03/22/2021 ICP SCCR & UL 508A Supplement SB Joe Pavia, P.E. Field Application Engineer Bussmann division Contact info: Phone: 317-665-1956 Email: joempavia@eaton.com © 2020 Eaton. All rights reserved.. 3 www.menti.com Code: 50 10 79 Passing the UL508A MTR © 2020 Eaton. All rights reserved.. 4 4 www.menti.com Code: 36 79 81 8 Agenda • Industrial Control Panel SCCR & UL 508A Supplement SB • • • • • NEC Requirements Definitions Determining component ratings Use of current limiting devices Interactive session on analyzing the assembly SCCR of example control panels. © 2020 Eaton. All rights reserved.. 5 5 1 03/22/2021 www.menti.com Code: 36 79 81 8 NEC Industrial Control Panels & Industrial Machinery © 2020 Eaton. All rights reserved.. 6 6 www.menti.com Code: 36 79 81 8 What is short-circuit current rating (SCCR)? NEC Article 100 Definition Short-Circuit Current Rating. The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding defined acceptable criteria. Hazards of insufficient SCCR Available fault current: 20 kA • • • Shock: Enclosure becomes energized from conductors pulling away from terminations Fire: Explosive power blows off door exposing flames and molten metal to exterior Projectile (shrapnel): Enclosure door explosively blows open emitting failing device debris SCCR: 5 kA © 2020 Eaton. All rights reserved.. 7 7 Another misapplication YouTube video https://www. youtube.com /watch?v=8a 9B9jgVmys © 2020 Eaton. All rights reserved.. 8 8 2 03/22/2021 Section 110.10, Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics Slide: 9 © 2021 Eaton. All rights reserved.. 9 www.menti.com Code: 36 79 81 8 Industrial control panel definition NEC Article 100 Definition Industrial Control Panel. An assembly of two or more components consisting of one of the following: (1) power circuit components only, such as motor controllers, overload relays, fused disconnect switches, and circuit breakers; (2) control circuit components only, such as push buttons, pilot lights, selector switches, timers, switches, and control relays; (3) a combination of power and control circuit components. The industrial control panel does not include the controlled equipment. 409.110(4) Exception to (4): Short-circuit current rating markings are not required for industrial control panels containing only control circuit components. © 2020 Eaton. All rights reserved.. 10 10 www.menti.com Code: 36 79 81 8 Industrial control panels Code requirements 409.110(4) • SCCR marked on nameplate “plainly visible” • Note: UL 508A currently requires the nameplate marking to be visible without opening the door or cover of the enclosure. 409.22(A) • Do not install when SCCR is less than the available fault current 409.22(B) • Determine available fault current • Date and documentation to AHJ © 2020 Eaton. All rights reserved.. 11 11 3 03/22/2021 www.menti.com Code: 36 79 81 8 Industrial machinery definition NEC 670.2 Definition Industrial Machinery (Machine). A power-driven machine (or a group of machines working together in a coordinated manner), not portable by hand while working, that is used to process material by cutting; forming; pressure; electrical, thermal, or optical techniques; lamination; or a combination of these processes. It can include associated equipment used to transfer material or tooling, including fixtures, to assemble/ disassemble, to inspect or test, or to package. [The associated electrical equipment, including the logic controller(s) and associated software or logic together with the machine actuators and sensors, are considered as part of the industrial machine.] For Machine assembly requirements see: NFPA 79 Electrical Standard for Industrial Machinery © 2020 Eaton. All rights reserved.. 12 12 Industrial machinery Code requirements 670.3(A)(4) • SCCR marked on nameplate and “plainly visible” • Note: NFPA 79 requires the nameplate to be attached to the outside of the enclosure, or on the machine immediately adjacent to the enclosure 670.5(1) • Do not install when SCCR is less than the available fault current 670.5(2) • Field marked with maximum available fault current © 2020 Eaton. All rights reserved.. 