A M E R I C A N N A T I O N A L S T A N D A R D NECA 100-2006 xxAF yyAT zzA Symbols for Electrical Construction Drawings Published by National Electrical Contractors Association Table of Contents Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii 1. 1.1 1.2 1.3 Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Symbols Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Symbols Not Included . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Regulatory and Other Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 2. 2.1 2.2 2.3 Purpose of Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Organization of this Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Alternate Safety Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Referrences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 3. 3.1 3.2 3.3 3.4 Drafting Practices for Electrical Construction Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Symbol Design and Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 General Drafting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 CADD Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Electrical Construction Drawing Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Contents for Symbol Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Annex A: Alternate Fire Safety Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45 Annex B: Typical Risers, One-Line Diagrams, and Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48 Annex C: Reference Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56 i ■ 1. Scope This publication describes graphic symbols used to represent electrical wiring and equipment on construction drawings. In this publication, the term “electrical” is used to include electrical, electronic, and communications systems covered by the National Electrical Code (NFPA 70). This publication also summarizes recommended drawing practices for electrical construction drawings. 1.1 Symbols Included This standard is limited to North American symbols for electrical wiring and equipment. 1.2 1.3 Regulatory and Other Requirements a) All information in this publication is intended to conform to the National Electrical Code (ANSI/NFPA 70). b) General requirements for installing electrical products and systems are described in NECA 1, Standard Practices for Good Workmanship in Electrical Contracting (ANSI). Other National Electrical Installation Standards provide additional guidance for installing particular types of electrical products and systems. A complete list of NEIS is provided in Annex C. Symbols Not Included Symbols from publications of the International Electrotechnical Commission (IEC) are not included in this standard. Symbols for equipment and systems not covered by the NEC are not included in this standard. 1 ■ 2. Purpose of Symbols Symbols are a shorthand way of showing the locations, types, and sizes or ratings of electrical wiring Table 1: Symbol Groups Group 1.0 1.1 1.2 2.0 2.1 2.2 2.3 2.4 3.0 4.0 5.0 5.1 6.0 7.0 7.1 7.2 8.0 9.0 9.1 9.2 10.0 11.0 11.1 11.2 12.0 13.0 14.0 ■ 2 Descrption Wiring Methods Raceways—Indicators Raceways—Boxes and Busways Luminaire (Lighting Fixtures) Luminaire Fixtures—Basic Modifiers Mounting Luminaire Fixtures—Basic Modifiers Orientation Luminaire Fixtures—Basic Modifiers Emergency Luminaire Fixtures—Extended Fixtures Outlets and Receptacles Switches and Sensors Motors—Controls Motorized & HVAC Equipment Security Fire Alarm Communications & Panels Fire Alarm Indicators Fire Alarm Sensors Distribution Equipment Communications—Teledata Communications—Audio/Visual Communications—Equipment Site Work Schematic Fault Circuit Interrupter, Personal Protection One-Line Diagram Symbols— Switchboard Meters Schematic and One-Line Diagram Symbols—Switches Miscellaneous Abbreviations Nurse Call System and equipment, and the interrelationships between these items. It should be emphasized that drawings need to be supplemented with specifications in order to establish the details of the electrical systems. 2.1 Organization of this Standard This standard contains symbols commonly and primarily used on electrical construction drawings. Related symbols are organized into different groups, and each symbol within a group has its own unique identifying number. The group and symbol numbers are not significant except as a convenient way to identify individual symbols. See Table 1 for groups. 