Wilo-Comfort Series Pressurisation Unit en Installation and operating instructions 4 523 676-Ed.01 / 2012-05-Wilo Models: P130-WM P135 P135-Midi P160 P180 P230-WM P235 P235-Midi P260 P280 P135-TS P160-TS P180-TS 1) Installation 1.7 1.1 Wholesome water supply can be connected directly to the float valve as back contamination is prevented by the AB airgap within the pressurisation unit. This unit can be connected to systems up to and including CAT5. Location The following should be considered when chosing the position of the pump set: - The area should be dry and well ventilated - There must be protection against frost - There must be adequate drainage facilities - The area must be sucure to prevent unauthorised access/tampering - There must be at least 1 meter clear arean in front of panel and 0.5m at the right hand side to aid maintenance 1.2 Foundations (Floor standing units only) Foundations must be ridged and level, a plinth is not essential though it will assist in keeping the set clear of any damp. When fixing car must be taken not to distort the set by tightening unevenly. 1.3 Wall mounts (Wall mounted units only) Care should be taken to ensure the proposed mounting location is suitable for bearing the load. Appropriate wall fixings should be used in all cases. 1.4 Pipework Pipework connections to the set should be at least the same size as the connections of the set,. (If you require different sizes please contact Wilo UK Ltd for advice) 1.5 Impurities The water should be clean of all impurities. The sand content should not exceed 0.01g/l. The size of any suspended bodies should not be such as to clog or wear the hydraulic components. On dirty water applications a filter must be installed on the suction pipe. 1.6 Electrical connections The installer must check that the available supply is compatible with the voltage and frequency stamped on the CE label. Cable and fuses used for the incoming electricity supply must be rated to cover all pumps running. Earth bonding in line with current IEE regulations is the responsibility of the installer. Water connections Attention! The pressurisation unit must NOT be used to fill the system. The initial filling of the system must be carried out by other means. 2.2 Auto Restart This unit will automatically restart on power up after mains failure of power down. The BMS volt free contact 8 can be configured to mains failure if required. 2.3 Low Pressure (LP This parameter can be altered in the USER menu. If the system pressure drops below the LP setting an audible, visual and volt free alarm activates. If alarm latching is OFF then the alarm will reset once the duty pump has increased the pressure past the LP setting. P180-TS 7.0 6.6 2.7 5.0 OFF OFF P160-TS 4.0 3.6 6.7 5.0 OFF OFF P135-TS 1.0 0.6 2.7 5.0 OFF OFF P280 7.0 6.6 8.7 5.0 OFF OFF P260 4.0 3.6 6.7 5.0 OFF OFF P235-Midi 1.0 0.6 2.7 5.0 OFF OFF P235 1.0 0.6 2.7 5.0 OFF OFF P230-WM 1.0 0.6 2.7 5.0 OFF OFF These values can be altered in USER mode to suit particular site conditions by entering the password, 1234, and following the flow diagram. P180 7.0 6.6 2.7 5.0 OFF OFF See fig 1. - These values can be viewed in VIEW mode by pressing the down arrow and scrolling through the menu. Pump configuration can be altered between Hand-Off-Auto in this mode. P160 4.0 3.6 6.7 5.0 OFF OFF Note: On Twin System Sets each pump if responsible for one system, therefore no standby pump exists for eith system. P135-Midi 1.0 0.6 2.7 5.0 OFF OFF Wilo-Pressurisation Units work on closed loop pressure control via a transducer and electronic controller. The control philosophy will allow the duty pump to run ensuring that the CF pressure (Bar) is constantly met. On two pump systems the duty will rotate between both pumps after each cycle to ensure even wear. If the duty pump fails the standby pump will automatically start P135 1.0 0.6 2.7 5.0 OFF OFF General P130-WM 1.0 0.6 2.7 5.0 OFF OFF 2.1 Abv. CF LP HP ES SF AL Wilo-Pressurisation Units are available in 1 & 2 pump (Duty/Standby_ configurations) Bar Factory Setting Cold fill pressure Low pressure alarm High pressure alarm Excess starts alarm System fill Alarm latching 2) Operation 2.4 High Pressure (HP) 2.9 Pump check This parameter can be altered in the USER menu. All Wilo pressurisation units will automatically check the operation of the pump by running them for a If the system pressure rises above HP setting the short period of time if they have been inactive for a pump stops and an audible, visual and volt free alarm long period of time. activates. This parameter can be changed by following flow diagram. The pump check variables can be altered at time of commissioning. If alarm latching is OFF then the alarm will reset once the system pressure has fallen below the HP setting. 