100.0
%
1.0
10.0
Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio
5.0 - 100.0
%
1.0
10.0
Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
SendInterTrip
No
Yes
-
-
Yes
Send inter-trip to remote ends
Line differential protection RED670
Technical manual
167
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
7.3.7
1MRK 505 377-UEN Rev. P
Monitored data
PID-7277-MONITOREDDATA v1
Table 102: L4CPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
IDL1MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L1
IDL2MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L2
IDL3MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L3
IBIASL1
REAL
-
A
Magnitude of the bias current, L1
IBIASL2
REAL
-
A
Magnitude of the bias current, L2
IBIASL3
REAL
-
A
Magnitude of the bias current, L3
ICL1
REAL
-
A
Amount of compensated charging
current, phase L1
ICL2
REAL
-
A
Amount of compensated charging
current, phase L2
ICL3
REAL
-
A
Amount of compensated charging
current, phase L3
7.3.8
Operation principle
7.3.8.1
Differential currents
Instantaneous differential currents
GUID-BC1C8ADA-B281-43F8-A04D-4D90AFB999DB v2
Instantaneous differential currents represent sums of all synchronized instantaneous currents
(current samples) from all ends of a protected line. They also include charging currents since
instantaneous differential currents are formed by directly measured raw currents (true current
samples).
Instantaneous differential currents are generated because they can be analyzed with higher
harmonic Fourier filters. Higher harmonics are calculated only when a start signal has been issued
and a disturbance has not been recognized as an internal fault. The 2nd and 5th harmonic differential
currents are compared to the fundamental frequency differential current. If the measured ratio is
greater than the values specified by settings I2/I1Ratio and I5/I1Ratio respectively, and the
disturbance has not been recognized as internal, L4CPDIF does not issue a trip command.
Fundamental frequency differential currents
GUID-AAFA17A5-9890-465C-8D32-C6596F90E0E7 v2
Fundamental frequency differential current is a vector sum of current phasors measured at all ends
of a protected line. Input currents are first Fourier filtered so that each current is expressed as a
phasor with its real and imaginary component.
Calculating the fundamental frequency differential current in a given phase is performed using
operation on complex numbers. All real and imaginary parts of currents from different ends are
summed separately. Each differential current is thus a phasor with a real and imaginary component,
and the magnitude of the current can be calculated from those components.
In normal conditions, the sum of all load currents in a given phase should be zero as defined by
Kirchhoff's law. However, some minor differential current composed of capacitive currents may flow
into the protected zone through all ends of the protection. The sum of these relatively small
capacitive currents is typically 5–15% of IBase (IBase reflects the nominal current of a power line).
L4CPDIF can compensate for the capacitive currents, and the resulting differential current is
therefore close to zero. Even though these currents are compensated for, sensitivity for setting IdMin
168
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
must be set above the total value of the uncompensated charging currents. It is recommended to set
IdMin ≥ 125% of the maximum value of the total charging current at rated voltage.
Fundamental frequency differential current is compared to a value required to trip. This value is a
function of the set operate-restrain characteristic where the bias (restrain) current acts as the
independent variable. The bias (restrain) current is considered the highest total current of all currents
in a phase from all separate ends of a protected line. If the differential current higher than the actual
trip value, it is likely that an internal fault has occurred. However, this may not always be the case as
a relatively high false differential current can arise also with severe external faults with transient CT
saturation. The internal fault detector must confirm, based on incremental currents, that the fault is
internal.
7.3.8.2
Internal fault detector
GUID-BF5AFA0F-9440-4716-807C-7276071A6FD8 v2
The internal fault detector used in L4CPDIF is a new feature in an otherwise classical differential
protection. Each phase has its own detector, and they function completely independently from each
other.
The internal fault detector calculates the relative angle between purely fault current components
(incremental current components expressed as phasors). Incremental currents of an internal fault
flow into the protected zone, and incremental currents of an external fault flow through the protected
zone.
The internal fault detector is very reliable, and information gained from it is mostly used to enhance
the dependability of L4CPDIF. This is achieved by declaring a fault as internal very quickly, which
results in an immediate trip command with no regard to eventual 2nd or 5th harmonic in the
instantaneous differential current.
When a fault is declared as internal (typically in 3 ms), the harmonic block scheme is deactivated and
a trip command is issued very fast when it is still unlikely that a CT can reach saturation and produce
high amounts of harmonics.
At internal faults, the relative angle between incremental currents is ideally zero, but can slightly
deviate from that. This depends on the different X/R factors of equivalent circuits on both sides of the
equivalent electrical circuit as seen from the position of the internal fault. If the relative angle is less
than 55 degrees, a fault is recognized as internal. A boolean start signal is produced to indicate this
internal fault. The harmonic block logic scheme is deactivated for as long as the internal fault signal
exists. This ensures fast tripping even in the presence of higher harmonics.
With external faults, the relative angle between incremental currents is theoretically 180 degrees, but
can be less (even down to approximately 120 degrees) if CT saturation sets in.
Calculating pre-fault average currents to determine incremental currents
GUID-6238F0A8-9B51-4759-B7FB-E25212B7F798 v2
The average of every total pre-fault normal load current, based on the last period, is calculated to
have a reliable and stable pre-fault current reference value so that the incremental (purely fault)
component of every current can be determined.
The average values of the currents, expressed as phasors with their real and imaginary parts, are
calculated based on current values from the last period. The on-line calculated average values are
sequentially memorized in a special memory for one period back in time. The oldest average stored
is thus one period old. It is this oldest average that serves as the reference for the pre-fault normal
current if a fault occurs.
The averaging operation is executed continuously until a disturbance (possibly an internal fault) is
detected. A disturbance is suspected when the differential current exceeds the set value for IdMin.
The pre-fault current calculation is stopped after the disturbance, and the oldest stored average - not
affected by the disturbance - is used as a reference for the normal pre-fault current to calculate the
incremental (pure fault) current. This process takes place independently in all three phases (see
Figure 53).
Line differential protection RED670
Technical manual
169
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
IEC15000474-1-en.vsd
IEC15000474 V1 EN-US
Figure 53:
Simplified logic diagram for the internal fault detector shown for a two-end power
line (one detector for each phase)
The pre-fault current calculation resumes when the disturbance has disappeared, that is, when the
differential current falls below 0.95 x IdMin.
Incremental currents are determined by subtracting the pre-fault (load) currents from the actual total
currents (fault and load), and this happens separately for each phase. Incremental currents are
calculated continuously regardless of the status of pre-fault current calculation. Under stable load
condition, these incremental currents are practically zero.
If there are more than two ends in a protected line, the system is automatically
reduced to a two-end equivalent line before the relative angle is determined.
Calculating the relative angle between incremental currents
GUID-63CAB758-64B5-4665-BFA7-A07705C44D26 v2
Incremental currents are expressed as phasors so that the relative angle between them can be
calculated. This angle makes it possible to determine if a fault is internal.
Normal sudden change in symmetrical load is felt as an external disturbance. In that case,
incremental currents at both ends of a single power line have the same direction: through the power
line and out. An external fault is, in principle, identical to a sudden change in load so the incremental
currents at both ends of a power line have the same direction: through the power line and out. On the
other hand, at internal faults, both incremental currents are flowing towards the fault point so they
have opposite directions in relation to the power line (see Figure 54).
170
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
IEC15000462-1-en.vsd
IEC15000462 V1 EN-US
Figure 54:
Incremental currents flowing towards the internal fault point with a default
orientation of CTs
However, keeping in mind the default orientation of CTs at all ends of a power line, the relative angle
is approximately 180 degrees for external and 0 degrees for internal faults. With internal faults, the
angle can deviate a little from 0 degrees depending on possible different source impedance angle of
equivalent electrical circuits at opposite ends of an internal fault.
With CT saturation, the angle value for an external fault can differ somewhat from 180 degrees, and
for an internal fault from 0 degrees. However, measurement of the angle is stopped before severe CT
saturation occurs because a fault is characterized as internal (or external) very quickly (typically in
3-5 ms). Measurement of the angle does not resume until the disturbance disappears.
The relative angle is only determined if each incremental current is equal to or greater than 2.5% of
IBase in a protected power line. In normal load conditions with no or slow/small changes in load, no
big enough incremental currents occur to measure the relative angle with the required high precision.
In that case, the angle is automatically set to 90 degrees, which usually means that neither internal
nor external disturbances exist. With internal faults, such as single-phase earth faults, the angle
between the incremental currents at both ends falls quickly to approximately 0 degrees.
If a protected power line circuit is delimited by more than two CT groups, a reliable algorithm is
applied to measure the angle between incremental currents. In that case, the protected power line is
reduced to a two-end line. This is done so that first the highest incremental current among all
incremental currents in a given phase is found, and then the relative angle between this highest
incremental current and the geometrical sum of other currents is calculated. For example, if a
protected line has three physical line ends with a CT group in each of them and the incremental
current at end 1 is found to be the highest, the angle between that current and the geometric sum of
incremental currents at ends 2 and 3 is calculated.
7.3.8.3
Operate-restrain characteristic
GUID-5978B231-F7EF-4730-9ACD-C73DD1E32611 v2
L4CPDIF uses two limits, and the actual magnitudes of the three fundamental frequency differential
currents are compared to these limits at each execution of the function.
The unrestrained (non-stablized) part of L4CPDIF is used for very high differential currents when it
should be clear that a fault is internal. This limit is a constant and not proportional to the bias
(restrain) current. No harmonic or any other restrain is applied to it, and that is why it is called the
unrestrained limit. When this limit is set, a value higher than the highest short circuit current for an
external fault plus some extra margin must be used.
The restrained (stabilized) part of L4CPDIF calculates the differential (operate) and the bias (restrain)
currents in each phase, and applies them to the operate-restrain characteristic. The function can also
provide the instantaneous operate level as outputs (IREQSTLX) to indicate the required value to start
according to the characteristic. If any differential current enters the operate region above the
characteristic, a start signal is issued, and it is quickly followed by a trip command if the fault is
internal.
Line differential protection RED670
Technical manual
171
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
In L4CPDIF, the operate-restrain characteristic is represented by a three-section, double-slope and
double-breakpoint characteristic as shown in Figure 55. The operate value is a function of the bias
(restrain) current. The restrain characteristic is determined by five settings:
•
•
•
•
•
IdMin: sensitivity of section 1, set as multiple of IBase
EndSection1: end of section 1, set as multiple of IBase
EndSection2: end of section 2, set as multiple of IBase
SlopeSection2: slope of section 2, set as percentage
SlopeSection3: slope of section 3, set as percentage
Operate current
[ x IBase ]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate
3
conditionally
2
Section 1
Section 2
Section 3
SlopeSection3
1
IdMin
SlopeSection2
Restrain
0
0
1
2
3
EndSection1
EndSection2
4
Restrain current
[ x IBase ]
IEC15000463-1-en.vsd
IEC15000463 V1 EN-US
Figure 55:
5
Description of the restrained and unrestrained operate characteristics
where:
slope = D Ioperate × 100%
D Irestrain
EQUATION1246 V1 EN-US
and where the restrained characteristic is defined by settings:
1.
IdMin
2.
EndSection1
3.
EndSection2
4.
SlopeSection2
5.
SlopeSection3
Section 1 is the most sensitive part on the operate-restrain characteristic. In this section, normal
currents flow through the protected circuit and its CTs, and the risk for higher false differential
currents is relatively low. Charging currents present a typical example of false differential currents
172
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
here. The slope in section 1 is always 0%. The default value for sensitivity IdMin = 0.30 of IBase. The
default length of section 1 is 1.00 of IBase.
Section 2 introduces a minor slope to cope with false differential currents that are proportional to
higher than normal currents through the CTs. The default slope in section 2 is 50%. The default
length of section 2 is 2.00 of IBase, which means that, when section 1 is included, section 2 ends at
3.00 of IBase.
Section 3 has a more pronounced slope designed to result in higher tolerance of substantial CT
saturation at high through-fault currents which may be expected in this section. The default slope in
section 3 is 100%.
The operate-restrain characteristic is tailor-made so it can be constructed by the user. Construction
for a given protection application should be done so that with internal faults, the differential currents
are always safely (with a good margin) above, and with external faults below the operate-restrain
characteristic. It is not always possible to achieve both of these requirements. However, the default
operate-restrain characteristic is known to give good results in majority of applications. The reset
ratio in all parts of the characteristic equals to 0.95.
7.3.8.4
2nd and 5th harmonics
GUID-BC40AE81-D38E-4ABD-A2CA-FCB03FC3B506 v2
High stability against unwanted operations under severe external faults is achieved by using the
operate-restrain characteristic and applying the 2nd and the 5th harmonic block scheme.
Even though a good operate-restrain characteristic ignores the majority of external disturbances,
some severe external faults can produce enough false differential current at a relatively low bias
current so that the operate region of the characteristic is entered. This causes an unwanted trip
command if not prevented by the 2nd or the 5th harmonic.
The generated false differential current has a substantial 2nd or 5th harmonic component. The 2nd
harmonic component produced by transient CT saturation is high, typically 20–60% of the false
fundamental harmonic differential current. A relatively low value, such as 10%, is recommended for
the relative limit of the 2nd harmonic in comparison to the fundamental frequency differential current.
It can be expected that under severe external faults, the 2nd harmonic differential current is always
greater than 10% of the fundamental frequency component of the differential current. This is the
classical solution that efficiently helps prevent an unwanted trip for external faults.
The 2nd harmonic has traditionally been used to prevent unwanted operation of differential protection
in cases like energizing power transformers. It has also been used to prevent unwanted operation
under external fault conditions where a false differential current can arise only if one or more CTs are
transiently saturated. This false differential current is characterized by a high amount of the 2nd
harmonic. Without CT saturation, there is usually no or very little differential current under external
faults. In such cases the external fault will not be felt by the protection at all.
Using the 2nd and the 5th harmonic makes most traditional differential protections slow in cases of
severe internal faults with transient CT saturation. This does not apply to L4CPDIF. In L4CPDIF, the
2nd and the 5th harmonic block logic is always active except in cases where the internal fault or
switch-on-to-fault condition is detected. The switch-on-to-fault condition is identified if only one end
currents are high and the rest currents are below the limit (2.5% of IBase).
A small tap transformer (up to 10–15% of the power line transmission capacity) can be included
somewhere in the protected line without its currents being measured. Any currents flowing through
this transformer are thus felt as differential currents. Switching a tap transformer on the protected line
(a legal event) may cause inrush currents that are correctly detected as internal faults. Fortunately
these instantaneous differential currents are rich with the 2nd harmonic which is used to prevent an
unwanted operation of L4CPDIF. The 5th harmonic is also calculated in the instantaneous differential
current. This is done to prevent an unwanted trip command at sudden over-excitation of the tap
transformer.
Line differential protection RED670
Technical manual
173
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Setting TapTransformer = On is used to specify if a tap transformer is included and connected/
disconnected to/from the protected zone. The default value for TapTransformer = Off.
If TapTransformer = On, harmonic blocking is checked whenever the bias current is less than the
relatively low value of 1.25 x IBase. An internal fault is not declared if the bias current is lower than
1.25 x IBase. This leaves the harmonic block logic scheme active.
The 5th harmonic is also calculated in the instantaneous differential current. This is done to prevent
an unwanted trip command at sudden over-excitation of the tap transformer.
Relative limits for the harmonics are specified as follows:
•
•
2nd harmonic: setting I2/I1Ratio, default value 0.10
5th harmonic: setting I5/I1Ratio, default value 0.10
Low setting values can be used since the harmonic block is deactivated under internal fault
conditions, and cannot delay the protection response for those faults.
7.3.8.5
Charging current compensation
GUID-0750DEF2-8B50-412A-B366-42D921AE635E v3
Underground cables and long overhead lines generate charging currents which L4CPDIF detects as
differential currents. Charging currents on overhead lines increase with the length of the power line..
They are relatively low, typically 5–15% of IBase, which is significant for the setting and operation of
L4CPDIF.
Power cables can, at fundamental frequency, have charging currents high enough to significantly
influence the necessary setting of the minimum operating current. This, in turn, can impact the
sensitivity of the algorithm applied by L4CPDIF. To improve this, L4CPDIF uses charging current
compensation. This compensation is a special algorithm, included in the L4CPDIF
Even if charging current compensation is applied, the best sensitivity (IdMin) of
L4CPDIF must still be above the total maximum charging current. This is because
charging current can shortly appear as a false differential current in its full value
under some dynamic conditions such as line re-closing.
L4CPDIF offers two methods to perform charging current compensation:
•
•
The exact method that processes both currents and voltages. When using this method,
protected circuit capacitances must be known and the information on voltage must be available.
