Storing Flammable and Combustible Liquids in Containers using NFPA 30 2021 Michigan Safety Conference (MSC) April 13, 2021 | Mike Marando, P.E. | Senior Engineer mmarando@nfpa.org NFPA.ORG | © National Fire Protection Association. All rights reserved. NFPA data shows that an average of 1,400 warehouse fires occur every year (2014-2018) Annual averages • $159 million in direct property damage • 20 civilian injuries • 2 civilian deaths Flammable and combustible liquids, gases, piping and filters first ignited in 7% of fires, causing 31% of civilian injuries and 9% of direct property damage. NFPA.ORG | © National Fire Protection Association. All rights reserved. 2 Sherwin Williams (Dayton, Ohio - 1987) NFPA.ORG | © National Fire Protection Association. All rights reserved. 3 Magnablend (Waxahachie, Texas, 2011) NFPA.ORG | © National Fire Protection Association. All rights reserved. 4 NFPA 30 Overview and General Definitions Accessing NFPA Document Information Pages • www.nfpa.org – Codes and Standards tab NFPA.ORG | © National Fire Protection Association. All rights reserved. 6 Accessing NFPA Document Information Pages www.nfpa.org/30 Current and Prior Editions Ask a Technical Question NFPA.ORG | © National Fire Protection Association. All rights reserved. 7 Properties Fundamental hazardous property of flammable and combustible liquid is: Their ability to produce vapors that are ignitible. NFPA.ORG | © National Fire Protection Association. All rights reserved. 8 Flammable Liquid Any liquid that has a closed-cup flash point below 100°F (38°C) and a Reid vapor pressure that does not exceed 40 psia (276 kPa) at 100°F (38°C) Class I NFPA.ORG | © National Fire Protection Association. All rights reserved. Combustible Liquid Any liquid that has a closed-cup flash point at or above 100°F (38°C) Class II and III Note that Class II and III liquids should be treated as Class I liquids if they are heated above their flash point. 4.2 9 Ignitible Liquid Classes and Examples NFPA.ORG | © National Fire Protection Association. All rights reserved. 3.3.34, 4.2 10 Nomenclature change in the 2021 edition “Flammable and Combustible” is replaced with “Ignitible (Flammable and Combustible)” Transitioning from “flammable” and “combustible” which have varying definitions between government agencies Ignitibility of liquids will be indicated by liquid class (Class IA, IB, IC, II, IIIA, or IIIB) The liquid class uses flash point and/or boiling point NFPA.ORG | © National Fire Protection Association. All rights reserved. 11 What is a “Flammable Liquid” or “Combustible Liquid?” NFPA.ORG | © National Fire Protection Association. All rights reserved. 12 Scope and Purpose NFPA 30 applies to the storage, handling, and use of ignitible (flammable and combustible) liquids, including waste liquids Provides fundamental requirements for the safe storage and handling of flammable and combustible liquids NFPA.ORG | © National Fire Protection Association. All rights reserved. 1.1. and 1.2 13 NFPA 30 Roadmap Containers, IBCs, Portable Tanks or Fixed Tanks? Containers, IBCs, Portable Tanks Fixed Tanks NFPA.ORG | © National Fire Protection Association. All rights reserved. See the Navigating NFPA 30 flowchart Start with Chapter 9 then Chapters 10-18 as necessary Start with Chapter 21 then Chapters 22-27 as necessary A.1.3 NFPA 30 1. 2. 3. 4. 5. 6. Administrative References Definitions Liquid Classification Reserved Fire/Explosion Prevention and Control 7. Electrical Systems 8. Reserved NFPA.ORG | © National Fire Protection Association. All rights reserved. 9. 10. 11. 12. 13. Container Storage – General Mercantile Industrial Storage Detached, Unprotected Buildings 14. Hazardous Material Lockers 15. Outdoor Storage 16. Fire Protection Design Criteria 15 NFPA 30 17. 18. 19. 20. Processing Facilities Dispensing and Handling Specific Operations Reserved NFPA.ORG | © National Fire Protection Association. All rights reserved. 21. 22. 23. 24. 25. 26. 27. 28. 