electronics Article High Frequency Transformer’s Parasitic Capacitance Minimization for Photovoltaic (PV) High-Frequency Link-Based Medium Voltage (MV) Inverter Himanshu 1 , Harsimran Singh 2 , Pandiyan Sathish Kumar 1 , Muhammad Umair Ali 1 Ho Yeong Lee 1 , Muhammad Adil Khan 1 , Gwan Soo Park 1 and Hee-Je Kim 1, * 1 2 * ID , School of Electrical Engineering, Pusan National University, Busandaehak-ro 63 beon-gil 2, Busan 46241, Korea; himanshuhimanshu820@gmail.com (H.); sathishnano2013@gmail.com (P.S.K.); umairali.m99@gmail.com (M.U.A.); hyl@pusan.ac.kr (H.Y.L.); engradilee@gmail.com (M.A.K.); gspark@pusan.ac.kr (G.S.P.) Institute of Robotics and Mechatronics, German Aerospace Center (DLR), 82234 Wessling, Germany; harsimran.smit@gmail.com Correspondence: heeje@pusan.ac.kr; Tel.: +82-51-510-2364 Received: 18 June 2018; Accepted: 6 August 2018; Published: 8 August 2018 Abstract: The high-frequency-based medium voltage (MV) inverter is used in renewable energy power sources for power transmission. However, power quality is compromised as a result of the increase in common mode noise currents by the high inter-winding parasitic capacitance in high-frequency link transformers. This fast voltage transient response leads to harmonic distortion and transformer overheating, which causes power supply failure or many other electrical hazards. This paper presents a comparative study between conventional and modified toroid transformer designs for isolated power supply. A half bridge high-frequency (10 kHz) MV DC–AC inverter was designed along with power source; a 680 W solar module renewable system was built. An FEM-simulation with Matlab-FFT analysis was used to determine the core flux distribution and to calculate the total harmonics distortion (THD). A GWInstek LCR meter and Fluke VT04A measured the inter-winding capacitance and temperature in all four transformer prototypes, respectively. The modified design of a toroid ferrite core transformer offers more resistance to temperature increase without the use of any cooling agent or external circuitry, while reducing the parasitic capacitance by 87%. Experiments were conducted along with a mathematical derivation of the inter-winding capacitance to confirm the validity of the approach. Keywords: high-frequency-based MV inverter; transformer’s parasitic capacitance; total harmonic distortion; toroidal transformer; sector windings 1. Introduction A transformer plays a vital role in energy conversion and is at the heart of the electric power system. The transformer size decreases with increasing frequency, which allows for the building of smaller, less expensive, and compact portable electrical devices [1,2]. Therefore, high frequency power transformers are preferred over traditional frequency transformers (50–60 Hz) in the power electronic fields, such as switching power supplies; converters; and inverters, including medium voltage (MV) inverters, which offer a step-up transformer-less solution to interconnect photovoltaic (PV) arrays to the MV grid [3–8]. Green energy is a priority of many researchers because of population and industrial growth, which are leading the world towards an extensive rise of global warming threats and visible climate change. Therefore, renewable energy sources are in high demand, particularly solar and wind energy. Electronics 2018, 7, 142; doi:10.3390/electronics7080142 www.mdpi.com/journal/electronics Electronics 2018, 7, 142 2 of 15 These sources Electronics 2018, 7, x are projected to fulfill 50% of the energy requirement by the year 2050 [9]. On2 the of 16 other hand, the intermittent nature of these power sources is a major limitation to connecting them straight to electrical/electronic national This criticalcan obstacle can be overcome using electrical/electronic systems or systems national or grids. Thisgrids. critical obstacle be overcome using external external devices, such as energy storage, converters, and inverters (see Figure 1) [10–13]. As a result of devices, such as energy storage, converters, and inverters (see Figure 1) [10–13]. As a result of the high the high penetration of these high-frequency-based MV inverters into the renewable energy power penetration of these high-frequency-based MV inverters into the renewable energy power plants, plants,demands energy demands befor fulfilled for industries home power requirements. However, energy could be could fulfilled industries and homeand power