13 13 How much SCCR is necessary? Equipment short-circuit current rating must be equal to or greater than the available short-circuit current at the location where the control panel is installed. Switchboard required to be marked/documented with available fault current per NEC 110.24 switchboard transformer switchboard panelboards panelboards x x switchboard x x x x x x x x x All Switchboards, Switchgear & Panelboards required to be field marked with the available fault current per 2020 NEC 408.6 © 2020 Eaton. All rights reserved.. x Use utility worst case if available versus specific transformer = machine/equipment location 14 14 4 03/22/2021 Setting an SCCR requirement SCCR is based on the available fault current of each machine (use FC2). May consider relocation of equipment and impact on SCCR. SCCR Min: 22,000 amps short-circuit current: 18,450 amps switchboard switchboard switchboard panelboards panelboards x x transformer SCCR Min: 35,000 amps short-circuit current: 33,302 amps x x x x x x x x short-circuit current: 38,499 amps SCCR Min: 42,000 amps x short-circuit current: 8,944 amps short-circuit short-circuit short-circuit short-circuit short-circuit short-circuit short-circuit current: 7,634 current: 11,093 current: 3,021 current: 19,954 current: 13,027 current: 15,732 current: 24,395 amps amps amps amps amps amps amps SCCR Min: 10,000 amps SCCR Min: 10,000 amps x SCCR Min: 18,000 amps SCCR Min: 5,000 amps SCCR Min: 22,000 amps SCCR Min: 18,000 amps SCCR Min: 18,000 amps SCCR Min: 30,000 amps © 2020 Eaton. All rights reserved.. = machine/equipment location 15 15 Determining the equipment SCCR 1. Short-circuit testing in high power laboratory • Tested and listed to UL product standard 2. Analysis methods (for device or apparatus) • Example: UL 508A Industrial Control Panel product standard, Supplement SB • Or other approved method (Engineering Method) Paul P. Gubany Center for High Power Technology © 2020 Eaton. All rights reserved.. 16 16 Definitions UL 508A SB Industrial Control Panels © 2020 Eaton. All rights reserved.. 17 17 5 03/22/2021 Industrial control panel circuit types UL 508A Definitions Exception: SCCR does NOT apply to: 2.41 POWER CIRCUIT – Conductors and components of branch and feeder circuits. 1) 2.11 CONTROL CIRCUITS – A circuit that carries the electric signals directing the performance of a controller, and which does not carry the main power circuit. A control circuit is, in most cases, limited to 15 amperes. • SCCR applies only to POWER CIRCUIT devices, not CONTROL CIRCUIT devices (SB4.1.1 and SB4.2.1) Transformers, reactors, CT’s, drytype capacitors, resistors, varistors, one-port SPDs and voltmeters. 2) Wye-delta “S” contactor 3) Cord & plug connected enclosure AC 4) Wiring ferrules used for internal wiring 5) Components on the load side of a variable speed drive. (SB4.2.1 Exceptions) © 2020 Eaton. All rights reserved.. 18 18 Industrial control panel circuit locations UL 508A Definitions Feeder circuits 2.3 BRANCH CIRCUIT – The conductors and components following the last overcurrent protective device protecting a load. Branch circuits 2.19 FEEDER CIRCUIT – The conductors and circuitry on the supply side of the branch circuit overcurrent protective device. • 1 Branch and feeder power circuits supply external loads: motors, lighting, heating, appliances, convenience receptacles, etc. © 2020 Eaton. All rights reserved.. 19 19 Industrial control panel transformer types UL 508A Definitions 2.42 POWER TRANSFORMER – A transformer Power Transformer Control Transformer whose secondary winding supplies power to loads or a combination of loads and control circuit devices operating at the secondary voltage. 2.12 CONTROL TRANSFORMER – A transformer whose secondary supplies power to control circuit devices only (excluding loads).. • Power transformers feed external loads and secondary devices supplying loads are considered in panel SCCR • Control transformers and secondary control devices are not considered in panel SCCR External Control Load Circuits Considered in SCCR © 2020 Eaton. All rights reserved.. NOT Considered in SCCR 20 20 6 03/22/2021 Example panel SCCR also applies to 1) The branch circuit OCPD protecting the common control circuit or the primary of a control transformer or power supply. 