29. Tank Storage – General ASTs USTs Storage Tank Bldgs. Storage Tank Vaults Reserved Piping Systems Loading/Unloading Wharves 16 Scope NFPA 30 does not apply to Transportation (USDOT) Liquefied petroleum gas (propane - NFPA 58) or cryogenic liquids (NFPA 55) Aerosol products (NFPA 30B) Use and installation of individual alcoholbased rub (ABHR) dispensers (NFPA 1 – Fire Code/ NFPA 101® – Life Safety Code®) NFPA.ORG | © National Fire Protection Association. All rights reserved. 1.1.2 17 NFPA 30 Related Documents Facilities that comply with the following also comply with NFPA 30 NFPA 1 – Fire Code NFPA 45 – Laboratories Using Chemicals NFPA 101® – Life Safety Code® NFPA.ORG | © National Fire Protection Association. All rights reserved. 1.5.3 18 NFPA 30 Related Documents Operations that comply with the following also comply with NFPA 30 NFPA 30A – Fuel dispensing for vehicles/marine craft/fleet operations/repair garages NFPA 31 – Indoor fuel storage tanks for oil-burning appliances NFPA 32 – Dry cleaning operations NFPA 33 – Spray application of liquids/Glass-fiber reinforced plastics NFPA 34 – Dipping and roll-coating operations NFPA 35 – Manufacture of organic coatings/ Storage and handling of nitrocellulose NFPA 36 – Solvent extraction of edible oils NFPA 37 – Fuel storage tanks for stationary engines and turbines NFPA.ORG | © National Fire Protection Association. All rights reserved. 1.1.2 and A.1.1.2 19 Equivalency NFPA 30 does not intend to prevent use of systems, methods, or devices of equivalent or superior quality, effectiveness, or safety. Authority Having Jurisdiction (AHJ) determines equivalency. NFPA.ORG | © National Fire Protection Association. All rights reserved. 1.5 20 Retroactivity NFPA 30 does not apply retroactively unless Authority having jurisdiction (AHJ) determines that a distinct and identifiable hazard exists NFPA 30 specifies that a requirement is retroactive. NFPA.ORG | © National Fire Protection Association. All rights reserved. 1.4 21 Definitions Shall – Mandatory Used in the main code Should – Recommended Used in the annexes NFPA.ORG | © National Fire Protection Association. All rights reserved. 22 Authority Having Jurisdiction (AHJ) - Enforcer An organization, office, or individual Approve equipment, materials, an installation, or a procedure Fire department, fire marshal, insurance company, building inspector, electrical inspector, site safety officer NFPA.ORG | © National Fire Protection Association. All rights reserved. 3.2.2/A.3.2.2 23 Who is my AHJ? – It depends… Who can levy fines or shut down a plant? Who is in charge in an emergency? Who is in charge of day-today safety operations? Who imposes the strictest requirements? NFPA.ORG | © National Fire Protection Association. All rights reserved. There may be more than one AHJ! 24 MAQs, Storage Areas and Containers Containers within NFPA 30 Scope Drums/Containers ≤ 119 gal IBCs ≤ 793 gal Overpack Containers ≤ 60 gal NFPA.ORG | © National Fire Protection Association. All rights reserved. Portable tanks ≤ 660 gal Courtesy of Greif, Inc. and National Packaging Services 9.1 26 Key Definitions Maximum Allowable Quantity (MAQ) Control Area A building or portion thereof within which ignitible liquids are allowed to be stored, dispensed, and used or handled in quantities that do not exceed the maximum allowable quantity (MAQ) The quantity of ignitible liquid permitted in a control area without additional safeguards A threshold for each liquid class stored in an area having no special protection measures Not applicable to liquid processing facilities. (Chemical plants) NFPA.ORG | © National Fire Protection Association. All rights reserved. 3.3.2.1/3.3.39/A.3.3.39/17.1 27 Protected vs. Unprotected Storage Protected Storage Areas having automatic fire protection that prevents a fire from spreading beyond the design area. Unprotected Storage Areas have a risk of fire spreading beyond the design area Meets Chapter 16 requirements and/or AHJ approved for alternative protection systems NFPA.ORG | © National Fire Protection Association. All rights reserved. 