Cable connection Guideline

advertisement
1. FOR CABLE LUG HOLE SIZE =16.2
2. FOR CABLE LUG HOLE SIZE <16.2
RMU BUSHING
COPPER CONTACT SURFACE
OF BUSHING
REDUCER STUD
(2REA024265P0001)
RMU BUSHING
COPPER CONTACT SURFACE
OF BUSHING
SILVER PLATED
COPPER WASHER
(2REA026992P0001)
CABLE LUG (TINNED)
M16 CUP WASHER
(9ADJ490084P0213)
M16x30 MS HEX BOLT
(9ABA450023P0462)
TIGHTNING TORQUE : 50 Nm
CABLE LUG (TINNED)
M10 CUP WASHER
(9ADJ490084P0210)
M10 MS HEX NUT
TIGHTNING TORQUE : 30 Nm
(9ABA450025P5020)
NOTES : 1. CABLE LUG SHOULD BE CLEANED PRIOR TO MAKING CONNECTION.
2. COPPER WASHER SHOULD BE DIRECTLY IN CONTACT WITH BUSHING CONTACT SURFACE.