requirements. However, these highthese high-frequency links, for example, high-frequency transformer, H-bridge inverter dead time, frequency links, for example, high-frequency transformer, H-bridge inverter dead time, and non-linear and non-linear harmonic This can cause serious to the equipment load, generates load, high generates harmonichigh content. This content. can cause serious damage to damage the equipment including including overheating, powerfailure, supplyor failure, or electric shock hazards [14,15]. Consequently, to protect overheating, power supply electric shock hazards [14,15]. Consequently, to protect the the component and the connected loads from overheating and to provide a power supply without any component and the connected loads from overheating and to provide a power without any disturbances,the thepower powerquality qualityofofthese theseMV MVinverters invertersneeds needsto tobe betaken takeninto intoconsideration consideration[16–19] [16–19]. disturbances, . Figure 1. Renewable energy source on and off grid system. Figure 1. Renewable energy source on and off grid system. An electromagnetic interference (EMI) in inverters can affect the power quality of transients, both An electromagnetic interference (EMI) in inverters can affect the power quality of transients, short time and longtime deviation, which can cause harmonics. In these devices, harmonics can be both short time and longtime deviation, which can cause harmonics. In these devices, harmonics can categorized into two classes: common and differential conduction modes (CCM and DCM) [20–22]. The be categorized into two classes: common and differential conduction modes (CCM and DCM) [20–22]. high-frequency transformer is one of the sources of EMI and contributes to the common mode The high-frequency transformer is one of the sources of EMI and contributes to the common mode harmonics because of the intrinsic coupling capacitance, and electric and magnetic fields [23]. The duty harmonics because of the intrinsic coupling capacitance, and electric and magnetic fields [23]. The duty cycle is inversely proportional to the harmonics. Therefore, DCM operations of pulse-width cycle is inversely proportional to the harmonics. Therefore, DCM operations of pulse-width modulation modulation (PWM) converters increase the harmonics, which adds power losses in transformer (PWM) converters increase the harmonics, which adds power losses in transformer windings. Similarly, windings. Similarly, high-frequency operation causes skin and proximity effects that elevate the high-frequency operation causes skin and proximity effects that elevate the harmonic losses, winding harmonic losses, winding power losses, and rapid growth in the operating temperature [24,25]. On the power losses, and rapid growth in the operating temperature [24,25]. On the other hand, high frequency other hand, high frequency winding losses and lowering the leakage inductance has been a major winding losses and lowering the leakage inductance has been a major research focus, while the winding research focus, while the winding capacitance requires equally serious attention during the design of capacitance requires equally serious attention during the design of transformers. Capacitive coupling transformers. Capacitive coupling is one of the paths that can carry high frequency noise; premature is one of the paths that can carry high frequency noise; premature resonance; electrostatic coupling resonance; electrostatic coupling to other circuits; and fast transient voltages from primary to secondary to other circuits; and fast transient voltages from primary to secondary circuitry, which produces circuitry, which produces common mode noise currents and an increase in transformer temperature in common mode noise currents and an increase in transformer temperature in the device, resulting in a the device, resulting in a deterioration of the overall system operation, noise, health, and safety threats. deterioration of the overall system operation, noise, health, and safety threats. This capacitive coupling is an eruption effect of a transformer parasitic, rooted by a wide range of This capacitive coupling is an eruption effect of a transformer parasitic, rooted by a wide range of capacitance across the transformer, which circulates as a result of winding arrangements. Therefore, capacitance across the transformer, which circulates as a result of winding