9.2.1/A.9.2.1, 9.2.2/A.9.2.2 28 MAQ flow chart Does Chapter 9 apply? (9.1.4) Container Size Table 9.4.3 Yes No MAQ Table Special 9.6.1 Occupancy? No 9.6.2.1 Yes Control Area Table 9.7.2 MAQ Table 9.6.2.1 MAQ Exceeded per Control Area? Yes No additional construction requirements NFPA 30 Ch 10-18/NFPA 1 Fire Code Unprotected Warehouse Building MAQ Limitation Unprotected Construction/ Table 12.6.2.2 Yes Warehouse Sprinkler (if applicable) (>500 sq ft)? Flow Chart Protected Warehouse No Liquid-Container Combination Table 12.8.1 (if applicable) NFPA.ORG | © National Fire Protection Association. All rights reserved. No Quantity Limitation for Liquid Storage Rooms Table 12.6.1.1 Yes Liquid Storage Room (≤500 sq ft)? No 29 Exceptions to Chapter 9 container requirements Containers, IBCs, tanks in operations areas (Ch. 17) Distilled spirit and wines in casks Certain medicines, foodstuffs, cosmetics, consumer products (<20% concentration) Lowered from 50% based on fire testing Rescinded beverage exemption for containers < 1.3 gal (5 L) NFPA.ORG | © National Fire Protection Association. All rights reserved. 9.1.4 30 Additional container exemptions/requirements When packaged according to commonly accepted practices for retail, the following are exempt from 9.4.1 and 9.4.3 Medicines, beverages, foodstuffs, cosmetics, and other common consumer products NFPA.ORG | © National Fire Protection Association. All rights reserved. 9.4.1.2 31 Acceptable Containers in a Control Area Reference Table 9.4.3 for the maximum allowable size for the following: Any DOT-approved metal can, drum, portable tank, IBC Certain DOT-approved plastic containers, IBCs Certain fiber drums and IBCs Metal and plastic safety cans Glass containers NFPA.ORG | © National Fire Protection Association. All rights reserved. 9.4.1 and Table 9.4.3 32 A sample of maximum container sizes Container Type Metal (other than drums) or approved plastic Metal drum (UN 1A1/1A2) Approved metal portable tanks and IBCs Class Class Class Class Class IA IC IIIA IB II 1.3 gal 5.3 gal (5 L) (20 L) 119 gal (450 L) 793 gal (3000 L) Rigid plastic IBCs (UN 31H1 or 31H2) and composite IBCs with rigid inner receptacle (UN31HZ1) NP 793 gal (3000 L) Fiber drum - NMFC or UFC Type 2A; Types 3A, 3B-H, or 3B-L; or Type 4A NP 119 gal (450 L) NP: Not permitted unless an approved fire protection system for the specific container and protection against static electricity are provided. NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 9.4.3 (excerpt) 33 IBCs for Class I liquid storage Acceptable for Class I liquid storage Not Acceptable for Class I liquid storage (Plastic or plastic lined containers) Courtesy of National Packaging Services, Joseph Scheffey (Hughes Associates), and Snyder Industries. NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 9.4.3 34 When is an IBC/container in storage? Staging a container/IBC/portable tank is limited to the following: In use for a process Are filled during a single shift Required to supply a continuous 24-hour shift Otherwise, the IBC/container is considered to be in storage Only NFPA approved IBCs and portable tanks used in a process and staged in a process area can be filled in a process area. (Except Class IIIB liquids or intermediate products manufactured in the process area). NFPA.ORG | © National Fire Protection Association. All rights reserved. 18.4.8/18.4.9 35 MAQs per Control Area – General Occupancy MAQs are defined in Table 9.6.1 for General Occupancy The following have additional requirements Chapter 10 - Mercantile operations Chapter 12 - Maximum storage heights and total quantity per Pile or Rack (Table 12.6.2.2) Section 13.6 - Detached, unprotected buildings (which mostly refer to 12.6) Section 18.5.4 - Incidental operations NFPA.ORG | © National Fire Protection Association. All rights reserved. 9.6.1 36 General Occupancy MAQs per Control Area Liquid Class(es) IA IB and IC IA, IB, IC combined II IIIA IIIB Quantity Notes gal 30 L 115 120 460 330 13,200 1,265 50,600 1, 2 1, 2 1, 2, 3 1, 2 1, 2 1, 2, 4 1. 2. 3. 