2) The OCPD protecting control circuits supplied from the load side of motor branch circuits. Feeder circuits Branch circuits Exception: Secondary circuits operating at 24 vdc maximum and supplied from a source with a maximum output power of 100 VA, shall be considered control circuits. See SB3.2.1 © 2020 Eaton. All rights reserved.. 21 21 Slash voltage ratings NEC Requirement 240.85 Applications. A circuit breaker with a straight voltage rating, such as 240V or 480V, shall be permitted to be applied in a circuit in which the nominal voltage between any two conductors does not exceed the circuit breaker’s voltage rating… A circuit breaker with a slash rating, such as 120/240V or 480Y/277V, shall be permitted to be applied in a solidly grounded circuit where the nominal voltage of any conductor to ground does not exceed the lower of the two values of the circuit breaker’s voltage rating and the nominal voltage between any two conductors does not exceed the higher value of the circuit breaker’s voltage rating. All fuses are straight voltage rated © 2020 Eaton. All rights reserved.. 22 22 480V 480/277 Slash rating examples 277 V C 480 V C 480 V 480 V A G B Solidly grounded wye A G N 277 V 480 V C Corner grounded B delta C 480 V 480 V A G High B resistance grounded N wye © 2020 Eaton. All rights reserved.. A Ungrounded delta B 23 23 7 03/22/2021 Nameplates for Industrial Control Panels UL 508A Nameplate NEC 409.110 Nameplate 1. 1. Manufacturer’s Name 2. Supply Voltage, # Phases, Frequency & Full load current Manufacturer’s Name 2. Complete electrical per 49.1 a) Voltage Rating b) Total FLA c) HP/A Largest Motor d) # Phases e) Frequency 3. Marked if more than one Supply 3. Short Circuit Current Rating 4. Short Circuit Current Rating 4. Field wiring diagram number when required load ratings 5. Field wiring diagram number when required load ratings 5. Factory identification 6. Enclosure Type rating 6. Enclosure Type rating © 2020 Eaton. All rights reserved.. 24 24 UL 508A Nameplates Supply Voltage • 49.1 The input terminals intended to be connected to each source of supply shall be rated in volts, total full-load amperes, ampere or horsepower rating of the largest motor (when multiple loads are controlled), number of phases when other than single phase, and the frequency. • 49.6 The voltage rating of an industrial control panel shall not exceed the voltage rating of any component connected to the source of supply. When an industrial control panel contains components marked with a slash voltage rating, such as 120/240, 480Y/277, or 600Y/347, the voltage rating of the industrial control panel shall be: • a) The complete slash voltage rating, when intended for connection to the higher voltage; or • b) Not more than the lower voltage rating. © 2020 Eaton. All rights reserved.. 25 25 Determining overall panel SCCR © 2020 Eaton. All rights reserved.. 26 26 8 03/22/2021 Overview of component SCCRs Short-circuit current ratings Panel SCCR is based on: Drives, soft-starters, contactors, overloads, disconnects, fuseholders, busbars, contactors, receptacles, multi-wire lugs, power distribution blocks, etc. • Power circuit component SCCRs • Overcurrent protective device interrupting ratings • Includes those supplying common control, control transformer, and power supply Interrupting ratings UL Class fuses, UL 489 molded case circuit breakers © 2020 Eaton. All rights reserved.. 27 27 Per SB4.4: Three Step Method for calculating SCCR Per SB4.4: 1. OCPD Interrupting Rating 2. Component SCCR with OCPD protection 3. Increasing Branch circuit SCCR with C.L. Feeder device © 2020 Eaton. All rights reserved.. 28 28 Step #1 Determine SCCR of each branch circuit Per SB4.4: 1. Identify OCPD interrupting rating a) Identify the lowest OCPD I.R. in the feeders and branch circuits. 1 b) The panel can not have a SCCR higher than the lowest OCPD I.R. What is the SCCR Goal??? © 2020 Eaton. All rights reserved.. 29 29 9 03/22/2021 Step #2 Determine SCCR of each branch circuit Per SB4.4: 2. Determine the SCCR of each Component with its associated OCPD in the branch circuit. a) Identify component SCCRs of each branch circuit device (SB4.2.2) 1 © 2020 Eaton. All rights reserved.. 