The approximate method that processes only currents. This method assumes that persistent,
small differential currents in normal steady state represent capacitive charging currents. These
small currents are subtracted in a phase-wise manner.
When a tap transformer or shunt reactor is included in the protected zone, charging
current cannot be calculated using the exact method because the capacitive current
is partly compensated for by the tap power transformer or shunt reactor. In that case,
the approximate method should be used instead.
Under the condition that any terminal goes out of service (all data from that terminal will be forced to
zero), the charging current compensation function will automatically switch to approximate method if
the exact method was selected previously. During the transition period, 200% of IdMin will be applied
for 200 ms. When all terminals are back to service again, the charging current compensation function
will switch back to the exact method as selected previously.
Charging current calculation using the exact method
GUID-748E13D3-E102-4D21-891A-461E885B78F6 v3
Charging currents of cables and overhead lines are capacitive and of the positive-sequence. They
relate to distributed capacitances between line phase conductors and between each phase
conductor and earth. These capacitances give rise to line charging currents which L4CPDIF detects
as false differential currents as shown in Figure 56.
174
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
IC1
Idi ff, false = IC1 + IC2
IED
Communication channel
IC2
IED
IEC15000464-1-en.vsd
IEC15000464 V1 EN-US
Figure 56:
Charging currents fed from all voltage sources
Charging current in a transmission line or cable is proportional to the capacitance and time derivative
of voltage. Time derivative of a signal can be estimated through straightforward numerical
differentiation:
dy yk  yk  1

dt
t
(Equation 9)
IECEQUATION15157 V1 EN-US
When calculating capacitance in one phase, both capacitance to earth (Cn) and to other phases (Cp)
must be considered (see Figure 57).
L1 (UL1)
Cp
Cp
L3 (UL3)
L2 (U L2)
Cn
IEC15000465-1-en.vsd
IEC15000465 V1 EN-US
Figure 57:
Capacitances for phaseL1 of a transmission line
Charging currents in phase L1 are calculated as:
d (uL1  0)
d (uL1  uL 2)
d (uL1  uL 3)
 Cp 
 Cp 
dt
dt
dt
duL1
duL1
duL 2
duL1
duL 3
icL1  Cn 
 Cp 
 Cp 
 Cp 
 Cp 
dt
dt
dt
dt
dt
duL1
duL 2
duL 3
icL1  (Cn  2Cp) 
 Cp 
 Cp 
dt
dt
dt
icL1  Cn 
(Equation 10)
IECEQUATION15158 V1 EN-US
Line differential protection RED670
Technical manual
175
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
In real power systems, zero and positive sequence capacitances C0 and C1 are usually known
instead of Cn and Cp.
The zero sequence capacitance per phase is calculated as:
C 0  Cn
(Equation 11)
IECEQUATION15160 V1 EN-US
The positive sequence capacitance is calculated from Cp and Cn (by applying delta-star
transformation) as:
C1  3  Cp  Cn
(Equation 12)
IECEQUATION15159 V1 EN-US
Using the above equations, Cn and Cp can be expressed in terms of C0 and C1:
Cn  C 0
C1  C 0
Cp 
3
(Equation 13)
IECEQUATION15161 V1 EN-US
When studying all three phases, charging currents can be expressed as:
 duL1 


 icL1   (2C1  C 0) / 3 (C 0  C1) / 3 (C 0  C1) / 3   dt 
  
  duL 2 
 icL 2    (C 0  C1) / 3 (2C1  C 0) / 3 (C 0  C1) / 3    dt 
 icL 3   (C 0  C1) / 3 (C 0  C1) / 3 (2C1  C 0) / 3  
  
 duL 3 


dt


(Equation 14)
IECEQUATION15162 V1 EN-US
The calculated capacitive charging currents are fed into fundamental frequency Fourier filters. Output
from these filters represents charging currents expressed as phasors with their real and imaginary
parts: IcL1, IcL2 and IcL3. These capacitive charging currents are then subtracted from total
differential currents which are also expressed as phasors:
IdiffcompL1  IdiffL1  IcL1
IdiffcompL 2  IdiffL 2  IcL 2
IdiffcompL 3  IdiffL 3  IcL 3
(Equation 15)
IECEQUATION15163 V1 EN-US
176
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
where:
IdiffcompLx denotes compensated differential currents (as phasors) to be used in the differential algorithm
Figure 58 shows an example of Charging Current Compensation using exact current. In the example,
the charging current is approximate 92 A in normal condition and subtracted from each of the three
phases.
TOTAL COMPENSATED CURRENT IN PHASE L1
CCC starts
after 100 ms
92 A subtracted from the fundamental
frequency differential current
fault
37 A subtracted under
fault conditions
TOTAL COMPENSATED CURRENT IN PHASE L2
fault
92 A subtracted
37 A subtracted
TOTAL COMPENSATED CURRENT IN PHASE L3
92 A subtracted
fault
37 A subtracted
Time in seconds
IEC15000466-1-en.vsd
IEC15000466 V1 EN-US
Figure 58:
Charging current compensation using the exact method (CCCOpMode = U based)
As seen on the Figure 58 current compensation starts 100 ms after the power line was switched on
to normal load. Under normal load conditions, approximately 92 A is subtracted in this particular
example, which results in all fundamental frequency differential currents being close to zero. Under
fault conditions with very low voltage at the fault and decreased voltages at both ends, the charging
current is smaller, and only 37 A is subtracted from the differential currents.
When CCBLK input is TRUE, the exact method charging current compensation will
be disabled. During blocking period, 200% of Idmin will be applied in order to avoid
mal-operation due to the stop of charging current compensation.
Charging current compensation using the approximate method
GUID-B23CD440-BB53-4A89-B111-A0078F6F3FD8 v2
The approximate method does not calculate the exact charging currents in separate phases using an
algorithm that processes voltages and power line capacitances. Instead, it assumes that relatively
small persistent differential currents, equal or smaller than IdMin in all 3 phases, represent the
resultant total charging currents in each phase. These relatively small differential currents are
considered as charging currents, and they are subtracted from differential currents in a phase-wise
way. The resultant differential currents are thus approximately zero.
The approximate method can be used as an alternative in cases where voltages at all ends are not
available or where shunt reactors are switched on and off on a daily basis without available
information on their status to L4CPDIF.
The amount of pre-fault differential current that can be subtracted is limited by 75% of the base
sensitivity of L4CPDIF, and the limit is defined by setting IdMin. It is recommended to set IdMin to
125–150% of the total charging current even when the charging currents are eliminated.
Since false pre-fault differential currents are continuously subtracted, the magnitude of the pre-fault
fundamental frequency differential current is zero or close to zero. Under fault conditions, when a
start signal exists, the subtraction algorithm continues to subtract the pre-fault charging currents.
Therefore, under fault conditions, fundamental frequency differential currents are generated
exclusively because of faults.
Line differential protection RED670
Technical manual
177
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Because L4CPDIF does not know the voltage profiles, it assumes that the relatively small pre-fault
differential currents are mostly due to capacitive charging currents. All small pre-fault differential
currents are subtracted regardless of their origin. In addition to the true charging currents, the
following currents are also eliminated:
•
•
Small false differential currents generated because of small errors (inequalities) in CTs.
Load currents of small tap transformers if included in the protected zone. A tap transformer that
is connected to a protected zone, reduces the capacitive charging currents, but its load current
is considered and treated as charging currents.
If a communication failure is signalled to L4CPDIF, the elimination process of
charging currents based on approximate method is interrupted and all values reset.
The process is resumed after the communication failure signal SUBSTITUTE is reset
to FALSE (0). All L4CPDIF outputs are blocked during communication failure and for
200 ms after it has been cleared.
Figure 59 shows the charging current that is subtracted from each of the three phases.
TOTAL COMPENSATED CURRENT IN PHASE L1
CCC compensated
in app. 100 ms
92 A subtracted from the fundamental
frequency differential current
fault
92 A subtracted under fault
conditions
TOTAL COMPENSATED CURRENT IN PHASE L2
92 A subtracted
fault
92 A subtracted
TOTAL COMPENSATED CURRENT IN PHASE L3
92 A subtracted
fault
92 A subtracted
Time in seconds
IEC15000467-1-en.vsd
IEC15000467 V1 EN-US
Figure 59:
Charging current compensation using the approximate method (CCCOpMode =
Idiff reduction)
Charging current compensation is achieved 100 ms after the power line was switched on to normal
load. Under normal load conditions, in the example case, shown in Figure 59, approximately 92 A is
subtracted, which results in all fundamental frequency differential currents being close to zero. Since
voltage profiles are not known, the approximate method continues, even under fault conditions, to
subtract the pre-fault charging current of 92 A.
With low resistance faults, the 55 A difference of the approximate method in comparison to the exact
method, is relatively small when considering high fault currents. With high-resistance faults, the
charging current will not change much so it is acceptable to continue subtracting the pre-fault values
of charging currents.
7.3.8.6
Open CT detection
GUID-FE8DF833-02E1-4923-A1A6-48BCA863AD41 v3
L4CPDIF has a built-in, advanced open CT detection feature. A suddenly and inadvertently opened
CT circuit may cause an unexpected and unwanted operation of L4CPDIF in normal load conditions.
Damage to secondary equipment may occur due to high voltage from open CT circuit outputs. It is
thus advantageous from security and reliability point-of-view that open CT detection blocks the
L4CPDIF function, and produces an alarm signal so that the open CT condition can be quickly
corrected.
Open CT detection is enabled/disabled using setting OpenCTEnable (On/Off). When enabled, it tries
to prevent mal-operation when a loaded main CT, connected to L4CPDIF, is open-circuited by
mistake on the secondary side. Open CT detection can only detect the interruption of one CT phase
178
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
current at a time. It will thus not operate if two or all three-phase currents of a CT group are
accidentally interrupted at precisely the same time.
L4CPDIF generates a trip signal if the false differential current is sufficiently high. An open CT circuit
is typically detected in 12–14 ms, and if the load in the protected circuit is relatively high (close to
nominal load), it is not always possible to prevent this unwanted trip. However, it is still vital to receive
information on what caused the unwanted trip command.
The principle applied to detect an open CT circuit is based on simple pattern recognition method.
Current in a phase with an open CT circuit suddenly drops to zero (detected by L4CPDIF) while
currents in the other two phases stay on the same level as before. Open CT detection detects an
open CT circuit under normal conditions, that is, when the protected multi-end circuit is under normal
load (12–125% of the rated load). If the load currents are very low or zero, open CT detection cannot
detect an open CT circuit.
In addition to load condition requirements, open CT detection checks the differential current in a
faulty phase. If the differential current is lower than 10% of IBase, open CT circuit is not detected. If
there is an open CT circuit at one end of a protected line, there are no immediate changes in currents
at other ends. Therefore, open CT condition is only declared if the zero sequence current (iL1 + iL2 +
iL3) is relatively high at the faulty end and low at all other ends. The limit for checking the zero
sequence current is set to 10 % of IBase. Searching for an open CT starts if the bias current has
been higher than energization limit for 1s and has entered the 12–125% range.
When an open CT circuit is detected, output OPENCT is set to 1. If setting OCTBlockEnable = On,
all differential functions, except for the unrestrained (instantaneous) differential function, are blocked.
Otherwise, open CT detection sets OPENCT to indicate an open CT circuit so that no action is taken
to prevent the trip from differential functions.
When the open CT condition is removed (that is, the previously open CT circuit is reconnected), the
functions remain blocked for a specified time interval defined by setting tOCTResetDelay. This is to
prevent an eventual mal-operation immediately after re-connecting the previously open CT circuit.
The open CT detection algorithm provides detailed information on the location of the defective CT
circuit. The algorithm clearly indicates the IED side, CT input and phase of the open CT circuit.
These indications are provided from the Transformer differential protection function via the following
outputs:
•
•
•
OPENCT: provides instant information to indicate that an open CT circuit has been detected.
OPENCTIN: provides information on local HMI about which open CT circuit has been detected
(1 = CT input No 1, 2 = CT input No 2, and so on).
OPENCTPH: provides information on local HMI about the phase in which an open CT circuit has
been detected (1 = Phase L1, 2 = Phase L2, 3 = Phase L3).
Once an open CT condition is declared, the algorithm stops to search for further open CT circuits,
and waits until the first open CT circuit has been corrected. The open CT condition can be reset
automatically in L4CPDIF (this is not possible through external reset). To do this, the following
conditions must be fulfilled:
•
•
Open CT condition in the defective CT circuit has been corrected (for example, current
asymmetry disappears).
The corrected CT circuit has remained reconnected for a longer time than specified by setting
tOCTResetDelay.
If an open CT circuit has been detected in a separate group of three CTs, the algorithm is reset either
when the missing current returns to the normal value or when all three currents become zero. After
the reset, the open CT detection algorithm restarts to search for open CT circuits within the protected
zone.
Line differential protection RED670
Technical manual
179
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
IEC15000468-2-en.vsdx
IEC15000468 V2 EN-US
Figure 60:
7.3.8.7
Simplified logic for open CT detection
Loss of data synchronism detection
GUID-F229078D-F0E8-4351-A4B8-D70F8C034C7B v2
L4CPDIF has a build-in feature to detect a loss of data synchronism condition and, as a result, block
the L4CPDIF function.
L4CPDIF calculates the current difference from all IEDs in the protection scheme. To obtain the
correct differential current, the current samples must be correctly time-aligned and synchronized.
When a synchronization error occurs, current phasors on different sides slowly drift apart, and a false
differential current emerges which will eventually cause the relay to mal-operate.
Loss of data synchronism detection is enabled/disabled with setting LossSynEn (On/Off). If enabled,
the feature tries to prevent mal-operation when loss of data synchronism occurs. L4CPDIF is blocked
as soon as loss of data synchronism condition is detected.
The operation of loss of data synchronism detection is based on all three-phase differential currents
having practically the same magnitudes at a relatively low bias current when loss of data
synchronism occurs between IEDs. This type of situation would not occur as a result of a threephase fault where the fault currents would be much higher than normal.
Loss of data synchronism detection detects a synchronization error under normal conditions, that is,
when a protected circuit is under normal load (less than 110% of the rated load). If the load currents
are very low or higher than 110% of the rated load, synchronization error cannot be detected
When the load condition is fulfilled, loss of data synchronism detection starts to check the differential
currents. If all three-phase differential currents are within the range between IdMin and 2 x IBase,
loss of data synchronism condition is detected. Figure 61 shows the operate region for loss of data
synchronism detection.
180
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
IEC15000469-1-en.vsd
IEC15000469 V1 EN-US
Figure 61:
Operate region for loss of data synchronism detection
When loss of data synchronism is detected, output SYNLOSS is set to TRUE and L4CPDIF is
blocked. If SYNLOSS is set, that is TRUE, for more than 120 ms, a settable reset delay
tLossSynReset is added when the function output is reset. If SYNLOSS is set, that is TRUE, for more
than 5 s, it will be latched, and reset when all three-phase differential currents drop below IdMin.
IEC15000470-1-en.vsd
IEC15000470 V1 EN-US
Figure 62:
7.3.8.8
Simplified logic for loss of synchronism detection
Line differential coordination logic
GUID-1159CC47-43BE-4B74-8F12-8B41F1F8ACCF v3
Line differential coordination logic gathers and coordinates remote IED signals between L4CPDIF
and the LDCM communication module. For example, when local IED decides to trip, the local trip
command is transferred to other IEDs by the coordination logic. The sending of the local trip to the
Line differential protection RED670
Technical manual
181
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
other IEDs can be controlled with the setting SendInterTrip. If setting SendInterTrip is set to No, the
trip will only be activated locally.
When L4CPDIF in a local IED is set to Test mode, the coordination logic sets the remote IEDs to
remote Test mode and blocks the trip outputs in those IEDs. Figure 63 shows the block signal
handling by the coordination logic. When L4CPDIF receives a local block, local test mode or local
open CT signal, it is blocked and this blocking signal is sent out to remote ends.
TestModeRemoteTerm1
TestModeRemoteTerm2
TestModeRemoteTerm3
TestModeRemoteTerm4
OR
50 ms
t
OR
BlockRemoteTerm1
BlockRemoteTerm2
BlockRemoteTerm3
BlockRemoteTerm4
OR
LocalDiffBlock
LOCADIFFBLOCKED
OR
50 ms
CTFAIL
t
CTFailToRemote
(signal to LDCM)
TestModelnput
AND
50 ms
AND
TestModeTo Remote
t
AND
TestModeset
1
TripToRemoteBlock
OR
ReleaseLocal
RemoteTripBlock
OR
TERMINALOUTOFSERVICE
OR
BLOCK
100 ms
t
BlockToRemote
OR
IEC15000471-1-en.vsd
IEC15000471 V1 EN-US
Figure 63:
Block signal logic for line differential coordination logic
When the coordination logic receives a trip signal from a remote IED, the signal is transferred to the
local IED in the protected zone. Figure 64 shows the trip signal handling by the coordination logic.