arrangements. Therefore, the key to overcoming this critical hurdle is lowering the inter-winding capacitance. Conventional the key to overcoming this critical hurdle is lowering the inter-winding capacitance. Conventional methods to reduce the emergence of capacitive coupling at the transformer include increasing the methods to reduce the emergence of capacitive coupling at the transformer include increasing the insulation between the primary and secondary winding or increasing the distance between the primary insulation between the primary and secondary winding or increasing the distance between the primary and secondary winding by winding them on opposite sides of the toroidal core. These changes in the and secondary winding by winding them on opposite sides of the toroidal core. These changes in the transformer will, however, cause other drawbacks, such as high leakage inductance, larger physical transformer will, however, cause other drawbacks, such as high leakage inductance, larger physical size, and poor inductive coupling. Accordingly, conventional methods are not completely effective in improving the power quality. On the other hand, previous studies [26–32] examined the techniques on smart transformers fuzzy logic based transformers by winding using fiber optic sensors and certain oils Electronics 2018, 7, 142 3 of 15 Electronics 2018, 7, x 3 of 16 size, and inductive They, coupling. Accordingly, methods are effective in and for cooling thepoor transformer. however, were conventional arranged specifically fornot thecompletely coupling capacitance improving the power quality. On the other hand, previous studies [26–32] examined the techniques on temperature control and showed no significant difference when compared with the less expensive smart transformers conventional solutions. fuzzy logic based transformers by winding using fiber optic sensors and certain oils for cooling the transformer. They, however, were arranged specifically for the coupling capacitance The leakage inductance and primary/secondary capacitance are mutually exclusive and are and temperature control and showed no significant difference when compared with the less expensive governed by the distance between the windings and the unwounded core. As a result of this, it is conventional solutions. difficult to achieve both low capacitive coupling and a high degree of inductive coupling in a power The leakage inductance and primary/secondary capacitance are mutually exclusive and are transformer [33,34]. circumvent this this study,core. the conventional toroid governed by theTo distance between theinherent windingstradeoff and thein unwounded As a result of this, it isferrite core transformer was modified an additional 3Dand printed (PLA) mold, which separates difficult to achieve both lowby capacitive coupling a highpolylactic degree of acid inductive coupling in a power the primary and [33,34]. secondary windings,this and helps tradeoff to implement unique winding. Although transformer To circumvent inherent in this study, the sector conventional toroid ferrite the distance windings will introduce leakage thereacid is some capacitance corebetween transformer was modified by an additional 3D inductance, printed polylactic (PLA)gain mold,inwhich separatesdue to the primary and secondary windings, and to implement unique and sectorwinding winding.arrangements Although the have the dielectric constant of PLA. However, the helps magnetic core geometry distance between will introduce leakage inductance, is some gain in capacitance due toof the a large influence on windings self-capacitance and leakage inductancethere of the transformer and because the dielectric constant of PLA. However, the magnetic geometryarrangements. and winding arrangements addition of a mold, it enables access to various types core of winding This paperhave reports a a large influence on self-capacitance and leakage inductance of the transformer and of the comparative analysis on the high frequency-link MV inverter for power-qualitybecause improvement by addition of a mold, it enables access to various types of winding arrangements. This paper reports effective subtraction of capacitive coupling and reducing the temperature increase without using any a comparative analysis on the high frequency-link MV inverter for power-quality improvement by extra circuitry or cooling agents. effective subtraction of capacitive coupling and reducing the temperature increase without using any extra circuitry or cooling agents. 