Classification: General Business Use ENGINEERING STANDARD NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 1 OF 28 Design Criteria for Concrete and Steel Structures This document is issued by PED, SABIC E&PM, Jubail Industrial City, Kingdom of Saudi Arabia. The information contained in this document is the confidential property of SABIC. It cannot be disclosed, copied or used for any purpose without approval from SABIC. If you are not authorized to possess this document, please destroy it immediately. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 2 OF 28 CONTENTS 1. SCOPE ............................................................................................................. 3 2. REFERENCES ............................................................................................... 3 3. DEFINITIONS ................................................................................................. 4 4. DESIGN LOADS ............................................................................................. 5 5. LOAD COBINATIONS ................................................................................. 16 6. STRUCTURAL DESIGN.............................................................................. 22 7. ALLOWABLE DEFLECTIONS .................................................................... 25 8. EXISTING STRUCTURES .......................................................................... 27 9. REVISION HISTORY ................................................................................... 27 TABLES Table I Minimum Live Loads .......................................................................................... 8 Table II Basic Wind Speed (V)........................................................................................ 9 Table III Seismic Design Parameters ............................................................................ 10 Table IV Load Increase Factors for Impacts .................................................................. 11 Table V Maximum Wheel Load Increase Factors ....................................................... 182 Table VI Friction Coefficients ....................................................................................... 183 Table VII Load Combinations for Buildings , General Plant and Process Structures ...... 18 Table VIII Load Combinations for Vertical Vessels ........................................................ 188 Table IX Load Combinations for Horizontal Vessels and Heat Exchangers ................. 199 Table X Load Combinations for Pipe Racks.................................................................. 20 Table XI Load Combinations for Ground Supported Storage Tank ................................ 21 Table XII ASTM Material Equivalency............................................................................. 22 Table XIII Maximum Allowable Wind Drifts ...................................................................... 25 Table XIV Maximum Allowable Vertical Deflection of Beams ........................................... 26 Table XV Maximum Allowable Vertical Deflection of Crane Girders................................ 26 Classification: General Business Use Design Criteria for Concrete and Steel Structures 1. NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 3 OF 28 Scope This standard establishes the minimum requirements for the structural design of buildings, structures and foundations for SABIC facilities and shall be used in conjunction with Basic Engineering Design Data (BEDD) of the project site. 2. References Reference is made in this standard to the following documents. The latest issues, amendments and supplements to these documents shall apply unless otherwise indicated. Any conflict(s) between this standard/specification, SES and industry standards, engineering drawings, and contract documents shall be resolved at the discretion of SABIC. SABIC Engineering Standards (SES) B01-E03 Design of Buildings for Petrochemical Plants B02-S01 Fabrication of Structural and Miscellaneous Steel B02-S02 Erection of Structural and Miscellaneous Steel B02-S05 Design, Fabrication and Installation of Gratings and Floor Plates B03-S01 Design and Construction of Concrete Masonry Structures B04-F01 Fixed Ladders and Cages B04-F02 Fixed Industrial Stairs B04-F03 Pipe Railings B04-F04 Angle Railings B51-S01 Cast-In-Place Reinforced Concrete B51-S03 Grouting for Equipment and Structural Foundations B52-E02 Dynamic Analysis of Foundations for Reciprocating and Rotating Equipment B55-S01 Design, Fabrication and Installation of Anchor Bolts C02-E02 Shallow Foundations C02-S06 Driven Piles C02-S07 Cast-In-Situ Bored Piles Basic Engineering Design Data (BEDD) of the Project site Process Industry Practices (PIP) STC01015 Structural Design Criteria STE01100 Constructability Design Guide American Association of State Highway Transportation Officials (AASHTO) HB17 Standard Specification for Highway Bridges (17th Edition) American Concrete Institute (ACI) 318M Building Code Requirements for Structural Concrete and Commentary 350M Code requirements for Environmental Engineering Concrete Structures and Commentary 530 Building Code Requirements for Masonry Structures 376 Code Requirements for Design and Construction of Concrete Structures for the Containment of Refrigerated Liquefied Gases and Commentary American Institute of Steel Construction (AISC) AISC Manual of Steel Construction 15th Edition - Allowable Stress Design (ASD) and Load and Resistance Factor Design (LRFD) AISC Specification for Structural Joints Using High-Strength Bolts Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 4 OF 28 American National Standard Institute (ANSI) MH 27.1 Specifications for Patented Track under Hung Cranes and Monorail Systems MH 27.2 Specifications for Enclosed Track under Hung Cranes and Monorail Systems American Petroleum Institute (API) 650 Welded Tanks for Oil Storage 625 Tank Systems for Refrigerated Liquefied Gases and Commentary American Society for Testing and Materials (ASTM) A 36M Standard Specification for Carbon Structural Steel A 325M Standard Spec. for Structural Bolts, Steel, Heat Treated 830Mpa Minimum Tensile Strength A 490M Standard Spec. for High Strength Steel Bolts, Classes 10.9 and 10.9.3 for Strc. Steel Joints A 572M Standard Specification for High Strength Low Alloy Columbium-Vanadium Structural Steel A 992M Standard Specification for Structural Steel Shapes American Society of Civil Engineers (ASCE) ASCE/SEI 7-10 Minimum Design Loads for Buildings and Other Structures ASCE/SEI 34-14 Design Loads on structure during construction American Welding Society (AWS) AWS D1.1/D1.1M Structural Welding Code - Steel European Norms (EN) 10025-2 Technical Delivery Conditions for non-Alloy Structural Steels Crane Manufacturers Association of America (CMAA) CMAA No. 70 Specifications for Top Running Bridge and Gantry Type Multiple Girder Overhead Electric Travelling Cranes CMAA No. 74 Specifications for Top Running and Under Running Single Girder Overhead Electric Travelling Cranes Utilizing Under Running Trolley Hoist Saudi Building Code (SBC) SBC 301 Structural – Loading and Forces High Commission for Industrial Security, Ministry of Interior, K.S.A. (HCIS) SAF-03 Buildings for Industrial Facilities 3. Definitions For the purpose of understanding this standard, the following definitions apply. Stability Ratio. Stability Ratio is defined as the stabilizing moment divided by the overturning moment. In the case of structures supported by a single foundation, the stabilizing moment shall be taken about the outside edge of the foundation. BEDD: Basic Engineering Design Data of the Project Site Classification: General Business Use Design Criteria for Concrete and Steel Structures 4. NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 5 OF 28 Design Loads 4.1 4.2 General 4.1.1 New facilities, buildings, and other structures, including floor slabs and foundations, shall be designed to resist the minimum loads defined in ASCE/SEI 7-10, SBC 301 and this section. 