The common trip signal is initiated either by a local trip from L4CPDIF or by trips from the remote
ends.
182
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
LocalDiffBlocked
RemoteTripBlock
IEC15000472-1-en.vsd
IEC15000472 V1 EN-US
Figure 64:
Trip signal logic for line differential coordination logic
Some of the signals in the block and trip logic diagrams are used as internal signals by the
coordination logic (see Table 103).
Table 103: Internal signals
Internal signals
Source of destination
Description
testModeRemoteTerm1
Signal from LDCM
Test mode from remote terminal 1
testModeRemoteTerm2
Signal from LDCM
Test mode from remote terminal 2
testModeRemoteTerm3
Signal from LDCM
Test mode from remote terminal 3
testModeRemoteTerm4
Signal from LDCM
Test mode from remote terminal 4
blockRemoteTerm1
Signal from LDCM
Block from remote terminal 1
blockRemoteTerm2
Signal from LDCM
Block from remote terminal 2
blockRemoteTerm3
Signal from LDCM
Block from remote terminal 3
blockRemoteTerm4
Signal from LDCM
Block from remote terminal 4
testModeInput
Signal from test mode function
Input for forcing the function into test
mode
diffTripL1
Signal from differential function
Trip from local differential function in
phase L1
Table continues on next page
Line differential protection RED670
Technical manual
183
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Internal signals
7.3.9
Source of destination
Description
diffTripL2
Signal from differential function
Trip from local differential function in
phase L2
diffTripL3
Signal from differential function
Trip from local differential function in
phase L3
tripL1RemoteTerm1
Signal from LDCM
Trip from remote terminal 1 in phase L1
tripL1RemoteTerm2
Signal from LDCM
Trip from remote terminal 2 in phase L1
tripL1RemoteTerm3
Signal from LDCM
Trip from remote terminal 3 in phase L1
tripL1RemoteTerm4
Signal from LDCM
Trip from remote terminal 4 in phase L1
tripL2RemoteTerm1
Signal from LDCM
Trip from remote terminal 1 in phase L2
tripL2RemoteTerm2
Signal from LDCM
Trip from remote terminal 2 in phase L2
tripL2RemoteTerm3
Signal from LDCM
Trip from remote terminal 3 in phase L2
tripL2RemoteTerm4
Signal from LDCM
Trip from remote terminal 4 in phase L2
tripL3RemoteTerm1
Signal from LDCM
Trip from remote terminal 1 in phase L3
tripL3RemoteTerm2
Signal from LDCM
Trip from remote terminal 2 in phase L3
tripL3RemoteTerm3
Signal from LDCM
Trip from remote terminal 3 in phase L3
tripL3RemoteTerm4
Signal from LDCM
Trip from remote terminal 4 in phase L3
tripL1ToRemote
Signal to LDCM
Trip to remote terminals phase L1
tripL2ToRemote
Signal to LDCM
Trip to remote terminals phase L2
tripL3ToRemote
Signal to LDCM
Trip to remote terminals phase L3
localDiffBlock
Signal to differential function
Block local line differential function
operation
blockToRemote
Signal to LDCM
Block to be sent to remote terminals
testModeToRemote
Signal to LDCM
Test mode indication to be sent to
remote terminals
Logic diagrams
GUID-F67293D2-2C80-4FDA-9DEF-9320A0C04D4A v2
Simplified logic diagram for L4CPDIF is shown in Figure 65. Open CT detection feature, approximate
charging current compensation method and loss of data synchronism detection feature are not
included.
184
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
IEC15000473-1-en.vsd
IEC15000473 V1 EN-US
Figure 65:
Simplified logic for L4CPDIF
L4CPDIF is fed by instantaneous values of all currents through raw current and voltage samples.
Voltages are required only if the exact method of charging current compensation is needed.
Raw current samples are used to calculate instantaneous differential currents. These currents are
used for harmonic analysis, which means that the 2nd and the 5th harmonics are extracted from the
currents using Fourier filtering. The analysis is done only on a phase with a start signal. If the fault is
characterized as internal, the harmonic block logic is deactivated.
The charging current compensation algorithm is fed by both voltage and current samples. Capacitive
charging currents are calculated based on instantaneous values. When total capacitive currents are
calculated separately for each phase, these currents are fed to the fundamental frequency Fourier
filters. Applying the charging current compensation algorithm results in three charging currents
expressed as phasors with their real and imaginary parts. These currents are then geometrically
subtracted from the fundamental frequency differential currents in a phase-wise manner if the
charging current compensation algorithm is activated.
Samples of all input currents, separate for each end of a protected line for all three phases, are fed to
the internal fundamental frequency Fourier filters. This results in separate currents expressed as
phasors with their real and imaginary parts. These current are used to form the fundamental
frequency differential current, one for each phase.
The internal fault detector also uses currents expressed as phasors with their real and imaginary
parts as shown in Figure 66.
Line differential protection RED670
Technical manual
185
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
IEC15000474-1-en.vsd
IEC15000474 V1 EN-US
Figure 66:
Simplified logic for the internal fault detector shown for a two-end power line (one
detector for each phase)
Pre-fault normal load currents are processed so that a reliable reference can be assured after a fault
has been detected. An average value of each current stored for one fundamental frequency period
(20 ms in 50 Hz power systems) before the fault is used to form the pure fault (incremental) currents.
An incremental current is obtained if the pre-fault average current is subtracted geometrically from
the total fault current. The relative angle between two incremental currents at both ends in a given
phase provides reliable indication on whether a fault is internal or external. If the internal fault
detector classifies the fault as internal, the harmonic block scheme is deactivated, and a trip is issued
immediately after a trip request has been confirmed three times in succession.
L4CPDIF consists of three totally independent internal fault detectors, one for each phase. In this
way, an event in one phase (for example external fault in phase L1) has no negative impact on an
event in another phase (for example internal fault in phase L1).
7.3.10
Technical data
IP14336-1 v1
GUID-6746298E-4C29-44C6-AB59-41EBF408A5E4 v5
Table 104: L4CPDIF with 2 Mbit/s communication technical data
Function
Range or value
Accuracy
Minimum operate current
(20-200)% of IBase
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
SlopeSection2
(10.0-100.0)%
-
SlopeSection3
(30.0-100.0)%
-
EndSection1
(20–200)% of IBase
-
EndSection2
(100–1000)% of IBase
-
Unrestrained limit function
(100–10000)% of IBase
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Table continues on next page
186
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Function
Range or value
Accuracy
Second harmonic blocking
(5.0–100.0)% of fundamental
±1.0% of Ir
Note: fundamental magnitude = 100% of Ir
Fifth harmonic blocking
(5.0–100.0)% of fundamental
±3.0% of Ir
Note: fundamental magnitude = 100% of Ir
Critical impulse time
2 ms typically at 0 to 10 x
IdMin
-
Operate time with two input groups'
currents, restrained function, in a 50
Hz system1)
Min. = 10 ms
Max. = 20 ms
-
Operate time with two input groups'
currents, restrained function, in a 60
1)
Hz system
Min. = 8 ms
Max. = 17 ms
-
Operate time, restrained function at
2)
0 to 10 x IdMin, in a 50 Hz system
Min. = 10 ms
Max. = 20 ms
-
Operate time, restrained function at
2)
0 to 10 x IdMin, in a 60 Hz system
Min. = 8 ms
Max. = 17 ms
-
Reset time, restrained function at
2)
10 x IdMin to 0
Min. = 45 ms
Max. = 65 ms
-
Operate time, unrestrained function
at 0 to 10 x IdUnre2)
Min. = 5 ms
Max. = 17 ms
-
Reset time, unrestrained function at
2)
10 x IdUnre to 0
Min. = 45 ms
Max. = 65 ms
-
The data in the table are valid for single IED with 2 Mbit/s communication in loop-back mode.
The operate (trip) time is measured from general operate (trip) signal. In case of phase selective trip, the discrepancy
between different phases might be few milliseconds for a three-phase fault.
1) This data is obtained by applying two three-phase input groups' currents to simulate an internal fault with default
settings. Ir is applied to both input groups as pre- and post-fault currents. The fault is performed by simultaneously
increasing one group's currents to 10 x IdMin and decreasing the other group's currents to 0.
2) This data is obtained by applying one three-phase input group's currents only.
Line differential protection RED670
Technical manual
187
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
7.4
Line differential protection
7.4.1
Identification
IP13934-1 v1
M14844-1 v4
Function description
Line differential protection, 3 CT sets,
2-3 line ends
IEC 61850
identification
IEC 60617
identification
L3CPDIF
3Id/I>
ANSI/IEEE C37.2
device number
87L
SYMBOL-HH V1 EN-US
Line differential protection, 6 CT sets,
3-5 line ends
L6CPDIF
3Id/I>
87L
SYMBOL-HH V1 EN-US
Line differential protection 3 CT sets,
with in-zone transformers, 2-3 line ends
LT3CPDIF
3Id/I>
87LT
SYMBOL-HH V1 EN-US
Line differential protection 6 CT sets,
with in-zone transformers, 3-5 line ends
LT6CPDIF
Line differential logic
LDLPSCH
3Id/I>
87LT
SYMBOL-HH V1 EN-US
-
87L
7.4.2
Functionality
7.4.2.1
Line differential protection, 3 or 6 CT sets L3CPDIF, L6CPDIF
M14917-3 v7
Line differential protection applies the Kirchhoff's law and compares the currents entering and leaving
the protected multi-terminal circuit, consisting of overhead power lines and cables. Under the
condition that there are no in-line or tap (shunt) power transformers within the zone of protection, it
offers a phase segregated fundamental frequency current based differential protection with high
sensitivity and provides phase selection information for single-pole tripping
L3CPDIF is used for conventional two-terminal lines with or without a 1½ circuit breaker arrangement
in one end, as well as three-terminal lines with single breaker arrangements at all terminals.
Protected zone
IED
IEC05000039 V3 EN-US
Figure 67:
Communication channel
IED
IEC05000039-3-en.vsd
Example of application on a conventional two-terminal line
188
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
L6CPDIF is used for conventional two-terminal lines with 1½ circuit breaker arrangements in both
ends, as well as multi-terminal lines with up to five terminals.
Protected zone
Comm. Channel
IED
IED
Comm. Channel
Comm. Channel
IED
IEC05000040_2_en.vsd
IEC05000040 V2 EN-US
Figure 68:
Example of application on a three-terminal line with 1½ breaker arrangements
The current differential algorithm provides high sensitivity for internal faults and it has excellent
stability for external faults. Current samples from all CTs are exchanged between the IEDs in the line
ends (master-master mode) or sent to one IED (master-slave mode) for evaluation.
A restrained dual biased slope evaluation is made where the bias current is the highest phase
current in any line end, giving a secure through-fault stability even with heavily saturated CTs. In
addition to the restrained evaluation, an unrestrained (instantaneous) high differential current setting
can be used for fast tripping of internal faults with very high currents.
A special feature with this function is that applications with small power transformers (rated current
less than 50% of the differential current setting IdMin) connected as line taps (that is, as shunt power
transformers), without measurements of currents in the tap, can be handled. The normal load current
is considered to be negligible, and special measures must be taken in the event of a short circuit on
the LV side of the transformer. In this application, the tripping of the differential protection can be
time-delayed for low differential currents to achieve coordination with downstream overcurrent IEDs.
The local protection of the small tap power transformer is given the time needed to disconnect the
faulty transformer.
A line charging current compensation provides increased sensitivity of line differential protection.
7.4.2.2
Line differential protection 3 or 6 CT sets, with in-zone transformers
LT3CPDIF , LT6CPDIF
M14932-3 v9
Two two-winding power transformers or one three-winding power transformer can be included in the
line differential protection zone. In such application, the differential protection is based on the ampere
turns balance between the transformer windings. Both two- and three-winding transformers are
correctly represented with vector group compensations made in the algorithm. The function includes
2nd and 5th harmonic restraint and zero-sequence current elimination. The phase-segregated
differential protection with single-pole tripping is usually not possible in such applications.
Line differential protection RED670
Technical manual
189
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Protected zone
Comm. Channel
IED
Comm. Channel
IED
Comm. Channel
IED
IEC05000042_2_en.vsd
IEC05000042 V2 EN-US
Figure 69:
7.4.2.3
Example of application on a three-terminal line with an in-line power transformer in
the protection zone
Analog signal transfer for line differential protection
M13647-3 v9
The line differential protection function can be arranged as a master-master system or a masterslave system alternatively. In the former, current samples are exchanged between all IEDs, and an
evaluation is made in each IED. This means that a 64 kbits/s or 2 Mbit/s communication channel is
needed between every IED included in the same line differential protection zone. In the latter, current
samples are sent from all slave IEDs to one master IED where the evaluation is made, and trip
signals are sent to the remote ends when needed. In this system, a 64 kbits/s or 2 Mbit/s
communication channel is only needed between the master and each one of the slave IEDs. The
Master-Slave condition for the differential function appears automatically when the setting Operation
for the differential function is set to Off.
For line differential protection we recommend that all feeder ends use the same
version of RED670 and the line data communication module LDCM. The line
differential protection in the latest version of RED670 is compatible with older
versions of RED670. Older versions than 670 1.2.3 must be verified with Hitachi
Power Grids.
Protected zone
IED
IED
Comm.
Channels
IED
IED
IED
IEC0500043_2_en.vsd
IEC05000043 V2 EN-US
Figure 70:
Five terminal lines with master-master system
190
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Protected zone
IED
IED
Comm. Channels
IED
IED
IED
IEC050000 44-2en.vsd
IEC05000044 V2 EN-US
Figure 71:
Five terminal line with master-slave system
Current samples from IEDs located geographically apart from each other, must be time coordinated
so that the current differential algorithm can be executed correctly, this is done with the echo method.
Networks with fixed routes where symmetric time delay is applied, or networks with fixed route
switching where both directions have the symmetric time delay even after route switching has been
performed. In these types of networks, different channel delay times are automatically compensated
for, and echo timing can be used.
Networks with unspecified route switching require that the line differential protection IED's built-in
GPS receiver, PTP or IRIG-B is used. This way the protection function can operate correctly
independent of the symmetric delays in communication channels.
The communication link is continuously monitored, and an automatic switchover to a standby link is
possible after a preset time.