2.2 Alternate Fire Safety Symbols The fire protection industry has developed and published symbols, not all of which are currently in widespread use on electrical construction drawings. They are shown for reference in Annex A. 2.3 References This publication does not include every known North American symbol for electrical equipment shown on construction drawings. Some older symbols are either becoming obsolete over time or have been superseded by newer symbols (which are shown in this publication). Some electrical symbols are not widely used on construction drawings, but usually on wiring schematics and other types of more specialized drawings. Other drawing symbol standards and publications are listed for reference in Annex C. 3. Drafting Practices for Electrical Construction Drawings 3.1 Symbol Design and Presentation a) The symbols in this standard are widely understood by those in the electrical design and construction field. Other symbols may also be used, provided that a suitable explanation of their meaning is included on the drawing where that symbol is used, or on a symbol legend sheet. b) The orientation of a symbol on a drawing does not alter the meaning of the symbol. c) Every symbol making up part of an electrical circuit must begin with and end with another symbol. When a circuit continues on a different drawing, the end of the circuitry symbol must be appropriately noted on both drawings. This circuitry continued notice is necessary for both vertical and horizontal circuits. d) Circuitry symbols may cross one another at any angle. e) The angle at which a circuitry symbol meets another symbol has no particular significance unless otherwise noted. Circuits normally meet one another at a junction box, pull box, or piece of electrical utilization or communications equipment. f) Future circuits and future equipment should be indicated by dashed lines and clearly marked as future circuits or future equipment on every drawing where applicable. g) Luminaire symbols should be drawn whenever possible in their appropriate proportions, orientation, and shape. Where a luminaire symbol drawn to scale is too small to reproduce clearly, the symbol may be enlarged to an appropriate size while maintaining proportion and orientation. 3.2 General Drafting Practices a) Electrical systems should be shown on plans separate from the architectural, structural, mechanical, and other systems. For clarity, it is recommended that the electrical symbols be drawn darker than the background drawing showing the building structure and/or other systems. b) Different electrical systems such as power distribution, luminaire, voice/data, fire alarm, and security/ access control should be shown on separate plans if combining them on the same drawings would reduce clarity. c) Electrical plans are generally drawn to scale. However, graphic symbols indicate only the approximate locations of electrical equipment. Provide dimensions, details, elevations, and sections where accurate locations of outlets, lighting fixtures, and other equipment are required. d) Electrical wiring required for other systems such as HVAC, manufacturing equipment, data processing systems, etc, should be shown on the electrical drawings where practical, if the installation is included in the electrical contract. 3.3 CADD Practices The following drafting practices are recommended when using computer-aided design and drafting (CADD) systems to prepare electrical construction drawings. a) All CADD electrical construction drawings should be created at full scale, (1" = 1"), and should be plot3 ■ NECA 100 Symbols for Electrical Construction Drawings ted at an appropriate scale on uniform sheets of sufficient size and separate from architectural, structural, mechanical or other drawings. Within a single drawing set, the drawing scale should be the same on as many drawings as possible. b) All electronic files should include no more than one floor level of a building per electronic file. In no case should two different floors of any building be included in one electronic file. c) Architectural, structural or mechanical items on the electrical construction drawings should be plotted with lighter weight lines than the electrical items. d) Electronic files should use blocks (or cells) for all symbology. Blocks (or cells) should use a uniform scale. Non-uniformly scaled blocks and nested blocks should not be used. Instead of exploding blocks to achieve a desired graphic effect, create different variations of an existing block to accomplish the graphic symbol appearance needed. e) No entities should reside on layer 0. This layer is used for referencing of blocks and blocks only. f) All entities should be placed on layers related to their disciplines as defined by the CAD Layer Guidelines published by the American Institute of Architects. These include Electrical, Plumbing, HVAC, Architectural, Structural, Civil/Site, Mechanical, Process Piping, and Telecommunications/Data. The purpose of using different layers is to rationally develop designs using shared drawings. Therefore, it is suggested that the AIA layer naming convention be followed. Ordering information for CAD Layer Guidelines is