4.1.2 Future loads shall be considered if specified by SABIC. 4.1.3 Risk Category for buildings and structures in SABIC facilities shall be considered as Category III for the purpose of applying wind and earthquake load provisions in accordance with section 1.5 of ASCE/SEI 7-10. For other classifications, SABIC approval shall be obtained. Dead Load (D) 4.2.1 Dead loads are the actual weight of materials forming the building, structure, foundation, and all permanently attached appurtenances and fixed service equipment including the weight of cranes and material handling systems. 4.2.2 Weights of fixed process equipment and machinery, piping, valves, electrical cable trays, and the contents of these items shall be considered dead loads. 4.2.3 For this Standard, dead loads are designated by the following nomenclature: Ds, Df, De, Do, and Dt, where; Ds = Structure dead load is the weight of materials forming the structure (not the empty weight of process equipment, vessels, tanks, piping, nor cable trays), foundation, soil above the foundation resisting uplift, and all permanently attached appurtenances (e.g. lighting, instrumentation, HVAC, sprinkler and deluge systems, fireproofing, and insulation, etc.). Df = Erection dead load is the fabricated weight of process equipment or vessels (as further defined in Section 4.2.4). De = Empty dead load is the empty weight of process equipment, vessels, tanks, piping, and cable trays (as further defined in Sections 4.2.4 through 4.2.6). Do = Operating dead load is the empty weight of process equipment, vessels, tanks, piping, and cable trays plus the maximum weight of contents (fluid load) during normal operation (as further defined in Sections 4.2.4 through 4.2.7). Dt = Test dead load is the empty weight of process equipment, vessels, tanks, and/or piping plus the weight of the test medium contained in the system (as further defined in Section 4.2.4). 4.2.4 Process Equipment and Vessel Dead Loads: a. Erection dead load (Df) for process equipment and vessels is normally the fabricated weight of the equipment or vessel and is generally taken from the certified equipment or vessel drawing. b. Empty dead load (De) for process equipment and vessels is the empty weight of the equipment or vessels, including all attachments, trays, internals, insulation, piping, fireproofing, agitators, ladders, platforms, etc. Empty dead load also Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 6 OF 28 includes weight of machinery (e.g. pumps, compressors, turbines, and packaged units). 4.2.5 c. Operating dead load (Do) for process equipment and vessels is the empty dead load plus the maximum weight of contents (including packing/catalyst) during normal operation. d. Test dead load (Dt) for process equipment and vessels is the empty dead load plus the weight of test medium contained in the system. The test medium shall be as specified in the contract documents or as specified by SABIC. Unless otherwise specified, a minimum specific gravity of 1.0 shall be used for the test medium. Equipment and pipes that may be simultaneously tested shall be included. Cleaning load shall be used for test dead load if the cleaning fluid is heavier than the test medium. Pipe Rack Piping Loads: a. 4.2.6 Dead loads for piping on pipe racks shall be estimated as follows, unless actual load information is available. i. Operating dead load (Do): A uniformly distributed load of 1.9 kN/m2 (equivalent to 8 inch diameter, Schedule 40 pipes, full of water, at 38 cm spacing) for piping, product, and insulation. Engineering judgement shall be used to increase this load if average pipe sizes are larger than abovementioned assumption. ii. Empty dead load (De): For checking uplift and components controlled by minimum loading. 40% to 60% of the estimated piping operating loads shall be used as determined by engineering judgement if combined with wind or earthquake unless the actual conditions require a different percentage. iii. Test dead load (Dt): The empty weight of the pipe plus the weight of test medium contained in a set of simultaneously tested piping systems. The weight of the test medium shall be based on the type of test. A minimum specific gravity of 1.0 shall be used for the test medium if test medium is not specified. b. For any pipe at least two sizes larger than average pipe size on the piping level under consideration, an additional uniform or concentrated load, including the weight of piping, product, valves, fittings, and insulation shall be used for the dead load not included in the regular uniform distributed piping load of 1.9 kN/m2. c. Design shall consider the actual operating weight of the lines with lighter medium particularly when assessing uplift behavior of the structure. d. Pipe racks and their foundations shall be designed to support loads associated with full utilization of the available rack space. Pipe Rack Cable Tray Loads: a. Dead loads for cable trays on pipe racks shall be estimated as follows, unless actual load information is available. i. Operating dead load (Do): A uniformly distributed dead load of 1.0 kN/m2 for a single level of cable trays and 1.9 kN/m2 for a double level of cable trays. These values estimate the full (maximum) level of cables in the trays. ii. Empty dead load (De): For checking uplift and components controlled by minimum loading, a reduced level of cable tray load (i.e., the actual Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 7 OF 28 configuration) should be considered as the empty dead load. Engineering judgment shall be exercised in defining the dead load for uplift conditions. 4.2.7 4.3 Ground-Supported Storage Tank Loads: a. Dead loads for ground-supported storage tanks are shown in Table X with the same nomenclature as other dead loads in this standard for consistency. b. The individual load components making up the dead loads shall be separated for actual use in design, as follows: i. Operating dead load (Do): Operating dead load for a ground-supported storage tank is made up of the metal load from the tank shell and roof, vertically applied through the wall of the tank, in addition to the fluid load from the stored product. The fluid load acts through the bottom of the tank and does not act vertically through the wall of the tank. Therefore, the metal dead load and the fluid load shall be used separately in design. ii. Empty dead load (De): For checking uplift and components controlled by minimum loading, the corroded metal weight (if a corrosion allowance is specified) shall be considered as the empty dead load. iii. Test dead load (Dt): Test dead load for a ground-supported storage tank is made up of the metal load from the tank shell and roof, vertically applied through the wall of the tank, in addition to the fluid load from the test medium. The fluid load acts through the bottom of the tank and does not act vertically through the wall of the tank. Therefore, the metal dead load and the fluid load shall be used separately in design. Unless otherwise specified, a minimum specific gravity of 1.0 shall be used for the test medium. Live Load (L) 4.3.1 Live loads are gravity loads produced by the use and occupancy of the building or structure. These include the weight of all movable loads, such as personnel, tools, movable partitions, miscellaneous equipment, wheel loads, parts of dismantled equipment, stored material, etc. 4.3.2 Minimum live loads shall be in accordance with ASCE/SEI 7-10, applicable codes and standards, and in Table I, unless otherwise specified. For major equipment, the manufacturer certified loads shall be used in the design. 