Uploaded by Samtech Switchgear

is.3231.3.3.1987

advertisement
इंटरनेट
मानक
Disclosure to Promote the Right To Information
Whereas the Parliament of India has set out to provide a practical regime of right to
information for citizens to secure access to information under the control of public authorities,
in order to promote transparency and accountability in the working of every public authority,
and whereas the attached publication of the Bureau of Indian Standards is of particular interest
to the public, particularly disadvantaged communities and those engaged in the pursuit of
education and knowledge, the attached public safety standard is made available to promote the
timely dissemination of this information in an accurate manner to the public.
“जान1 का अ+धकार, जी1 का अ+धकार”
“प0रा1 को छोड न' 5 तरफ”
“The Right to Information, The Right to Live”
“Step Out From the Old to the New”
Mazdoor Kisan Shakti Sangathan
Jawaharlal Nehru
IS 3231-3-3 (1987): Electrical Relays for Power System
Projection, Part 3: Requirements for Particular Group of
Relays, Section 3: Biased (Percentage) Differential Relays
[ETD 35: Power Systems Relays]
“!ान $ एक न' भारत का +नम-ण”
Satyanarayan Gangaram Pitroda
“Invent a New India Using Knowledge”
“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह”
है”
ह
Bhartṛhari—Nītiśatakam
“Knowledge is such a treasure which cannot be stolen”
( Reaffirmed 2001 )
IS : 3231 ( Part 3/Set 3 ) - 1987
Indian Standard
SPECIFICATION FOR
ELECTRICAL RELAYS FOR
POWER SYSTEM PROJECTION
PART
3
REQUIREMENTS
Section
3
Biased
FOR PARTICULAR
RELAYS
( Percentage
) Differential
Relays Sectional Committee,
Chairman
GROUP
OF
Relays
ETDC 35
Refmssnting
*SHRI V. S. DORAI
Tata
Hydro-Electric
Bombay
Power
Supply
Co
Ltd,
Members
SHRI R. D. BATRA
Hindustan Steel Ltd, Ranchi
SH~I G. K. SARAN ( Alternate )
Delhi Electric Supply Undertaking, New Delhi
SHRI R. C. BHATIA
SHRI M. K. CHAUDHARY ( Alternuts )
Tamil Nadu Electricity Board, Madras
SHRI T. B. CHIKKOBA
SHRI V. V. SAMPATE ( Alternate )
Railway Board, New Delhi
DEPUTY DIRECTOR ( PSI-II )
DEPUTY DIRECTOR, S&T ( Alternate )
Central Electricity Authority, New Delhi
DIRECTOR ( CIP )
Directorate
General
of Supplies & Disposals
SHRI K. L. GARQ
( Inspection Wing ), New Delhi
SHRI S. KRISHNA ( Alternate )
Bombay Electric
Supply & Transport
UnderSHRI S. G. KARADKAR
taking, Bombay
SHRI M. A. KARIX ( Alternate )
Larsen & Toubro Ltd. Bombay
SHRI V. S. KAUSHIKKAR
SHRI DEVE~DER NATH ( Alternate )
Universal Electrics Ltd, 24 Parganas
SERI G. K. MALAVIYA
SHRI C. GHOSH ( Alternate )
National Test House, Calcutta
SHRI B. C. MUKRERJEE
Snar D. P. MUKRERJEE ( Alternate )
Bharat Heavy Electricals Ltd, Bombay
SHRI NACHHATTER SINQ~
SARI R. RA~ASUBBAIAH ( Altcrnnte I )
SHRI S. G. DESHPANDE ( Alternate II )
*Shri V. S. Dorai was Chairman
for the meeting
in which this standard
wm
fmalized.
( Continued on page 2 )
0
BUREAU
Copyright 1987
OF INDIAN
STANDARDS
This publication
is protected under the fndian Copyright dct ( XIV of 1957 ) and
reproduction in whole or in part by any meana except with written permission ot the
publisher shall be deemed to be an infringement of copyright under the said Act.