Line differential protection RED670
Technical manual
191
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
7.4.3
1MRK 505 377-UEN Rev. P
Function block
SEMOD54630-1 v1
M14921-3 v3
L3CPDIF
I3P1*
I3P2*
I3P3*
TRIP
TRL1
TRL2
TRL3
STARTRES
STARTUNR
STARTENH
START
STL1
STL2
STL3
INTFAULT
EXTFAULT
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000252-3-en.vsd
IEC06000252 V3 EN-US
Figure 72:
L3CPDIF function block
M14920-3 v3
L6CPDIF
I3P1*
I3P2*
I3P3*
I3P4*
I3P5*
I3P6*
TRIP
TRL1
TRL2
TRL3
STARTRES
STARTUNR
STARTENH
START
STL1
STL2
STL3
INTFAULT
EXTFAULT
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000253-3-en.vsd
IEC06000253 V3 EN-US
Figure 73:
L6CPDIF function block
192
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
M14937-3 v3
LT3CPDIF
I3P1*
I3P2*
I3P3*
TRIP
TRL1
TRL2
TRL3
STARTRES
STARTUNR
STARTENH
START
STL1
STL2
STL3
INTFAULT
EXTFAULT
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000254-3-en.vsd
IEC06000254 V3 EN-US
Figure 74:
LT3CPDIF function block
M14936-3 v2
LT6CPDIF
I3P1*
I3P2*
I3P3*
I3P4*
I3P5*
I3P6*
TRIP
TRL1
TRL2
TRL3
STARTRES
STARTUNR
STARTENH
START
STL1
STL2
STL3
INTFAULT
EXTFAULT
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
ALARM
OPENCT
OPENCTAL
IDL1
IDL2
IDL3
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC06000255-3-en.vsd
IEC06000255 V3 EN-US
Figure 75:
LT6CPDIF function block
Line differential protection RED670
Technical manual
193
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
M12591-3 v4
LDLPSCH
CTFAIL
OUTSERV
BLOCK
TRIP
TRL1
TRL2
TRL3
TRLOCAL
TRLOCL1
TRLOCL2
TRLOCL3
TRREMOTE
DIFLBLKD
IEC13000302-1-en.vsd
IEC13000302 V1 EN-US
Figure 76:
7.4.4
LDLPSCH function block
Signals
PID-6750-INPUTSIGNALS v1
Table 105: L3CPDIF Input signals
Name
Type
Default
Description
I3P1
GROUP
SIGNAL
-
Three phase current grp1 samples and DFT values
I3P2
GROUP
SIGNAL
-
Three phase current grp2 samples and DFT values
I3P3
GROUP
SIGNAL
-
Three phase current grp3 samples and DFT values
PID-6750-OUTPUTSIGNALS v1
Table 106: L3CPDIF Output signals
Name
Type
Description
TRIP
BOOLEAN
Common, main, trip output signal
TRL1
BOOLEAN
Trip signal from phase L1
TRL2
BOOLEAN
Trip signal from phase L2
TRL3
BOOLEAN
Trip signal from phase L3
STARTRES
BOOLEAN
Start of restrained differential protection
STARTUNR
BOOLEAN
Start of unrestrained differential protection
STARTENH
BOOLEAN
Start of enhanced restrained differential protection
START
BOOLEAN
Common, main, start output signal
STL1
BOOLEAN
Start signal from phase L1
STL2
BOOLEAN
Start signal from phase L2
STL3
BOOLEAN
Start signal from phase L3
INTFAULT
BOOLEAN
Internal fault has been detected
EXTFAULT
BOOLEAN
External fault has been detected
BLK2H
BOOLEAN
Common block signal, due to 2nd harmonic
BLK2HL1
BOOLEAN
Block signal due to 2nd harmonic, phase L1
BLK2HL2
BOOLEAN
Block signal due to 2nd harmonic, phase L2
BLK2HL3
BOOLEAN
Block signal due to 2nd harmonic, phase L3
BLK5H
BOOLEAN
Common block signal, due to 5-th harmonic
BLK5HL1
BOOLEAN
Block signal due to 5th harmonic, phase L1
BLK5HL2
BOOLEAN
Block signal due to 5th harmonic, phase L2
Table continues on next page
194
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Name
Section 7
Differential protection
Type
Description
BLK5HL3
BOOLEAN
Block signal due to 5th harmonic, phase L3
ALARM
BOOLEAN
Alarm for sustained differential current
OPENCT
BOOLEAN
An open CT was detected
OPENCTAL
BOOLEAN
Open CT Alarm output signal. Issued after a delay ...
IDL1
REAL
Instantaneous differential current, phase L1
IDL2
REAL
Instantaneous differential current, phase L2
IDL3
REAL
Instantaneous differential current, phase L3
IDL1MAG
REAL
Magnitude of fund. freq. differential current, phase L1
IDL2MAG
REAL
Magnitude of fund. freq. differential current, phase L2
IDL3MAG
REAL
Magnitude of fund. freq. differential current, phase L3
IBIAS
REAL
Magnitude of the bias current, common for L1, L2, L3
IDNSMAG
REAL
Magnitude of the negative sequence differential current
PID-6748-INPUTSIGNALS v1
Table 107: L6CPDIF Input signals
Name
Type
Default
Description
I3P1
GROUP
SIGNAL
-
Three phase current grp1 samples and DFT values
I3P2
GROUP
SIGNAL
-
Three phase current grp2 samples and DFT values
I3P3
GROUP
SIGNAL
-
Three phase current grp3 samples and DFT values
I3P4
GROUP
SIGNAL
-
Three phase current grp4 samples and DFT values
I3P5
GROUP
SIGNAL
-
Three phase current grp5 samples and DFT values
I3P6
GROUP
SIGNAL
-
Three phase current grp6 samples and DFT values
PID-6748-OUTPUTSIGNALS v1
Table 108: L6CPDIF Output signals
Name
Type
Description
TRIP
BOOLEAN
Common, main, trip output signal
TRL1
BOOLEAN
Trip signal from phase L1
TRL2
BOOLEAN
Trip signal from phase L2
TRL3
BOOLEAN
Trip signal from phase L3
STARTRES
BOOLEAN
Start of restrained differential protection
STARTUNR
BOOLEAN
Start of unrestrained differential protection
STARTENH
BOOLEAN
Start of enhanced restrained differential protection
START
BOOLEAN
Common, main, start output signal
STL1
BOOLEAN
Start signal from phase L1
STL2
BOOLEAN
Start signal from phase L2
STL3
BOOLEAN
Start signal from phase L3
INTFAULT
BOOLEAN
Internal fault has been detected
EXTFAULT
BOOLEAN
External fault has been detected
BLK2H
BOOLEAN
Common block signal, due to 2nd harmonic
Table continues on next page
Line differential protection RED670
Technical manual
195
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Name
Type
Description
BLK2HL1
BOOLEAN
Block signal due to 2nd harmonic, phase L1
BLK2HL2
BOOLEAN
Block signal due to 2nd harmonic, phase L2
BLK2HL3
BOOLEAN
Block signal due to 2nd harmonic, phase L3
BLK5H
BOOLEAN
Common block signal, due to 5-th harmonic
BLK5HL1
BOOLEAN
Block signal due to 5th harmonic, phase L1
BLK5HL2
BOOLEAN
Block signal due to 5th harmonic, phase L2
BLK5HL3
BOOLEAN
Block signal due to 5th harmonic, phase L3
ALARM
BOOLEAN
Alarm for sustained differential current
OPENCT
BOOLEAN
An open CT was detected
OPENCTAL
BOOLEAN
Open CT Alarm output signal. Issued after a delay ...
IDL1
REAL
Instantaneous differential current, phase L1
IDL2
REAL
Instantaneous differential current, phase L2
IDL3
REAL
Instantaneous differential current, phase L3
IDL1MAG
REAL
Magnitude of fund. freq. differential current, phase L1
IDL2MAG
REAL
Magnitude of fund. freq. differential current, phase L2
IDL3MAG
REAL
Magnitude of fund. freq. differential current, phase L3
IBIAS
REAL
Magnitude of the bias current, common for L1, L2, L3
IDNSMAG
REAL
Magnitude of the negative sequence differential current
PID-3701-INPUTSIGNALS v4
Table 109: LT3CPDIF Input signals
Name
Type
Default
Description
I3P1
GROUP
SIGNAL
-
Three phase current grp1 samples and DFT values
I3P2
GROUP
SIGNAL
-
Three phase current grp2 samples and DFT values
I3P3
GROUP
SIGNAL
-
Three phase current grp3 samples and DFT values
PID-3701-OUTPUTSIGNALS v4
Table 110: LT3CPDIF Output signals
Name
Type
Description
TRIP
BOOLEAN
Common, main, trip output signal
TRL1
BOOLEAN
Trip signal from phase L1
TRL2
BOOLEAN
Trip signal from phase L2
TRL3
BOOLEAN
Trip signal from phase L3
STARTRES
BOOLEAN
Start of restrained differential protection
STARTUNR
BOOLEAN
Start of unrestrained differential protection
STARTENH
BOOLEAN
Start of enhanced restrained differential protection
START
BOOLEAN
Common, main, start output signal
STL1
BOOLEAN
Start signal from phase L1
STL2
BOOLEAN
Start signal from phase L2
STL3
BOOLEAN
Start signal from phase L3
INTFAULT
BOOLEAN
Internal fault has been detected
EXTFAULT
BOOLEAN
External fault has been detected
Table continues on next page
196
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Name
Section 7
Differential protection
Type
Description
BLK2H
BOOLEAN
Common block signal, due to 2nd harmonic
BLK2HL1
BOOLEAN
Block signal due to 2nd harmonic, phase L1
BLK2HL2
BOOLEAN
Block signal due to 2nd harmonic, phase L2
BLK2HL3
BOOLEAN
Block signal due to 2nd harmonic, phase L3
BLK5H
BOOLEAN
Common block signal, due to 5-th harmonic
BLK5HL1
BOOLEAN
Block signal due to 5th harmonic, phase L1
BLK5HL2
BOOLEAN
Block signal due to 5th harmonic, phase L2
BLK5HL3
BOOLEAN
Block signal due to 5th harmonic, phase L3
ALARM
BOOLEAN
Alarm for sustained differential current
OPENCT
BOOLEAN
An open CT was detected
OPENCTAL
BOOLEAN
Open CT Alarm output signal. Issued after a delay ...
IDL1
REAL
Instantaneous differential current, phase L1
IDL2
REAL
Instantaneous differential current, phase L2
IDL3
REAL
Instantaneous differential current, phase L3
IDL1MAG
REAL
Magnitude of fund. freq. differential current, phase L1
IDL2MAG
REAL
Magnitude of fund. freq. differential current, phase L2
IDL3MAG
REAL
Magnitude of fund. freq. differential current, phase L3
IBIAS
REAL
Magnitude of the bias current, common for L1, L2, L3
IDNSMAG
REAL
Magnitude of the negative sequence differential current
PID-3699-INPUTSIGNALS v4
Table 111: LT6CPDIF Input signals
Name
Type
Default
Description
I3P1
GROUP
SIGNAL
-
Three phase current grp1 samples and DFT values
I3P2
GROUP
SIGNAL
-
Three phase current grp2 samples and DFT values
I3P3
GROUP
SIGNAL
-
Three phase current grp3 samples and DFT values
I3P4
GROUP
SIGNAL
-
Three phase current grp4 samples and DFT values
I3P5
GROUP
SIGNAL
-
Three phase current grp5 samples and DFT values
I3P6
GROUP
SIGNAL
-
Three phase current grp6 samples and DFT values
PID-3699-OUTPUTSIGNALS v4
Table 112: LT6CPDIF Output signals
Name
Type
Description
TRIP
BOOLEAN
Common, main, trip output signal
TRL1
BOOLEAN
Trip signal from phase L1
TRL2
BOOLEAN
Trip signal from phase L2
TRL3
BOOLEAN
Trip signal from phase L3
STARTRES
BOOLEAN
Start of restrained differential protection
STARTUNR
BOOLEAN
Start of unrestrained differential protection
STARTENH
BOOLEAN
Start of enhanced restrained differential protection
Table continues on next page
Line differential protection RED670
Technical manual
197
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Name
Type
Description
START
BOOLEAN
Common, main, start output signal
STL1
BOOLEAN
Start signal from phase L1
STL2
BOOLEAN
Start signal from phase L2
STL3
BOOLEAN
Start signal from phase L3
INTFAULT
BOOLEAN
Internal fault has been detected
EXTFAULT
BOOLEAN
External fault has been detected
BLK2H
BOOLEAN
Common block signal, due to 2nd harmonic
BLK2HL1
BOOLEAN
Block signal due to 2nd harmonic, phase L1
BLK2HL2
BOOLEAN
Block signal due to 2nd harmonic, phase L2
BLK2HL3
BOOLEAN
Block signal due to 2nd harmonic, phase L3
BLK5H
BOOLEAN
Common block signal, due to 5-th harmonic
BLK5HL1
BOOLEAN
Block signal due to 5th harmonic, phase L1
BLK5HL2
BOOLEAN
Block signal due to 5th harmonic, phase L2
BLK5HL3
BOOLEAN
Block signal due to 5th harmonic, phase L3
ALARM
BOOLEAN
Alarm for sustained differential current
OPENCT
BOOLEAN
An open CT was detected
OPENCTAL
BOOLEAN
Open CT Alarm output signal. Issued after a delay ...
IDL1
REAL
Instantaneous differential current, phase L1
IDL2
REAL
Instantaneous differential current, phase L2
IDL3
REAL
Instantaneous differential current, phase L3
IDL1MAG
REAL
Magnitude of fund. freq. differential current, phase L1
IDL2MAG
REAL
Magnitude of fund. freq. differential current, phase L2
IDL3MAG
REAL
Magnitude of fund. freq. differential current, phase L3
IBIAS
REAL
Magnitude of the bias current, common for L1, L2, L3
IDNSMAG
REAL
Magnitude of the negative sequence differential current
PID-3560-INPUTSIGNALS v6
Table 113: LDLPSCH Input signals
Name
Type
Default
Description
CTFAIL
BOOLEAN
0
CT failure indication from local CT supervision
OUTSERV
BOOLEAN
0
Input for indicating that the terminal is out of service
BLOCK
BOOLEAN
0
Block of function
PID-3560-OUTPUTSIGNALS v7
Table 114: LDLPSCH Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip from differential protection system
TRL1
BOOLEAN
Trip signal from phase L1
TRL2
BOOLEAN
Trip signal from phase L2
TRL3
BOOLEAN
Trip signal from phase L3
TRLOCAL
BOOLEAN
Trip from local differential function
TRLOCL1
BOOLEAN
Trip from local differential function in phase L1
TRLOCL2
BOOLEAN
Trip from local differential function in phase L2
Table continues on next page
198
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Name
7.4.5
Type
Description
TRLOCL3
BOOLEAN
Trip from local differential function in phase L3
TRREMOTE
BOOLEAN
Trip from remote differential function
DIFLBLKD
BOOLEAN
Local line differential function blocked
Settings
PID-6750-SETTINGS v1
Table 115: L3CPDIF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IdMin
0.20 - 2.00
IB
0.01
0.30
Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh
0.20 - 10.00
IB
0.01
0.80
Initial lower sensitivity, as multiple of
IBase
tIdMinHigh
0.000 - 60.000
s
0.001
1.000
Time interval of initial lower sensitivity, in
sec
IdUnre
1.00 - 50.00
IB
0.01
10.00
Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn
Off
On
-
-
On
Off/On selection for internal / external
fault discriminator
NegSeqROA
30.0 - 120.0
Deg
1.0
60.0
Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq
0.01 - 0.20
IB
0.01
0.04
Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn
No
Yes
-
-
No
Off/On selection of the cross -block logic
ChargCurEnable
Off
On
-
-
Off
Off/On selection for compensation of
charging currents
AddDelay
Off
On
-
-
Off
Off/On selection for delayed diff. trip
command
IMaxAddDelay
0.20 - 5.00
IB
0.01
1.00
Below limit, extra delay can be applied,
multiple of IBase
tDefTime
0.000 - 6.000
s
0.001
0.000
Definite time additional delay in seconds
tMinInv
0.001 - 6.000
s
0.001
0.010
Inverse Delay Minimum Time. In
seconds
CurveType
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
-
-
IEC Def. Time
19 curve types. Example: 15 for definite
time delay.
Table continues on next page
Line differential protection RED670
Technical manual
199
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
Name
1MRK 505 377-UEN Rev. P
Values (Range)
Unit
Step
Default
Description
k
0.05 - 1.10
-
0.01
1.00
Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm
0.05 - 1.00
IB
0.01
0.15
Sustained differential current alarm,
factor of IBase
tAlarmdelay
0.000 - 60.000
s
0.001
10.000
Delay for alarm due to sustained
differential current, in s
Table 116: L3CPDIF Group settings (advanced)
Name
Unit
Step
EndSection1
Values (Range)
0.20 - 1.50
IB
0.01
Default
1.25
Description
End of section 1, as multiple of reference
current IBase
EndSection2
1.00 - 10.00
IB
0.01
3.00
End of section 2, as multiple of reference
current IBase
SlopeSection2
10.0 - 50.0
%
0.1
40.0
Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3
30.0 - 100.0
%
0.1
80.0
Slope in section 3 of operate- restrain
characteristic, in %
I2/I1Ratio
5.0 - 100.0
%
1.0
10.0
Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio
5.0 - 100.0
%
1.0
25.0
Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
p
0.01 - 1000.00
-
0.01
0.02
Settable curve parameter, userprogrammable curve type.
a
0.01 - 1000.00
-
0.01
0.14
Settable curve parameter, userprogrammable curve type.
b
0.01 - 1000.00
-
0.01
1.00
Settable curve parameter, userprogrammable curve type.
c
0.01 - 1000.00
-
0.01
1.00
Settable curve parameter, userprogrammable curve type.