4.3.3 Uniform and concentrated live loads listed in Table I shall not be applied simultaneously. 4.3.4 Areas specified for maintenance (e.g. heat exchanger tube bundle servicing) shall be designed to support the live loads. 4.3.5 Concentrated loads equal to or greater than 4.5 kN may be assumed to be uniformly distributed over an area of 750 mm by 750 mm and shall be located to produce the maximum load effects in the structural members. 4.3.6 Live load reductions shall be in accordance with ASCE/SEI 7-10. Roof live loads shall not be reduced. 4.3.7 The loadings on handrails and guardrails for process equipment structures shall be in accordance with ASCE/SEI 7-10. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 8 OF 28 Table I Minimum Live Loads UNIFORM LOAD CATEGORY (kN/m2) CONCENTRATED LOAD (kN) Platform: - Operating floor areas and platforms - Platforms where heavy maintenance occur - Personnel access, inspection platforms and catwalks. 3.6 7.0 2.5 4.5 Stairs, ramps 5.0 4.5 Exit ways, corridors and lobbies 5.0 4.5 Air-conditioning equipment and transformers (1) 10.0 - 7.5 - 10.0 - 7.5 - Laboratories (1) 5.0 - Control room, rack room, locker room, remote instrument building, analyzer shelters (1) 5.0 9.0 Storage areas: (1) - Light - Heavy 6.0 - Electrical switchgear room (1) Battery rooms (1) Communication equipment room, data center (1) 4.5 3.0 12.0 Notes: (1) The provided loads shall be used for preliminary design until the actual equipment data becomes available. Use actual weight of equipment when it is greater than tabulated values. 4.4 Wind Load (W) 4.4.1 Wind loads shall be determined and applied in accordance with ASCE/SEI 7-10. 4.4.2 Site specific design parameters shall be in accordance with the BEDD of the project site and as specified below. 4.4.3 Basic wind speed (V) is a 3 second gust speed at 10 m above ground for plant site exposure category ‘C’ and associated with 1700 years return period (annual probability of 0.000588). Basic wind speed (V) used in the calculation of design wind loads on buildings and other structures shall be determined from Table II. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 9 OF 28 Table II Basic Wind Speed (V) V (1) PLANT SITE km/hr m/sec Jubail 180 50 Yanbu 170 47 Riyadh 198 55 Dammam 180 50 Notes: (1) See clause 4.4.4 4.4.4 Velocities of Table II generate wind loads for use in Strength Design method with a wind load factor of 1.0. These velocities shall be used in conjunction with that of combinations specified in this standard and in section 2.3 and 2.4 of ASCE/SEI 7-10. 4.4.5 Exposure category ‘C’ shall be used unless the terrain condition of the site justifies a different exposure category subject to the approval of the SABIC. For structures located within 0.46 km from shorelines, Exposure category D shall be used. 4.4.6 The full design wind load shall be used when calculating wind drift. 4.4.7 A solid width of 450 mm shall be assumed when calculating the wind load on ladder cages unless actual geometry is considered in analysis. 4.4.8 Partial Wind Load (Wp) : Only 50 percent of calculated wind load shall be considered as a Partial Wind Load in test or erection phase having a duration of less than 6 weeks. For test or erection, periods longer than six weeks refer to ASCE/SEI 37-14. 4.4.9 Force coefficients (Cf) for typical petrochemical facilities not specifically covered by ASCE/SEI 7-10, such as multiple bay equipment support structures, pipe racks, vessels with appurtenances etc., shall be determined based on guidelines provided in ASCE Guidelines for Wind Loads and Anchor Bolt Design for Petrochemical Facilities. 4.4.10 Gust effect factors for main wind resisting systems of flexible buildings, structures, stacks, process columns and vessels having a height exceeding four times the least horizontal dimension or a fundamental natural frequency less than 1.0 Hz shall be calculated. Calculations shall be based on a rational analysis that incorporates the dynamic properties of the main wind force resisting system. One such procedure for determining gust response factor is described in ASCE/SEI 7-10. 4.4.11 The total wind force on equipment support structures shall be determined as the sum of the forces on each component in the structure. Components shall include equipment and supports (without considering shielding), piping, structural framing, ladders, stairs, and Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 10 OF 28 other miscellaneous objects attached to the structure. However, the total force due to wind for an ordinary structure need not exceed that of an enclosed structure that would completely envelope the structure and attachments. 4.4.12 No reduction shall be made for the shielding effect of vessels or structures adjacent to the structure being designed. 4.4.13 Wind and earthquake loads shall not be assumed to act concurrently. 4.5 Earthquake Load (E) 4.5.1 Earthquake loads shall be computed and applied in accordance with ASCE/SEI 7-10 and the parameters of Table III. 4.5.2 Earthquake loads for storage tanks at grade shall be in accordance with Appendix E of API 650 and the parameters of Table III. 4.5.3 ASCE/SEI 7-10 generates earthquake loads for use in Strength Design method with seismic load factor of 1.0. This shall be taken into account if using Allowable Stress Design Methods or applying load factors from other codes. 4.5.4 Site specific design parameters shall be in accordance with the BEDD of the project site and as specified below in Table III. Table III Seismic Design Parameter EARTHQUAKE PARAMETER JUBAIL DAMMAM RIYADH YANBU 11 11 4 20 S1 : 1 second spectral response acceleration in % g 6 6 1 3.5 PGA (% Peak Ground Acceleration) (1) 5 5 2 9.5 Ss : Short period (0.2 Sec) spectral response acceleration in %g Notes: (1) The spectral values and PGA represent a 2% probability of exceedance in 50 years (recurrence interval of approximately 2500 years). (2) The Site Class is B. 4.5.5 The site classification shall be determined based on site-specific geotechnical investigation. In the absence of site specific classification, Class C shall be assumed only for preliminary design purposes. 4.5.6 Seismic loads shall not be considered in test or erection load combination. 4.5.7 The importance factor “I” of 1.25 shall be used for all structures. Classification: General Business Use Design Criteria for Concrete and Steel Structures 4.5.8 NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 11 OF 28 For the load combinations in Section 5.0, the following designations are used: Eo = Earthquake load considering the unfactored operating dead load and the applicable portion of the unfactored structure dead load. Ee = Earthquake load considering the unfactored empty dead load and the applicable portion of the unfactored structure dead load. 4.5.9 4.6 The equipment mass shall be considered as a lumped mass added to the structural mass in seismic analysis rather than externally applied seismic force. Impact Load 4.6.1 The weight of machinery and moving loads shall be increased by the percentages shown in Table IV to allow for impact. All percentages of Table IV shall be increased where specified by the manufacturer. 