IS : 3231 ( Part J/Set 3 ) - 1987
( Continrredfrom pugs1 )
Rsprcssnting
Members
Easun Reyrolle
Relays
and
Devices,
Tamil Nadu
Tata Consulting Engineers, Bombay
SHRI S. NATARAJAN
SHRI A. A. PAUL
SHW
P. P. KARHADB (
Ltd,
Altenrate)
University of Roorkee, Roorkee
Aluminium Industries Ltd, Trivandrum
SHRI R. RAMANUJAN
SHRI B. NAEAYANAN ( Alternate )
Hindustan Brown Boveri Ltd, Vadodara
SHRI U. V. RAO
SHRI P. U. BEAT ( Altcmafe )
Tata
Hydro-Electric
Power SuppIy Co Ltd,
SHRI
A. M. SAHNI
Bombay
*SHRI V. S. DORAI (Alternate )
ASEA Ltd, Bangalore
DRM.T.S~NT
_.
.
SHRI B. S. PALKI ( Alternate 1
U. P. State Electricity Board, Lucknow
SHRI B.S. SHARMA
SHRI C. P. GUPTA ( Alternate)
Directorate General of Technical
Development,
SHRI
S. SIVASUBRA~IANIAN
New Delhi
&RI P. K. HALDAR
( Alternate )
Haryana State Electricity Board, Chandigarh
SUPERINTENDINOENOINEER
SRRI HARNARINDER SINEW ( Alternate )
National
Physical
Laboratory
( CSIR
),
SHRI S. I’. SURI
New Delhi
SHRI S. C. GARQ ( Alternate )
Engineers India Ltd, New Delhi
SHRI G. N. THADANI
SHRI
S. G. GOKHALE ( Altcrnate )
Jyoti Ltd, Vadodara
DR K. K. THAKKAR
DR B. K. DASWPTA ( Alternate)
English Electric Co of India Ltd, Madras
SHF.I K. VASUDEVAN
SHRI A. K. BAJA
SHRI T. V. G. MENON ( Alterpate )
Karnataka Electricity Board, Bangalore
B. IS. VENRATESE
SHRI K. T. RAMASWAMY ,( Alternate )
Director
General, BIS ( Ex-o&o Member )
SHRI
S. P. SACHDEV,
Director ( Elec tech )
Smrrtary
SHRI K. M. BHATIA
Joint Director ( Elec tech ), BIS
SHRI
(Continued
*Ski V. 5. Dorai wils Chairmanfor the meeting in whichthis standard was finalized.
2
on
baga 16 )
IS : 3231 ( Part J/Set 3 ) - 1987
Indian Standard
SPECIFICATION
FOR
ELECTRICAL RELAYS FOR
POWER SYSTEM PROTECTION
PART
3
Section
REQUIREMENTS
3
Biased
0.
FOR PARTICULAR
RELAYS
( Percentage
) Differential
GROUP
OF
Relays
FOREWORD
0.1 This
Indian Standard ( Part 3/Set 3 ) was adopted by the Indian
Standards Institution on 29 January 1987, after the draft finalized by the
Relays Sectional Committee had been approved by the Electrotechnical
Division Council.
0.2 This standard is one of the series of standards being brought out to
cover requirements of protection relays. General introduction to this series
is given in IS : 3231 ( Part 0 )-1986*.
The standards published in the series so far are:
IS: 3231 Specification
for electrical
relays power system protection:
(Part O)-1986
General
introduction
(jirst revision)
(Part l/Set l)-1986
General requirements;
mance (jnt revision)
Section 1 Contact perfor-
(Part 1jSec 2)-1986
General requirements;
(jrst revision)
Section 2 Insulation tests
(Part l/Set 3)-1986
General requirements; Section 3 High frequency
disturbance test for static relays (jirst revision)
(Part 2/Set 1).1987
Requirements for principal families; Section
All-or-nothing relays
Requirements for principal families; Section
General requirements for measuring relays
(Part B/Set 2)-1987
*Specification for electrical relays for power system
duction and list of parts ( jrst revision ).
3
and
list
of
parts
1
2
protection: Part 0 General intro-
IS : 3231 ( Part 3/Set 3 ) - 1987
(Part
3/Set
l)-1987
Requirements
for particular
group of relays;
Section 1 Non-specified
time or independent
specified time measuring relays
(Part
S/Set 2)-1987
Requirements
for particular
group of relays;
Section
2 Dependent specified time measuring
relays
(Part
3)Sec
Requirements
for particular
Section 3 Biased (percentage)
3)-1987
group of relays;
differential relays.