shown in Annex C. 3.4 Electrical Construction Drawing Set A typical set of electrical construction drawings includes the following: a) Plan for each floor, roof, surrounding site, and other area with electrical installations. b) Site plan(s) showing incoming utility services and substations; exterior transformers; feeders, trunk ■ 4 lines and backbone cables between buildings; and site lighting. c) Symbol list and abbreviation list. d) Schedule(s) of lighting fixtures, mechanical equipment connections, transformers, etc. as appropriate. Typical schedules are shown in Annex B. e) Riser and/or one-line diagram(s) for power distribution and other systems, as appropriate. Typical risers and one-line diagrams are shown in Annex B. Contents for Symbol Groups 1.0 Wiring Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.1 Raceways - Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.2 Raceways - Boxes and Busways . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.0 Luminaire Fixtures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.1 Luminaire Fixtures—Basic Modifiers—Mounting. . . . . . . . . . 11 2.2 Luminaire Fixtures —Basic Modifiers—Orientation. . . . . . . . 11 2.3 Luminaire Fixtures —Basic Modifiers—Emergency . . . . . . . . 12 2.4 Luminaire Fixtures—Extended Modifiers . . . . . . . . . . . . . . . . . 12 3.0 Outlets and Receptacles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 4.0 Switches and Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 5.0 Motors—Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 5.1 Motorized and HVAC Equipment . . . . . . . . . . . . . . . . . . . . . . . 20 6.0 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 7.0 Fire Alarm Communications and Panels. . . . . . . . . . . . . . . . . . . . . . . . 23 7.1 Fire Alarm Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 7.2 Fire Alarm Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 8.0 Power Distribution Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 9.0 Communications - Teledata . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 9.1 Communications - Audio/Visual . . . . . . . . . . . . . . . . . . . . . . . . 30 9.2 Communications - Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . 31 10.0 Site Work. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 11.0 Schematic Fault Circuit Interrupter, Personal Protection . . . . . . . . . . 33 11.1 One-Line Diagram Symbols—Switchboard Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 11.2 Schematic and One-Line Symbol Diagrams—Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 12.0 Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 13.0 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 14.0 Nurse Call System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 5 ■ NECA 100 Symbols for Electrical Construction Drawings 1.0 Raceways Number Preferred Symbol Description 1.001 Conduit concealed in finished areas, exposed in unfinished areas. 1.002 Conduit concealed in or under floor slab. 1.003 Non-rigid raceway system. 1.004 NE Normal/emergency circuit. 1.005 EB Emergency battery system wiring, minimum 10 AWG. 1.006 HT Heat trace. 1.007 P Underfloor power raceway. 1.008 T Underfloor telecommunications raceway. 1.009 PT 1.010 S 1.011 PTD Underfloor raceway for power, telephone, and data. 1.012 UCP Undercarpet flat conductor cable (FCC) wiring system, power. UCT Undercarpet flat conductor cable (FCC) wiring system, telephone 1.013 ■ 6 Underfloor raceway for power and telecommunications. Underfloor signal raceway. NECA 100 Symbols for Electrical Construction Drawings 1.1 Raceways—Indicators Number Preferred Symbol Description 1.101 Conduit stub. Terminate with bushing or cap if underground. 1.102 Conduit turning up. 1.103 Conduit turning down. 1.104 SZ 2C,4#1&1#6GND. OR SZ 53cm,4#1&1#6GND. 1.105 (2)SZ 2C,4#1&1#6GND. OR (2)SZ 53cm,4#1&1#6GND. 1.106 Indicates trade size 2” or 53 mm conduit with (4) 1 AWG and (1) 6 AWG ground. Indicates (2) trade size 2” or 53 mm conduits with (4) 1 AWG and (1) 6 AWG ground conductors in each conduit. Homerun to panelboard. Number of arrows indicates number of circuits. (Example: Homerun to panel L211 CKTS. #1 and #3.) L211–1,3 1.107 Flexible connection to equipment. 1.108 Direct connection to equipment. 1.109 Branch circuit, full hashes indicate ungrounded-“hot” (or switch-leg) circuit conductors. Half hashes indicates grounded neutral circuit conductors. (No hashes indicates 1 hot and 1 neutral.) Dots indicate grounding conductors. Equipment bond size U.N.O. “IG” indicates an isolated grounding conductor. IG ■ 8 Symbols for Electrical Construction Drawings NECA 100 1.2 Raceways—Boxes and Busways Number Preferred Symbol 1.201 Description Underfloor raceway system junction box, flush floor mounted. J 1.202 P Power pole with devices indicated in the specifications and on the drawing, “P” indicates type, “2” indicates circuit. 