4.6.2 Impact loads shall not be considered in load combinations comprising wind and earthquake loads. Table IV Load Increase Factors for Impacts CATEGORY 4.7 LOAD INCREASE FACTOR For supports of elevators (dead and live load) 100 % Light machinery, shaft or motor driven 20 % Reciprocating machinery or power driven units 50 % Crane Load 4.7.1 The crane live load shall be the rated capacity of the crane. Design loads for the runway beams, including connections and support brackets, of moving bridge cranes and monorail cranes shall include the maximum wheel loads of the crane and the vertical impact, lateral, longitudinal and crane stop force induced by the moving crane. 4.7.2 The maximum wheel loads shall be the wheel loads produced by the weight of the bridge, plus the sum of the rated capacity and the weight of the trolley positioned on its runway at the location where the resulting load effect is maximum. 4.7.3 The maximum wheel loads of the crane shall be increased by the percentages shown in Table V to determine the induced vertical impact or vibration. 4.7.4 The lateral force on crane runway beams with electrically powered trolleys shall be calculated as 20 percent of the sum of the rated capacity of the crane and the weight of the hoist and trolley. The lateral force shall be assumed to act horizontally at the traction surface of a runway beam in either direction perpendicular to the beam, and shall be distributed with due regard to the lateral stiffness of the runway beam and supporting structure. The lateral force on Davits shall be 20 percent of its rated capacity. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 12 OF 28 4.7.5 The longitudinal force on crane runway beams, except for bridge cranes with handgeared bridges, shall be calculated as 10% of the maximum wheel loads of the crane. The longitudinal force shall be assumed to act horizontally at the traction surface of a runway beam in either direction parallel to the beam. The longitudinal force on Davits shall be 20 percent of its rated capacity. 4.7.6 The crane stop forces shall be based on manufacturer’s requirements. In the absence of such recommendations, ASCE 7-10 guidelines shall be followed. Table V Maximum Wheel Load Increase Factors CATEGORY VERTICAL IMPACT FORCE Monorail cranes (powered) 25 % Cab-operated or remotely operated bridge cranes (powered) 25 % Pendant-operated bridge cranes (powered) 10 % Lifting lugs or pad eyes and internal members, including both end connections, framing into the joint where the lifting lug or pad eye is located 100 % All other structural members transmitting lifting forces 15 % Bridge cranes or monorail cranes with hand-geared bridge, trolley, and hoist 0% Davits (1) Notes: (1) 4.8 Vertical impact force on Davits shall be 25 percent of rated capacity. Thermal Load (T) 4.8.1. Thermal loads are designated by the following nomenclature: Tp, Ts, Af, and Ff, where Tp = Forces on vertical vessels, horizontal vessels, or heat exchangers caused by the thermal expansion of the pipe attached to the vessel under normal operating conditions ( loads from a pipe stress analysis or from manufacturer). Ts = The self-straining thermal forces caused by the restrained expansion or contraction of vessels, structural steel members in pipe racks or structures caused by sustained change in ambient temperature. Af = Pipe anchor and guide forces (loads from a pipe stress analysis). Ff = Friction forces caused by the sliding of pipes, horizontal vessels or heat exchangers on their supports, in response to thermal expansion or contraction. 4.8.2. All support structures and elements shall be designed to accommodate the loads or effects produced by thermal expansion and contraction of equipment and piping. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 13 OF 28 4.8.3. Thermal loads shall be included with operating loads in the appropriate load combinations. Thermal load shall have the same load factor as dead load. 4.8.4. Thermal loads and displacements shall be calculated on the basis of the difference between ambient temperature or equipment design temperature and installed temperature (30 C). To account for the significant increase in temperatures of steel exposed to sunlight, 20 C shall be added to the maximum ambient temperature. 4.8.5. Thermal loads due to environmental condition shall be based on ambient temperature range from a minimum of 0 C to a maximum of 50 C unless otherwise specified in the BEDD. 4.8.6. Friction loads caused by thermal expansion shall be determined using the appropriate static coefficient of friction. Coefficients of friction shall be in accordance with Table VI. Table VI Friction Coefficients SURFACE FRICTION COEFFICIENT Steel-to-steel 0.4 Steel-to-concrete 0.6 Proprietary sliding surfaces or coatings Teflon to stainless steel According to manufacturer’s instructions 0.10 4.8.7. Friction loads shall be considered temporary and shall not be combined with wind or earthquake loads. However, anchor and guide loads (excluding their friction component) shall be combined with wind or earthquake loads. 4.8.8. For pipe racks supporting multiple pipes, 10 percent of the total piping weight shall be used as an estimated horizontal friction load applied only to local supporting beams. However, an estimated friction load equal to 5 percent of the total piping weight shall be accumulated and carried into pipe rack struts, columns, braced anchor frames, and its foundations. 4.8.9. If the definitive information is available, a concentrated load of 30 percent of the total pipe weight of the heaviest pipe shall be used to produce greatest loading. 4.8.10. Under normal loading conditions with multiple pipes, torsional effects on the local beam need not be considered because the pipes supported by the beam limit the rotation of the beam to the extent that the torsional stresses are minimal. Under certain circumstances, engineering judgment shall be applied to determine whether a higher friction load and/or torsional effects should be used. 4.8.11. Pipe anchor and guide loads shall have the same load factor as dead loads. 4.8.12. Internal pressure and surge shall be considered for pipe anchor and guide loads. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 14 OF 28 4.8.13. Beams, struts, columns, braced anchor frames, and foundations shall be designed to resist actual pipe anchor and guide loads. 4.8.14. For local beam design, only the top flange shall be considered effective for horizontal bending unless the pipe anchor engages both flanges of the beam. 4.9 Bundle Pull Load (Bp) 4.9.1. Structures and foundations supporting heat exchangers subject to bundle pulling shall be designed for a horizontal bundle pushing and pulling load equal to 100 percent of the weight of the removable tube bundle. 