0.3 According to classification on hierarchical
basis [ see IS : 3231 (Part O)1986* 1, this standard is a third level document.
0.4 In preparing
following:
this
standard,
assistance
has
been
drawn
from
the
IEC Pub 255-l 3 (1980) Electric relays : Part 13 Biased ( percentage ) differential relays. Internationa!
Electrotechnical
Commission,
BS 142 : Section
4.1:1984
Electrical
protection
relays: Part 4
Requirements
for multi-input
energizing
quantity
relays:
Section
4.1 Specification
for biased ( percentage ) differential
relays. British Standards Institution.
0.5 This standard ( Part 3/&c 3 ) should be read in conjunction
with
IS : 3231 ( Part P/Set 2 ) -1987-t to which a reference has been made, as
these relays constitute a particular sub-family (group) of measuring
relays
with more than one input energizing quantity.
1. SCOPE
1.1 This standard (Part 3/Set 3) specifies the performance requirements of
electrically
biased
(percentage)
differential
relays and the parameters
whose values are to be declared by the manufacturer
of such relays. It also
specifies methods of presentation
of the characteristics
and performance
of
these relays.
1.2 This standard
applies to relays designed for the
particularly
in ac generators,
motors and transformers.
detection
of faults
1.3 This standard covers the majority
of biased (percentage)
differential
relays and also, for example, those where the restraint percentage increases
as the through-current
increases.
For particular
cases, supplementary
requirements
may be stated in lower level standards.
*Specification
for electrical
relays for power system protection:
Part 0 General
introduction and list of parts ( jirst revision 1.
@pecification
for electrical relays for power system protection: Part 2 Requirements
for principsl families, Section 2 General requirements for measuring relays.
I$ : 3231 ( Part 3/$ec 3 ) - 1987
1.4 This standard
applies only to relays in a new condition.
1.5 This standard does not apply to relays designed for busbar protection,
nor does it apply to current differential (for example, pilot wire) relays
used for the protection of transmission lines.
2. TERMINOLOGY
2.0 For the purpose of this standard, the definitions
(Part 9) -1986* and the following shall apply.
2.1 Differential
Relay
A relay which,
respond to differential current.
2.2 Biased
(or Percentage) Differential
in which the designed response is modified
by
given
its design,
in IS : 1885
is intended
Relay A differential
by a restraint current.
2.3 Differential
Current
In a differential
the phasor difference between specified incoming
to
relay
relay, a current which is
and outgoing currents.
2.4 Restraint
Current
In a differential relay, the combination of incoming and outgoing currents, which restrains operation of the relay.
2.5 Restraint
Percentage
The ratio, expressed as a percentage,
ween the differential current and the restraint current(s) up to which
relay does not operate.
betthe
NOTE - The definition of restraint percentage ignores an error, which may not
be negligible, due to the finite operating current required under zero restraint conditions. This may be taken into account when necessary.
2.6 Through Current In a differential relay, that portion of the total
incoming current which is also present in the outgoing current.
3. STANDARD
VALUES
3.1 Input and Auxiliary
Energizing
Quantities
The standard values of input and energizing quantity
specified in IS : 3231 ( Part P/Set 2 )-1987j-.
3.2 Standard
Factors
and
Ranges
Reference
Standard
Values
Values
and Frequency and of frequency are
of
Influencing
Quantities
and
of Their
Nominal
and Extreme
3.2.1 Influencing Quantities and Factors The standard reference conditions are specifiedin Table 1 of IS : 3231 (Part P/Set 2) -1987’1. In addition, the standard conditions given in Table 1 in this standard apply to
biased (percentage)
differential relays.
*Electrotechnical
vocabulary : Part 9 Electrical relays (first revision ).
jSpecification for electrical I clays for power system protection: Part 2 Rcquirrments
for principal families, Section 2 General requirements for measuring relays.
5
IS : 3231 ( Part
TABLE
1
3/Set 3 ) - 1987
STANDARD
REFERENCE
CONDITIONS
AND TEST
OF INFLUENCING
QUANTITIES
AND FACTORS
TOLERANCES
( Clause 3.2.1 )
INFLUENCINO QUANTI’PP OR FACTOR
REFERENCE
CONDITIONS
TEST TOLERANCES
(3)
r
1
1
Characteristic
and input
energizing
quantities
[
<
1
I
1 Phase angle between input
energizing quantities
I
{
1 Transient
in ac
!