2.10 Alarm latching 2.5 Excess starts (ES) If OFF then all alarms will reset once alarm condition has deactivated. If ON the alarm will activate and stop the pumps if the pump has started too many times within a set If ON then alarms will have to be manually reset via period of time, this will activate an audible, visual and reset button on the front panel. volt free alarm. 2.11 Alarm log The excess starts variables can be altered at time of commissioning. The alarm log, logs the last 30 alarm events and these can be viewed from the VIEW or USER mode. 2.6 System fill (SF) 2.12 Volt free contacts If ON will overide System Leak alarm and allow pump to run for 24 hours or until the CF pressure has been This unit has the facility for 8 volt free alarms for met, then the controller returns back to normal remote monitoring, operation. Note: To be used for initial System Fill during All contacts are rated at 230V 5 Amp max. commissioning. Pump no. 1 fail/trip Normaly open 2.7 Pump trip Pump no. 1 run Normaly open Pump no. 2 fail/trip Normaly open (If fitted) The FLC of the pump is monitored by the controller Pump no. 2 run Normaly open (If fitted) whilst running and if exceeded will stop the pump Low Pressure Normaly open and activate an audible, visual and volt free alarm. On High Pressure Normaly open a 1 pump unit or if both pumps are stopped via a trip Excess Starts Normaly open alarm the boiler interlock volt free alarm is also Low Water Normaly open activated. Boiler Interlock Normaly closed 2.8 Pump fail The unit also has one off change over contact that is The FLC of the pump is monitored by the controller rated for 230V 10Amp max, which can be whilst running and if no current is drawn it will stop programmed at time of commissioning between: the pump and activate an audible, visual and volt free alarm. On a 1 pump unit or if both pumps are - Common pressure alarms stopped via a fail alarm the boiler interlock volt free - Mains failure alarm is also activated. - Common alarm 3) Commissioning 3.1 Pre-commissiong checks • The pressurisation unit is piped up to system and water is available. • The unit is wired up correctly in accordance with wiring diagram, that all connections are tight and the installation has been earth bonded to current regulations. • System has been filled by the system fill function or quick fill loop 3.2 Commissioning Calculate the Cold Fill Pressure (CF): CF= (A + 2.5)/10.2 Bar Where A is the height of the building above the pressurisation unit in meters. In cases of Roof Top plant rooms the minimum CF = 0.8 Bar. Switch pumps(s) into Auto Test High Pressure alarm by reducing the HP setting to 0.5 bar above the CF and running one pump in Hand. Test Low Pressure alarm by switching the pumps OFF, close main discharge valve and slowly drain water from the system via drain cock until the LP setting has been reached. Ensure all settings are returned to normal and all valves are open. Check the units and system pipework for any leaks and flooding. Warning! When running the init in System Fill mode the system leak alarm is switched OFF and the pump will continue to run if there is a leak int he system. Check air pressure in vessel whilst empty of water, air Note - Twin System Units (TS): pressure should be equal to CF pressure, use nitrogen When commissioning any twin system units, the above steps should be followed for both systems to increase pressure if necessary. individually. Turn switch to OFF position. Close all isolating valves. Open any inlet valves to unit and allow break tank to fill ensuring ball float valve closes before water level is 25mm below overflow. If water does reach over flow adjust height of ball float. Prime each pump in turn, by opening the vent plug on each pump. Ensure common main discharge isolating valve is closed. Turn switch to ON position. Key in password, 1234, to enter the Main Menu and scroll through windows entering settings to suit the installation, CF as above, LP should be at least 0.2 bar below CF and HP which should be 0.5 bar below the setting on system safety valve. If the system has not been filled by a quick fill loop the System Fill function can be utilised by selecting ON. This will allow the pump to run for 24 hours or until the CF pressure has been met. 4) Maintenance Wilo pressurisation units are designed to ensure minimum maintenance is required. However routine inspection is necessary and can be carried out by Wilo, please contact our service department for details. Every 6 months: Check unit for leaks. Check for corrosion especially on vessel and ensure water is not present when Schrader valve (on top of vessel) is pressed down. Every 12 months: Check pump set for leaks. Check for corrosion especially on vessel and ensure water is not present when Schrader valve (on top of vessel) is pressed down. Isolate vessel, drain down, check and recharge vessel with nitrogen. Check motor / pump shafts are free to rotate. Check operation of all valves to ensure they have not seized and or letting by. Check operation of pressurisation to ensure it is still working within design parameters. Warning! Wilo would advise that the power to the unit be isolated before any of the above is undertaken, as the pump will start automatically. 