4.9.2. Bundle pull load shall be applied at the center of the bundle and be considered in load combinations as live load. 4.9.3. The foundation at the fixed end shall be designed for 100 percent of the calculated bundle pushing and pulling horizontal load. 4.9.4. The foundation at the sliding end shall be designed for at least 50 percent of the calculated bundle pushing and pulling horizontal load. 4.9.5. If it can be assured that the bundles will be removed strictly by the use of a bundle extractor attaching directly to the exchanger (such that the bundle pull force is not transferred to the structure or foundation), the structure or foundation need not be designed for the bundle pull force. Such assurance shall be provided by the addition of a sign posted on the exchanger to indicate bundle removal by an extractor only. 4.10 Erection Load 4.10.1 Erection loads are temporary loads caused by the installation or erection of equipment or structures. Erection loads are considered in load combinations as live load. 4.10.2 Beams and floor slabs in multi-storey structures shall be designed to carry the full construction loads imposed by the props supporting the floor immediately above. The locations of props used in design shall be shown on design/construction drawings to highlight the adopted design philosophy. 4.10.3 Heavy equipment lowered onto a supporting structure can introduce extreme point loads on structural members, exceeding operating or test loads. After placing of equipment, the exact positioning (lining out and leveling) can also introduce extreme point loads. This potential loading condition shall be considered in design calculations where appropriate. 4.11 Traffic Loads 4.11.1 Bridges, trenches, and underground installations accessible to truck loading shall be designed to withstand HS20 loading as defined by AASHTO HB 17 Standard Specifications for Highway Bridges. Maintenance or construction crane loads shall also be considered. 4.11.2 For the design of structural element, crane loads or moving loads shall be assumed to be at the most unfavorable position and at maximum values including lifting capacity and horizontal loads caused by braking or acceleration. 4.11.3 Truck or crane loads shall have the same load factor as live loads. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 15 OF 28 4.11.4 Vehicular loads due to tired-vehicles (moving equipment) that operate on paved areas shall be as per AASHTO specification. 4.12 Blast Loads 4.12.1 Blast load is the load on a structure caused by overpressure resulting from the ignition and explosion of flammable material or overpressure resulting from a vessel burst. 4.12.2 Blast load shall be computed and applied in accordance with SES B01-E02. 4.13 Differential Settlement 4.13.1 Provisions shall be made for forces arising from assumed differential settlements of foundations and from restrained dimensional changes due to temperature changes, moisture expansion, shrinkage, creep, and similar effects. These loads are considered in load combinations as dead load. 4.14 Earth and Water Pressure 4.14.1 Earth and hydrostatic water pressures on retaining walls and underground structures shall be determined. Outward pressures on liquid-retaining structures shall also be determined. 4.14.2 Earth and water pressures are considered in load combinations as live load. 4.15 Pressure Loads (Ground-supported tanks only) 4.15.1 Pressure loads for ground supported tanks are designated by the following nomenclature: Pi = Design internal pressure Pe = External pressure Pt = Test internal pressure 4.16 Special Design Considerations 4.16.1 Vibration Loads: Where vibration induced by equipment or operation is specified or anticipated, supporting members shall be designed to prevent fatigue failure. Where it is anticipated that vibrations will be transmitted through columns and other portions of a building or structure to the foundations, vibration forces shall be considered in the foundation design. Vibration loads shall be considered as live loads in the applicable load combinations. 4.16.2 Structures providing support for rotating and reciprocating machinery shall provide safe and tolerable response to dynamic loadings imposed by the machinery. Design of the structural system or foundation supporting rotating or reciprocating machinery shall comply with SES B52-E02. 4.16.3 The effect of wind forces acting on temporary scaffolding erected during construction, or later for maintenance, which will be transferred to the vessel or column shall be considered. When considering these effects, the actual projected area of the scaffold members together with the correct shape factor and drag coefficient shall be used. As an initial Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 16 OF 28 approximation, the overall width of the scaffolding itself can be taken as 1.5 m on each side of the vessel or column with 50 percent closed surface and shape factor 1.0. 4.16.4 Hydrostatic loads and buoyancy shall be considered when a structure or equipment extends below water level, either temporarily or long term as follows: a. Structure or equipment shall be considered as empty when evaluating impact of buoyancy. b. Water table level shall be considered as per recommendations of Geotechnical investigation report unless otherwise approved by SABIC. 4.16.5 Dike walls shall be designed for accidental load condition when the bund is completely filled with water/fluid to the crest. Only the hydrostatic fluid pressure acting in the outward direction and gravity loading need to be considered. The factor of safety shall not be less than 1.3 for this loading condition. 5. Load Combinations 5.1 5.2 General 5.1.1 Buildings, structures, equipment, vessels, tanks, and foundations shall be designed for the appropriate load combinations from this standard, ASCE 7-10, and any other probable and realistic combination of loads. 5.1.2 Engineering judgment shall be used in establishing all appropriate load combinations. 5.1.3 Load combinations shall include erection, testing, maintenance and operating conditions with or without climatic overloads like wind or earthquake loads. 5.1.4 The non-comprehensive list of typical load combinations (for both ASD and Strength Design) specified through Table VII to Table XI for each type of structure shall be considered and used as applicable. 5.1.5 The use of a one-third stress increase for load combinations including wind or earthquake loads shall not be allowed for designs using AISC ASD. However, a 20 percent allowable stress increase shall be permitted for any test load combination. 5.1.6 For Strength Design, no load factor reduction shall be permitted for any test load combination. Load Combinations for Buildings , General Plant and Process Structures 5.2.1 Load combinations for buildings, general plant structures and process structures shall be in accordance with ASCE/SEI 7–10, Chapter 2. Load combinations for Allowable Stress Design and Strength Design are provided in the Table VII shall be as applicable. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 17 OF 28 Table VII Load Combinations for Buildings and general plant structures and process structures LOAD COMBINATION (1) LOAD COMB. NO. DESCRIPTION SERVICE LOADS (Allowable Stress Design) FACTORED LOADS (Strength Design) 1 Operating Weight + Thermal Ds + D o + T 1.4 (Ds + Do + T) 2 Operating Weight + Live + Thermal Ds + D o + T + L 1.2 (Ds + Do + T) + 1.6 L 3 Operating Weight + Live + Thermal(3) + wind or Earthquake Ds + Do + 0.75 L + T + 0.75 (0.7 Eo ) or 0.75 (0.6 W) 1.2 (Ds + Do + T) + L + W or Eo 4 Operating Weight + Thermal (3) + Wind or Earthquake Ds + Do + T + (0.6 W or 0.7 Eo) 1.2 (Ds + Do + T) + (W or Eo) 0.6 (Ds + De)+ 0.6 W 0.9 (Ds + De) + W 0.6 (Ds + Do ) + T + 0.7 Eo 0.9 (Ds + Do) +1.2 T+ Eo 0.6 (Ds + De) + 0.7 Ee 0.9 (Ds + De) + Ee 5 6a 6b Empty Weight + Wind (uplift case) Operating Weight + Thermal (3) Earthquake (Earthquake uplift case) Empty Weight + Earthquake (Earthquake uplift case) 7(4) Test Weight + Partial Wind Ds + Dt + 0.6 W p(2) 1.2 (Ds + Dt) + W p(2) 8(4) Test Weight D s + Dt 1.4 (Ds + Dt) Notes: (1) See section 4 for notations. (2) Roof live loads shall not be reduced in any above load combinations. (3) Only operating thermal loads (Af and Tp) which are not relieved by sliding shall be considered in operating load combinations with wind or earthquake. (4) Engineering judgment shall be used in establishing the appropriate application of test load combinations to adequately address actual test conditions and test sequence in accordance with project and code requirements while avoiding overly conservative design. 