[
Auxiliary
energizing
quantities
Input energizing currents
Restraint current
Differential
current
{
Setting
1
~.%Ye
r
Transient
in ac
1
dc
component
value(s)
where
adjustments
are
dc
component
AS agreed between
and the user
0”
Zero
( see Note )
As agreed between
and the user
Zero
( see Note )
the manufacturer
f2”
5 percent of peak
ac value
the manufacturer
5 percent of peak
ac value
NOTE - In the special case of relays in which polyphase
measurements
are
made on a single relay, the manufacturer
shall define which of the input currents
shall be under reference conditions.
3.2.2 Limits of the Nominal Ran*Tes af Injluencing Quantities and Factors The standard values are specified m Table 2 of IS : 3231 ( Part 2ISec 2 )1987*. In addition, the standard values given in Table 2 of this standard
shall apply to biased ( percentage ) differential relays.
3.3 Characteristic
Quantity(ies)
and Setting Range(s) - There are
no standard rated values of either characteristic
quantity(ies)
or setting
range(s).
The values and the limits of setting range(s) shall be as agreed
to between the manufacturer
and the user.
3.4 Restraint Percentage - There are no standard values of restraint
percentage.
The setting values shall be as agreed to between the manufacturer and the user.
__~____~
*Specification
for electrical relays for power system protection : Part 2 Requirements
for principal families, Section 2 General requirements
for measuring relays.
6
IS : 3231 ( Part 3/Set 3 ) - 1987
TABLE
2 STANDARD
VALUES
RANGES OF INFLUENCING
OF THE LIMITS OF THE NOMINAL
QUANTITIES
AND FACTORS
( Clause 3.2.2 )
INFLTJENCINGQUANTITYOR
FACTOR
NOMINAL
(2)
(1)
Characteristic
and input
energizing
quantities
I
1
{
f
I
:
Auxiliary
energizing
quantities
I
I
I
{
Reference input energizing quantity
Non-reference input energizing quantity
Phase angle between input energizing
quantities
Frequency
Waveform
Steady-state dc component in ac
Transient dc component in ac
Voltage or current frequency
Frequency
Waveform
ac component
r
I1 As agreed to between the
<
manufacturer and the
user
I
r As agreed to between the
manufacturer and the
f
user unless specified
I in this standard
0 to 12 percent of the
rated dc value
in dc ( ripple )
Steady-state dc component in ac
r As agreed to between the
Transient dc component in ac
i
manufacturer and the
I
3.5 Resetting and Disengaging
Ratios of the resetting and disengaging
ratios. The
between the manufacturer
and the user.
4. OPERATION
RANGE
user unless specified
in this standard
There are no standard values
values shall be as agreed to
AND ACCURACY
4.1 Operation
4.1.1 Operating
Characteristics - The
manufacturer
shall declare the
operating
characteristics
of the relay under reference
conditions,
these
including the reference setting of the differential circuit, and as the maximum and minimum
setting of the restraint
circuits, when applicable.
Minimum
differential
current shall be declared by the manufacturer.
4.1.2 E$rcfive
Range range of restraint current
*Electrotechnical
vocabulary
The manufacturer
shall declare
the effective
values [ see 6.7 of IS : 1885 ( Part 9 )-1986* 1.
: Part 9 Electrical
7
relays (first revision).
IS : 3231 ( Part J/See 3 ) - 1987
4.1.3 Muximum Through Current - The manufacturer
shall declare the
maximum through current up to which the relay produces no output. The
relay shall be able to withstand
the sudden application and removal
of
through current up to this value. This duration shall be declared by the
manufacturer
and shall be at least 100 ms.
NOTE - This maximum value is based on a test in which there is no intentional differential current, the incoming and outgoing ( through ) current should
be equal.
restraint,
4.1.4 Harmonic Restraint - For relays which have harmonic
the manufacturer
shall declare which of the harmonics
have a restraining
effect and explain how the harmonic
restraint
interacts with the fundamental frequency restraint. The amount of each of these harmonics
which
will prevent operation of the relay shall be declared,
the amount being
expressed as a percentage of the differential current at the rated frequency.