30 30 Step #2 SCCR of individual power circuit components UL 508A Requirement SB4.2.2 The short circuit current rating of a feeder or branch circuit component shall be established by one of the following methods: a) The short circuit current rating marked on the component or on instructions provided with the component; 1 b) The short circuit current rating determined by the voltage rating of the component and the assumed short circuit current from Table SB4.1; or c) The short circuit current rating for a component that has been investigated in accordance with the performance requirements, including short circuit test requirements for standard fault currents or high fault currents specified in the associated product standard, and described in the manufacturer’s Procedure. Technical Literature, White Papers, Catalogs, Manufacturer Website – INFORMATION ONLY! © 2020 Eaton. All rights reserved.. 31 31 Step #2 Component short-circuit current ratings SB4.2.2 a) All components tested with an upstream OCPD to obtain compliant SCCR SCCR details: • Component SCCR value • Upstream OCPD type and size • Other conditions • Standard or High Fault SCCR © 2020 Eaton. All rights reserved.. 32 32 10 03/22/2021 Step #2 Component SCCR – standard fault SB4.2.2 b) UL 508A Table SB4.1 • Minimum rating for component when tested with OCPD • Found on product label, instruction sheet or UL website • Default rating in Table SB4.1 can be used if unknown © 2020 Eaton. All rights reserved.. 33 33 Step #2 Component SCCR – high fault SB4.2.2 c) Cautionary marking required per SB5.2 • Optional higher rating • Specifies maximum amp rating of OCPD • Found on product label or instruction sheet (not UL website) WARNING: Risk of Fire or Electric Shock – The opening of the branch-circuit protective device may be an indication that a fault current has been interrupted. All current-carrying parts and other components protected by this device should be examined and replaced if damaged. If burnout of a current element of an overload relay occurs, the complete overload relay must be replaced. • Must mark panel (component) accordingly © 2020 Eaton. All rights reserved.. 34 34 Step #2 Component SCCR – high fault examples PDB in the Feeder Circuit must be Listed to UL1953 © 2020 Eaton. All rights reserved.. 35 35 11 03/22/2021 Step #2 SCCR of individual power circuit components UL 508A Requirement SB4.2.3 A high fault short circuit current rating for a feeder or branch circuit component, as specified in SB4.2.2 (a) or (c), shall only be used as the short circuit current rating of the component when the specified branch circuit protective device is provided. Replace RK5 with RK1 Exception No. 1: • • A fuse with equal to or less than peak letthru current can be substituted for the fuse specified in the SCCR Replace RK1 with J Equal or Better See Table SB4.2 for peak let-through of fuses Replace J with Class CF CUBEFuse © 2020 Eaton. All rights reserved.. 36 36 Step #2 SCCR of individual power circuit components UL 508A Requirement SB4.2.3 A high fault short circuit current rating for a feeder or branch circuit component, as specified in SB4.2.2 (a) or (c), shall only be used as the short circuit current rating of the component when the specified branch circuit protective device is provided. Exception No. 2: • If the panel is marked according to SB5.1.2, the specified branch circuit protection can be provided in the field. Can be provided in the field if marked according to SB5.1.2 ABC Company Machine XYZ Serial No: 1234567 123 Main St, City, ST 01234 Model: XZY123 480/277 Max HP Volts Phase 50 3 FLA Frequency 60Hz SCCR SYM: 65kA WHEN FED BY 200 AMP CLASS J FUSE.. 124 UL © 2020 Eaton. All rights reserved.. 37 37 Step #2 SCCR of individual power circuit components UL 508A Requirement SB4.2.3 A high fault short circuit current rating for a feeder or branch circuit component, as specified in SB4.2.2 (a) or (c), shall only be used as the short circuit current rating of the component when the specified branch circuit protective device is provided. Equal or Better 1 1 Exception No. 3: • • A listed current-limiting breaker with equal to or less than peak let-thru and I2t can be substituted for the specified breaker per the SCCR, provided the specified breaker is current-limiting. Can be replaced if both marked current-limiting and equal to or better performance See circuit breaker manufacturer let-through charts © 2020 Eaton. All rights reserved.. 