OpenCTEnable
Off
On
-
-
On
Open CTEnable Off/On
tOCTAlarmDelay
0.100 - 10.000
s
0.001
1.000
Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay
0.100 - 10.000
s
0.001
0.250
Reset delay in s. After delay, diff.
function is activated
OCTBlockEn
Off
On
-
-
On
Enable Open CT blocking function trip
Off/On
Table 117: L3CPDIF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
NoOfUsedCTs
2
3
-
-
2
Total number of 3-Ph CT sets connected
to diff protection
200
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
PID-6748-SETTINGS v1
Table 118: L6CPDIF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IdMin
0.20 - 2.00
IB
0.01
0.30
Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh
0.20 - 10.00
IB
0.01
0.80
Initial lower sensitivity, as multiple of
IBase
tIdMinHigh
0.000 - 60.000
s
0.001
1.000
Time interval of initial lower sensitivity, in
sec
IdUnre
1.00 - 50.00
IB
0.01
10.00
Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn
Off
On
-
-
On
Off/On selection for internal / external
fault discriminator
NegSeqROA
30.0 - 120.0
Deg
1.0
60.0
Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq
0.01 - 0.20
IB
0.01
0.04
Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn
No
Yes
-
-
No
Off/On selection of the cross -block logic
I2/I1Ratio
5.0 - 100.0
%
1.0
10.0
Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio
5.0 - 100.0
%
1.0
25.0
Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
ChargCurEnable
Off
On
-
-
Off
Off/On selection for compensation of
charging currents
AddDelay
Off
On
-
-
Off
Off/On selection for delayed diff. trip
command
IMaxAddDelay
0.20 - 5.00
IB
0.01
1.00
Below limit, extra delay can be applied,
multiple of IBase
tDefTime
0.000 - 6.000
s
0.001
0.000
Definite time additional delay in seconds
tMinInv
0.001 - 6.000
s
0.001
0.010
Inverse Delay Minimum Time. In
seconds
CurveType
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
-
-
IEC Def. Time
19 curve types. Example: 15 for definite
time delay.
Table continues on next page
Line differential protection RED670
Technical manual
201
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
Name
1MRK 505 377-UEN Rev. P
Values (Range)
Unit
Step
Default
Description
k
0.05 - 1.10
-
0.01
1.00
Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm
0.05 - 1.00
IB
0.01
0.15
Sustained differential current alarm,
factor of IBase
tAlarmdelay
0.000 - 60.000
s
0.001
10.000
Delay for alarm due to sustained
differential current, in s
Table 119: L6CPDIF Group settings (advanced)
Name
Unit
Step
EndSection1
Values (Range)
0.20 - 1.50
IB
0.01
Default
1.25
Description
End of section 1, as multiple of reference
current IBase
EndSection2
1.00 - 10.00
IB
0.01
3.00
End of section 2, as multiple of reference
current IBase
SlopeSection2
10.0 - 50.0
%
0.1
40.0
Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3
30.0 - 100.0
%
0.1
80.0
Slope in section 3 of operate- restrain
characteristic, in %
p
0.01 - 1000.00
-
0.01
0.02
Settable curve parameter, userprogrammable curve type.
a
0.01 - 1000.00
-
0.01
0.14
Settable curve parameter, userprogrammable curve type.
b
0.01 - 1000.00
-
0.01
1.00
Settable curve parameter, userprogrammable curve type.
c
0.01 - 1000.00
-
0.01
1.00
Settable curve parameter, userprogrammable curve type.
OpenCTEnable
Off
On
-
-
On
Open CTEnable Off/On
tOCTAlarmDelay
0.100 - 10.000
s
0.001
1.000
Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay
0.100 - 10.000
s
0.001
0.250
Reset delay in s. After delay, diff.
function is activated
OCTBlockEn
Off
On
-
-
On
Enable Open CT blocking function trip
Off/On
Table 120: L6CPDIF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
NoOfUsedCTs
2
3
4
5
6
-
-
2
Total number of 3-Ph CT sets connected
to diff protection
PID-6605-SETTINGS v3
Table 121: LT3CPDIF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IdMin
0.20 - 2.00
IB
0.01
0.30
Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh
0.20 - 10.00
IB
0.01
0.80
Initial lower sensitivity, as multiple of
IBase
Table continues on next page
202
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Name
Section 7
Differential protection
Values (Range)
Unit
Step
Default
Description
tIdMinHigh
0.000 - 60.000
s
0.001
1.000
Time interval of initial lower sensitivity, in
sec
IdUnre
1.00 - 50.00
IB
0.01
10.00
Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn
Off
On
-
-
On
Off/On selection for internal / external
fault discriminator
NegSeqROA
30.0 - 120.0
Deg
1.0
60.0
Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq
0.01 - 0.20
IB
0.01
0.04
Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn
No
Yes
-
-
No
Off/On selection of the cross -block logic
ChargCurEnable
Off
On
-
-
Off
Off/On selection for compensation of
charging currents
AddDelay
Off
On
-
-
Off
Off/On selection for delayed diff. trip
command
IMaxAddDelay
0.20 - 5.00
IB
0.01
1.00
Below limit, extra delay can be applied,
multiple of IBase
tDefTime
0.000 - 6.000
s
0.001
0.000
Definite time additional delay in seconds
tMinInv
0.001 - 6.000
s
0.001
0.010
Inverse Delay Minimum Time. In
seconds
CurveType
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
-
-
IEC Def. Time
19 curve types. Example: 15 for definite
time delay.
k
0.05 - 1.10
-
0.01
1.00
Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm
0.05 - 1.00
IB
0.01
0.15
Sustained differential current alarm,
factor of IBase
tAlarmdelay
0.000 - 60.000
s
0.001
10.000
Delay for alarm due to sustained
differential current, in s
Table 122: LT3CPDIF Group settings (advanced)
Name
Unit
Step
EndSection1
Values (Range)
0.20 - 1.50
IB
0.01
Default
1.25
Description
End of section 1, as multiple of reference
current IBase
EndSection2
1.00 - 10.00
IB
0.01
3.00
End of section 2, as multiple of reference
current IBase
SlopeSection2
10.0 - 50.0
%
0.1
40.0
Slope in section 2 of operate-restrain
characteristic, in %
Table continues on next page
Line differential protection RED670
Technical manual
203
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
Name
1MRK 505 377-UEN Rev. P
Unit
Step
SlopeSection3
Values (Range)
30.0 - 100.0
%
0.1
Default
80.0
Description
Slope in section 3 of operate- restrain
characteristic, in %
I2/I1Ratio
5.0 - 100.0
%
1.0
10.0
Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio
5.0 - 100.0
%
1.0
25.0
Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
p
0.01 - 1000.00
-
0.01
0.02
Settable curve parameter, userprogrammable curve type.
a
0.01 - 1000.00
-
0.01
0.14
Settable curve parameter, userprogrammable curve type.
b
0.01 - 1000.00
-
0.01
1.00
Settable curve parameter, userprogrammable curve type.
c
0.01 - 1000.00
-
0.01
1.00
Settable curve parameter, userprogrammable curve type.
OpenCTEnable
Off
On
-
-
On
Open CTEnable Off/On
tOCTAlarmDelay
0.100 - 10.000
s
0.001
1.000
Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay
0.100 - 10.000
s
0.001
0.250
Reset delay in s. After delay, diff.
function is activated
OCTBlockEn
Off
On
-
-
On
Enable Open CT blocking function trip
Off/On
Table 123: LT3CPDIF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
NoOfUsedCTs
2
3
-
-
2
Total number of 3-Ph CT sets connected
to diff protection
ZerSeqCurSubtr
Off
On
-
-
Off
Off/On for elimination of zero seq. from
diff. and bias curr
TraAOnInpCh
No Transf A
1
2
3
-
-
No Transf A
Power transformer A applied on input
channel X
RatVoltW1TraA
1.0 - 9999.9
kV
0.1
130.0
Transformer A rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraA
1.0 - 9999.9
kV
0.1
130.0
Transformer A rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransA
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
-
-
0 [0 deg]
Transf. A phase shift in multiples of 30
deg, 5 for 150 deg
TraBOnInpCh
No Transf B
1
2
3
-
-
No Transf B
Power transformer B applied on input
channel X
Table continues on next page
204
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Name
Section 7
Differential protection
Unit
Step
Default
RatVoltW1TraB
Values (Range)
1.0 - 9999.9
kV
0.1
130.0
Description
Transformer B rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraB
1.0 - 9999.9
kV
0.1
130.0
Transformer B rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransB
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
-
-
0 [0 deg]
Transf. B phase shift in multiples of 30
deg, 2 for 60 deg
PID-6606-SETTINGS v3
Table 124: LT6CPDIF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IdMin
0.20 - 2.00
IB
0.01
0.30
Oper - restr charact., section 1
sensitivity, multiple IBase
IdMinHigh
0.20 - 10.00
IB
0.01
0.80
Initial lower sensitivity, as multiple of
IBase
tIdMinHigh
0.000 - 60.000
s
0.001
1.000
Time interval of initial lower sensitivity, in
sec
IdUnre
1.00 - 50.00
IB
0.01
10.00
Unrestrained differential current limit,
multiple of IBase
NegSeqDiffEn
Off
On
-
-
On
Off/On selection for internal / external
fault discriminator
NegSeqROA
30.0 - 120.0
Deg
1.0
60.0
Internal/external fault discriminator
Operate Angle, degrees
IMinNegSeq
0.01 - 0.20
IB
0.01
0.04
Min. value of neg. seq. curr. as multiple
of IBase
CrossBlockEn
No
Yes
-
-
No
Off/On selection of the cross -block logic
I2/I1Ratio
5.0 - 100.0
%
1.0
10.0
Max. ratio of 2nd harm. to fundamental
harm dif. curr. in %
I5/I1Ratio
5.0 - 100.0
%
1.0
25.0
Max. ratio of 5th harm. to fundamental
harm dif. curr. in %
ChargCurEnable
Off
On
-
-
Off
Off/On selection for compensation of
charging currents
AddDelay
Off
On
-
-
Off
Off/On selection for delayed diff. trip
command
IMaxAddDelay
0.20 - 5.00
IB
0.01
1.00
Below limit, extra delay can be applied,
multiple of IBase
tDefTime
0.000 - 6.000
s
0.001
0.000
Definite time additional delay in seconds
tMinInv
0.001 - 6.000
s
0.001
0.010
Inverse Delay Minimum Time. In
seconds
Table continues on next page
Line differential protection RED670
Technical manual
205
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
Name
1MRK 505 377-UEN Rev. P
Values (Range)
Unit
Step
Default
Description
CurveType
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
-
-
IEC Def. Time
19 curve types. Example: 15 for definite
time delay.
k
0.05 - 1.10
-
0.01
1.00
Time Multiplier Setting (TMS) for inverse
delays
IdiffAlarm
0.05 - 1.00
IB
0.01
0.15
Sustained differential current alarm,
factor of IBase
tAlarmdelay
0.000 - 60.000
s
0.001
10.000
Delay for alarm due to sustained
differential current, in s
Table 125: LT6CPDIF Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
EndSection1
0.20 - 1.50
IB
0.01
1.25
End of section 1, as multiple of reference
current IBase
EndSection2
1.00 - 10.00
IB
0.01
3.00
End of section 2, as multiple of reference
current IBase
SlopeSection2
10.0 - 50.0
%
0.1
40.0
Slope in section 2 of operate-restrain
characteristic, in %
SlopeSection3
30.0 - 100.0
%
0.1
80.0
Slope in section 3 of operate- restrain
characteristic, in %
p
0.01 - 1000.00
-
0.01
0.02
Settable curve parameter, userprogrammable curve type.
a
0.01 - 1000.00
-
0.01
0.14
Settable curve parameter, userprogrammable curve type.
b
0.01 - 1000.00
-
0.01
1.00
Settable curve parameter, userprogrammable curve type.
c
0.01 - 1000.00
-
0.01
1.00
Settable curve parameter, userprogrammable curve type.
OpenCTEnable
Off
On
-
-
On
Open CTEnable Off/On
tOCTAlarmDelay
0.100 - 10.000
s
0.001
1.000
Open CT: time in s to alarm after an
open CT is detected
tOCTResetDelay
0.100 - 10.000
s
0.001
0.250
Reset delay in s. After delay, diff.
function is activated
OCTBlockEn
Off
On
-
-
On
Enable Open CT blocking function trip
Off/On
206
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Table 126: LT6CPDIF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
NoOfUsedCTs
2
3
4
5
6
-
-
2
Total number of 3-Ph CT sets connected
to diff protection
ZerSeqCurSubtr
Off
On
-
-
Off
Off/On for elimination of zero seq. from
diff. and bias curr
TraAOnInpCh
No Transf A
1
2
3
4
5
6
-
-
No Transf A
Power transformer A applied on input
channel X
RatVoltW1TraA
1.0 - 9999.9
kV
0.1
130.0
Transformer A rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraA
1.0 - 9999.9
kV
0.1
130.0
Transformer A rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransA
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
-
-
0 [0 deg]
Transf. A phase shift in multiples of 30
deg, 5 for 150 deg
TraBOnInpCh
No Transf B
1
2
3
4
5
6
-
-
No Transf B
Power transformer B applied on input
channel X
RatVoltW1TraB
1.0 - 9999.9
kV
0.1
130.0
Transformer B rated voltage (kV) on
winding 1 (HV winding)
RatVoltW2TraB
1.0 - 9999.9
kV
0.1
130.0
Transformer B rated voltage (kV) on
winding 2 (LV winding)
ClockNumTransB
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
-
-
0 [0 deg]
Transf. B phase shift in multiples of 30
deg, 2 for 60 deg
Line differential protection RED670
Technical manual
207
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
PID-3560-SETTINGS v6
Table 127: LDLPSCH Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
TestModeSet
Off
On
-
-
Off
Test mode On/Off
ReleaseLocal
Block all
Release local
-
-
Block all
Release of local terminal for trip under
test mode
7.4.6
Monitored data
PID-6750-MONITOREDDATA v1
Table 128: L3CPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
IDL1MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L1
IDL2MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L2
IDL3MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L3
IBIAS
REAL
-
A
Magnitude of the bias current, common
for L1, L2, L3
IDNSMAG
REAL
-
A
Magnitude of the negative sequence
differential current
NSANGLE
REAL
-
deg
Angle between local and remote neg.
seq. currents
ICHARGE
REAL
-
A
Amount of compensated charging
current
PID-6748-MONITOREDDATA v1
Table 129: L6CPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
IDL1MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L1
IDL2MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L2
IDL3MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L3
IBIAS
REAL
-
A
Magnitude of the bias current, common
for L1, L2, L3
IDNSMAG
REAL
-
A
Magnitude of the negative sequence
differential current
NSANGLE
REAL
-
deg
Angle between local and remote neg.
seq. currents
ICHARGE
REAL
-
A
Amount of compensated charging
current
208
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
PID-3701-MONITOREDDATA v3
Table 130: LT3CPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
OPENCTIN
INTEGER
-
-
Open CT on Input : 1 for input 1, 2 for
input 2
OPENCTPH
INTEGER
-
-
Open CT in Phase : 1 for L1, 2 for L2, 3
for L3
IDL1MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L1
IDL2MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L2
IDL3MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L3
IBIAS
REAL
-
A
Magnitude of the bias current, common
for L1, L2, L3
IDNSMAG
REAL
-
A
Magnitude of the negative sequence
differential current
NSANGLE
REAL
-
deg
Angle between local and remote neg.
seq. currents
ICHARGE
REAL
-
A
Amount of compensated charging
current
PID-3699-MONITOREDDATA v3
Table 131: LT6CPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
OPENCTIN
INTEGER
-
-
Open CT on Input : 1 for input 1, 2 for
input 2
OPENCTPH
INTEGER
-
-
Open CT in Phase : 1 for L1, 2 for L2, 3
for L3
IDL1MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L1
IDL2MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L2
IDL3MAG
REAL
-
A
Magnitude of fund. freq. differential
current, phase L3
IBIAS
REAL
-
A
Magnitude of the bias current, common
for L1, L2, L3
IDNSMAG
REAL
-
A
Magnitude of the negative sequence
differential current
NSANGLE
REAL
-
deg
Angle between local and remote neg.
seq. currents
ICHARGE
REAL
-
A
Amount of compensated charging
current
7.4.7
Operation principle
7.4.7.1
Algorithm and logic
M13652-3 v7
The Line differential protection function evaluates measured current values from local and remote
line ends in order to distinguish between internal or external faults or undisturbed conditions.
The local currents are fed to the IED via the analog input modules and then they pass the analog-todigital converter, as shown in Figure 77.
