Uploaded by oliver.fmx

Volts amps calculation derate factor

advertisement
Cable Derating Factors - Electrical Engineering
1 of 5
https://www.electrical-engineering.net/cable-derating-factors/
Home » Engineering » Design Consideration » Cable Derating Factors
Cable Derating Factors
March 19, 2021
A conductor section size will carry a rated current without damage to cable
insulation. Cable manufacturer will announce that rated current in their product
catalog. Rated current should be read in conjunction with ambient conditions.
However, site actual conditions are always different from the manufacturer
statements.
In addition, there is a stage during a project cable data is not available. IEC
standards also provide cable ampacity, of course at their standards ambient and
installation conditions.
This article will explain cable derating factors and provide these factors for several
installations.
Contents [ hide ]
• What Affect Cable Ampacity ?
• Cable Derating Factor Due to Ambient Air Temperature
• Cable Derating Factor Due to Ground Temperature
• Cable Derating Factor Due to Ground Thermal Resistivity
• Cable Derating Factor Due to Cable Arrangement
• Most Adverse Installation
• What Affect Cable Ampacity ?
Cable conductors will need to carry current to maintain a surface temperature
according to their insulation material. For example, XLPE insulation cable will allow a
normal operating temperature of 90°C. Adding more layers beyond thermal
insulation i.e. screens, sheathing, armor will reduce rated current at the same
ambient temperature.
See also: Cable Construction
In short, cable construction and surrounding arrangement will affect thermal
dissipation and therefore impact cable carrying current. There are four (4) factors
composed of overall cable derating factor namely ambient or soil temperature, buried
depth, soil thermal resistivity, and cable arrangement.
13/02/2023, 15:27
Cable Derating Factors - Electrical Engineering
2 of 5
https://www.electrical-engineering.net/cable-derating-factors/
• Cable Derating Factor Due to Ambient Air Temperature
The following table will give the conversion factor between different ambient air
temperatures. Note that all IEC cable ratings are based on air temperature of 30 oC
Table 1 – Ambient Air Temperature Derating Other than 30 degree C
See also: Electrical Cable Sizing • Aboveground Cable Derating Calculation •
Underground Cable Derating Calculation • Cable Installation
13/02/2023, 15:27
Cable Derating Factors - Electrical Engineering
3 of 5
https://www.electrical-engineering.net/cable-derating-factors/
• Cable Derating Factor Due to Ground Temperature
The following table will give conversion factor between different ground
temperatures.
Table 2 – Ambient Ground Temperature Derating Other than 20 degree C
• Cable Derating Factor Due to Ground Thermal Resistivity
Cables that are laid in the ground need to dissipate heat into their surroundings. The
thermal conductivity
of soil varies considerably due to soil characteristics i.e. near a water source, coastal
areas, dry soil, desert sand.
The higher the value of thermal resistivity the more difficult it becomes to remove the
heat from the cable.
13/02/2023, 15:27
The following table will give conversion factor between different ground thermal
resistivities.
Table 3 – Soil Thermal Resistivity Derating Other than 2,5 K*m/W
• Cable Derating Factor Due to Cable Arrangement
The cable manufacturer will provide derating factors for several possibilities i.e.,
number of installed cables in a layer, number of layers, cable spacing horizontally
and vertically. The actual condition is a combination of cable installation and cable
manufacturer factors are not sufficient.
International standards (IEC, ERA, etc) has developed to cover this concern.
Likewise, standards introduced deduction factor for a group of cables in cable ladder
or inside duct bank, see detail in IEC 60364-5-52. •
• Most Adverse Installation
It is commonplace that electrical cable experiences various different arrangements
and ambient conditions along its route. The environment that creates the most
derating factor of the rated current should be taken and used for the whole cable
route. However, this requirement can normally neglected if the length of the cable
route is less than 0,35 m (IEC 60364-5-52) or 6 ft (IEEE Std 141).
Design Consideration
Cable
MV Variable Speed Drive Standards
Voltage Drop Calculation
Cable Derating Factors - Electrical Engineering
5 of 5
https://www.electrical-engineering.net/cable-derating-factors/
Shock Risk Assessment
Arc Flash Calculator
Conduit Fill Chart
Cable Short Circuit Rating
Aboveground Cable Derating Calculation
Underground Cable Derating Calculation
Voltage Drop Calculator
Conduit Fill Calculation
Cable Construction
Usage Terms
Privacy
Contact Us
2023 © Electrical-Engineering.net
13/02/2023, 15:27
Download