38 38 12 03/22/2021 Step #2 SCCR of individual power circuit components UL 508A Requirement SB4.2.3 A high fault short circuit current rating for a feeder or branch circuit component, as specified in SB4.2.2 (a) or (c), shall only be used as the short circuit current rating of the component when the specified branch circuit protective device is provided. Exception No. 4: • A current limiting fuse is permitted to be substituted for a non-current limiting OCPD provided the interrupting rating is equal to or greater and the ampacity is equal to or less than the specified overcurrent protective device. Allows current-limiting fuse to replace non-current limiting OCPD Previously was any currentlimiting overcurrent device now only current limiting fuse. © 2020 Eaton. All rights reserved.. 39 39 Step #2 NEW - High fault SCCR for bus bar UL 508A Requirement NEW • Bus bar systems SB4.2.4 A high fault short circuit current rating of a bus bar can additionally be determined by one of the following methods: a) Use of a bus bar system, that complies with the Standard for Industrial Control Equipment, UL508, with the short circuit current rating marked on the component or on instructions provided with the component and installed according to the installation instructions provided by the product; or • Construction method based on Appendix D b) Use of a bus bar system constructed with electrical ratings and short circuit current rating in accordance with Appendix D. • For custom bus bar configurations © 2020 Eaton. All rights reserved.. 40 40 Step #3 Determine SCCR of each branch circuit Current-limiting fuse Per SB4.4: 3. Determine if the Branch component SCCR can be raised using the Current Limiting OCPD in the feeder. 1 a) Determine if branch component SCCR can be raised using a current limiting OCPD in the feeder circuit (SB4.3) © 2020 Eaton. All rights reserved.. 41 41 13 03/22/2021 Step #3 Raise branch SCCR using current-limitation Methods to raise branch SCCR utilizing upstream components in the feeder (SB4.3) 1. Power transformer (SB4.3.1) Feeder circuits Branch circuits 2. Current-limiting circuit breaker (SB4.3.2) 3. Current-limiting fuse (SB4.3.3) 1 4. Current-limiting breaker or currentlimiting fuse supplied in the field when the panel is marked per SB5.1.3 (SB4.3.4) © 2020 Eaton. All rights reserved.. 42 42 Step #3 Circuits supplied by power transformer Per SB4.3.1: For circuits supplied by power transformer with isolated secondary, SCCR shall be one of the following: a) The interrupting rating of the primary side OCPD if the component SCCR’s or interrupting ratings are greater than or equal to the secondary short circuit current calculated or defined in Table SB4.3 or SB4.4. b) The lowest SCCR or interrupting rating of the downstream devices if the secondary short-circuit current is greater than any of the downstream component SCCRs or interrupting ratings Primary OCPD IR Feeder Short-circuit current Branch IR Branch Component SCCR Branch Applies to feeder and branch circuits External Load © 2020 Eaton. All rights reserved.. 43 43 Step #3 Circuits supplied by power transformer example • Single phase 3 kVA XFMR with 120 V secondary • Maximum secondary short-circuit current = 1,200A • Downstream OCPD IR/Component SCCR = 10 kA/5 kA • Primary side OCPD IR = 200 kA • SCCR = 200 kA (primary OCPD IR) since 1.2 kA < 5 kA 200 kA IR: 200 kA Short-circuit current = 1.2 kA IR: 10 kA Table SB4.3 Single phase transformer secondary available short circuit currents (Amps) SCCR: 5 kA External Load © 2020 Eaton. All rights reserved.. 44 44 14 03/22/2021 Step #3 Current-limiting fuse in the feeder 200A Per SB4.3.3: For branch circuits supplied by a Class CC, G, J, L, RK1, RK5, or T, SCCR shall be determined by: 1. Feeder IR Determine the peak let-through current at a selected available short-circuit current from Table SB4.2 2. If peak let-through current is less than the component SCCR, adjust the component SCCR to the selected available shortcircuit current Feeder Let-thru current @ short-circuit current Branch IR 3. Compare adjusted component SCCR to branch IR/SCCR – the lower value is the branch circuit SCCR. Branch 1 Component SCCR © 2020 Eaton. All rights reserved.. Branch 45 45 Step #3 UL508A Table SB4.2 • Identifies peak let-through current and I2t let-through at 50kA, 100kA and 200kA • Can not use manufacturer’s published data or Irms letthrough per UL 508A. Excerpt from Table SB4.2 © 2020 Eaton. All rights reserved.. 