5.3 Load Combinations for Vertical Vessel supports and foundations 5.3.1 Load combinations for Allowable Stress Design and Strength Design are provided in the Table VIII. 5.3.2 Erection weight + Partial wind load combinations is required if the erection weight of the vessel is significantly less than the empty weight of the vessel. Classification: General Business Use Design Criteria for Concrete and Steel Structures 5.3.3 NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 18 OF 28 Thrust forces caused by thermal expansion of piping shall be included in the calculations for operating load combinations, if deemed advisable. The pipe stress engineer shall be consulted for any thermal loads that are to be considered. Table VIII Load Combinations for Vertical Vessel supports and foundations LOAD COMBINATION (1) LOAD COMB. NO. DESCRIPTION SERVICE LOADS (Allowable Stress Design) FACTORED LOADS (Strength Design) 1 Operating Weight Ds + D o 1.4 (Ds + Do) 2 Operating Weight + Live Load Ds + D o + L 1.2 (Ds + Do) + 1.6 L 3 Operating Weight + Wind or Earth quake Ds + Do + 0.6 W or 0.7 Eo 1.2 (Ds + Do) + W or Eo 4 Empty Weight + Wind (Wind uplift case) 0.6 (Ds + De) + 0.6 W 0.9 (Ds + De) + W 5a Operating Weight + Earthquake (Earthquake uplift case) 0.6 (Ds + Do) + 0.7 Eo 0.9 (Ds + Do) + Eo 5b Empty Weight + Earthquake (Earthquake uplift case) 0.6 (Ds + De) + 0.7 Ee 0.9 (Ds + De) + Ee 6 Erection Weight + Partial Wind (Wind uplift case) 0.6 (Ds + Df) + 0.6 W p 0.9 (Ds + Df) + W p 7 Test Weight + Partial Wind Ds + Dt + 0.6 W p 1.2 (Ds + Dt) + W p 8 Test Weight D s + Dt 1.4 (Ds + Dt) Notes: (1) See section 4 for notations. 5.4 Load Combinations for Horizontal Vessels and Heat Exchanger foundations 5.4.1 Load combinations for Allowable Stress Design and Strength Design are provided in Table IX. 5.4.2 Wind and earthquake forces shall be applied in both transverse and longitudinal directions, but shall not necessarily be applied simultaneously. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 19 OF 28 Table IX Load Combinations for Horizontal Vessels and Heat Exchanger supports and foundations LOAD COMBINATION (1) LOAD COMB. NO. DESCRIPTION SERVICE LOADS (Allowable Stress Design) FACTORED LOADS (Strength Design) 1 Operating Weight + Thermal (2) Ds + Do + (Ts or Ff) 1.4 (Ds + Do) + 1.4 (Ts or Ff) 2 Operating Weight + Live Load + Thermal (2) Ds + Do + L + (T or Ff) 1.2 (Ds + Do) + 1.6 L + 1.2 (T or Ff) 3 Operating Weight + Wind or Earth quake Ds + Do + 0.6 W or 0.7 Eo 1.2 (Ds + Do) + W or Eo 4 Empty Weight + Wind (Wind uplift case) 0.6 (Ds + De)+ 0.6 W 0.9 (Ds + De) + W 5a Operating Weight + Earthquake (Earthquake uplift case) 0.6 (Ds + Do) + 0.7 Eo 0.9 (Ds + Do) + Eo 5b Empty Weight + Earthquake (Earthquake uplift case) 0.6 (Ds + De) + 0.7 Ee 0.9 (Ds + De) + Ee 6 Erection Weight + Partial Wind (2) (Wind uplift case) 0.6 (Ds + Df) + 0.6 W p 0.9 (Ds + Df) + W p 7 Test Weight + Partial Wind (2) (For horizontal vessels only) Ds + Dt + 0.6 W p 1.2 (Ds + Dt) + W p 8 Empty Weight + Bundle Pull (For heat exchangers only) Ds + De + Bp 1.2 (Ds + De) + 1.6 Bp 9 Test Weight (For Horizontal vessels only) D s + Dt 1.4 (Ds + Dt) 10 Empty Weight + Bundle Pull (For heat exchangers only) Bundle pull uplift case 0.6 (Ds + De) + Bp 0.9 (Ds + De) + 1.6 Bp Notes: (1) See section 4 for notations. (2) The design thermal force shall be the lesser of the force (Ts) required to deflect foundation pier an amount equal to half of the thermal growth between the exchanger or vessel saddles and the force (Ff) required to overcome static friction at the sliding surface between the bottom of the exchanger or vessel saddle and the support pier. 5.4.3 Erection Weight + Partial Wind load combinations is required if the erection weight of the vessel or exchanger is significantly less than the empty weight of the vessel or exchanger. Classification: General Business Use Design Criteria for Concrete and Steel Structures 5.5 NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 20 OF 28 5.4.4 Heat exchanger empty dead load will be reduced during bundle pull because of the removal of the exchanger head. 5.4.5 Sustained thermal loads not relieved by sliding caused by vessel or exchanger expansion shall be considered in operating load combinations with wind or earthquake. 5.4.6 Thrust forces caused by thermal expansion of piping shall be included in the calculations for operating load combinations, if deemed advisable. The pipe stress engineer shall be consulted for any thermal loads that are to be considered. Load Combinations for Pipe Rack and Pipe Bridge Design 5.5.1 Load combinations for Allowable Stress Design and Strength Design are provided in the Table X. Table X Load Combinations for Pipe Racks LOAD COMBINATION (1) LOAD COMB. NO. DESCRIPTION SERVICE LOADS (Allowable Stress Design) FACTORED LOADS (Strength Design) 1 Operating Weight + Thermal Ds + D o + T 1.4 (Ds + Do + T) 2 Operating Weight + Thermal(2) + Wind or Earthquake Ds + Do + T + 0.6 W or 0.7Eo 1.2 (Ds + Do + T) + W or Eo 0.6 (Ds + De)+ 0.6 W 0.9 (Ds + De) + W 0.6 (Ds + Do ) + T + 0.7 Eo 0.9 (Ds + Do) + 1.2 T + Eo 0.6 (Ds + De) + 0.7 Ee 0.9 (Ds + De) + Ee 3 4a 4b Empty Weight + Wind (Wind uplift case) Operating Weight + Thermal(2) +Earthquake (Earthquake uplift case) Empty Weight + Earthquake (Earthquake uplift case) 5 Test Weight + Partial Wind Ds + Dt + 0.6 W p(2) 1.2 (Ds + Dt) + W p 6 Test Weight D s + Dt 1.4 (Ds + Dt) Notes: (1) See section 4 for notations. (2) Only operating thermal loads (Af and Tp) which are not relieved by sliding shall be considered in operating load combinations with wind or earthquake. 5.5.2 Earthquake forces shall be applied in both transverse and longitudinal directions, but shall not necessarily be applied simultaneously. 5.5.3 Full Ds + Do value shall be used for calculation of Eo in load combination. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 21 OF 28 5.5.4 0.6 Do is used as a close approximation of the empty pipe condition De. 5.5.5 Test Weight + Partial Wind is required only for local member design where test is not performed on all pipes simultaneously. 5.5.6 For pipe racks with air coolers or other types of equipment and vessels, loads and load combinations used for corrsepsonding equipment structures and vessel supports shall also be considered as applicable. 