4. Quantities may be doubled where stored in approved liquid storage cabinets or in safety cans. Quantities may be doubled in buildings equipped with an automatic sprinkler system per NFPA 13. Containing not more than the MAQ per control area of Class IA, IB, or IC liquids, individually. Unlimited quantities in a building equipped with an NFPA 13 compliant automatic sprinkler system and designed in accordance with NFPA 30 Chapter 16 protection criteria 5. Where both (1) and (2) apply the increase is permitted to be applied accumulatively (four times MAQ) Exception: As modified by 9.6.2 and Chapters 10 through 14. NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 9.6.1 37 Special Occupancies Assembly Ambulatory health care Business Day care Detention and correctional Educational Health care Residential These occupancies can apply to a room or an entire building For mixed occupancies see NFPA 101 – higher MAQs may be possible than those in NFPA 30. - A chemical storage area that meets NFPA 101 requirements within a school NFPA.ORG | © National Fire Protection Association. All rights reserved. 9.6.2.1 38 Special Occupancy MAQs per Control Area The MAQ for Classes I, II, and IIIA liquids can be exceeded if, All liquids are stored in cabinets and Total aggregate quantity ≤180 gallons Where protected with sprinklers per NFPA 13, Class IIIB MAQs can be doubled for: Quantity Liquid Class(es) I and II IIIA IIIB gal L 10 60 120 38 227 454 Ambulatory health care/Health care Day care/Educational facilities NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 9.6.2.1, 9.6.2.2 and 9.6.2.4 39 Requirements for elevated or basement locations Above Grade Below Grade Floor Maximum Allowable Number of Fire Resistance Level Quantity per Control Rating for Control Area Areas per Fire Barriers (percent)* Floor (hour)† >9 1 5 7–9 2 4–6 12.5 2 3 50 2 75 3 1 100 4 1 1 75 3 2 50 2 Lower Not Allowed than 2 NFPA.ORG | © National Fire Protection Association. All rights reserved. * - Permitted increases in Table 9.6.1 allowed † - Fire barriers include floors and walls to isolate control areas from each other Class I liquid storage is not allowed in basements. Table 9.7.2 and 9.7.3 40 Ignitible Liquid Density Limitations for Liquid Storage Rooms Total Automatic Fire Total Allowable Floor Protection Quantity Area (ft2) Provided?* (gal/ft2 of floor area) No 2 ≤150 Yes 5 No 4† >150 and ≤500 Yes 10 For SI units, 1 ft2 = 0.09 m2 1 gal = 3.8 L * - The fire protection system can be automatic sprinklers, water spray, carbon dioxide, dry chemical, or other approved system. (See Chapter 16) † - Total allowable quantities of Class IA and IB liquids [FP < 73°F (22.8°C)] cannot exceed the quantities permitted in Table 12.6.2.2 or Section 12.6.2.3 NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 12.6.1.1 41 MAQs* for Unprotected Liquid Warehouses Containers Liquid Class IA IB IC II IIIA IIIB Maximum Max Total Maximum Storage Quantity Total Height (ft) per Pile Quantity (gal) or Rack Section (gal) 660 5 1,375 2,750 10 4,125 8,250 27,500 15 13,750 55,000 Metal Portable Tanks and Rigid Nonmetallic IBCs and Metal IBCs Composite IBCs Maximum Max Total Maximum Maximum Max Total Maximum Storage Quantity Total Storage Quantity Total Height per Pile Quantity Height per Pile Quantity (gal) (gal) (ft) or Rack (ft) or Rack Section Section (gal) (gal) NP 2,000 NP 4,000 7 5,500 11,000 4,125 8,250 7 44,000 27,500 22,000 13,750 88,000 55,000 * – Except as indicated in Chapter 9 and Chapter 13; NP – Not Permitted (see Table 9.4.3) See 12.6.2.3 for mixed liquid classes in one rack or pile. NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 12.6.2.2 42 Liquid-Container Combinations Permitted in Protected General-Purpose Warehouses Liquid Type Storage Arrangement Max Roof Height Container Size 30 ft 40 ft Unlimited ≤5 gal (19 L) ≤48 oz (1.4 L) ≤5 gal (19 L) ≤2 oz (60 ml) ≤1 gal (4L) ≤6 oz (180 ml) ≤1 gal (4 L) ≤59 oz (1.75 L) Solid pile or palletized 40 ft ≤59 oz (1.75 L) Glass Palletized or rack or solid pile 30 ft ≤5 gal (19 L) Steel FP ≥450°F (232°C) FP ≥200°F (93°C) FP ≤200°F (93°C) Ethanol or isopropanol (100%) Ethanol or isopropanol (≤50% by volume in water) Any flash point, boiling point >100°F (38°C) Rack Unlimited 30 ft NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 12.8.1 Container Construction Plastic/glass 43 Building and Sprinkler Requirements Protection Levels/High Hazard Levels "Protection Level" identifies additional building construction and fire protection requirements imposed by NFPA 1 and NFPA 5000® when the MAQ is exceeded Protection Level 2 (High Hazard Level 2) Protection Level 3 (High Hazard Level 3) Accelerated burning or deflagration hazard Support combustion Normally open containers or System pressure of 15 psig or greater Normally closed containers or System pressure less than 15 psig NFPA.ORG | © National Fire Protection Association. All rights reserved. NFPA 5000 6.3.2.4.3 and 6.3.2.4.4 45 Building Construction/Sprinkler Flow Chart Building Construction Requirements NFPA 5000® From MAQ Fire Resistance NFPA 5000 Flow Chart Ratings Tables 34.1.1.2 9.9.1 and 9.9.3/ Exemptions Manual Fire Applicable? Protection 9.10.2 Automatic Fire Protection Requirements Yes NFPA 30 Follow code listed in Chapter 16 34.1.1.2 where applicable Fire Protection Criteria Decision Trees • Metal Containers → Figure 16.4.1 (a) • Nonmetallic Containers → Figure 16.4.1 (b) • Water-Miscible Nonmetallic Containers → Figure 16.4.1 (c) No • Protection Level 2 → NFPA 5000 34.3.4 • Protection Level 3 → NFPA 5000 34.3.5 • Allowable Building Height and Area NFPA 5000 Table 7.4.1 Sprinkler Design Criteria • Tables 16.5.2.1 – 16.5.2.18 • New Tables 16.5.2.13 – 16.5.2.18 NFPA.ORG | © National Fire Protection Association. All rights reserved. Sprinkler Discharge Containment • Figure 16.8.1 Sprinkler Layout Schemes • Figures in 16.6 • New Schemes “D” “E” & “F” Fire resistance ratings for ignitable liquid storage areas Type of Storage Area Fire Resistance Rating (hr) Interior Walls, Ceilings, Exterior Intermediate Floorsa Walls Liquid storage room Floor area ≤ 150 ft2 Floor area > 150 ft2, but ≤ 500 ft2 Liquid warehouse 1 2 4b NR NR 4c NR: No requirement. No requirement for roofs. For SI units, 1 ft2 = 0.09 m2 aBetween liquid storage areas and any adjacent areas not dedicated to liquid storage. bA 4-hour firewall, in accordance with NFPA 221 is required except as follows: (1) Where storage is only Class IIIB liquids below their flash point, 2-hour fire resistance rated assemblies permitted. (2) Where protected by an automatic system (Ch. 16), 2-hour fire resistance rated assemblies are permitted. (3) Where protected by an automatic system (Ch. 16), accessory use areas (offices and restrooms) having a total area less than 10% of the liquid warehouse area do not require a fire resistance rating for the interior walls and ceilings. cThe fire resistance rating for walls located 10 ft to 50 ft from an important building or adjoining property that can be built upon is permitted to be 2 hours. Walls located greater than 50 ft or more from an important building or adjoining property that can be built upon do not require a fire resistance rating. NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 9.9.1 47 Protection Ratings for Fire Doors Fire Resistance Fire Protection Rating of Wall as Rating of Door Required by (hr) Table 9.9.1(hr) 1 3⁄4 2 11⁄2 4 3* *One fire door required on each side of interior openings for attached liquid warehouses. NFPA.ORG | © National Fire Protection Association. All rights reserved. Table 9.9.3 48 Fire Protection Portable extinguishers 40:B within 10 ft of the entrance to and outside of liquid storage area, and 40:B within 30 ft of Class I or II liquids located outside of a liquid storage area or 80:B within 50 ft of a storage area Hose connections where provided Sprinkler system per NFPA 13 Standpipe system per NFPA 14 NFPA.ORG | © National Fire Protection Association. All rights reserved. 9.10.2 49 Fire Protection Criteria Decision Trees Figure Liquid Container 16.4.1(a) Miscible / Nonmiscible Metal containers/ portable tanks, IBCs 16.4.1(b) Nonmiscible Nonmetallic containers and IBCs 16.4.1(c) Watermiscible Nonmetallic containers and IBCs NFPA.ORG | © National Fire Protection Association. All rights reserved. Generally used to select appropriate Section 16.5 design tables, but may reference NFPA 13 16.4 Fire Protection System Design Tables Tables 16.5.2.1 through 16.5.2.18 Provide design criteria for ceiling and in-rack sprinklers Establish maximum ceiling and storage heights Based on full-scale tests with horizontal ceilings Courtesy of FM Global NFPA.ORG | © National Fire Protection Association. All rights reserved. 