MM 300 RELAY CONFIRICATION
1.
2.
3.
4.
5.
6.
7.
8.
CONFIRICATION LOSS
NOTE DOWN IP ADDRESS IN THE MOTOR FROM DIRECTORY
BY USING MM300 HAND DISPLAY
ASK PASSWORD- ENTER THE PASSWORD-0000
THEN USE UP AND DOWN RIGHT LEFT FOR MOVING THE CONFIRICATION
THEN SET POINT – CONFIRICATION-COMMUNICATION
THEN COMMUNICATION DATA WILL OPEN
NTP IP ADDRESS – 192.168.128.201
8.1 ETHERNET IP ADDRESS – 192.168.129.127
8.2 ETHERNET SUB MASS – 255.255.252.0
8.3 ETHERNET GATE WAY EDM – 192.168.128.201
CHECK COMMUNICATION OK EVALUATION –ETHERNET
ENTER THE SETTING SAME
AFTER ESTABLISHED THE COMMUNICATION RACKED OUT THE BREAKER AND THEN RACK IN
BREAKER
NOW CHECK THE COMMUNICATION OK INDICATION
NOW PARAMETER SETTING DOWN LOAD IN THE IPCS SYSTEM
IPS SYSTEM OPEN AND ENTER VISTA
OPEN THE MM300 /C/PROGRAM FILES/MM300/BACKUP
HOME PAGE OF ENTER VISTA WILL OPEN
THEN GO TO QUICK CONNECT- THEN WINDOW PAGE WILL OPEN AND ENTER THE ETHERNET
IP ADDRESS AND CONNECT
NOW THE DEVICE HAS ADDED TO THE ONLINE BOX
QUICK CONNECT DEVICE
SELECT OFFLINE FROM THE TRACE BAR AND SELECT OFFLINE
ADD EXITING SETTING FILE – WINDOW WILL BE OPEN
SELECT MY COMPUTER –DATAF-SS503-BACK UP
SELECT-MODULE NO BACK UP FILE- WILL OPEN
NOW THE BACKUP FILE WILL BE ADD IN THE OFFLINE WINDOW
CHECK PANEL NO IN BACK UP FILE
GO TO QUICK CONNECT DEVICE – DEVICE DEFINITION
WE CAN FIND SERIAL NO BMBC- 13008034
SERIAL NO SHOULD BE THE SAME
IF NOT THE SAME CHANGE CHANGE THE SERIAL NO OF BACK UP FILE
WRIGHT CLICK- CHANGE THE SERIAL NO THEN SELECT EDIT SETTINGS FILE PROPERTIES
CHANGE THE NEW SERIAL NO LOCAL TO MATCH SERIAL NO OF DEVICE CONNECT
SETTING OF QUICK CONNECT DEVICE
WRIGHT CLICK THE SETTINGS-FILES ON OFFLINE WINDOW
THEN SELECT SETTINGS FILE TO DEVICE
ONLINE WINDOW DEVICE QUICK CONNECT DEVICE THEN PRESS SEND