5.6 Load Combinations for Ground Supported Storage Tank Foundations 5.6.1 Load combinations for ground supported storage tank shall be as shown in Table XI. 5.6.2 For internal pressures (Pi) sufficient to lift the tank shell according to the rules of API 650, tank, anchor bolts, and foundation shall be designed to the additional requirements of API 650 Appendix F.7. Table XI Load Combinations for Ground Supported Storage Tank Foundations LOAD COMB. NO. DESCRIPTION SERVICE LOADS (1) (Allowable Stress Design) 1 Operating Weight + Internal Pressure Ds + Do + Pi 2 Test Weight + Test Pressure Ds + Dt + Pt 3 Empty or Operating Weight + Wind + Internal Pressure Ds + (De or Do) + 0.6 W + 0.4 Pi 4 Empty or Operating Weight + Wind + External Pressure Ds + (De or Do) + 0.6 W + 0.4 Pe 5 Operating Weight + Live Load + External Pressure Ds + Do + L + 0.4 Pe 6 Empty or Operating weight + Live load + External Pressure Ds + (De or Do) + 0.4 L + Pe 7 Operating Weight + Earthquake(2) + Internal Pressure (Earthquake uplift case) Ds + Do + Eo(2) + 0.4 Pi 8 Operating Weight + Earthquake(2) Ds + Do + Eo(2) Notes: (1) See section 4 for notations. (2) Earthquake loads (Eo) shall be calculated in accordance with Annex E of API 650. Earthquake loads in API 650 taken from ASCE/SEI 7-10 “bridging equations” already include the 0.7 ASD seismic load factor. Classification: General Business Use Design Criteria for Concrete and Steel Structures 5.7 B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 22 OF 28 Load Combinations for Machinery Static Analysis, Skid and Modular Equipment, Filters, and Other Equipment 5.7.1 6. NUMBER Load combinations for machinery, skid and modular equipment, filters, etc. shall be similar to the load combinations for vertical vessels. Structural Design 6.1 6.2 General 6.1.1. Structural steel framed structures shall be utilized for most equipment support, all pipe racks and some buildings specified by SABIC. In case of a cost or schedule advantage, concrete or precast concrete may be used, provided structural adequacy is maintained. 6.1.2. For the building structures located in OSBL areas, the feasibility of special modular building systems such as ConXtech shall be evaluated considering cost, schedule and possibility of future modifications. 6.1.3. Guidelines given in PIP STE01100 should be considered in the structural design of the project for improving the constructability of civil and structural works. Structural Steel 6.2.1. Steel design shall be in accordance with AISC ASD or AISC LRFD specifications. 6.2.2. Plastic design method shall not be used in the design of structures subject to sustained vibration or stress reversal caused by operating equipment. 6.2.3. Structural steel shapes, plates and bars shall be in accordance with ASTM A 36M, ASTM A 572M Grade 50 or ASTM A 992M. Unless otherwise specified in contract documents, structural steel wide flange shapes, including WT shapes, shall be in accordance with ASTM A992/A992M or ASTM A 572M Grade 50. Grade substitutions shall not be made without SABIC approval. 6.2.4. Subject to SABIC approval, ASTM equivalent material shown on Table XII can be used. Any differences in material dimensions, section properties, yield strengths and tensile strengths shall be accounted for in design calculations. However, mixed use of the structural material in the same plant is not permitted without SABIC approval. Table XII ASTM Material Equivalency ASTM MATERIALS EN MATERIALS A 36M EN 10025-2, Gr S275 Jr/J0 A 572M Grade 50 EN 10025-2, Gr S355 Jr/J0 A 992M EN 10025-2, Gr S355 Jr/J0 Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 23 OF 28 6.2.5. Fabrication and erection of structural steel shall be in accordance with SES B02-S01 and SES B02-S02 respectively. 6.2.6. Equipment structures, pipe racks, and buildings shall be designed to provide adequate lateral stability with bracing systems or rigid moment connection design. The preferred method of providing stability will be to use a bracing system in both lateral and longitudinal directions of equipment structures and buildings. When access or clearance requirements, or both, preclude the use of bracing in both directions, the next preferred method shall be the use of moment connected rigid frames or knee-braced frames with simple connections to provide stability in the lateral direction and the use of bracing in the longitudinal direction. The use of moment connected rigid frames or knee-braced frames to provide lateral stability in both directions is not permitted without the prior approval by SABIC. 6.2.7. Bracing in structures supporting equipment, pipe racks, and buildings shall be either Kbracing or single diagonal or X braces. Care shall be taken to ensure that the bracing shall not interfere with equipment access for maintenance. 6.2.8. Compression flanges of floor beams, not supporting equipment, can be considered braced by decking (Concrete or floor plate) if positively connected. Grating shall not be considered as lateral bracing for support beams. 6.2.9. Preference in design shall be given to Shop-welded, field-bolted connections. 6.2.10. Bolted joints shall conform to the requirements of the latest edition of AISC Specification for Structural Joints Using High-Strength Bolts. European equivalents shall be used with prior SABIC approval. 6.2.11. All structural strength welding shall be continuous. All welding shall conform to ANSI/AWS D 1.1. 6.2.12. Minimum bolt size shall be 20mm for structural members and 16mm for railings, ladders, purlins and girts. 6.2.13. Minimum thickness of bracing gusset plates shall be 10mm. 6.2.14. For structural elements subject to prolonged exposure to heat above 93 oC, allowable design stress shall be reduced in proportion to reductions in yield strength of the steel at the design temperature. The modulus of elasticity shall also be reduced to account for the effect of elevated temperature. 6.2.15. Where the structure is continuously exposed to an environmental temperature exceeding 260oC, such as flare support structures or adjacent to fired equipment, the structural steel mechanical properties shall be thoroughly reviewed as per AISC Manual of Steel Construction. 6.2.16. For structural elements exposed to severe corrosion, wear conditions, or other extraordinary environmental conditions, special materials, protection, or material thickness allowance shall be used instead of decreasing allowable stresses. 6.2.17. Platforms, Stairways, Ladders and Handrails: a. Fixed ladders and cages shall be designed and fabricated as per SES B04-F01. Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 24 OF 28 b. As a minimum, platforms and walkways shall be covered with 30 mm x 5 mm grating or 6 mm thick checkered plate. These shall be designed for a maximum deflection of 6 mm. Gratings shall be as specified in SES B02-S05. c. Fixed stairways shall be designed and fabricated as per SES B04-F02. d. Hand railing shall be as per SES B04-F03. e. Handrails shall be removable where required for periodic maintenance. 6.2.18. Monorail Beams: 6.3 6.3.3. 6.3.4. 6.3.5. The material of beams shall conform to ASTM A 36 or equivalent. c. Monorail beam selection shall be limited to AISC S series. When wide flange beam (AISC W series) is required to support flat wheels of hoist trolley, then a wide flange beam equivalent to S series beam shall be substituted for preliminary design. Concrete design shall be in accordance with ACI 318M. Concrete design for liquid-containing structures shall also be designed in accordance with ACI 350M. Concrete, reinforcing steel, welded wire fabric and other materials shall be in accordance with SES B51-S01. The minimum rebar size shall be a. 12 mm for use as tension, compression or temperature reinforcement, except where welded wire fabric is used, b. 16mm for reciprocating machine foundation piers, c. 10mm for ties and spirals. Precast and prestressed concrete shall be in accordance with ACI 318M. Masonry design shall be in accordance with SES B03-S01 and ACI 530. Foundations 6.5.1. 