If different values are obtained under steady-state and dynamic conditions
the highest value shall be stated.
4.2 Accuracy
- For biased ( percentage ) differential relays, considerations of accuracy apply to the operating characteristics
and to the operatFor these items, the manufacturer
ing time under reference
conditions.
shall declare the assigned errors in accordance with IS : 323 1 (Part 2/Set 2)198i”.
4.2.1 Operating Characteristics - The accuracy of the operating
characteristics may be shown graphically
by maximum
and minimum lines, as
in Fig. 1. Alternatively,
the manufacturer
may declare the restraint
percentage,
with a plus or minus tolerance,
over the effective range of
restraint current.
4.2.2 Operating Time - The accuracy
of the operating times may be
shown graphically
as in Fig. 2, or it may be declared by the ma’nufacturer
for a specific range ( normally 3 to 10 times ) of differential currents.
NOTE -
5. METHODS
Normally
only a maximum
OF PRESENTING
AND PERFORMANCE
operating
RELAY
time is specified.
CHARACTERISTICS
5.1 Operating
Characteristics
- When
presenting
the
characteristics
of a relay, the manufacturer
may use the average
ing and outgoing currents as a restraint current.
operating
of incom-
*Specification for electrical relays for power system protection:Part
2 Requirements
for principal families, Section 2 General requirements for measuring relays.
8
IS : 3231 ( Part 3/Set 3) - 1387
LIMITS
OF ERROR
UNDER
REFERENCE
CONDITIONS
NON-OPERATE
RESTRAINT
NOTE -
CURRENT
ZONE
(FOR
EXAMPLE
ll’)
Setting value shall be stated.
FIQ. 1 OPERATING CHARACTERISTIC UNDER REFERENCE CONDITIONS
5.1.1 Figure 1 shows the recommended
method of presenting the operation characteristics
and associated limits. Differential
current is shown on
the vertical axis and restraint current on the horizontal
axis.
NOTE 1 - Methods other than graphical
the operating characteristics.
NOTE 2 - Where appropriate,
a single and a three-phase basis.
may be used for the presentation
the manufacturer
should declare
5.2 Operating
Time
- Figure 2 shows the recommended
presenting
the operating
time and associated
limits over
currents to be declared by the manufacturer
( see 4.2.2 ).
of
results both on
method
a range
of
of
5.2.1 The manufacturer
shall declare the operating times of the relay
under reference
conditions
at three and ten times the operating value of
the differential
current at its minimum
and maximum
settings ( if any ).
Where necessary, this shall be done on a three-phase basis.
5.3 Harmonic
Restraint
- Figure 3 shows a recommended
method of
presenting
in graphical
form, the harmonic
restraint characteristic
of a
differential
relay which uses only the harmonic frequency
to restrain.
Figure 4 shows a recommended
method
for a differential
relay that
responds to more than one harmonic frequency.
9
IS a 3231 ( Part 3ISec 3 ) - 1987
A
:
F
UPPER
LIMIT
OF TIME
::
F
2
5;DIFFERENTIAL
CURRENT
’
f MULTIPLE OF SETT ‘ING
I
((,=il)
VALUE
I _ LIMITS OF EFFECTIVE H I
RANGE
FIG. 2
‘C
5
f
u
OPERATING TIME UNDER REFERENCE CONDITIONS
OPERA1
E
AT RATED
FREQUENCY
IxF = CURRENT
Af SPECIFIED
HARMONIC
FREQUENCY
IFfCURRENT
NON-OPERATE
NOTE -
FIG. 3
Setting value shall be stated.
HARMONIC RESTRAINT CHARACTERISTICSHOWIKO RESPONSE
TO A SINGLE HARMONIC FREQUENCY
10
IS : 3231 ( Part 3/Set 3 ) - 1987
0I
50
loo
150
200
250
FREQUENCY
FIG. 4
300
OF
(t-k)
w
IXF
HARMONICRESTRAINTCHARACTERISTIC
SHOWINGRESPONSE
TO DIFFERENTHARMONICFREQUENCIES
6. THERMAL
REQUIREMENTS
6.1 The thermal requirements
as specified in IS: 3231 (Part P/Set 2)-1987*
In addition,
the following requirement
applies to
shall be applicable.
biased ( percentage
) differential
relays:
When a differential
the restraint circuit,
manufacturer.