16.5.2 New Fire Protection System Design Tables Table System Configuration 16.5.2.13 Sprinkler or Foam-Water Single- and DoubleRow Rack II and III Rack IB, IC, II and IIIA 16.5.2.14 IIIB (FP ≥ 450 °F) 16.5.2.15 16.5.2.16 Sprinkler Single- and DoubleRow Rack Ethanol/Propanol/ Methanol Pallets 50% Ethanol/Propanol/ Methanol and 50% Water 16.5.2.17 16.5.2.18 Liquid Class or Liquid NFPA.ORG | © National Fire Protection Association. All rights reserved. Container Metal (5-60 gal) Glass/plastic (Cartoned, <2 oz) Plastic (Cartoned or uncartoned, ≤5 gal, ≤48 oz) Glass/plastic (Cartoned, ≤ 6 oz) Glass/plastic (Cartoned, ≤1 gal, ≤59 oz) Glass/plastic (Cartoned, ≤59 oz) 16.5.2.13 – 16.5.2.18 Fire Protection Design Schemes Referenced in section 16.5 design tables Provide details on in-rack sprinkler placement and design criteria Describe barrier construction and placement Fire protection design schemes “D” “E” and “F” added for 2021 NFPA.ORG | © National Fire Protection Association. All rights reserved. 16.6 and Figure 16.6.2.1(a) Containment, Drainage, and Spill Control Figure 16.8.1 shows options for spill control Refer to Section 9.13 or Limit the spread of the sprinkler liquid discharge (Section 16.8.2) NFPA.ORG | © National Fire Protection Association. All rights reserved. 16.8/A.16.8 Other Automatic Fire Protection Systems Types of protection allowed with AHJ approval Automatic water spray and water mist systems Alternative sprinkler system configurations High expansion foams Gaseous or dry chemical systems Courtesy of FOGTEC® Fire Protection NFPA.ORG | © National Fire Protection Association. All rights reserved. 16.9 NFPA 5000 compared to IBC NFPA 5000® 34.2.3 34.2.4 34.2.5 34.2.6 34.3 34.3.1 34.3.2 34.3.3 34.3.4 34.3.5 34.3.6 34.3.7 Hazardous Materials Code. Special Information for Permit Application. Control Areas. Weather Protection. Requirements for Occupancies Exceeding the Maximum Allowable Quantity (MAQ) per Control Area for High Hazard Contents Protection Levels. General Requirements. Protection Level 1. Protection Level 2. Protection Level 3. Protection Level 4. Protection Level 5. 414.1.3 414.2 414.6.1 IBC Information Required Control Areas Weather protection Groups H-1, H-2, H-3, H-4 and H-5 415 415.1 415.1 415.7 415.8; 415.9 415.8; 415.10 415.10 415.11 NFPA.ORG | © National Fire Protection Association. All rights reserved. Scope Scope Special provisions for Group H-1 occupancies Special provisions for Group H-2 and H-3 occupancies; Group H-2 Special provisions for Group H-2 and H-3 occupancies; Groups H-3 and H-4 Groups H-3 and H-4 Group H-5 Summary NFPA 30 is moving towards standardizing ignitible liquid classification NFPA 30 provides requirements for ignitible liquids in a variety of storage configurations Additional requirements were added for 2021 based on fire testing Additional building construction requirements from NFPA 5000® Building Construction Safety Code® may be required NFPA.ORG | © National Fire Protection Association. All rights reserved. 57 THANK YOU! Find More NFPA 30 Content & Information: Visit nfpa.org/30 news tab for resources to help implement NFPA 30. Stay up-to-date with Mike’s hot topics on Mike's blog. Subscribe to NFPA LiNK™ for digital access to NFPA 30 with enhanced content coming soon at nfpa.org/link. 2-week Free Trials available! Connect with NFPA at nfpa.org. The material in this presentation contains some basic information about NFPA 30, Flammable and Combustible Liquids Code, 2021 edition. This material is not the official position of any NFPA Technical Committee on any referenced topic which is represented solely by the NFPA documents on such topic in their entirety. For free access to the complete and most current version of all NFPA documents, please go to www.nfpa.org/docinfo. The NFPA makes no warranty or guaranty of the completeness of the information in this material and disclaims liability for personal injury, property, and other damages of any nature whatsoever, from the use of or reliance on this information. In using this information, you should rely on your independent judgment and, when appropriate, consult a competent professional. © 2021 National Fire Protection Association / April 2021 ®