2 1.203 T 1.204 TP Telecom pole with devices indicated in the specifications and on the drawings, “T” indicates type. Telecom/Power pole with devices indicated in the specifications and on the drawings, “TP” indicates type, “2” indicates power circuit. 2 1.205 Pull box—size as indicated or required. PB OR 1.206 Cabletray size as indicated. TR TR TR TR TR TR BW BW BW Busway with cable tap box, rating and type as indicated on drawings. BW Busway with plug-in device as indicated, shown with fused disconnect. 1.207 Cabletray size as indicated, concealed. 1.208 CTB 1.209 BW BW F 1.210 Busway feeding up. 1.211 Busway feeding down. 1.212 Busway expansion joint. BW 1.213 Wireway, size as indicated or required. WW WW WW 9 ■ NECA 100 Symbols for Electrical Construction Drawings 2.0 Luminaire (Lighting Fixtures) Number Preferred Symbol Description 2.001 Luminaire: (drawn to approximate shape and to scale or large enough for clarity). 2.002 Luminaire strip type (length drawn to scale). 2.003 Fluorescent strip luminaire. 2.004 Fixture—double or single head spotlight. 2.005 Exit luminaire fixture. Arrows and exit face as indicated on drawings (mounting heights to be determined by job specifications). 2.006 Light track. Length as indicated on the drawings, with number of fixtures as indicated on drawings, and as indicated in the fixture schedule. 2.007 Emergency battery remote luminaire heads. 2.008 Emergency battery unit with luminaire heads. 2.009 Single luminaire pole mounted site luminaire fixture. 2.010 Tw i n l u m i n a i r e p o l e m o u n t e d s i t e l u m i n a i r e f i x ture. 2.011 Roadway luminaire—cobra head. 2.012 Bollard type site luminaire. 2.013 Outdoor wallpack. ■ 10 Symbols for Electrical Construction Drawings NECA 100 2.1 Luminaire Fixtures—Basic Modifiers Mounting Number 2.100 Preferred Symbol Description Surface mounted fixture. Recessed fixture. Wa l l m o u n t e d f i x t u r e . Suspended, pendant, chain, stem or cable hung fixture. Pole mounted with arm. Pole mounted on top. In-ground or floor mounted. (Box around symbol.) 2.2 Luminaire Fixtures—Basic Modifiers Orientation 2.200 A c c e n t / d i r e c t i o n a l a r r o w, w i t h o r w i t h o u t t a i l . (Drawn from photometric center in direction of optics or photometric orientation.) Directional aiming line. (Drawn from photometric center and may be extended to actual aiming point if required.) Tr a c k m o u n t e d ; l e n g t h , l u m i n a i r e t y p e s a n d q u a n t i t i e s a s s h o w n . ( Tr a c k l e n g t h d r a w n t o scale.) 11 ■ NECA 100 Symbols for Electrical Construction Drawings 2.3 Luminaire Fixtures—Emergency Number Preferred Symbol Description 2.300 NOTE: Luminaire providing emergency illumination. (Filled in.) M o d i f i e r s a r e s h o w n w i t h s p e c i f i c b a s e s y m b o l s f o r c l a r i t y. Each modifier can be used with any of the base symbols. 2.4 Luminaire Fixtures—Extended Modifiers 2.401 A a 2 2.402 A a +48” NL 2 Standard designations for all luminaire fixtures. “A” = Fixture type, refer to fixture schedule “NL” = Unswitched night light “2” = Circuit number “a” = Switch control Mounting height. 2.403 Louvers. 2.404 Recessed, emergency fixture. ■ 12 Symbols for Electrical Construction Drawings NECA 100 3.0 Outlets and Receptacles Number Preferred Symbol 3.001 Description Floor duplex receptacle. F=flush MTD. S=surface MTD. F 3.002 3.003 D u p l e x c o n v e n i e n c e r e c e p t a c l e . 2 0 A 1 2 5 V. Duplex convenience receptacle on emergency/standby circuit. Specify panelboard and circuit. EP–2 CKT.1 3.004 3.005 Single convenience receptacle. Single convenience receptacle on emergency/standby circuit. Specify panelboard and circuit. EP–2 CKT.3 3.006 3.007 Double duplex convenience receptacle. Double duplex convenience receptacle on emergency/standby circuit. Specify panelboard and circuit. EP–2 CKT.5 3.008 Multi-outlet assembly with outlets on centers as indicated on the drawings and in the specifications, mounted 6" above counter or at height as directed, A - indicates type. A 3.009 M u l t i o u t l e t a s s e m b l y, d e v i c e s a s i n d i c a t e d . 1 3.010 1 Special receptacle - typical notation: 1— indicates example 1 OR “ 1 ” = _ _ A , _ _ _ / _ _ _ V. , _ P o l e , _ W i r e , _ N E M A _ _ - _ _ “ 2 ” = _ _ A , _ _ _ / _ _ _ V. , _ P o l e , _ W i r e , _ N E M A _ _ - _ _ “ 3 ” = _ _ A , _ _ _ / _ _ _ V. , _ P o l e , _ W i r e , _ N E M A _ _ - _ _ 3.011 Clock hanger outlet recessed mounted 8’-0” AFF or 8” below ceiling as appropriate and as directed. 