7. MECHANICAL
circuit has a lower thermal capability
than
the thermal capability shall be declared by the
REQUIREMENTS
7.1 The mechanical
1987*
requirements
shall be applicable.
as specified
8. VALUES
OF LIMITS OF OPERATIVE
ENERGIZING
QUANTITIES
in IS : 3231 ( Part P/Set 2)-
RANGE
OF AUXILIARY
8.1 The values of limits of operative range of auxiliary energizing
ties shall be as specified in IS : 3231 ( Part P/Set 2 )-1987*.
9. SHOCK
quanti-
AND VIBRATION
9.1 The relevant
applicable.
provisions
of IS : 3231
( Part P/Set 2 )-1987*
shall be
*Specification for electrical relays for power system protection: Part 2 Requirements
for principal familirs, Section 2 General requirements for measuring relays.
11
( Part a/SecP ) - 1987
1s : 3231
10. CONTACT
PERFORMANCE
10.1 Requirements
11. RATED
of IS : 3231 ( Part
in IS:
apply
shall
apply.
3231 ( Part P/Set 2 )-1987t. In
to baised ( percentage
) diffe-
If the differential
circuit
has a lower thermal capacity ( and,
therefore,
a lower rated value ) than the restraint circuits it
should
be considered
to have the same rated value as the
restraint circuits for the purpose of making burden measurements;
and
b) The manufacturer
shall declare
priate set of input terminals:
1) with no differential
2) with differential
12.
I )-1986*
BURDEN
11.1 The rated burdens are specified
addition, the following requirements
rential relays:
a)
l/Set
current
current
the burden
flowing;
between
each appro-
and
equal to input current.
INSULATION
12.1 The relevant
applicable.
provisions
of IS
13. MARKINGS
AND DATA
: 3231 ( Part l/Set 2 )-19861
13.1 The markings and data requirements
( Part P/Set 2 )-1987t.
14.
HIGH-FREQUENCY
14.1 Where
required
frequency
disturbance
shall be applicable.
15.
DISTURBANCE
shall
be
shall be as specified in IS : 323 1
TEST
for static relays, the requirements
for the hightest specified
in IS : 3231 ( Part l/Set 3 )-19868
TESTS
15.1
General
15.1.1
The
classification
ing shall be in accordance
of tests and the requirements
for routine testwith 12 of IS : 3231 ( Part P/Set 2 )-19877.
*Specification
for electrical
relays for power system protection: Part 1 General
requirements, Section 1 Contact performance (Jirst revision ).
tspecification
for electrical relays for power system protection : Part 2 Requirements
for principal families, Section 2 General requirements for measuring relays.
SSpecification
for electrical
relays for power system protection: Part 1 General
requirements,
Section 2 Insulation tests (Jirsl revision ).
EjSpecification for electrical
relays for power system protection : Part 1 General
requirements, Section 3 High frequency disturbance test for static relays (f;rsl reuisiorr ).
12
IS : 3231 ( Part 3/&c 3 ) - 1987
15.1.2 Unless
in 15.2 to 15.5.
otherwise
specified,
the
test methods shall be as given
15.2 Tests Related to Accuracy and Operating Characteristics
15.2.1 TestConditions
a) All influencing quantities and factors shall be at the reference
values ( within the specified test tolerances ) unless otherwise
stated in this standard;
b) The auxiliary energizing quantities shall be at the rated value for
all tests unless otherwise stated in this standard;
c) The method of applying the input energizing quantity (for example, suddenly or gradually) shall be declared by the manufacturer
if not prescribed in this standard; and
d) Timing tests shall be done with only one of the restraint windings
energized over the range of values of differential current for
which specified times are indicated by the manufacturer.
Other
tests with through current present may be agreed to between the
manufacturer and the user.
15.2.2 Test Circuits and Methods for Measuring Relay Characteristics - The
test instructions in this clause are based on single-phase relays. Where
polyphase relays are provided, they shall be tested with relevant combinations of phase currents and magnitudes of the test currents shall be as
declared by the manufacturer.