46 46 Step #3 Current-limiting fuse in the feeder 200A IR: 14 kA 14 kA 1 Fuse Fuse Let-thru 30 kA @200kA Fuse Fuse Let-thru 20 kA @100kA Excerpt from Table SB4.2 Scenario 2 IR: 300 kA Fuse IR: 300 kA Fuse Scenario 1 200 kA IR: 200 kA 100 kA SCCR: SCCR: 100 kA SCCR: 22 kA (w/Class CC/J fuse) 22 kA © 2020 Eaton. All rights reserved.. Ip at 200kA = 30kA 47 47 15 03/22/2021 Step #3 Current-limiting feeder device supplied in the field Marking: • Type and size of feeder protection required Machine XYZ ABC Company Serial No: 1234567 SCCR: 100 kA rms sym. Model: XZY123 when fedPhase by 3max 200 A Frequency Volts 480/277 60Hz MaxClass HP FLA 1245 J50fuse otherwise SCCR SYM: 65kA WHEN FED BY 200kA AMP CLASS J FUSE.. Fuse Fuse SB4.3.4 The specified circuit breaker marked “current limiting” or current-limiting Class of fuse supplied in the feeder circuit that limits the peak let-through current available in accordance with SB4.3.2 and SB4.3.3 is able to be provided in the field when the panel is marked in accordance with SB5.1.3. Fuse UL 508A Requirement Can be provided in the field if marked according to SB5.1.3 123 Main St, City, ST 01234 UL Example label Benefits: 1) Reduces enclosure size and cost 2) Eliminates exposure to live parts in panel 3) Upstream overcurrent device can be used for arc flash protection © 2020 Eaton. All rights reserved.. 48 48 Next Gen CCP2 – Class CF CCP Finger safe Lockout/tagout IP20 finger safe with 10 AWG or larger wire Padlockable handle accepts standard ¼” lock or hasp lock Lug options Handle mechanism Available with single box lug with expanded wire torque ratings & multiwire accessory Accepts the addition of a rotary or flange through the door operator Compact size Fuse indication 20% less footprint than MCCB and 2/3 of the size of a standard fusible switch For both AC and DC voltages Switch interlock Fuse rejection Built-in switch interlock prevents removing the fuse under load Ampacity rejecting CUBEFuse rating greater than the switch rating Note: Blue indicates new features from previous version © 2020 Eaton. All rights reserved.. 49 49 CCP size comparison Fuse indication Local open fuse indication for both AC and DC Lockout/tagout ¼” LOTO on handle mechanism Fuse interlock Built-in fuse interlock helps prevent removing fuse under load 200A fuse switch 30A Class CC fuse switch 100A fuse switch © 2020 Eaton. All rights reserved.. 50 50 16 03/22/2021 Compact Circuit Protector handle mechanism Rotary Features Flange Firm snapping action Distinct feel for confidence of ON/OFF status Compact No footprint impact; allows user to maintain compact size CABLE Easy access to fuses Speeds fuse replacement Easy mounting connection Four screws secure mechanism UL listed UL Recognized accessory ROD © 2020 Eaton. All rights reserved.. 51 51 Identify OCPD interrupting ratings Per SB4.4: 1. Identify the interrupting rating for each overcurrent protective device. 2. Determine the SCCR of each branch circuit & Feeder component. 1 3. Increase the Branch Component with a C.L. Feeder OCPD 4. The panel SCCR is the lowest value from steps 1-3. © 2020 Eaton. All rights reserved.. 52 52 Determine SCCR of the branch & feeder components Per SB4.4: 1. Identify the interrupting rating for each overcurrent protective device. 2. Determine the SCCR of each branch circuit & Feeder component. 1 3. Increase the Branch Component with a C.L. Feeder OCPD 4. The panel SCCR is the lowest value from steps 1-3. © 2020 Eaton. All rights reserved.. 53 53 17 03/22/2021 Increase Branch component using C.L. in Feeder Per SB4.4: Current-limiting fuse 1. Identify the interrupting rating for each overcurrent protective device. 2. Determine the SCCR of each branch circuit & Feeder component. 1 3. Increase the Branch Component with a C.L. Feeder OCPD 4. The panel SCCR is the lowest value from steps 1-3. © 2020 Eaton. All rights reserved.. 