3.012 Flush mounted floor box, adjustable, with both power and voice/data receptacles. F 3.013 J J Junction box. “AxBxC” indicates dimensions of junction box in either inches or centimeters. AxBxC 13 ■ NECA 100 Symbols for Electrical Construction Drawings 3.0 Outlets and Receptacles Number Preferred Symbol Description 3.014 D u p l e s r e c e p t a c l e c e i l i n g m o u n t e d 2 0 A 1 2 5 V. 3.015 Double duplex receptacle—ceiling mounted. Receptacles And Outlets Ty p i c a l O u t l e t N o t a t i o n s : “a” = Switched outlet, “a”—indicates switch control. “B” = Pedestal mounted on bench top. “BF” = B e l o w f l o o r. “C” = M o u n t e d 6 ” a b o v e c o u n t e r o f 4 2 ” A F F. C o o r d i n a t e e x a c t m o u n t i n g h e i g h t w i t h architectural drawings. “CLG” = Ceiling mounted. “D” = Dedicated device on individual branch circuit. “E” = E m e r g e n c y. Existing device/equipment. “F” = Flush floor box with fire/smoke rated penetration. “GFCI” = G r o u n d f a u l t c i r c u i t i n t e r u p t e r, p e r s o n a l p r o t e c t i o n . “GFPE” = Ground fault protection of equipment. “H” = Horizontally mounted. “IG” = Isolated ground receptacle with separate green ground conductor to isolated ground bus in panel. “M” = Modular furniture service—provide flexible connection, coordinate exact location with furniture plans. “PED” = Pedestal mounted with two hour fire/smoke rated penetration. “PT” = Poke thru with two hour fire/smoke rated penetration. “S” = Surface mounted floor box. “SP” = Surge protection receptacle. “T” = Ta m p e r r e s i s t a n t s a f e t y r e c e p t a c l e . “TL” = Tw i s t - l o c k . “W” = Wa l l m o u n t e d d e v i c e a t 4 8 ” A F F u n l e s s o t h e r w i s e i n d i c a t e d . “WP” = We a t h e r p r o o f r e c e p t a c l e w i t h “ N RT L ” l i s t e d c o v e r p l a t e f o r w e t l o c a t i o n w i t h plug installed. MTD. 48” AFF unless otherwise indicated. +XX = Dimensioned height. . “ E X I S T. ” = ■ 14 Symbols for Electrical Construction Drawings NECA 100 4.0 Switches and Sensors Number Preferred Symbol Description 4.001 $ or S Single pole switch. 4.002 $2 or S2 Double pole switch. 4.003 $3 or S3 Three way switch. 4.004 $4 or S4 Four way switch. 4.005 $a or Sa Switch control (lower case letter). 4.006 $CB or SCB Circuit breaker switch. 4.007 $DT or SDT Single pole/double throw switch. 4.008 $G or SG G l o w s w i t c h t o g g l e , g l o w s i n o ff p o s i t i o n . 4.009 $H or SH Horizontally mounted—with on position to the left. 4.010 $K or SK Key operated switch. 4.011 $KP or SKP Key operated switch with pilot light on when switch is on. 4.012 $LV or SLV Low voltage switch. 4.013 $LM or SLM Low voltage master switch. 15 ■ Symbols for Electrical Construction Drawings NECA 100 5.0 Motorized and HVAC Equipment—Controls Number Preferred Symbol 5.001 Disconnect switch, unfused type, size as indicated on drawings. “xxA” indicates amperage. xxA 5.002 xxAF yyAT 5.003 F xxAF CB yyAT 5.004 ASD 5.006 $M RV NEMA x 5.008 Disconnect switch, fused type, size as indicated on d r a w i n g s . “ x x A F ” i n d i c a t e s f r a m e s i z e . “ x x AT ” i n d i cates trip size. E n c l o s e d c i r c u i t b r e a k e r, s i z e a s i n d i c a t e d . “ x x A F ” i n d i c a t e s f r a m e s i z e . “ x x AT ” i n d i c a t e s t r i p s i z e . M a g n e t i c c o n t a c t o r, s i z e a s i n d i c a t e d o n d r a w i n g s . C 5.005 5.007 Description F NEMA x xxA–xP Adjustable speed drive. Motor starter switch. M a g n e t i c m o t o r s t a r t e r. “ RV ” i n d i c a t e s r e d u c e d voltage. Starter size as indicated. Combination magnetic starter and disconnect switch. Starter size and fuse rating as indicated. 5.009 ATC Automatic temperature control panel. 5.010 CP Equipment control panel. 5.011 5.012 5.013 R TD TS P R e l a y. To g g l e d i s c o n n e c t s w i t c h . Thermal motor switch with handle guard and padl o c k c a p a b i l i t y. “ P ” — i n d i c a t e s p i l o t l i g h t . 17 ■ NECA 100 Symbols for Electrical Construction Drawings 5.1 Motorized and HVAC Equipment Number Preferred Symbol 5.101 Description C a p a c i t o r. 5.102 M o t o r “ 3 ” — i n d i c a t e s h o r s e p o w e r. 3 5.103 M o t o r i z e d d a m p e r. D 5.104 B a s e b o a r d h e a t e r. 5.105 Baseboard heater with box. 5.106 R e s i s t a n c e h e a t e r. 5.107 U n i t t y p e h e a t e r. 5.108 Ceiling fan. 5.109 Paddle fan. 5.110 Wa l l f a n . 5.111 Wa t e r h e a t e r. WH ■ 20 Symbols for Electrical Construction Drawings NECA 100 7.0 Fire Alarm Communications and Panels Number 7.001 Preferred Symbol M 7.002 Description Fire alarm master box. F i r e f i g h t e r ’s p h o n e . 7.003 FT C o d e d t r a n s m i t t e r. 7.004 DK Drill key switch. 7.005 K Key repository (knox box). 7.006 FAA Annunciator panel. 7.007 FACP Fire alarm control panel. 7.008 EVAC Vo i c e e v a c u a t i o n p a n e l . 