5) Written Scheme of Examination Accumulator vessels are classed as a pressure system under the Health and Safety Executive ‘Pressure system safety regulations 2000’. This regulation imposes a legal requirement on the user/maintainer to have the equipment inspected by a competent company on a regular basis as a mandatory duty under parts 7 & 8 of the regulations. A supplier / installer may not fall under the category of user / maintainer, however they are still obliged to inform the user / maintainer of their legal and mandatory duties under the HSE Regulation. Wilo recommend that any vessel over 250 bar / litres should have a working test every 6 months and a thorough examination every 24 months. Bar/Litre = Maximum Working Pressure (Bar) x Volume of vessel (Litres) 6) Warranty This equipment is covered against manufacturing defects for 12 months from date of purchase. This warranty covers the replacement of parts or products, verified as having a manufacturing defect, when inspected in the factory. WILO reserve the right to inspect an installation to verify that the equipment has been installed in accordance with the written instructions. Any modifications to the supplied equipment must be approved in writing; failure to do so will invalidate the warranty Site Visit Before requesting a site visit, the following information must be available to the service team: • Article number of the equipment • A purchase order to cover the work in the event that no manufacturing defect is found. • A site contact name and number • A FULL description of the alleged fault 7) Fault Finding Chart Indication Possible Reason Action Pump/s Don’t Run Power Fail, Pressure not below CFDifferential pressure. Pump Drive fault. Check: Power to the Unit; Discharge valve is open; Pressure settings; Electrical connections. Boiler Not Running. Power Failure, Low Pressure Alarm. Check: for Low Pressure Alarm; Electrical connections. LCD is blank; Power Contrast fault. Connection fault, firmware LED & Backlighting OK lock-up error. Reset the Display by pressing Reset Key for 5seconds. Check ribbon cable connectors. Reset the Control PCB by Power-down & Restart. LCD Blank, No Power Power failure. PCB Failure. LED or backlighting. Check: Mains feed to Unit; PCB fuse F3; Ribbon cable connectors; Electrical connections . Pump Trip Alarm Pump draws excessive current. Reset Alarm. Pump may require servicing. Check: Pump rotates freely; Water flow. Pump Fail Alarm Pump draws zero current. Check: Fuse (replace if required); Wiring; Pump. Low Pressure Alarm System Pressure is below Low Pressure Alarm setting. Check: Pumps operate correctly; System for leaks/flooding; Alarm Latching is OFF. High Pressure Alarm System Pressure is above High Pressure Alarm setting. Check: Pumps operate correctly; ‘Pump Check’ settings (adjust frequency if required); Discharge Isolation valve; Alarm Latching is OFF. System Fill Alarm Pump has run for 24-hours, with System Fill Check: System Pressure. Reset audible alarm. active, & not yet reached CFP. Press Rest Key again to clear Alarm. Switch System Fill ON if required. Service Due Alarm Service Period expired. Ensure that the Pressurisation unit is serviced. Low Water Alarm Water Level in break tank low. Check mains water inlet. Check ball valve operation. Check Float switch operation. High Water Alarm Water level in break tank high. Check ball valve operation. Check float switch operation. Pump Hunting Settings incorrect for system. Pressure Vessel/connection faulty Check: Settings for Minimum Run & Start Delay; Discharge valve; NRVs; Pressure vessel operation & Connection; Transducer wiring Pumps running continuously System Pressure not reaching CF. Check: System for leaks; NRVs; Pumps; Transducer & wiring. Check/Adjust System Leak timer. Transducer Fail Excessive pressure rise or fall; Pressure not Check: Discharge valve open; Transducer Wiring; changing with Pump running Reading Rises & Falls with pressure changes. Parameter Flow Chart - Wilo Comfort Series Pressurisation Unit Wiring Diagram - Wilo Comfort Series Pressurisation Unit