Easy way to calculate Range for Differential Pressure Level Transmitter? Basic of Instrumentations Another installation method for level measurement using a Differential Pressure level transmitter is by utilizing the diaphragm seal plus capillary tube. To determine the calibrated range for the Differential Pressure level transmitter, the filling fluid density within the capillary must be taken into account in the calculation since the fill fluid also creates hydrostatic force exerting both the DP level transmitter ports. The density of fill fluid must be known, and the information could be obtained from manufacturer specifications. The example below describes the calculation in determining the calibrated range for Differential Pressure level transmitter with a capillary tube. Simple Differential Pressure Level Calculation Diaphragm Seal DP Transmitter Level Measurement Sample Process Data Process fluid density = 0.96 g/cm3 Fill fluid density = 1.05 g/cm3 100% from Process Connection (h) = 4 m = 4,000mm Height Difference between Process Connection (h2) = 5 m = 5,000mm When level at 0% = 4mA (Left Image) ∆P at 0% level ∆P = P1 – P2 P1 = 0 mmH2O P2 = 1.05 x 5,000 = 5,250 mmH2O Therefore Range at 0% is P1 – P2 = 0 – 5,250 = -5,250 mmH2O When level at 100% = 20mA (Right Image) ∆P at 100% level ∆P = P1 – P2 P1 = 0.96 x 4000 = 3,840 mmH2O P2 = 1.05 x 5,000 = 5,250 mmH2O Therefore ∆P at 100% is P1 – P2 = 3,840 – 5,250 = -1,410 mmH2O Scaling to set to Differential Pressure Transmitter 0% to 100% = -5,250 ~ -1,410 mmH2O Level Calculation with Remote Seals by Diaphragm seals for tanks under Vacuum The transmitter must be mounted level with or below the lowest tap to ensure positive pressure at the transmitter. Dist. Between Taps = H DP = Hside – Lside DP = (L*SGp + h*SGf ) – (H+h)*SGf DP = L*SGp – H*SGf Double Remote Seal Application Calibration Range LRV or 4mA point = Phigh – Plow LRV = Head2 – Head1 LRV = (0.9*30”) – (0.9*100”) LRV = -63”H2O URV or 20mA Point = Phigh – Plow URV = (Head2 + Head3) – Head1 URV = [(0.9*30”) + (1.1*50”)] – (0.9*100”) URV = -8”H2O Cal. Range = -63 to -8 in H2O Density Calculation with Remote Seals Transmitter Max. Allowable ΔS.G = 0.2 Dist. Betw. Taps = 10 ft = 10 x 12” = 120” Calibration Range LRV or 4mA point = 120” * (SGp – SGf) LRV = 120” * (1.1 – 0.95) LRV = 18”H2O URV or 20mA Point = 120” * (SGp – SGf) URV = 120” * (1.3 – 0.95) URV = 42”H2O Cal. Range = 18 to 42 inH2O Interface Calculation with Remote Seals Transmitter Application Example: To determine % of interface of Liquid A with respect to Liquid B. Dist. Betw. Taps = 10 ft = 10 x 12” = 120” Calibration Range LRV or 4mA point = 120” * (SG1 – SGf) LRV = 120” * (1.1 – 0.95) LRV = 18”H2O URV or 20mA Point = 120” * (SG2 – SGf) URV = 120” * (1.3 – 0.95) URV = 42”H2O Cal. Range = 18 to 42 inH2O How to Calculate mmWC Range of Level Transmitter with Examples? by R Jagan Mohan Rao How to calculate the inch or mmWC range of the level transmitter and explain with different examples. We need to configure the Lower Range Value (LRV) and Upper Range Value (URV) for the level transmitters after installation in the field. The formula to calculate the LRV (4mA) and URV (20mA) will always change based on the transmitter mounting or installation position. The below example shows the different types of level transmitters installation. Remote Capillary Level Transmitter Mounted at Zero Level dH = Vertical distance from the transmitter to high-pressure seal dL = Vertical distance from the transmitter to low-pressure seal Lmax = the maximum level of the process above the high-pressure seal and typically the 20 mA lower range value Lmin = the minimum level of the process above the high-pressure seal and typically the 4 mA lower range value SGf = specific gravity of fill fluid SGp = specific gravity of process fluid Tank span = Lmax *SGp – Lmin *SGp Tank span = (108 in.* 0.75) – (0 in.* 0.75) = 81 inH2O 4 mA = Lmin *SGp + dH *SGf 4 mA = (0 in. 0.75) + (0 in.* 0.934) = 0 inH2O 20 mA = Lmax* SGp + dH * SGf 20 mA = (108 in.* 0.75) + (0 in.* 0.934) = 81 inH2O Span = 81 inH2O (81 to 0 inH2O) Note: Both installations would have the same calculated range points. Note: Silicone 200 has a specific gravity of 0.934. Remote Capillary Level Transmitter Mounted below Zero Level Tank span = Lmax* SGp – Lmin * SGp Tan span = (108 in.* 0.75) – (0 in*. 0.75) = 81 inH2O 4 mA = Lmin *SGp + (dH* SGf) 4 mA = (0 in.* 0.75) + (60 in.* 0.934) = 56.04 inH2O 20 mA = Lmax *SGp + (dH *SGf) 20 mA = (108 in* 0.75) + (56.04* inH2O) = 137.04 inH2O Span = 81 inH2O (137.04 to 56.04 inH2O) Note: Silicone 200 has a specific gravity of 0.934. Remote Capillary Level Transmitter Mounted Above Seal Tank span = Lmax SGp – Lmin SGp Tank span = (108 in. 0.75) = 81 inH2O 4 mA = Lmin * SGp +(dH * SGf) 4 mA = (0 in * 0.75) + (–120 in *. 0.934) = –112.08 inH2O 20 mA = Lmax * SGp + (dH* SGf) 20 mA = (108 in * 0.75) + (–120 in.* 0.934) = –31.08 inH2O Span = 81 inH2O (–112.08 to –31.08 inH2O) Note The height of the transmitter (Hd Sg) should not be greater than approximately 394 inH2O (14.2 PSI) not to exceed the 0.5 PSIA sensor limits of a coplanar DP or GP. Remote Capillary Level Transmitter Installed between Seals Tank span = Lmax SG Tank span = 108 in. 0.75 = 81 inH2O 4 mA = Lmin *SGp – (dL* SGF) +(dH * SGf) 4 mA = (0 in. 0.75) – (60 in.* 0.934) + (– 60 in.* 0.934) = –112.08 inH2O 20 mA = Lmax * SGp – (dL * SGf) +(dH SGf) 20 mA = (108 in. 0.75) – (60 in. 0.934) + (–60 in. 0.934) = –31.08 inH2O Span = 81 inH2O (–112.08 to –31.08 inH2O) Note: Silicone 200 has a specific gravity of 0.934. Remote Capillary Level Transmitter Mounted on Closed Tank Tank span = Lmax *SGp – Lmin *SGp Tank span = (108 in.* 0.75) = 81 inH2O 4 mA = Lmin *SGp – (dL*SGf) 4 mA = (0 in.* 0.75) – (120 in.* 0.934) = –112.08 inH2O 20 mA = Lmax *SGp – (dL* SGf) 20 mA = (108 in.* 0.75) – (120 in.* 0.934) = –31.08 inH2O Span = 81 inH2O (–112.08 to –31.08 inH2O) Note: Silicone 200 has a specific gravity of 0.934. Source: manual-rosemount-dp-level-transmitters