7.009 FATC Fire alarm terminal cabinet. 7.010 BATT B a t t e r y p a c k a n d c h a r g e r. 7.011 ASFP Air sampling control/detector panel with associated air sampling piping network. 7.012 TPR Tr a n s p o n d e r. 7.013 IAM Individual addressable module. 23 ■ NECA 100 Symbols for Electrical Construction Drawings 8.0 Power Distribution Equipment Number Preferred Symbol Description 8.001 Lighting or power panel, recessed. 8.002 Lighting or power panel, surface. 8.003 Distribution panel. 8.004 Lighting or power panel on normal/generator f e e d e r. 8.005 D i s t r i b u t i o n p a n e l o n n o r m a l / g e n e r a t o r f e e d e r. MCC 8.006 8.007 M o t o r c o n t r o l c e n t e r. T T45-1 XFMR NUMBER D r y t y p e t r a n s f o r m e r, r e f e r t o t r a n s f o r m e r s c h e d u l e , “T45”—indicates transformer type floor mounted. Unless otherwise indicated, “W”—indicates wall, “S”—indicates suspended. “R”—indicates K rating. 8.008 T 8.009 CT 8.010 G 8.011 M Meter—single. 8.012 M Meter and socket. Tr a n s f o r m e r — p a d m o u n t . Current transformer cabinet. xxkW 8.013 TS ■ 28 G e n e r a t o r. S i z e a s n o t e d . Tr a n s f e r s w i t c h . “ T S ” = m a n u a l t r a n s f e r s w i t c h . “ AT S ” = a u t o m a t i c t r a n s f e r s w i t c h . NECA 100 Symbols for Electrical Construction Drawings 10.0 Site Work Number Description 10.001 UF U n d e r g r o u n d f e e d e r. 10.002 UT Underground telephone. 10.003 UFA Underground fire alarm. 10.004 UTV U n d e r g r o u n d t e l e v i s i o n ( C AT V ) . 10.005 E Above ground pole mounted electrical. 10.006 T Above ground pole mounted telephone. 10.007 F Above ground pole mounted fire alarm. 10.008 TV A b o v e g r o u n d p o l e m o u n t e d t e l e v i s i o n ( C AT V ) . 10.009 MH Manhole. 10.010 HH Handhole. 10.011 P 10.012 10.013 ■ Preferred Symbol 32 Pxxxx E T U t i l i t y p o l e . “ P x x x x ” i n d i c a t e s p o l e n u m b e r. Combination pre-fabricated manholes for power a n d t e l / d a t a s y s t e m s . “ E ” = d e n o t e s p o w e r, “ T ” = denotes tel/data. “J” hook. Symbols for Electrical Construction Drawings NECA 100 11.0 Schematic and One-line Diagram Symbols Number Preferred Symbol 11.001 Description C a p a c i t o r. 11.002 Circuit breaker (open). “xxAF” indicates frame size. “ y y AT ” i n d i c a t e s t r i p s i z e . xxAF yyAT 11.003 Circuit breaker (enclosed). “xxAF indicates frame s i z e . “ y y AT ” i n d i c a t e s t r i p s i z e . xxAF yyAT 11.004 P r i m a r y d r a w o u t t y p e c i r c u i t b r e a k e r. “ x x A F ” i n d i c a t e s f r a m e s i z e . “ y y AT ” i n d i c a t e s t r i p s i z e . xxAF yyAT 11.005 L o w v o l t a g e d r a w o u t t y p e c i r c u i t b r e a k e r. “ x x A F ” i n d i c a t e s f r a m e s i z e . “ y y AT ” i n d i c a t e s t r i p s i z e . xxAF yyAT 11.006 xxAF yyAT zzA Low voltage draw out type circuit breaker with current limiting fuses. “xxAF” indicates frame size. “yyAT” indicates trip size. “zzA” indicates fuse rating. 11.007 Contact, normally open (NO) (“TC”—with timed closing). 11.008 Contact, normally closed (NC). (“TO”—with timed opening). CT 11.009 11.010 Current transformer cabinet. Fused cutout. “zzA” indicates fuse rating. zzA 11.011 Disconnect switch unfused. 11.012 zzA 11.013 Disconnect switch air break with fuse. “zzA” indicates fused rating. Fuse. “zzA” indicates fuse rating. zzA zzA 33 ■ NECA 100 Symbols for Electrical Construction Drawings 11.0 Schematic and One-line Diagram Symbols Number Preferred Symbol Description 11.014 O v e r l o a d r e l a y. 11.015 Grounding connection—system and or equipment. 11.016 K2 11.017 Kirk key interlock system. “2”—indicates related kirk keys. Lightning arrester and grounding to protect all phases. 3 11.018 M o t o r a n d l a b e l . “ 3 ” d e n o t e s h o r s e p o w e r. xx-xx-x-x MO 11.019 11.020 Motor operator for circuit breakers or switches. N e t w o r k p r o t e c t o r. PANEL Panelboard. ▼ 11.021 11.022 11.023 Stress cone. 11.024 R e s i s t o r. ST 11.025 11.026 34 Shunt trip. Magnetic starter with NEMA size indicated. 1 ■ Pothead. Symbols for Electrical Construction Drawings NECA 100 11.0 Schematic and One-line Diagram Symbols Number Preferred Symbol 11.027 G r o u n d f a u l t c i r c u i t i n t e r r u p t e r, p e r s o n n e l p r o t e c tion. GFCI xxx KW xxxV-xø GENERATOR G ▼ 11.028 Description xxx KVA xxxV xø xW PRI OOOO G e n e r a t o r. ▼ Tx OOOO 11.029 Tr a n s f o r m e r, d r y t y p e . U n l e s s o t h e r w i s e i n d i c a t e d . xxxY/xxxV xø xW SEC P o t e n t i a l t r a n s f o r m e r. “ 3 ” — i n d i c a t e s q u a n t i t y. (3) (3) 400-5A OO 11.031 OO 11.030 C u r r e n t t r a n s f o r m e r. “ 3 ” — i n d i c a t e s q u a n t i t y, “ 4 0 0 5A” indicates ratio. 