15.2.2.1 Operating characteristics ( see Fig. 5 )- For differential relays,
the tests are performed as follows:
a) With I, equal to zero, check the threshold value of the relay;
b) With low values of It, increase Ia until relay operations;
c) Increase I, to higher value. Again increase Id until relay operates;
and
d) Repeat for a number of different 1% values up to the limit of the
effective range. Values shall be as declared by the manufacturer.
Frc. 5 TEST CIRCUITFOR OPERATINGCHARACTERISTIC
TEST
13
IS t 3231 ( Part 3/Set 3 ) - 1987
15.2.2.2 Operating time characteristics ( see Fig. 6 ) relays, the tests are performed as follows:
4
For differential
Set current level with switch closed;
b) Open
the switch;
4
4
Apply test current by closing switch, and measure operating time;
4
Repeat the test procedure for higher values of current.
If point-on-wave control is used, choose an angle which gives
maximum time. If this control is not available, take ten shots at
a random closing angle; and
FIG 6
TEST CIRCUIT FOR OPERATING TIME TEST
15.2.2.3 Harmonic restraint characteristics ( see Fig. 7 ) test procedure may be used:
The following
Let Ir be the current at rated frequency and let IxB be the current at
specified harmonic frequency ( see Fig. 3 ):
a) Set value of I,,
b) Increase
to initial value,
Ir from zero until relay operates.
The reference condition of the phase relationship
and Ixp shall be as declared by the manufacturer;
between IP
c) Repeat at different values of IxE;
d) Repeat (b) with different phase relationship
plotting additional curves, if necessary; and
between I= and 1.r
e) Having found the values under steady-state conditions, the test
shall be repeated under dynamic conditions by switching IF and
IXp simultaneously from zero.
The test shall be conducted with no transient dcin the fundamental current. If necessary, increase Ixr until relay is blocked
from operating.
14
IS t 3231 ( Part 3,Sec 3 ) - 1987
FIG. 7 TEST CIRCUITFOR HARMONIC RESTRAINT TEST
15.3 Thermal
formed
15.4
Tests - The tests for thermal requirements
in accordance
with IS : 3231 ( Part B/Set 2 )-1987*.
Performance
with Through
shall
be per-
Current
15.4.1 When testing to determine the limiting value of through current
the duration of application of
up to which the relay will not operate,
current shall be declared by the manufacturer.
15.4.2 For relays with more than two restraint circuits, the total current
shall be applied to one restraint circuit as an incoming
current, and divided approximately
equally among the other restraint circuits, as outgoing
currents. If one or more of the restraint windings are of minor importance,
the test procedure shall be declared by the manufacturer.
15.5 Mechanical
Tests be carried out in accordance
The tests for mechanical
requirements
shall
with 14 of IS : 3231 ( Part P/Set 2)-1987*.
15.5.1 In addition to the test conditions specified in 14.1.1 of IS : 3231
( Part P/Set 2 )-1987*,
the following condition
shall also be fulfilled for
differential
relays:
At values of the differential
current
of zero for the initial value
and three times the operating value for the final value. Unless otherwise agreed,
the differential
current
shall be applied
suddenly
( seeFig. 6 ),
*Specification for electrical relays for power system protection: Part 2 Requirements
for principal families, Section 2 General requirements for measuring relays.
15
--_I__
-_I_--_..-
____
_ ~_
1s : 3231 ( Part 3/Set 3 ) - 1987
[ Continned fram page 2 )
Panel for the Revision of IS : 3231-1965,
ETDC
35/P9
Convener
SHRI B. S. SHARBXA
U. P. State Electricity
Board, Lucknow
Mem hers
DR B. K. DASGUPTA
SHRI H. DE
I )IRECTOR ( CIP 1
SHRI P. K.&TuR;
Jyoti Ltd, Vadodara
Hindustan Brown Boveri Ltd, Vadodara
Central Electricity Authority, New Delhi
Power Supply
Co
TaLta Hydro-Electric
Bombay
EI iglish Electric Co of India Ltd, Madras
Tata Consulting Engineers, Bombay
I;nar T.
--___
-. V. G. M~N~N
~-- -Sasr A. A. PAUL
SHRI P. P. KARHADE ( dllernate )
University of Roorkee, Roorkee
SHRI A. K. RAJA
ASEA Ltd, Bangalore
DR M. T. SANT
Larsen & Toubro Ltd, Bombay
SEW J. V. VAIDYA
16
Ltd,
Download