6.5.2. 6.6 b. Masonry 6.4.1. 6.5 Monorail beams and hoists shall be designed and provided as per the specifications ANSI MH 27.1 and MH 27.2 as applicable. Reinforced Concrete 6.3.1. 6.3.2. 6.4 a. Design and construction of foundations for structures and equipment shall be as per this standard SES C02-E02, C02-S06 and C02-S07 The foundation requirments of storage tanks shall be as per API 625, API 650 or ACI 376 Stability against Overturning, Sliding, and Buoyancy 6.6.1. Structures, buildings, and structural units, which consist of stacks, exchangers, vertical and horizontal vessels, together with their foundations, shall have following minimum safety factors for load combinations through section 5.2 to 5.5 of this standard. a. The minimum overturning “stability ratio” shall be 1.0 b. The minimum factor of safety against sliding shall be 1.0 Classification: General Business Use Design Criteria for Concrete and Steel Structures 6.7 6.8 7. B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 25 OF 28 6.6.2. The safety factor against buoyancy shall be at least 1.2 against the highest anticipated water level. 6.6.3. Stability calculations of ground supported tank foundation shall be in accordance with API 650. 6.6.4. In determining the safety factors, allowance shall be made for future removal of weights, for example removal of soil. Anchor Bolts 6.7.1. Design, fabrication and installation of anchor bolts shall comply with SES B55-S01. 6.7.2. Minimum size of anchor bolts for structures shall be 20mm. Grouting 6.8.1. 6.9 NUMBER Grouting for steel column and equipment base plates shall comply with SES B51-S03. Buildings 6.9.1. Buildings shall comply with SES B01-E03 and HCIS Directive SAF-03. 6.9.2. Pre-Engineered Buildings shall comply with SES B02-S04. Allowable Deflections Deflection and drift limits shall be based on serviceability of interconnected, drift or deflection-sensitive equipment, piping systems, and/or building systems and components supported by the structure or building. Drift limits specified in this section are based on service level loads and should be evaluated by the engineer of record for application in particular circumstances. 7.1. Wind Drifts 7.1.1. Allowable wind drifts shall be as shown in Table XIII. Table XIII Maximum Allowable Wind Drifts BUILDINGS/ STRUCTURES LATERAL DISPLACEMENT (1) Pipe racks H/100 Process structures H/200 Occupied buildings H/200 Un-reinforced masonry buildings H/400 Pre-engineered metal buildings H/80 Buildings with bridge cranes H/200 or 50mm (whichever is less) Notes: (1) H = Height of pipe rack, structure or building Classification: General Business Use Design Criteria for Concrete and Steel Structures 7.2. B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 26 OF 28 Seismic Drifts 7.2.1. 7.3. NUMBER Allowable seismic drift limits shall be in accordance with ASCE 7-10. Vertical Deflections 7.3.1. The maximum allowable vertical deflection of beams supporting equipment/ piping shall be as shown on Table XIV. Table XIV Maximum Allowable Vertical Deflection of Beams SUPPORTED EQUIPMENT ALLOWABLE DEFLECTION (1) Piping L/300 Piping for pumps, compressors and high temperature/ pressure piping L/600 Equipment L/400 Rotating and vibratory equipment L/800 (2) Notes: (1) L represents the length of the beam (2) 7.3.2. Equipment manufacturer’s requirement shall be followed if more stringent. The vertical deflection of the girders supporting cranes, monorail hoists and jib cranes shall be as shown on Table XV. Table XV Maximum Allowable Vertical Deflection of Crane Girders SUPPORTED EQUIPMENT ALLOWABLE VERTICAL DEFLECTION (1), (2), (3) Motor driven cranes L/1000 Hand operated cranes L/800 Infrequent, Light and Medium cranes (Classes A, B, C) Monorails: - Supported at both ends - Cantilever Jib cranes L/600 L/800 L/450 L/225 Notes: (1) L represents the length of the beam (2) Allowable deflections shall consider maximum wheel load without impact (3) Allowable lateral deflections due to crane lateral loads shall be L/400 Classification: General Business Use Design Criteria for Concrete and Steel Structures 7.3.3. 8. B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 27 OF 28 The maximum allowable deflection of the reinforced concrete members shall be as specified in ACI 318M. Existing Structures 8.1. 8.2. Design Validation and Integrity Check of Existing Structure 8.1.1. Design validation or integrity check of an existing structure shall be performed based on the design code in effect at the time of original design. 8.1.2. Actual loads can be used in lieu of the minimum specified loads. Existing Structures Subject to Modification or New Load Conditions 8.2.1. 9. NUMBER Where the integrity of an existing structure is 100% of the original capacity, when checked based on the design code in effect at the time of original design, structural design shall be performed in accordance with the following: a. If additions or alterations to an existing structure do not increase the force in any structural element or connection by more than 5%, no further analysis is required. b. If the increased forces on the element or connection are greater than 5%, then entire structural system along with its connections and foundations shall be analyzed to show that the structural system is in compliance with this SES and referenced codes for new construction. Revision History Revision No.1, Oct 2000 Revised ICBO UBC in section 2 and Paragraph 4.2.7.2. Revised table number in Para 8.3. Revision No.2, Apr 2001 Revised section 5 to incorporate use of concrete and precast concrete. Revision No.3, Mar 2004 Updated. Revision No.4, Sep 2012 Major revision as per ASCE 7 and PIP STC01015. Wind, seismic data and calculation methodology, Load combinations revised. Revision No.5, Sep 2016 Updated : References Incorporated : Addendum 1 and 2 of Rev:4 Restructured : Section 4 and 8 Revision No.6, Jun 2018 Added : Crane Loads and PGA (Peak Ground Acceleration) Revised : Basic Wind Speed and Load Combinations to suit ASCE 7-10 Impact Loads; Bunddle Pulling Load Updated : References Incorporated : Addendum 1 of Rev:5 Updated : Crane loads and vertical deflections Classification: General Business Use Design Criteria for Concrete and Steel Structures NUMBER B01-E01 REV. NO. 8 DATE MAR 2021 PAGE 28 OF 28 Added Added Revised Revised : A reference temperature for structural analysis : High strength wide flange shapes are mandated : Pipe test loads are linked to medium of the test : Actual shape of ladder cage is qualified to be considered in load calculations Revision No.7, Dec 2018 Updated Added Added Updated Changed Changed Changed Refined : References : Partial Wind loading per ASCE SEI 34-14 : Load combination table general building and structures : All load combination tables as per latest PIP release : Safety factors for structural stability : Friction Co-effs are refined as per PIP : Thermal loads and thermal load factors : Test loads combination requirements Revision No.8, Mar 2021 Changed Added Changed : Wind Speed (Table II) based on SBC – 2018 revision : Exposure Category for structure within shorelines : Seismic Design Parameter (Table III) based on SBC – 2018 revision : The site Class (Table III, Note 2) based on SBC – 2018 revision : 6.2.4 – SABIC approval is added for the mixed use of the structural material in the same plant. : 4.5.5 – Site Class is updated to “C” for preliminary design purposes. Changed Updated Updated