TASK Title: SHEET 2.4-3E TESTING ROTARY SWITCH Performance Objective: In air conditioning shop scenario, the trainee must be able to test the different types of switches used in servicing the control circuit Supplies/Materials Equipment Tools : : Paint brush, Rotary Switch Air Conditioning unit : Long Nose Pliers , Multi-Tester Personal Protective Equipment : Gloves, mask, goggle, safety shoes Steps/Procedure: Selector switch is a mechanical control intended to turn on the fan and compressor of the air-conditioning unit. It is also the control for the different fan speed like low, medium and high cool. Defective switch may be mistaken as defective fan motor or defective compressor if not checked properly. Below is the procedure in testing selector switch. Procedure: 1. Analyze table 1. You will use this as reference in checking the selector switch. 2. Locate the common terminal of the selector switch. Usually the common terminal of the selector switch has the label L1. If the label has been erased, you can locate it by using an ohm meter or continuity tester. Switch Position Compressor Motor Fan Motor High Terminal Med Terminal Low Terminal Off 0 0 0 0 Fan 0 0 1 0 Low cool 1 0 0 1 Medium cool 1 0 1 0 High cool 1 1 0 0 Common terminal is used as reference for this table Legend: 0 – Open contact 1 – Closed The common terminal will be the source line of compressor motor and fan motor therefore it has a contact on the compressor terminal, low Cool terminal when the selector is switched to low cool mode; it has a contact on the compressor and medium terminal when the selector is switched to medium cool mode; or it has a contact on or high cool terminal every time the switches are activated (see table 1 for more information). 3. Switch the selector to OFF mode. Then measure the continuity of the terminals L1 - PL, L1 - 1, L1 - 4, L1 - 3 and L1 - 2. Based from the chart on step 1, there is no closed contact on any of the terminals in reference with common terminal when the selector is switched to OFF mode. 4. Turn the selector switch to fan mode. Measure the continuity of all Terminals in reference with the common terminal. Answer the table. Turn the selector switch to low cool mode. Measure the continuity of all terminals in reference with the common terminal. Answer the table. Turn the selector switch to medium cool mode. Measure the continuity of All terminals in reference with the common terminal. Answer the table. Turn the selector switch to high cool mode. Measure the continuity of all terminals in reference with the common terminal. Answer the table. Based on table 1. Analyze the result of your measurement (see table 2-6) The common terminal is the terminal which have continues connection when the selector is switched to low cool, medium cool and high cool. Low cool terminal is the terminal with connection every time the selector is switched to low cool. Medium cool is the terminal with connection every time the selector is switched to medium cool. High cool is the terminal with connection every time the selector is switched to high cool Assessment Method: Demonstration, Evaluate Using Performance criteria checklist Safety Reminders! In performing this activity, you must practice occupational health and safety procedures at all times. Trainees Name/Signature: Trainer Signature: _________________________ Date: Date : _____________ Performance Criteria Checklist Task Sheet #2.4-3E CRITERIA YES NO Did I.. Located the rotary switch from the control panel Removed the control panel cover Used long nose pliers, to remove the female terminal of rotary switch Tested the rotary switch terminal for continuity test using a multi-tester. Demonstrated correct sequence in disassembling and assembling of rotary switch Observed housekeeping Observed quality of work Followed technical specifications from manufacturer’s manual Observed work safety Comment/Feedback: Trainees Name/Signature: Date: Trainer Signature: _________________________ Date : _____________