Line differential protection RED670
Technical manual
209
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Remote end
Local end
Remote end IED
LDCM
Local end IED
Analog Input
Module
Current
samples from
local end
A/D
Converter
Current
samples from
remote end
LDCM
Pre-processing
Block
CH1IL2RE
CH1IL2IM
Currents from
all ends as
phasors
Calculation of
fundamental
frequency
differential
currents (3x)
& bias current
Magnitudes of
differential
currents
Bias current
Trip by unrestrained differential protection
Differential
and bias currents
applied to
operate / bias -,
and unrestrained
characteristics
³1
Start L1
Start L2
St L2 low sens
St L3 low sens
CH1IL2SM
CH1IL3SM
CH2IL1SM
Curr. samples
from all ends
Calculation
of
instantaneous
differential
currents
(3x)
2nd h. block
[samples]
Instantaneous
differential
currents
(samples)
Harmonic
analysis
nd
th
( 2 and 5 )
Output logic:
Start L3
St L1 low sens
CH1IL1SM
5th h. block
- 2nd
- 5th
-
CH1INSRE
CH1INSIM
Neg. seq.
currents from
all ends
as phasors
Calculation
of
negative-sequence
differential
current
(1x)
Two to six
contributions
to neg. seq.
differential
current as
phasors
High sensitive
internal/external fault
discriminator
Cross block logic
-
TRL1
TRL2
TRL3
STARTRES
STARTUNR
STARTENH
START
STL1
STL2
STL3
- Decreased
sensitivity for
external faults
Internal fault
External fault
harmonic block
harmonic block
- Enhanced trip for
internal faults
-
CH1INSRE
CH1INSIM
TRIP
Conditional trip for
simultaneous external
and internal faults
Conditional extra time
delay for trip signals
BLK2H
BLK2HL1
BLK2HL2
BLK2HL3
Information
[magnitude]
CH1IL1RE
CH1IL1IM
Trip commands
Line Diffferential Function
BLK5H
BLK5HL1
BLK5HL2
BLK5HL3
INTFAULT
EXTFAULT
IEC05000294-4-en.vsd
IEC05000294 V3 EN-US
Figure 77:
A simplified block diagram of the power line differential protection
The IED receives the remote currents as samples via a communication link. When entering the IED,
they are processed in the Line Differential Communication Module (LDCM) where they are timecoordinated with the local current samples, and interpolated in order to be comparable with the local
samples.
In the preprocessing block, the real and imaginary parts of the fundamental frequency phase currents
and negative sequence currents are derived by means of fundamental frequency numerical Fourier
filters. Together with the current samples, which are required to internally estimate the 2nd and the 5th
210
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
harmonic contents in the instantaneous differential currents, they are then forwarded to the
differential function block where three kinds of analyses are carried out.
The first analysis is the classical differential and bias current evaluation with the characteristic as
seen in Figure 78. Line differential protection is phase-segregated where the differential current is the
vectorial sum of all measured currents taken separately for each phase. The bias current, on the
other hand, is considered the greatest phase current in any line end and it is common for all the tree
phases. The two slopes (SlopeSection1, SlopeSection2) and breakpoints (EndSection1,
EndSection2) can be set in PCM600 or via the local human-machine interface (LHMI).
Current values found to be above the characteristic formed by IdMin and the dual slope will give a
start in that phase. The level IdMinHigh is a setting value that is used to temporarily decrease the
sensitivity in situations when the protected line circuit is just energized, that is, connected to the
power system at one end.
There is also an unrestrained high differential current setting that can be used for fast tripping of
internal faults with very high currents. This unrestrained protection is phase-segregated, that is, it is
known which phase(s) require a trip command.
Line differential protection RED670
Technical manual
211
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Operate current
[ in pu of IBase]
Operate
5
unconditionally
UnrestrainedLimit
4
Operate
3
IdMinHigh
C
conditionally
A
B
2
Section 1
Section 2
Section 3
SlopeSection3
1
IdMin
SlopeSection2
Restrain
0
0
1
2
3
EndSection1
EndSection2
4
5
Restrain current
[ in pu of IBase]
en05000300.vsd
IEC05000300 V1 EN-US
Figure 78:
Description of the restrained and the unrestrained operate characteristics
where:
slope = D Ioperate × 100%
D Irestrain
EQUATION1246 V1 EN-US
and where the restrained characteristic is defined by the
settings:
1. IdMin
2. EndSection1
3. EndSection2
4. SlopeSection2
5. SlopeSection3
The second analysis is the 2nd and 5th harmonic analysis of the three instantaneous differential
currents. Occurrence of these harmonics over a level that is set separately for each one blocks
tripping action from the biased slope evaluation. Harmonics blocking based on 2nd and 5th harmonics
is used only used if one of the following conditions are fulfilled:
•
•
•
When a power transformer is included in the protected zone.
When the bias current is less than 125 % Ibase.
When an external fault has been detected by the negative sequence internal/external fault
discriminator and 200 ms after that.
The third analysis is the negative sequence current analysis. Effectively this is a fault discriminator
that distinguishes between internal and external faults. The directional test is made so that the end
with the highest negative sequence current is found. Then, the sum of the negative sequence
currents at all other circuit ends is calculated. Finally, the relative phase angle between these two
212
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
negative sequence currents is determined. The characteristic for this fault discriminator is shown in
Figure 79, where the directional characteristic is defined by the two setting parameters IminNegSeq
and NegSeqRoa.
90 deg
120 deg
If one or the
other of
currents is too
low, then no
measurement
is done, and
120 degrees
is mapped
Internal/external
fault boundary
NegSeqROA
(Relay
Operate
Angle)
180 deg
0 deg
IMinNegSeq
Internal
fault
region
External
fault
region
270 deg
en05000188-3-en.vsd
IEC05000188 V3 EN-US
Figure 79:
Operate characteristic of the internal/external fault discriminator
The reference direction (that is, the positive direction) of currents in a power line is considered to be
towards the line. Thus, when both negative sequence currents to be compared have this direction,
the phase difference between them is ideally zero. In reality, the angle will usually be greater than
zero, and this because of the possible different negative sequence impedance angles on both sides
as seen from the fault location.
An internal fault can be suspected. In the opposite case, when one negative sequence current is
entering and the other is leaving the protected object, the phase difference will ideally be 180
degrees. An external fault can be suspected. If either the local or the sum of the remote negative
sequence currents or both is below the set level, the fault discriminator does not make any fault
classification and the value 120 degrees is set. This value is an indication that negative sequence
directional comparison has not been possible. In this case, neither internal nor external fault is
signalized. When an external fault is detected, the 2nd and 5th harmonic analysis is activated for 200
ms. This gives better stability against unwanted trips. Under an external fault condition, the cross
block logic algorithm is active as well.
When a fault is classified as internal by the negative sequence fault discriminator, a trip command is
issued under the condition that at least one start signal has been issued, while all eventual block
signals (issued by the harmonic analysis of the instantaneous differential currents) are ignored.
For all differential functions it is the common trip that shall be used to initiate a trip of
a breaker. The separate trip signals from the different parts lacks the safety against
maloperation. This does in some cases result in a 6 ms time difference between, for
example restrained trip is issued and common trip is issued. The separate trip
signals shall only be used for information purpose of which part that has caused the
trip.
Line differential protection RED670
Technical manual
213
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
With reference to Figure 77, the outputs from the three analysis blocks are fed to the output logic.
Figure 80 shows a simplified block diagram of this output logic where only trip commands and no
alarm signals are shown for simplicity.
Trip unrestrained L1
Trip unrestrained L2
OR
TRIP
Trip unrestrained L3
Start L1
AND
AND
OR
Start L2
TRL1
OR
OR
Start L3
TRL2
OR
AND
AND
OR
OR
AND
OR
St L1 IdMinHigh
TRL3
OR
AND
OR
St L2 IdMinHigh
St L3 IdMinHigh
Internal fault
AND
NegSeqDiffEn
AND
External fault
tIdMinHigh
t
tIdMinHigh
t
Line energizing
Diff curr L1 2nd harm
Diff curr L1 5th harm
Diff curr L2 2nd harm
Diff curr L2 5th harm
OR
OR
Diff curr L3 5th harm
AND
OR
AND
OR
AND
nd
Diff curr L3 2 harm
OR
OR
OR
OR
AND
CrossBlockEn
IEC05000295-4-en.vsd
IEC05000295 V4 EN-US
Figure 80:
Simplified block diagram
Remembering that current values plotted above the characteristic formed by IdMin and the dual
slope in Figure 79 are said to give a start, the output logic can be summarized as follows:
•
A start in one phase, gives a trip under the condition that the content of the 2nd and the 5th
harmonic is below the set level for these harmonics in the phase with start, if CrossBlockEn =
OFF. If CrossBlockEn = ON, then all phases with their start signals set, must be free of their
respective harmonic block signals; otherwise no trip command is issued. Otherwise it is blocked
as long as the harmonic is above the set level. However, when a line is energized the current
setting value IdMinHigh is used. Effectively this means that the line A-B-C in Figure 78 forms the
characteristic. The harmonic block scheme is generally not applied if there are no in-line or
shunt power transformers within the protection zone. In other words, if there are no in-line or tap
214
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
•
•
•
Section 7
Differential protection
(shunt) power transformers within the protection zone, then no harmonics can prevent a trip
command. This makes the response of the differential protection faster in approximately 90% of
all cases.
Current values above the unrestrained limit, gives a trip irrespective of any presence of
harmonics.
Classification of a fault as internal by the negative sequence currents based fault discriminator,
gives a trip under the condition that at least one start signal has been issued, that is, set to 1
(TRUE). The negative sequence current based fault discriminator itself is not phase-sensitive,
and the start signals are required to determine which phases were affected by the fault. Any
harmonic blocking is then ignored. The harmonic block scheme is not applied if there are no inline or tap (shunt) power transformers within the protection zone. In other words, if there are no
in-line or tap power transformers within the protection zone, then harmonics cannot prevent a
trip command. This makes the response of the protection faster in the majority of cases. If there
is no power transformer within the protected circuit, then the 2nd and 5th harmonic analysis is
only activated temporarily under external fault conditions, or when the bias current is lower than
1. 25 ⅹ IBase.
Classification of a fault as external by the negative sequence fault discriminator will cause the
harmonic logic scheme to be applied under the duration of the external fault signal, at least for
200 ms. Even the cross block logic scheme is then active.
The compensation of charging currents can be selected active or inactive by setting ChargCurEnable
Yes or No. The compensation works so that the fundamental frequency differential current that is
measured under steady state undisturbed conditions, is identified and then subtracted making the
resulting differential current zero (or close to zero). This action is made separately for each phase.
The magnitude of the subtracted pre-fault currents in Amperes can be read at any time as the service
value ICHARGE.
Values of the pre-fault differential currents are not updated under disturbance conditions. The
updating process is resumed 50 ms after normal conditions have been restored. Normal conditions
are only assumed if there are no start signals, neither internal nor external fault is declared, the
power system is symmetrical.
The change in the charging current that the fault causes by decreasing the system voltage is not
considered in the algorithm. For more information, see the application manual.
Note that the subtraction of the charging current is limited to a value specified by IdMin. Observe as
well that IdMin must always be set at least 25 % - 50 % above the value of charging currents.
Note that all small pre-fault differential currents are subtracted, regardless of their origin. Besides the
true charging currents, the following currents are eliminated:
•
•
•
7.4.7.2
Small false differential currents due to small errors (inequalities) of current transformers.
Small false differential currents because of off-nominal load tap changer positions when a power
transformer is included in the protected zone.
Load currents of tap power transformers included in the protected zone.
Time synchronization
SEMOD52396-4 v5
In a numerical line differential protection, current samples from protections located geographically
apart from each other, must be time coordinated so that the currents from the different line ends can
be compared without introducing irrelevant errors. Accuracy requirements on this time coordination
are extremely high.
As an example, an inaccuracy of 0.1 ms in a 50 Hz system gives a maximum amplitude error
approximately around 3% whilst an inaccuracy of 1 ms gives a maximum amplitude error of
approximately 31%. The corresponding figures for a 60 Hz system are 4% and 38% respectively.
In Line differential protection, the time coordination is made with the so-called echo method. The
echo method can be complemented with GPS synchronization as an option.
Line differential protection RED670
Technical manual
215
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Each IED has an accurate local clock with a very small time drift. This clock makes time tagging of
telegrams, and the echo method is then used to find out the time difference between the clocks in
two ends of a power line.
Referring to Figure 81, it works such that the transmission time to send a message from station B to
station A (T1 → T2) and receive a message from A to B (T3 → T4) is measured. The time instances
T2 and T3 are taken with the local clock reference of station A, and the time instances T1 and T4 are
taken with the local clock reference of station B.
T2
A
B
T3
T1
T4
en05000293.vsd
IEC05000293 V1 EN-US
Figure 81:
Measuring time differences
Calculation of the delay time one-way Td and the time difference Δt between the clocks in A and B is
then possible to do with equation 17 and equation 18, which are only valid under the condition that
the send and receive times are equal.
Td =
(T2 - T1 ) + (T4 - T3 )
2
(Equation 17)
EQUATION1358 V1 EN-US
Dt =
(T1 + T4 ) - (T2 + T3 )
2
(Equation 18)
EQUATION1359 V1 EN-US
Δt is calculated every time a telegram is received, and the time difference is then used to adjust and
interpolate the current measurements from the remote end before the current differential algorithm is
executed.
The echo method can be used in telecommunications transmission networks with varying signal
propagation delay as long as there is delay symmetry, that is, the send and receive delays are equal.
The delay variation can depend on the signal going different routes in the network from time to other.
When the delay symmetry is lost, the expression for Δt given above is no longer valid. Under these
conditions GPS synchronization of the local IED clocks must be used.
Including the optional GPS, means that there will be one GPS receiver module in each IED,
synchronizing its local IED clock. As GPS synchronization is very accurate, in the order of 1 μs, all
IEDs in the same line differential scheme will have the same clock reference. It is then possible to
detect asymmetric transmission time delay and compensate for it.
When the IED is equipped with GPS, this hardware is integrated in the IED. Besides the GPS
receiver itself, it also consists of filters and regulators for post processing of the GPS time synch
pulse, which is necessary to achieve a reliable GPS synchronization. Especially short interruptions
and spurious out of synch GPS signals are handled securely in this way.
When GPS synchronization is used, an interruption in the GPS signal leads to freewheeling during 8
seconds that is, during this time the synchronization benefits from the stability in the local clocks. If
the interruption persists more than 8 seconds, either fall back to the echo synchronization method or
216
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
blocking of Line differential protection function is made, as selected through setting parameter
GPSSyncErr.
7.4.7.3
Analog signal communication for line differential protection
SEMOD52424-1 v1
Communication principle
SEMOD52415-4 v3
For a two-terminal line, the current from the local CT needs to be communicated over a 64 kbit/s
channel to the remote line end, and the remote end current communicated back on the same
channel. If there is, for example, a three terminal line another 64 kbit/s channel will be needed to
exchange the same local current with the third line end current.
In one-and-a-half breaker arrangements, there are two local currents meaning two 64 kbit/s channels
to each remote substation. Alternatively, it is possible to add together the two local currents before
sending them and in that way reduce the number of communication channels needed. This is
achieved by selecting proper setting for parameter TransmCurr (CT-SUM, CT-DIFF1 or CT-DIFF2).
However, information about bias currents is reduced if the alternative option is followed. For further
information and discussions on this matter, refer to the Application manual.
The communication can be arranged as a master-master system or a master-slave system
alternatively. Figure 82 shows a master-master system for a five-terminal line. Here current samples
are exchanged between all IEDs, and an evaluation is made in each IED. This means that a 64 kbit/s
communication channel is needed between every IED included in the same line differential protection
zone.
Protected zone
IED
IED
Comm. Channels
IED
IED
IED
IEC05000292_2_en.vsd
IEC05000292 V2 EN-US
Figure 82:
5–terminal line with master-master system
In the master-slave system, current samples are sent from all slave IEDs to one master IED where
the evaluation is made and trip signals are sent to the remote ends when needed. In this system, a
64 kbit/s communication channel is only needed between the master, and each one of the slave
IEDs, as shown in figure 83.
Protected zone
IED
IED
Comm. Channels
IED
IED
IED
IEC05000291_2_en.vsd
IEC05000291 V2 EN-US
Figure 83:
5–terminal line with master-slave system
Line differential protection RED670
Technical manual
217
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
The master-slave configuration is achieved by setting parameter Operation in the slaves to Off for
Line differential protection function, and setting parameter ChannelMode to On for the LDCMs in the
slaves.
Test mode
SEMOD52415-48 v2
Line differential protection function in one IED can be set in test mode. This can block the trip outputs
on that IED, and set the remote IEDs in a remote test mode, so that injected currents can be echoed
back phase shifted and with a settable amplitude. The trip outputs in the remote IEDs can also be
blocked automatically. For further information, refer to the installation and commissioning manual.
Communication of current sampled values
SEMOD52415-22 v2
The currents are sampled twenty times per power system cycle in the protection terminals, but the
communication exchange is made only once every 5 ms. This means that at in each telegram sent, 5
consecutive current samples in a 50 Hz system and 6 consecutive current samples in a 60 Hz
system (three phases each sampling instant) are included. Figure 84 shows the principle.
