MWK Surge arresters Technical data - For system voltages up to Nominal discharge current I n 8/20 µs High current impulse Ihc 4/10 µs Short circuit rating (1) I s 50 Hz Line discharge class according to IEC 60099-4 - Service conditions: temperature (2) - Altitude (3) 36 kV rms 10 kA pk 100 kA pk 20 kA rms for 0.2s 2 - Long duration current impulse - Energy capability, 2 impulses acc. IEC clause 7.5.5 - Energy input with Ihc - Power frequency up to - Cantilever strength - Torsional strength - Vertical load - 600C up to + 450C up to 1800 m 550 A / 2000 µs 5.5 kJ / kV of Uc 3.4 kJ / kV of Uc 62 Hz 350 Nm 68 Nm 1200 N (1) Tested value acc. IEC 60099-4. (2) These values exceed IEC requirements. For installations in higher ambient temperatures, please contact the manufacturer. (3) This value exceeds IEC requirements. For installations in higher altitudes, please contact the manufacturer. Application Protection of medium voltage AC networks against both, multiple atmospheric and switching overvoltages as well as Very Fast Transients (VFT). Suitable for instance for the protection of transformers, cables, motors and other medium voltage equipment. For indoor and outdoor installation. Also available with increased creepage distance (MWK..K4). Advantages - Low residual voltage Long protection distance High energy input capacity Stable U-I characteristics even after multiple strokes Proof against ageing Explosion and shatter-resistant design - Pollution resistant and UV-stable Housing resistant to rough handling Maintenance free Stable against shock and vibration High mechanical resistance Temporary overvoltage capability (TOV) - Power frequency versus time characteristic - During 1 second (a: 1.362 x Uc or b: 1.317 x Uc) During 3 seconds (a: 1.337 x Uc or b: 1.287 x Uc) During 10 seconds (a: 1.310 x Uc or b: 1.256 x Uc) a: value tested with a sample that has not been prestressed by any energy input. b: value tetsted with a sample that has been prestressed with a prior energy input according to the operating duty test The values have been determined with a test sample preheated at 60 degrees Celsius according to IEC 60099-4 and refer to an ambient temperature up to 45 degrees Celsius. Guaranteed data Type Ur Rated voltage MWK 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 kV rms 5.0 6.3 7.5 8.8 10.0 11.3 12.5 13.8 15.0 16.3 17.5 18.8 20.0 21.3 22.5 23.8 25.0 26.3 27.5 28.8 30.0 31.3 32.5 33.8 35.0 36.3 37.5 38.8 40.0 41.3 42.5 43.8 45.0 46.30 47.50 48.80 50.00 51.30 52.50 53.80 55.0 UC Continuous operating voltage kV rms 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 Residual voltage (Ures) in kV pk at a specified impulse current Wave 1/.. µs 1 kA p k 10.5 13.1 15.7 18.3 21.0 23.6 26.2 28.8 31.4 34.1 36.7 39.3 41.9 44.5 47.2 49.8 52.4 55.0 57.6 60.3 62.9 65.5 68.1 70.7 73.4 76.0 78.6 81.2 83.9 86.5 89.1 91.7 94.3 97.0 99.6 102.2 104.8 107.4 110.1 112.7 115.2 5 kA p k 12.8 16.0 19.2 22.4 25.6 28.9 32.1 35.3 38.5 41.7 44.9 48.1 51.3 54.5 57.7 60.9 64.1 67.3 70.5 73.7 76.9 80.1 83.4 86.6 89.8 93.0 96.2 99.4 102.6 105.8 109.0 112.2 115.4 118.6 121.8 125.0 128.2 131.4 134.6 137.9 141.0 Wave 8/20 µs 1 0 kA p k 14.5 18.1 21.7 25.3 29.0 32.6 36.2 39.8 43.4 47.1 50.7 54.3 57.9 61.5 65.2 68.8 72.4 76.0 79.6 83.3 86.9 90.5 94.1 97.7 101.4 105.0 108.6 112.2 115.8 119.5 123.1 126.7 130.3 134.0 137.6 141.2 144.8 148.4 152.1 155.7 159.2 1 kA p k 10.4 13.0 15.6 18.2 20.8 23.4 26.0 28.6 31.2 33.8 36.4 39.0 41.6 44.2 46.8 49.4 52.0 54.6 57.2 59.8 62.4 65.0 67.6 70.2 72.8 75.4 78.0 80.6 83.2 85.8 88.4 91.0 93.6 96.2 98.8 101.4 104.0 106.6 109.2 111.8 114.4 5 kA p k 11.6 14.5 17.4 20.3 23.2 26.1 29.0 31.9 34.8 37.7 40.6 43.5 46.4 49.3 52.2 55.1 58.0 60.9 63.8 66.7 69.6 72.5 75.4 78.3 81.2 84.1 87.0 89.9 92.8 95.7 98.6 101.5 104.4 107.3 110.2 113.1 116.0 118.9 121.8 124.7 127.6 Wave 30/60 µs 1 0 kA p k 2 0 kA p k 1 2 5 A p k 2 5 0 