MM 300 RELAY CONFIRICATION 1. 2. 3. 4. 5. 6. 7. 8. CONFIRICATION LOSS NOTE DOWN IP ADDRESS IN THE MOTOR FROM DIRECTORY BY USING MM300 HAND DISPLAY ASK PASSWORD- ENTER THE PASSWORD-0000 THEN USE UP AND DOWN RIGHT LEFT FOR MOVING THE CONFIRICATION THEN SET POINT – CONFIRICATION-COMMUNICATION THEN COMMUNICATION DATA WILL OPEN NTP IP ADDRESS – 192.168.128.201 8.1 ETHERNET IP ADDRESS – 192.168.129.127 8.2 ETHERNET SUB MASS – 255.255.252.0 8.3 ETHERNET GATE WAY EDM – 192.168.128.201 CHECK COMMUNICATION OK EVALUATION –ETHERNET ENTER THE SETTING SAME AFTER ESTABLISHED THE COMMUNICATION RACKED OUT THE BREAKER AND THEN RACK IN BREAKER NOW CHECK THE COMMUNICATION OK INDICATION NOW PARAMETER SETTING DOWN LOAD IN THE IPCS SYSTEM IPS SYSTEM OPEN AND ENTER VISTA OPEN THE MM300 /C/PROGRAM FILES/MM300/BACKUP HOME PAGE OF ENTER VISTA WILL OPEN THEN GO TO QUICK CONNECT- THEN WINDOW PAGE WILL OPEN AND ENTER THE ETHERNET IP ADDRESS AND CONNECT NOW THE DEVICE HAS ADDED TO THE ONLINE BOX QUICK CONNECT DEVICE SELECT OFFLINE FROM THE TRACE BAR AND SELECT OFFLINE ADD EXITING SETTING FILE – WINDOW WILL BE OPEN SELECT MY COMPUTER –DATAF-SS503-BACK UP SELECT-MODULE NO BACK UP FILE- WILL OPEN NOW THE BACKUP FILE WILL BE ADD IN THE OFFLINE WINDOW CHECK PANEL NO IN BACK UP FILE GO TO QUICK CONNECT DEVICE – DEVICE DEFINITION WE CAN FIND SERIAL NO BMBC- 13008034 SERIAL NO SHOULD BE THE SAME IF NOT THE SAME CHANGE CHANGE THE SERIAL NO OF BACK UP FILE WRIGHT CLICK- CHANGE THE SERIAL NO THEN SELECT EDIT SETTINGS FILE PROPERTIES CHANGE THE NEW SERIAL NO LOCAL TO MATCH SERIAL NO OF DEVICE CONNECT SETTING OF QUICK CONNECT DEVICE WRIGHT CLICK THE SETTINGS-FILES ON OFFLINE WINDOW THEN SELECT SETTINGS FILE TO DEVICE ONLINE WINDOW DEVICE QUICK CONNECT DEVICE THEN PRESS SEND