Current
sample
telegram
sent
Current
sample
telegram
sent
Current
sample
telegram
sent
Current
sample
telegram
sent
Current
sample
telegram
sent
Current
sample
telegram
sent
Current
sample
telegram
sent
5
10
15
20
25
30
35
0
Current
sample
telegram
sent
Time
(ms)
en05000290.vsd
IEC05000290 V1 EN-US
Figure 84:
Communication of current sampled values.
where:
x
is the current sampling moment
Redundant communication channels
SEMOD52415-25 v5
With redundant communication channels, as shown in figure 85, both channels are in operation
continuously but with one of them favoured as a primary channel.
Telecom. Network
LD
CM
LD
CM
IEC05000289 V1 EN-US
Figure 85:
Telecom. Network
Primary
channel
Secondary redundant
channel
LD
CM
LD
CM
en05000289.vsd
Direct fiber optical connection between two IEDs with LDOM over longer distances.
If communication is lost on the primary channel, switchover to the secondary channel is made after a
settable time delay RedChSwTime. Return of the primary channel will cause a switchback after
another settable time delay RedChRturnTime.
218
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
For a three-, four- or five-terminals line in a master-master configuration, a loss of one
communication channel will not cause the line differential protection to be unserviceable. Instead it
will automatically revert to a partial master-slave mode with the two IEDs that have an unserviceable
communication link between them, will serve as slaves.
For more details about the remote communication see section remote communication and the
application manual.
7.4.7.4
Open CT detection feature
GUID-5B7ACC4D-4EC9-40F1-B18D-561F13945FE3 v1
Line differential protection has a built-in, advanced open CT detection feature.
A sudden inadvertently opened CT circuit may cause an unexpected and unwanted operation of the
Line differential protection under normal load conditions. Damage of secondary equipment may occur
due to high voltage from open CT circuit outputs. It is always an advantage, from the point of view of
security and reliability, to have the open CT detection function to block the line differential protection
function in case of an open CT condition, and produce an alarm signal to the operational personnel
to quickly correct the open CT condition.
The built-in open CT feature can be enabled or disabled by the setting parameter OpenCTEnable
(Off/On). When enabled, this feature tries to prevent mal-operation when a loaded main CT
connected to line differential protection is by mistake open circuited on the secondary side. Note that
this feature can only detect interruption of one CT phase current at a time. If two or even all threephase currents of one set of CTs are accidentally interrupted at precisely the same time, this feature
cannot operate. Line differential protection generates a trip signal if the false differential current is
sufficiently high. An open CT circuit is typically detected in 12–14 ms, and if the load in the protected
circuit is relatively high, about the nominal load, the unwanted trip cannot always be prevented. Still,
the information about what was the cause of the open CT secondary circuit, is vital.
The principle applied to detect an open CT is a simple pattern recognition method, similar to the
waveform check used by the Power transformer differential protection in order to detect the
magnetizing inrush condition. The open CT detection principle is based on the fact that for an open
CT, the current in the phase with the open CT suddenly drops to zero (that is, as seen by the
protection), while the currents of the other two phases continue as before.
The open CT function is supposed to detect an open CT under normal conditions, that is, with the
protected multi-terminal circuit under normal load (10...120% of the rated load). If the load currents
are very low or zero, the open CT condition cannot be detected. In addition to load condition
requirement, Open CT function also checks the differential current on faulty phase. If the differential
current is lower than 10% of IBase, the open CT condition cannot be detected. Therefore, the Open
CT algorithm only detects an open CT if the load on the power transformer protected object is
10...120% of rated load and the differential current is higher than 10% of IBase on that phase. The
search for an open CT starts 60 seconds (50 seconds in 60 Hz systems) after the bias current has
entered the 10...120% range. The Open CT detection feature can also be explicitly deactivated by
setting: OpenCTEnable = 0 ( Off).
The open CT function can be selected to either block the differential function or issue the alarm
signal via the setting OCTBlockEn.
When the setting OCTBlockEn is set to ON and an open CT is detected, the output OPENCT is set
to 1 and all the differential functions are blocked, except the unrestrained (instantaneous) differential.
An alarm signal is also produced after a settable delay (tOCTAlarmDelay) to report to operational
personnel for quick remedy actions once the open CT is detected. When the open CT condition is
removed (that is, the previously open CT is reconnected), the functions remain blocked for a
specified interval of time, which is also defined by a setting (tOCTResetDelay). This is to prevent an
eventual mal-operation after the reconnection of the previously open CT secondary circuit.
Otherwise when the setting OCTBlockEn is set to OFF, only an alarm signal is issued once an open
CT is detected.
Line differential protection RED670
Technical manual
219
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
The open CT algorithm provides detailed information about the location of the defective CT
secondary circuit. The algorithm clearly indicates the IED side, CT input and phase in which an open
CT condition has been detected. These indications are provided via the following outputs from the
Line differential protection function:
1.
2.
3.
4.
Output OPENCT provides instant information to indicate that an open CT circuit has been
detected.
Output OPENCTAL provides a time-delayed alarm that the open CT circuit has been detected.
Time delay is defined by the parameter tOCTAlarmDelay.
Integer output OPENCTIN provides information on the local HMI regarding which open CT
circuit has been detected (1=CT input No 1; 2=CT input No 2).
Integer output OPENCTPH provides information on the local HMI regarding in which phase an
open CT circuit has been detected (1=Phase L1; 2= Phase L2; 3= Phase L3).
Once the open CT condition is declared, the algorithm stops to search for further open CT circuits. It
waits until the first open CT circuit has been corrected. Note that once the open CT condition has
been detected, it can be reset automatically within the differential function. It is not possible to
externally reset an open CT condition. To reset the open CT circuit alarm automatically, the following
conditions must be fulfilled:
•
•
•
Bias current is for at least one minute smaller than 120%
The open CT condition in the defective CT circuit has been corrected (for example, current
asymmetry disappears)
The above two conditions are fulfilled for a longer time than defined by the setting parameter
tOCTResetDelay
If an open CT has been detected in a separate group of three CTs, the algorithm is reset either when
the missing current returns to the normal value, or when all three currents become zero. After the
reset, the open CT detection algorithm starts again to search for open CT circuits within the protected
zone.
7.4.7.5
Binary signal transfer
SEMOD52489-4 v4
There is space for eight binary signals integrated in the telegram of the line differential analog
communication.
7.4.7.6
Line differential protection logic LDLPSCH
GUID-687F26CE-20EF-424A-A355-6308CED80E6C v7
Line differential protection logic (LDLPSCH) is a support function to the Line differential protection
functions. The function gathers and coordinates local IED signals and the signals from remote IEDs
between the Line differential protection functions and the LDCM communication module.
The function acts as the interface to and from Line differential protection.
The task of LDLPSCH is to transfer the signals via LDCM between IEDs in the protection zone. Once
LDLPSCH receives a block or trip signal from one IED, this block or trip signal is transferred to other
IEDs by LDLPSCH function.
When the line differential protection function in local IED is set to test mode, LDLPSCH sets the
remote IEDs in a remote test mode and block the trip outputs in the remote IEDs. Figure 86 shows a
simplified block diagram which illustrates block signal handling by LDLPSCH.
220
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
TestModeRemoteTerm1
TestModeRemoteTerm2
TestModeRemoteTerm3
OR
50 ms
t
TestModeRemoteTerm4
OR
BlockRemote Ter m1
BlockRemote Ter m2
BlockRemote Ter m3
BlockRemote Ter m4
OR
LocalDiffB lock
OR
LOCAL DIFFB LOCKED
50 ms
OPE N CT BLK
t
CTFailOCTToRemote
(signal to L DCM)
TestModeInpu t
AND
TestModeToRemote
50 ms
t
AND
TestModeS et
AND
OR
Block Remote Tri p
ReleaseLo cal
OR
Block Remote Tri p
TERMINALOUTOFSERVICE
OR
BLO CK
100 ms
t
OR
BlockToRe mo te
IEC13000259-4-en.vsd
IEC13000259 V4 EN-US
Figure 86:
Block signal logic of LDLPSCH
When LDLPSCH receives the trip signal from local IED (or remote IED), this trip signal is transferred
to remote IEDs (or local IED) in the protection zone. Figure 87 shows a simplified block diagram
which illustrates trip signal handling by LDLPSCH.
Line differential protection RED670
Technical manual
221
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
TRL OCL1
DiffTripL1
AND
TRL1
OR
TripL1ToRemote
AND
TRIP
OR
TripL1Remote Te rm1
TripL1Remote Te rm2
TripL1Remote Te rm3
OR
AND
TripL1Remote Te rm4
TRL OCL2
DiffTripL2
AND
TRL2
OR
AND
TripL2ToRemote
AND
TripL2Remote Te rm1
OR
TRL OCAL
TripL2Remote Te rm2
TripL2Remote Te rm3
OR
TripL2Remote Te rm4
TRL OCL3
DiffTripL3
AND
BlockLocalTrip
TRL3
OR
BlockTripToRemo te
TripL3ToRemote
AND
TripL3Remote Te rm1
TripL3Remote Te rm2
TripL3Remote Te rm3
TripL3Remote Te rm4
OR
TRREMOTE
OR
AND
BlockRemote Trip
IEC130 00260-3-en.vsd
IEC13000260 V3 EN-US
Figure 87:
Trip signal logic of LDLPSCH
Some of the signals in the above block diagrams are used as the internal signals by LDLPSCH.
Table Internal signals describes the source or destination of these internal signals.
Table 132: Internal signals
Internal signals
Source of destination
Description
testModeRemoteTerm1
Signal from LDCM
Test mode from remote terminal 1
testModeRemoteTerm2
Signal from LDCM
Test mode from remote terminal 2
testModeRemoteTerm3
Signal from LDCM
Test mode from remote terminal 3
testModeRemoteTerm4
Signal from LDCM
Test mode from remote terminal 4
blockRemoteTerm1
Signal from LDCM
Block from remote terminal 1
blockRemoteTerm2
Signal from LDCM
Block from remote terminal 2
blockRemoteTerm3
Signal from LDCM
Block from remote terminal 3
blockRemoteTerm4
Signal from LDCM
Block from remote terminal 4
testModeInput
Signal from test mode function
Input for forcing the function into test
mode
Table continues on next page
222
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Internal signals
7.4.8
Source of destination
Description
diffTripL1
Signal from differential function
Trip from local differential function in
phase L1
diffTripL2
Signal from differential function
Trip from local differential function in
phase L2
diffTripL3
Signal from differential function
Trip from local differential function in
phase L3
tripL1RemoteTerm1
Signal from LDCM
Trip from remote terminal 1 in phase
L1
tripL1RemoteTerm2
Signal from LDCM
Trip from remote terminal 2 in phase
L1
tripL1RemoteTerm3
Signal from LDCM
Trip from remote terminal 3 in phase
L1
tripL1RemoteTerm4
Signal from LDCM
Trip from remote terminal 4 in phase
L1
tripL2RemoteTerm1
Signal from LDCM
Trip from remote terminal 1 in phase
L2
tripL2RemoteTerm2
Signal from LDCM
Trip from remote terminal 2 in phase
L2
tripL2RemoteTerm3
Signal from LDCM
Trip from remote terminal 3 in phase
L2
tripL2RemoteTerm4
Signal from LDCM
Trip from remote terminal 4 in phase
L2
tripL3RemoteTerm1
Signal from LDCM
Trip from remote terminal 1 in phase
L3
tripL3RemoteTerm2
Signal from LDCM
Trip from remote terminal 2 in phase
L3
tripL3RemoteTerm3
Signal from LDCM
Trip from remote terminal 3 in phase
L3
tripL3RemoteTerm4
Signal from LDCM
Trip from remote terminal 4 in phase
L3
tripL1ToRemote
Signal to LDCM
Trip to remote terminals phase L1
tripL2ToRemote
Signal to LDCM
Trip to remote terminals phase L2
tripL3ToRemote
Signal to LDCM
Trip to remote terminals phase L3
localDiffBlock
Signal to differential function
Block local line differential function
operation
blockToRemote
Signal to LDCM
Block to be sent to remote terminals
testModeToRemote
Signal to LDCM
Test mode indication to be sent to
remote terminals
Technical data
IP14336-1 v1
M16023-1 v13
Table 133: L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF single IED without communication technical data
Function
Range or value
Accuracy
Minimum operate current
(20-200)% of IBase
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
SlopeSection2
(10.0-50.0)%
-
SlopeSection3
(30.0-100.0)%
-
EndSection 1
(20–150)% of IBase
-
Table continues on next page
Line differential protection RED670
Technical manual
223
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Function
Range or value
Accuracy
EndSection 2
(100–1000)% of IBase
-
Unrestrained limit function
(100–5000)% of IBase
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Second harmonic blocking
(5.0–100.0)% of fundamental
±1.0% of Ir
Note: fundamental magnitude =
100% of Ir
Fifth harmonic blocking
(5.0–100.0)% of fundamental
±2.0% of Ir
Note: fundamental magnitude =
100% of Ir
*Inverse characteristics, see table
1292,1294 and table 1296
16 curve types
See table 1292,1294 and table 1296
Critical impulse time
2ms typically at 0 to 10 x IdMin
-
Charging current compensation
On/Off
-
LT3CPDIF and LT6CPDIF (With in-zone transformer enabled and tIdMinHigh set to 0) :
*Operate time, restrained function at 0
to 10 x IdMin
Min. = 25 ms
Max. = 35 ms
-
*Reset time, restrained function at 10 x
IdMinto 0
Min. = 5 ms
Max. = 15 ms
-
*Operate time, unrestrained function at
0 to 10 x IdUnre
Min. = 5 ms
Max. = 15 ms
-
*Reset time, unrestrained function at 10
x IdUnreto 0
Min. = 15 ms
Max. = 30 ms
-
**Operate time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 25 ms
-
**Reset time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 30 ms
-
L3CPDIF and L6CPDIF (With tIdMinHigh set to 0):
*Operate time, restrained function at 0
to 10 x IdMin
Min. = 10 ms
Max. = 20 ms
-
*Reset time, restrained function at 10 x
IdMinto 0
Min. = 15 ms
Max. = 30 ms
-
*Operate time, unrestrained function at
0 to 10 x IdUnre
Min. = 5 ms
Max. = 15 ms
-
*Reset time, unrestrained function at 10
x IdUnreto 0
Min. = 15 ms
Max. = 30 ms
-
**Operate time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 20 ms
-
**Reset time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 35 ms
-
The data in the table are valid for a single IED with two local current input groups.
*Note: Data obtained with single three-phase input current group.
**Note: Data obtained with two three-phase input current groups. The rated symmetrical currents are applied on both
sides as pre- and post-fault currents. The fault is performed by increasing one phase current to double on one side
and decreasing same phase current to zero on the other side.
224
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Table 134: L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 64 Kbit/s communication technical data
Function
Range or value
Accuracy
Minimum operate current
(20-200)% of IBase
±4.0% of Ir at I ≤ Ir
±4.0% of I at I > Ir
SlopeSection2
(10.0-50.0)%
-
SlopeSection3
(30.0-100.0)%
-
EndSection 1
(20–150)% of IBase
-
EndSection 2
(100–1000)% of IBase
-
Unrestrained limit function
(100–5000)% of IBase
±4.0% of Ir at I ≤ Ir
±4.0% of I at I > Ir
Second harmonic blocking
(5.0–100.0)% of fundamental
±3.0% of Ir
Note: fundamental magnitude =
100% of Ir
Fifth harmonic blocking
(5.0–100.0)% of fundamental
±10.0% of Ir
Note: fundamental magnitude =
100% of Ir
*Inverse characteristics, see table
1292,1294 and table 1296
16 curve types
See table 1292,1294 and table 1296
Critical impulse time
2 ms typically at 0 to 10 x IdMin
-
Charging current compensation
On/Off
-
LT3CPDIF and LT6CPDIF (With in-zone transformer enabled and tIdMinHigh set to 0) :
*Operate time, restrained function at 0
to 10 x IdMin
Min. = 30 ms
Max. = 50 ms
-
*Reset time, restrained function at 10 x
IdMinto 0
Min. = 10 ms
Max. = 25 ms
-
*Operate time, unrestrained function at
0 to 10 x IdUnre
Min. = 10 ms
Max. = 25 ms
-
*Reset time, unrestrained function at 10
x IdUnreto 0
Min. = 20 ms
Max. = 40 ms
-
**Operate time, unrestrained negative
sequence function
Min. = 15 ms
Max. = 35 ms
-
**Reset time, unrestrained negative
sequence function
Min. = 20 ms
Max. = 35 ms
-
L3CPDIF and L6CPDIF (With tIdMinHigh set to 0):
*Operate time, restrained function at 0
to 10 x IdMin
Min. = 10 ms
Max. = 35 ms
-
*Reset time, restrained function at 10 x
IdMinto 0
Min. = 20 ms
Max. = 45 ms
-
*Operate time, unrestrained function at
0 to 10 x IdUnre
Min. = 10 ms
Max. = 25 ms
-
*Reset time, unrestrained function at 10
x IdUnreto 0
Min. = 20 ms
Max. = 50 ms
-
Table continues on next page
Line differential protection RED670
Technical manual
225
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Function
Range or value
Accuracy
**Operate time, unrestrained negative
sequence function
Min. = 15 ms
Max. = 35 ms
-
**Reset time, unrestrained negative
sequence function
Min. = 15 ms
Max. = 40 ms
-
The data in the table are valid for a single IED with 64 Kbits/s communication in the loop-back mode.