A p k 5 0 0 A p k 12.3 13.6 9.0 9.5 9.8 15.4 17.0 11.3 11.9 12.3 18.4 20.4 13.6 14.3 14.8 21.5 23.8 15.8 16.7 17.2 24.6 27.2 18.1 19.0 19.7 27.6 30.6 20.3 21.4 22.1 30.7 34.0 22.6 23.8 24.6 33.8 37.4 24.9 26.2 27.1 36.8 40.8 27.1 28.6 29.5 39.9 44.2 29.4 30.9 32.0 43.0 47.6 31.7 33.3 34.5 46.1 51.0 33.9 35.7 36.9 49.1 54.4 36.2 38.1 39.4 52.2 57.8 38.4 40.5 41.8 55.3 61.2 40.7 42.9 44.3 58.3 64.6 43.0 45.2 46.8 61.4 68.0 45.2 47.6 49.2 64.5 71.4 47.5 50.0 51.7 67.5 74.8 49.7 52.4 54.1 70.6 78.2 52.0 54.8 56.6 73.7 81.6 54.3 57.1 59.1 76.8 85.0 56.5 59.5 61.5 79.8 88.4 58.8 61.9 64.0 82.9 91.8 61.0 64.3 66.4 86.0 95.2 63.3 66.7 68.9 89.0 98.6 65.6 69.0 71.4 92.1 102.0 67.8 71.4 73.8 95.2 105.4 70.1 73.8 76.3 98.2 108.8 72.3 76.2 78.7 101.3 112.2 74.6 78.6 81.2 104.4 115.5 76.9 80.9 83.7 107.5 118.9 79.1 83.3 86.1 110.5 122.3 81.4 85.7 88.6 113.6 125.7 83.7 88.1 91.1 116.7 129.1 85.9 90.5 93.5 119.7 132.5 88.2 92.8 96.0 122.8 135.9 90.4 95.2 98.4 125.9 139.3 92.7 97.6 100.9 128.9 142.7 95.0 100.0 103.4 132.0 146.1 97.2 102.4 105.8 135.0 149.6 99.4 104.8 108.2 1 kA p k 10.2 12.8 15.4 17.9 20.5 23.0 25.6 28.2 30.7 33.3 35.8 38.4 41.0 43.5 46.1 48.6 51.2 53.8 56.3 58.9 61.4 64.0 66.5 69.1 71.7 74.2 76.8 79.3 81.9 84.5 87.0 89.6 92.1 94.7 97.3 99.8 102.4 104.9 107.5 110.1 112.6 The manufacturer reserves the right to change technical data or design without prior notice 04/06 ABB Switzerland Ltd./PTHA 3210.2006-04E email: sales.sa@ch.abb.com / phone: +41 58 585 29 11 ABB Surge arresters MWK Clearances Dimensions (in mm) M 12 x 20 H 57 87 M 12 x 20 105 Insulation data, dimensions and weight Type 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 Creepage distance Flashover distance Recommended clearances (4) E min F min Height H Weight Insulation withstand voltage of empty housing BIL 1.2/50 µs req.values tested acc. to IEC values 50 Hz 60s wet req. values tested acc. to IEC values mm mm mm mm mm kg kV p k kV p k kV rms kV rms 269 269 269 269 269 344 344 418 418 418 418 418 492 492 492 492 492 567 567 567 567 641 641 641 641 641 641 865 865 865 865 865 865 865 865 865 865 865 939 939 939 183 183 183 183 183 223 223 263 263 263 263 263 303 303 303 303 303 343 343 343 343 383 383 383 383 383 383 503 503 503 503 503 503 503 503 503 503 503 543 543 543 51 61 71 81 91 101 112 122 132 142 152 162 172 183 193 203 213 223 233 244 254 264 274 284 294 304 315 325 335 345 355 365 376 385 396 406 416 426 437 446 457 60 71 81 91 101 111 121 131 141 152 162 172 182 192 202 212 222 233 243 253 263 273 283 293 303 313 324 334 344 354 364 374 384 394 404 414 424 435 444 454 465 187 187 187 187 187 227 227 267 267 267 267 267 307 307 307 307 307 347 347 347 347 387 387 387 387 387 387 507 507 507 507 507 507 507 507 507 507 507 547 547 547 1.3 1.4 1.4 1.5 1.5 1.9 1.9 2.2 2.2 2.3 2-3 2.4 2.7 2.7 2.8 2.8 2.9 3.2 3.2 3.3 3.3 3.6 3.6 3.7 3.7 3.8 3.8 4.7 4.7 4.8 4.8 4.9 4.9 5.0 5.0 5.1 5.1 5.2 5.2 5.4 5.4 16.0 20.0 24.0 28.0 32.0 36.0 40.0 44.0 47.9 51.9 55.9 59.9 63.9 67.9 71.9 75.9 79.9 83.9 87.9 91.8 95.8 99.8 103.8 107.8 111.8 115.8 119.8 123.8 127.8 131.8 135.7 139.7 143.7 147.7 151.7 155.7 159.7 163.7 167.7 171.7 175.7 90 90 90 90 90 112 112 132 132 132 132 132 152 152 152 152 152 172 172 172 172 192 192 192 192 192 192 252 252 252 252 252 252 252 252 252 252 252 252 252 252 7.4 9.3 11.1 13.0 14.8 16.7 18.5 20.3 22.2 24.0 25.9 27.7 29.6 31.4 33.3 35.1 36.9 38.8 40.6 42.5 44.3 46.2 48.0 49.9 51.7 53.5 55.4 57.2 59.1 60.9 62.8 64.6 66.5 68.3 70.1 72.0 73.8 75.7 77.5 79.4 81.2 28.0 28.0 28.0 28.0 28.0 36.0 36.0 43.0 43.0 43.0 43.0 43.0 50.0 50.0 50.0 50.0 50.0 56.0 56.0 56.0 56.0 62.0 62.0 62.0 62.0 62.0 62.0 82.0 82.0 82.0 82.0 82.0 82.0 82.0 82.0 82.0 82.0 82.0 82.0 82.0 82.0 (4) National and local requirements have priority and may be used. ABB Switzerland Ltd./PTHA 3210.2006-04E email: sales.sa@ch.abb.com / phone: +41 58 585 29 11 ABB