11.032 3-phase, 3-wire delta connection. 11.033 Corner grounded delta. 11.034 3-phase, 4-wire wye connection (grounded neutral). 11.035 AFD 3 xx-x-x Adjustable frequency drive. 3 r e f e r e n c e s d e t a i l n u m b e r. 11.036 XX’ xxxV BUSDUCT B u s d u c t o r b u s w a y. 11.037 XX’ xxxV WIREWAY W i r e w a y. 35 ■ NECA 100 Symbols for Electrical Construction Drawings 11.2 Schematic and One-line Diagram Symbols—Switches Number 11.201 Preferred Symbol N E L Tr a n s f e r s w i t c h . 11.202 Push button (start). 11.203 Push button (stop). 11.204 Limit switch. 11.205 Flow switch. 11.206 Pressure switch. 11.207 Float switch. 11.208 11.209 ■ AUTO/MANUAL TRANSFER SWTICH xxA-xP Description 38 R P i l o t l i g h t . L e t t e r i n d i c a t e s c o l o r. E x a m p l e : R = r e d . Solenoid. Symbols for Electrical Construction Drawings NECA 100 12.0 Miscellaneous Number Preferred Symbol Description 12.001 G G r o u n d b a r. L e n g t h t o b e n o t e d . 12.002 AC M e c h a n i c a l e q u i p m e n t t a g n u m b e r, r e f e r t o mechanical equipment schedule. 2 12.003 E q u i p m e n t t a g n u m b e r, r e f e r t o e q u i p m e n t s c h e d ule, “K”—indicates kitchen, “C”—indicates compute r. K2 B 12.004 Note symbol, refer to note as indicated. 12.005 1 F e e d e r n u m b e r, r e f e r t o “ f e e d e r s c h e d u l e ” . 12.006 A Ty p i c a l / s i m i l a r r o o m o r a r e a l a y o u t s y m b o l . “ A ” — indicates layout type. 12.007 A E–2 Ty p i c a l l a y o u t s y m b o l — r e f e r t o l a y o u t t y p e . “ A ” o n drawing E-2, circuits to be used are as indicated. CKT/ P21–5,7 E–4 SCALE: N.T.S. ▼ 12.009 DESCRIPTION ▼ 2 12.008 B E–2 12.010 2 E–4 D e t a i l h e a d e r, i n d i c a t i n g d e t a i l N o . 2 o n d r a w i n g E 4. S e c t i o n i d e n t i f i e r, i n d i c a t i n g s e c t i o n “ B ” o n d r a w i n g E - 2 . L e f t o r r i g h t a r r o w. D e t a i l i d e n t i f i e r, i n d i c a t i n g d e t a i l N o . 2 o n d r a w i n g E-4. 39 ■ NECA 100 Symbols for Electrical Construction Drawings 13.0 Abbreviations Abbreviation ■ Description Abbreviation Description 1P One pole DIST Distribution 2P Two pole DN Down 3P Three pole DWG Drawing 4P Four pole DT Dusttight(*) 1P1W One pole, one wire E Wired on emergency circuit 1P2W One pole, two wire EA Each 2P2W Two pole, two wire EC Electrical contractor 2P3W Two pole, three wire EF Exhaust fan 3P2W Three pole, two wire ELEC Electric(al) 3P3W Three pole, three wire EMER Emergency 3P4W Three pole, four wire EMT Electric metallic tubing 4P4W Four pole, four wire ENCL Enclosure A Ampere EOL End of line AC Alternating current EPO Emergency power off AF AMP frame EQUIP Equipment AFCI Arc-fault circuit interrupter EWC Electric water cooler AFF Above finished floor EWH Electric water heater AFG Above finished grade EXIST. Existing AHU Air handling unit F Flush AIC Ampere interrupting capacity FA Fire alarm AL Aluminum FBO Furnished by others AS AMP switch FC Fire protection contractor AT AMP trip FCU Fan coil unit ARCH Architect FDN Foundation ATS Automatic transfer switch FIXT Fixture AUD Audiometer box connection FLA Full load amps AUX Auxiliary FLEX Flexible A/V Audio visual FLR Floor AWG American wire gauge FMC Flexible metallic conduit BLDG Building FRE Fiberglass reinforced epoxy conduit C Conduit (Generic term for raceway. FURN Furniture Provide as specified.) GC General contractor CAM Camera GEN Generator CAT Catalog GFCI Ground fault circuit interrupter CATV Cable television GFPE Ground fault protection equipment CB Circuit breaker GND Grounded CKT Circuit GRC Galvanized rigid conduit COL Column HGT Height C.T. Current transformer HP Horsepower CU Copper HV High voltage CL Centerline HVAC Heating, ventilating and air DC Direct Current conditioning Delta HW Hot water DET Detector Hz Hertz (cycle) per second DISC Disconnect IAM Individual addressable module 40 Symbols for Electrical Construction Drawings NECA 100 13.0 Abbreviations Abbreviation Description Abbreviation Description IC Intercommunication # Number ID Identification NTS Not to scale IG Isolated ground O2 Oxygen IMC Intermediate metal conduit OHD Overhead door operator IPS Interruptible power supply P Pole IR Passive infrared PB Pull box JB Junction box PC Plumbing system contractor KCMIL Thousand circular mils PE Primary service K/O Knock-out PH ø Phase KVA Kilovolt ampere PNL Panel(board) KVAR Kilovolt ampere reactive PIV Post indicating valve KW Kilowatt PP Power panel LFMC Liquidtight flexible metallic conduit PR Pair LFNC Liquidtight flexible nonmetallic conduit PRI Primary LP Lighting panelboard PT Potential transformer LS Limit switch PVC Polyvinyl chloride conduit LTG Lighting PWR Power LV Low voltage RE Remove existing MAINT Maintained REC