*Note: Data obtained with single three-phase input current group. The operate and reset times for L3CPDIF are valid
for the static output from SOM.
**Note: Data obtained with two three-phase input current groups. The rated symmetrical currents are applied on both
sides as pre- and post-fault currents. The fault is performed by increasing one phase current to double on one side
and decreasing same phase current to zero on the other side.
Table 135: L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 2 Mbits/s communication technical data
Function
Range or value
Accuracy
Minimum operate current
(20-200)% of IBase
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
SlopeSection2
(10.0-50.0)%
-
SlopeSection3
(30.0-100.0)%
-
EndSection 1
(20–150)% of IBase
-
EndSection 2
(100–1000)% of IBase
-
Unrestrained limit function
(100–5000)% of IBase
±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir
Second harmonic blocking
(5.0–100.0)% of fundamental
±1.0% of Ir
Note: fundamental magnitude =
100% of Ir
Fifth harmonic blocking
(5.0–100.0)% of fundamental
±3.0% of Ir
Note: fundamental magnitude =
100% of Ir
*Inverse characteristics, see table
1292,1294 and table 1296
16 curve types
See table 1292,1294 and table 1296
Critical impulse time
2 ms typically at 0 to 10 x IdMin
-
Charging current compensation
On/Off
-
LT3CPDIF and LT6CPDIF (With in-zone transformer enabled and tIdMinHigh set to 0) :
*Operate time, restrained function at 0
to 10 x IdMin
Min. = 25 ms
Max. = 40 ms
-
*Reset time, restrained function at 10 x
IdMinto 0
Min. = 5 ms
Max. = 20 ms
-
*Operate time, unrestrained function at
0 to 10 x IdUnre
Min. = 5 ms
Max. = 20 ms
-
*Reset time, unrestrained function at 10
x IdUnreto 0
Min. = 15 ms
Max. = 35 ms
-
**Operate time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 25 ms
-
**Reset time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 30 ms
-
L3CPDIF and L6CPDIF (With tIdMinHigh set to 0):
*Operate time, restrained function at 0
to 10 x IdMin
Min. = 10 ms
Max. = 20 ms
-
*Reset time, restrained function at 10 x
IdMinto 0
Min. = 15 ms
Max. = 30 ms
-
Table continues on next page
226
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
Function
Range or value
Accuracy
*Operate time, unrestrained function at
0 to 10 x Id
Min. = 5 ms
Max. = 20 ms
-
*Reset time, unrestrained function at 10
x IdUnreto 0
Min. = 15 ms
Max. = 35 ms
-
**Operate time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 25 ms
-
**Reset time, unrestrained negative
sequence function
Min. = 10 ms
Max. = 30 ms
-
The data in the table are valid for a single IED with 2 Mbits/s communication in loop-back mode.
*Note: Data obtained with single three-phase input current group.
**Note: Data obtained with two three-phase input current groups. The rated symmetrical currents are applied on both
sides as pre- and post-fault currents. The fault is performed by increasing one phase current to double on one side
and decreasing same phase current to zero on the other side.
7.5
Additional security logic for differential protection
LDRGFC
GUID-0E064528-0E70-4FA1-87C7-581DADC1EB55 v2
7.5.1
Identification
GUID-3081E62B-3E96-4615-97B8-2CCA92752658 v2
Function description
Additional security logic for differential
protection
7.5.2
IEC 61850
identification
LDRGFC
IEC 60617
identification
-
Functionality
ANSI/IEEE C37.2
device number
11
GUID-8F918A08-E50E-4E7B-BDCA-FF0B5534B289 v3
Additional security logic for differential protection (LDRGFC) can help the security of the protection
especially when the communication system is in abnormal status or for example when there is
unspecified asymmetry in the communication link. It helps to reduce the probability for mal-operation
of the protection. LDRGFC is more sensitive than the main protection logic to always release
operation for all faults detected by the differential function. LDRGFC consists of four sub functions:
•
•
•
•
Phase-to-phase current variation
Zero sequence current criterion
Low voltage criterion
Low current criterion
Phase-to-phase current variation takes the current samples as input and it calculates the variation
using the sampling value based algorithm. Phase-to-phase current variation function is a major one
to fulfill the objectives of the startup element.
Zero sequence criterion takes the zero sequence current as input. It increases the security of
protection during the high impedance fault conditions.
Low voltage criterion takes the phase voltages and phase-to-phase voltages as inputs. It increases
the security of protection when the three-phase fault occurred on the weak end side.
Low current criterion takes the phase currents as inputs and it increases the dependability during the
switch onto fault case of unloaded line.
The differential function can be allowed to trip as no load is fed through the line and protection is not
working correctly.
Features:
Line differential protection RED670
Technical manual
227
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
•
•
•
Startup element is sensitive enough to detect the abnormal status of the protected system
Startup element does not influence the operation speed of main protection
Startup element would detect the evolving faults, high impedance faults and three phase fault on
weak side
It is possible to block the each sub function of startup element
Startup signal has a settable pulse time
•
•
7.5.3
Function block
GUID-A205A0BB-C09E-42E2-B664-1863E1FF2A0A v2
LDRGFC
I3P*
U3P*
BLOCK
BLKCV
BLKUC
BLK3I0
BLKUV
REMSTUP
START
STCVL1L2
STCVL2L3
STCVL3L1
STUC
ST3I0
STUV
IEC14000015-1-en.vsd
IEC14000015 V1 EN-US
Figure 88:
7.5.4
LDRGFC function block
Signals
PID-3558-INPUTSIGNALS v9
Table 136: LDRGFC Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
U3P
GROUP
SIGNAL
-
Group signal for voltage input
BLOCK
BOOLEAN
0
Block of function
BLKCV
BOOLEAN
0
Block of ph to ph current variation criterion
BLKUC
BOOLEAN
0
Block of the low current criterion
BLK3I0
BOOLEAN
0
Block of zero sequence current criterion
BLKUV
BOOLEAN
0
Block of under voltage criterion
REMSTUP
BOOLEAN
0
Startup signal of remote end
PID-3558-OUTPUTSIGNALS v9
Table 137: LDRGFC Output signals
Name
Type
Description
START
BOOLEAN
General startup signal
STCVL1L2
BOOLEAN
Start signal for current variation criterion for phase L1L2
STCVL2L3
BOOLEAN
Start signal for current variation criterion for phase L2L3
STCVL3L1
BOOLEAN
Start signal for current variation criterion for phase L3L1
STUC
BOOLEAN
Start signal for low current criterion
ST3I0
BOOLEAN
Start signal for zero sequence current criterion
STUV
BOOLEAN
Start signal for under voltage criterion
228
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
7.5.5
Section 7
Differential protection
Settings
PID-3558-SETTINGS v9
Table 138: LDRGFC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
tStUpReset
0.000 - 60.000
s
0.001
7.000
Reset delay for startup signal
OperationCV
Off
On
-
-
On
Operation current variation Off/On
ICV>
1 - 100
%IB
1
20
Fixed threshold for ph to ph current
variation criterion
OperationUC
Off
On
-
-
On
Operation low current criterion Off/On
IUC<
1 - 100
%IB
1
5
Start value for low current operation in %
of IBase
Operation3I0
Off
On
-
-
On
Operation zero sequence current
criterion Off/On
I3I0>
1 - 100
%IB
1
10
Start value for zero sequence current
criterion in % of IBase
OperationUV
Off
On
-
-
On
Operation under voltage criterion Off/On
UPhN<
1 - 100
%UB
1
60
Start value for phase voltage criterion in
% of UBase
UPhPh<
1 - 100
%UB
1
60
Start value for ph to ph voltage criterion
in % of UBase
Table 139: LDRGFC Group settings (advanced)
Name
Values (Range)
tCV
0.000 - 0.005
s
0.001
0.002
Time delay for phase to phase current
variation
tUC
0.000 - 60.000
s
0.001
0.200
Time delay for low current criterion
t3I0
0.000 - 60.000
s
0.001
0.000
Time delay for zero sequence current
criterion
tUV
0.000 - 60.000
s
0.001
0.000
Time delay for low voltage criterion
Unit
Step
Default
Description
Table 140: LDRGFC Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
7.5.6
Unit
1 - 12
Step
-
1
Default
1
Description
Selection of one of the Global Base
Value groups
Monitored data
PID-3558-MONITOREDDATA v8
Table 141: LDRGFC Monitored data
Name
Type
Values (Range)
Unit
Description
IL1
REAL
-
A
Current RMS value for phase L1
IL2
REAL
-
A
Current RMS value for phase L2
IL3
REAL
-
A
Current RMS value for phase L3
3I0
REAL
-
A
Zero sequence current value
Table continues on next page
Line differential protection RED670
Technical manual
229
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
Name
7.5.7
Type
Values (Range)
Unit
Description
UL1
REAL
-
kV
Voltage RMS value for phase L1
UL2
REAL
-
kV
Voltage RMS value for phase L2
UL3
REAL
-
kV
Voltage RMS value for phase L3
UL12
REAL
-
kV
Voltage RMS value for ph to ph L1L2
UL23
REAL
-
kV
Voltage RMS value for ph to ph L2L3
UL31
REAL
-
kV
Voltage RMS value for ph to ph L3L1
Operation principle
GUID-60091A2A-AC10-4E04-B4B8-C190E3E07D3E v6
The additional security logic for differential protection (LDRGFC) takes the current samples, current
RMS values, phase voltage values, phase-to-phase voltage values, zero sequence current and
remote side startup signals as inputs.
Startup signal becomes activated when any one of the current variation startup signal, zero
sequence current startup signal, voltage startup signal, and current startup signal is activated.
Phase-to-phase current variation takes current samples and generates the startup signal by
comparing with the start value.
If the zero sequence current value is greater than the start value of zero sequence current then the
zero sequence current startup signal will be activated.
Voltage startup signal becomes activated when the any of phase voltage and line voltage is less than
the voltage start value and the remote startup signal has to be activated.
Current startup signal becomes activated when the current value in all phases is less than current
start value.
Phase-to-phase current variation
The phase-to-phase current variation is the main startup element. It covers most of the abnormal
conditions of the system. The phase-to-phase current variation fails in high impedance faults, threephase faults on weak side and switch onto fault on unloaded line because of low sensitivity in these
cases.
Phase-to-phase current variation takes the current samples as input and the signal is evaluated
using the sampling value based algorithm.
The phase-to-phase current variation criterion is shown below:
DiFF > 1.8DIT + DI ZD
EQUATION2255 V1 EN-US
Where:
ΔiФФ
sampling value of phase-to-phase current variation
ΔIZD
setting of fixed threshold, which corresponds to setting ICV>. The default value for the setting is
0.2·IBase, where IBase is the base current.
ΔIT
float threshold
It is the full-circle integral of the phase-to-phase current variation
230
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
DI T =
Section 7
Differential protection
1 2T -1
å | DiFF (t - n) |
T n =T
EQUATION2256 V1 EN-US
Where:
T
count of sample values in one cycle
ΔiФФ is calculated using the below formula:
Di (k ) = [i ( k ) - i (k - N )] - [i (k - N ) - i (k - 2 N )]
= i ( k ) - 2i ( k - N ) + i (k - 2 N )
EQUATION2257 V1 EN-US
N is the number of samples in one cycle.
tCV
STCVL1L2
t
Current variation
subfunction
I3P
i
cont
tCV
STCVL2L3
t
tCV
STCVL3L1
t
OR
STCV
cont
IEC10000295-1-en.vsd
IEC10000295 V1 EN-US
Figure 89:
Current variation logic diagram
tCV is the time setting for the change of current criterion. Phase current samples are included in input
signal I3P.
Zero sequence current criterion
Zero sequence criterion is mainly for detection of remote IED high resistance faults or some gradual
faults. The criterion takes the zero sequence current as input. Zero sequence current is compared
with I3I0> for the t3I0 time to generate the zero sequence current startup signal.
Line differential protection RED670
Technical manual
231
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 7
Differential protection
1MRK 505 377-UEN Rev. P
I3P
a
b
I3IO>
BLK3I0
BLOCK
a>b
t3I0
t
AND
ST3I0
OR
IEC09000778-2-en.vsd
IEC09000778 V2 EN-US
Figure 90:
Zero sequence current criterion logic diagram
I3I0> is the setting of the maximum possible non-faulted zero sequence current for the protected line.
The default value for this setting is 0.1 · IBase where IBase is the rated current of the CT.
t3I0 is the time setting for the zero sequence current criterion.
The zero sequence current criterion can be blocked by activating the BLK3I0 input signal.
Low voltage criterion
Low voltage criterion is mainly for detection of the three phase faults occurring on weak side with prefault no load condition. The low voltage criterion takes the voltage phase values, voltage phase-tophase values and remote startup signals as inputs. The logic for low voltage criterion is shown below:
U3P (UPhN)
a
UPhN<
U3P (UPhPh)
b
a
UPhPh<
b
a<b
OR
a<b
tUV
REMSTUP (Recived)
AND
t
STUV
BLKUV
OR
BLOCK
IEC09000779-2-en.vsd
IEC09000779 V2 EN-US
Figure 91:
Low voltage criterion logic diagram
Voltage phase value is compared with the start value of voltage phase and voltage phase-to-phase
value is compared with the start value of voltage phase-to-phase. If any of the phase voltage or
phase-to-phase voltages is below the set voltage levels for some time duration (tUV) then the low
voltage START signal becomes activated after receiving the remote startup signal. Low voltage
criterion can be blocked by activating BLKUV input signal.
If there are more than one remote IED, all the startup signals of the remote ends are logically OR to
obtain the REMSTUP signal from the remote side as input.
Low current criterion
The current in each phase is compared to the set current level. If all currents are below setting IUC<,
the STUC output is activated after the set delay tUC.
232
Line differential protection RED670
Technical manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 505 377-UEN Rev. P
Section 7
Differential protection
I3P
a
IUC<
b
BLKUC
BLOCK
a<b
tUC
AND
t
STUC
OR
IEC09000780-2-en.vsd
IEC09000780 V2 EN-US
Figure 92:
Low current criterion logic diagram
Security logic for differential protection
The configuration for the additional security logic for differential protection is shown in Figure 93. The
function will release tripping of the line differential protection up to the end of timer tStUpReset.
Phase-phase
current variation
STCV
Zero sequence
current criterion
ST3IO
i
I0 >
tStUpReset
t
Low voltage
criterion
STUV
START
OR
ULOW <
Local side start-up
Send signal to
remote side
AND
REMSTUP
Low current
criterion
STUC
I0 <
IEC10000296-3-en.vsd
IEC10000296 V3 EN-US
Figure 93:
7.5.8
Additional security logic for differential protection. Logic diagram for start up
element.
Technical data
GUID-0BD8D3C9-620A-426C-BDB5-DAA0E4F8247F v5
Table 142: LDRGFC technical data
Function
Range or value
Accuracy
Operate current, zero sequence current
(1-100)% of lBase
±1.0% of Ir
Operate current, low current operation
(1-100)% of lBase
±1.0% of Ir
Operate voltage, phase to neutral
(1-100)% of UBase
±0.5% of Ur
Operate voltage, phase to phase
(1-100)% of UBase
±0.5% of Ur
Independent time delay, zero sequence
current at 0 to 2 x Iset
(0.000-60.000) s
±0.2% or ±35 ms
whichever is greater
Independent time delay, low current operation
at 2 x Iset to 0
(0.000-60.000) s
±0.2% or ± 35 ms
whichever is greater
Independent time delay, low voltage operation
at 2 x Uset to 0
(0.000-60.000) s
±0.2% or ±35 ms
whichever is greater
Reset time delay for startup signal at 0 to 2 x
Uset
(0.000-60.000) s
±0.2% or ±35 ms
whichever is greater
Line differential protection RED670
Technical manual
233
© 2017 - 2021 Hitachi Power Grids. All rights reserved
234
Download