54 54 Determine overall panel SCCR Per SB4.4: Current-limiting fuse 1. Identify the interrupting rating for each overcurrent protective device. 2. Determine the SCCR of each branch circuit & Feeder component. 1 3. Increase the Branch Component with a C.L. Feeder OCPD 4. The panel SCCR is the lowest value from steps 1-3. © 2020 Eaton. All rights reserved.. 55 55 Examples and practice © 2020 Eaton. All rights reserved.. 56 56 18 03/22/2021 www.menti.com Code: 36 79 81 8 Practice 1 – What is the panel SCCR? G 1 A 1 E 1 C D F B A 100 A Circuit Breaker IR = 35 kA at 480V B Power Distribution Block Default SCCR = 10 kA C 15 A Class CC Fuse & Holder IR = 200 kA at 600V SCCR (Holder) = 200 kA D 10 HP Drive SCCR = 100 kA at 480V with 15 A or less Class CC Fuse E 15 A Breaker IR = 14 kA at 480V F 20 A Contactor SCCR = 25 kA at 480V with 30 A or less breaker G 6 A Miniature Breaker IR = 10 kA at 480/277V © 2020 Eaton. All rights reserved.. 57 57 www.menti.com Code: 36 79 81 8 Practice 1 – What is the panel SCCR? The panel SCCR is: 10 kA 10 kA 480/277 351kA 1 14 kA 1 200 kA 100 kA 10 kA Step #1 – OCPD IR 10kA Step #2 – Component SCCR w/ OCPD 10kA 25 kA Step #3 – C.L. Feeder OCPD increasing Branch component © 2020 Eaton. All rights reserved.. 58 58 www.menti.com Code: 36 79 81 8 Practice 2 – What is the panel SCCR? G 1 A 1 E F 1 C D B © 2020 Eaton. All rights reserved.. A 100 A Eaton EGH Circuit Breaker IR = 65 kA at 480V B Power Distribution Block SCCR = 65 kA at 480V with max 125 A EGH (#10 AWG or larger wire) C 15 A Class CC Fuse & Holder IR = 200 kA at 600V SCCR (Holder) = 200 kA D 10 HP Drive SCCR = 100 kA at 480V with 15 A or less Class CC Fuse E 15 A Breaker IR = 14 kA at 480V F 20 A Contactor SCCR = 25 kA at 480V with 30 A or less breaker G 6 A Class CC Fuse & Holder IR = 200 kA at 600V SCCR (Holder) = 200 kA 59 59 19 03/22/2021 www.menti.com Code: 36 79 81 8 Practice 2 – What is the panel SCCR? The panel SCCR is: 200 kA 14 kA 480V 651kA 1 14 kA 1 200 kA 100 kA 65 kA Step #1 – OCPD IR 14kA Step #2 – Component SCCR w/ OCPD 25kA 25 kA Step #3 – C.L. Feeder OCPD increasing Branch component © 2020 Eaton. All rights reserved.. 60 60 www.menti.com Code: 36 79 81 8 Practice 3 – What is the panel SCCR? G A E F C D B A 100 A CUBEFuse and CCP2 IR = 300 kA, SCCR = 200 kA Ip let-through = 14kA at fault of 200kA B Power Distribution Block SCCR = 200 kA at 600V with max 200A Class J fuse (#12 AWG or larger wire) C 15 A CC Fuse & Holder IR = 200 kA SCCR (Holder) = 200 kA D 10 HP Drive SCCR = 100kA at 480V with 15 A Class CC Fuse E 15 A CUBEFuse and CCP2 IR = 300kA, SCCR = 200 kA F 20 A Contactor SCCR = 100 kA at 480V with 20 A max Class J fuse (Class CF or CC) G 6 A Class CC Fuse & Holder IR = 200 kA at 600V SCCR (Holder) = 200 kA © 2020 Eaton. All rights reserved.. 61 61 www.menti.com Code: 36 79 81 8 Practice 3 – What is the panel SCCR? The panel SCCR is: 200 kA 300 kA 300 kA 200 kA 100 kA 200 200 kA 200 kA 480V Step #1 – OCPD IR 200kA Step #2 – Component SCCR w/ OCPD 100kA Step #3 – C.L. Feeder OCPD increasing Branch component 200kA 200 100 kA © 2020 Eaton. All rights reserved.. 62 62 20 03/22/2021 Keys to achieve high assembly SCCR • Branch and feeder circuit OCPD with high interrupting rating • Branch and feeder components with high fault SCCR • Increase branch circuit component SCCR using currentlimiting feeder OCPD’s or transformer rules © 2020 Eaton. All rights reserved.. 63 63 Compliance is easy • Design and proposal • Ask for customer SCCR requirements • Determine a standard SCCR level – 65 kA possibly • Review and analysis • Look for the lowest rated SCCR or interrupting rating • Utilize high fault SCCR components and current limiting OCPDs for the highest SCCR © 2020 Eaton. All rights reserved.. 64 64 Additional resources and tools • 2017 SCCR Code changes booklet • Fault current calculator – FC2 • Fuseology Handbook • SPD – Electrical Protection Handbook • SCCR Protection Suite • SCCR and IR checklist • Available in the app store or play store © 2020 Eaton. All rights reserved.. 65 65 21 03/22/2021 Questions? Joe Pavia, P.E. Field Application Engineer JoemPavia@Eaton.com 317-665-1956 © 2018 Eaton. All rights reserved.. 66 © 2020 Eaton. All rights reserved.. 67 66 67 22