Uploaded by Srijan Agarwal ch19b092

Assignment 5

advertisement
Assignment 5
Somya Verma
CH19B028
PFD + Stream Table -
T = (a+b+10*c) = 0 + 2 + 10*8 = 82
X = 82 mod 9 = 1
Y = 82 mod 19 = 6
So outlet cold temperature = 90 + 6 = 96 F
Required purity of cumene in product stream = 99.1%
With the information provided in the problem, we are unable to meet all the requirements. We
change the values of variables like the propylene input flow rate and plug flow reactor length to
cancel out the degree of freedom of the problem.
We specify the purity of cumene to 99.5% by changing the propylene inlet flow rate.
We can customise the conversion of cumene to 99% by adjusting the reactor's length.
Ultimately, we may reduce the flow rate of waste gas to below 38 kmol/hr by adjusting the
vapour flow distillate rate.
Using the design specifications in the flowsheeting options, we can find values for these
variables.
Variable
Value of Specification
Variable varied
Value of Variable
Waste Gas Flow (to
be limited below 37
lbmol/hr)
33.96 lbmol/hr
Vapour flow in
distillate of benzene
column
0.02
Conversion of
Cumene
99%
Length of Reactor
782.174611
Purity of Cumene
99.5%
Propylene Inlet Flow
Rate
111.12
I) Design Specification 1 : Waste Gas Flow Rate
As seen in the image below, flow rate of the waste gas stream has been limited to 33.96
lbmol/hr
II) Design Specification 2: Purity of Cumene
If we look at the composition of the cumene product stream, the total flow rate = 89.37 lbmol/hr,
cumene flow rate = 88.93 lbmol/hr. This gives a purity of 99.5%
III) Conversion of 99% in plug flow reactor
For a conversion of 99% for a slightly less than 90 lbmol/hr flow rate, the target flow rate for the
product is 89 or 89.1 lbmol/hr.
B) Sensitivity Analysis
By varying the preheater temperature and measuring cumene product flow rate, we find an
optimal temperature of C. To maximize cumene product flow, we can use this temperature for a
marginal increase in energy costs.
Stream Table Link:
CH19B028
Download