Recessed MAU Make-up air unit RECP Receptacle MAX Maximum REF Roof exhaust fan MC Metal clad cable RL Relocate existing MCB Main circuit breaker RM Room MCC Motor control center RMC Rigid metal conduit MD Motorized damper RT Raintight(*) MDP Main distribution panel RTU Rooftop unit MISC Miscellaneous RSC Rigid steel conduit MFR Manufacturer S Surface mounted MLO Main lugs only SCH Schedule MOD Motor operated disconnect switch SD Smoke damper MTD Mounted SE Secondary electric service MTG Mounting SEC Secondary MTS Manual transfer switch SIG Signal N North SN Solid neutral N/A Not applicable SP Spare NC Normally closed SPKR Speaker NEC National Electrical Code SPL Splice NF Non-fused SS Stainless steel NIC Not in contract STP Shielded twisted pair NL Night light STL Carbon steel NM Nonmetallic sheathed cable SUSP Suspended NO Normally open SW Switch NRTL Nationally recognized testing lab SWBD Switchboard (*) It is recommended that the appropriate NEMA designation be used in place of this abbreviation. 41 ■ NECA 100 Symbols for Electrical Construction Drawings 13.0 Abbreviations Abbreviation ■ Description Abbreviation Description SWGR Switchgear UTP Unshielded twisted pair TC Telephone cabinet V Volt TCI Telecommunications cabling installer VT Vaportight(*) TCP Temperature control panel Y Wye TEL/DATA Telephone/data W Watt TEL Telephone W/ With TERM Terminal(s) WH Watthour TV Television WP Weatherproof TYP Typical WP Weatherproof UC Under counter WT Watertight(*) UG Underground XFMR Transformer UH Unit heater XP Explosion proof(*) U.O.I. Unless otherwise indicated ZAM Zone adapter module UPS Uninterruptible power source +72 UTIL Utility 42 TEMP Temporary Mounting units to centerline above finished floor or grade Annex B: Typical Risers, One-line Diagrams, and Schedules This annex provides examples of typical schedules, riser diagrams, and one-line diagrams that are included in electrical construction drawings. A given set of drawings will not necessarily include every typical example included here. This annex includes the following: Type Page Panel schedule . . . . . . . . . . . . . . . . . . . . . . . 49 Lighting fixture schedule . . . . . . . . . . . . . . . 50 Transformer schedule . . . . . . . . . . . . . . . . . 51 Mechanical equipment schedule. . . . . . . . . 52 Feeder schedule . . . . . . . . . . . . . . . . . . . . . . 53 Electrical one-line diagram . . . . . . . . . . . . . 54 Fire alarm riser . . . . . . . . . . . . . . . . . . . . . . . 55 ■ 48 49 ■ Load (VA) Trip 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 Trip Bkr. Frame Modifications: __________________________ Load Name Total VA: ________________________ Load (VA) Amps RMS. Sym.: ________________________________ Phase C: _____________________ 42 8 7 41 6 5 Ckt. No. 4 C 3 B 2 A Mains: __________________________ Location: _______________________________________________ Wires: ___________ 1 Ckt. No. Phase B: _____________________ Bkr. Frame Mfg./Type: ________________________ Phase A: _____________________ Load Name Phase: _____________ Enclosure: __________________________ Voltage: ___________________ Mount: _______________________ Panel: _____________ Panel Schedule ■ 50 Type Manufacturer Catalog No. Description Lighting Fixture Schedule Mounting Lamps 51 ■ Designation Manufacturer Catalog Number KVA ø PRI. Volts PRI. Conductor Size/No. Transformer Schedule Sec. Volts Sec. Conductor Size/No. Ground Conductor Size/No. Mounting ■ 52 Designation Description Quantity Volt ø FLA HP KVA Min. Wire Size/Type Mechanical Equipment Schedule Max. Fuse Size Min. CCT Amps Remarks/ Disconnect Type Feeder Schedule # No. No. Runs No. Wires/Size Insul. CU/AL Conduit Origin Termination 53 ■ NECA 100 Symbols for Electrical Construction Drawings Electrical One-Line Diagram FROM 480V U N I T S U B S TAT I O N # 8 FROM EMERG. SWITCHGEAR 3EH01B6 N 3EHA1B6B 1200A 4 8 0 V, 3 W + G , 3 P 65,000A RMS SYM CLOSING A N D W I T H S TA N D R AT I N G E L EMERGENCY DISTRIBUTION SWITCHBOARD 3 E H 0 1 C 6 B , 1 2 0 0 A , 4 8 0 V, 3 Ø , 3 W + G , 6 5 , 0 0 0 I E R 800A 800A 600A 1 1200A 125A 150A 3 2 4 EMERGENCY DISTRIBUTION SWITCHBOARD 3 E H M 8 D 8 B , 8 0 0 A , 4 8 0 V, 3 Ø , 3 W + G , 6 5 , 0 0 0 I E R 800A ▼ OOOO OOOO 400A 240A 240A 9 3EHT185 7 5 K VA 480V 3Ø 3W PRI 120/208V 3Ø 4W SEC 3EHL1B5 4 11 10 250/M 5 AFD 36-2-2 1 AFD 32-5-2 2 RV N R 22,000 IER 800 240A 6 5 1 AFD 32-2-2 54 250 150 F-36-2-2 P-32-5-2 EMERGENCY DISTRIBUTION SWITCHBOARD 3 E H M 1 D 4 B , 8 0 0 A , 4 8 0 V, 3 Ø , 3 W + G , 6 5 , 0 0 0 I E R 300A ■ 125 C-26-1-1 240A S PA R E 3 AFD 32-2-4 600 EMERGENCY DISTRIBUTION SWITCHBOARD 3 E H M 1 D 4 D , 6 0 0 A , 4 8 0 V, 3 Ø , 3 W + G , 6 5 , 0 0 0 I E R 240A 240A S PA R E 240A 8 7 1 AFD 32-2-8 150 125 125 EF-32-2-2 EF-32-2-4 EF-32-2-8 240A S PA R E 3 AFD 32-2-10 125 EF-32-2-10 S PA R E