2. High-Frequency Link Based MV Inverter Design Consideration 2. High-Frequency Link Based MV Inverter Design Consideration 2.1. Toroid Ferrite Core 2.1. Toroid Ferrite Core To utilize the intrinsic ferrite material properties, it is essential to use a ring configuration of the To utilize the intrinsic ferrite material properties, it is essential to use a ring configuration ferrite core. Therefore, the toroid core was used in this paper, as it is commonly used for high-frequency of the ferrite core. Therefore, the toroid core was used in this paper, as it is commonly used for square/sine wave-based applications, such as power input filters, ground-fault interrupters, commonhigh-frequency square/sine wave-based applications, such as power input filters, ground-fault modeinterrupters, filters, and common-mode pulse and broadband filters. filters, and pulse and broadband filters. A 77 A material ferrite toroid was used MVinverter inverterhigh-frequency high-frequency transformer. 77 material ferrite toroid was usedasasthe thecore core for for MV linklink transformer. FigureFigure 2 presents a schematic diagram andisisdefined defined outer diameter (A), inner 2 presents a schematic diagramofofthe the core core and byby its its outer diameter (A), inner diameter (B), and thickness (C) (See Table 1). Figure 3 shows how the increasing temperature affects diameter (B), and thickness (C) (See Table 1). Figure 3 shows how the increasing temperature affects the properties core properties Table 2 presents toroidferrite77 ferrite77 core core material’s properties. the core andand Table 2 presents toroid material’selectrical electrical properties. Figure 2. Ferrite 77 material core dimensions (courtesy: Fair-Rite products Corp). Figure 2. Ferrite 77 material core dimensions (courtesy: Fair-Rite products Corp). Table 1. Ferrite 7777 toroid (courtesy:Fair-Rite Fair-Rite products Corp). Table 1. Ferrite toroidcore coredimensions dimensions (courtesy: products Corp). Dim A A B B C C Dim mm mm 61.00 61.00 35.55 35.55 12.70 12.70 Mm tol Nominal Mm tol Nominal ±1.30 2.400 ±1.30 2.400 ±0.85 1.4001.400 ±0.85 ±0.50 ±0.50 0.5000.500 Electronics 2018, 7, 142 Electronics 2018, 7, x 4 of 15 4 of 16 Table 2. Table 2. Ferrite 77 toroid toroid core core electrical electrical properties properties (courtesy: (courtesy: Fair-Rite Fair-Rite products products Corp). Corp). Electrical Electrical Properties Properties A L (nH) 2950 ± 25% AL (nH) 2950 ± 25% 22) A E (cm 1.58000 1.58000 AE (cm ) − −11) ∑I/A (cm 9.20 9.20 ) ∑I/A I (cm) 14.50 Iee(cm) 14.50 22.80000 Vee (cm (cm33)) V 22.80000 Figure 3. Temperature effects on Ferrite 77 material properties (courtesy: Fair-Rite products Corp). Figure 3. Temperature effects on Ferrite 77 material properties (courtesy: Fair-Rite products Corp). 2.2. Harmonic Current Contribution on Transformer Losses and Temperature Rise 2.2. Harmonic Current Contribution on Transformer Losses and Temperature Rise Total widely-used notion notion to to define define the theharmonic harmoniccontent contentinin Total harmonics harmonics distortion distortion (THD) (THD) is is aa widely-used alternating signals. This value is defined as the ratio sum of the powers of all harmonic components alternating signals. This value is defined as the ratio sum of the powers of all harmonic components toto the used for for low, low, medium, medium,and andhigh highvoltage voltagesystems, systems, thepower powerof of the the fundamental fundamental frequency. frequency. THD THD is is used where I and THDV, and can be calculated using the wherethe thecurrent currentand andvoltage voltagedistortion distortionisisdefined definedasasTHD THD I and THDV , and can be calculated using following Equations (1)–(2). the following Equations (1)–(2). = THDv = H ∑ !1 | | 2 |Vh |2 | | × 100% /|V1 | × 100% (1) (1) h 6 =1 (2) ! 1 | | × 100% 2 h THD I = ∑ Ii /| I1 | × 100% (2) where h is the harmonic content order, and Vhh6=and Ih are the voltage and current amplitude of order “h” 1 harmonic component, respectively. V1 and I1 are the voltage and current amplitude of the fundamental where h is the harmonic content order, and Vh and Ih are the voltage and current amplitude of order “h” component, respectively. harmonic component, respectively. V 1 and I1 are the voltage and current amplitude of the fundamental The International Electrotechnical Commission (IEC) 61727 imposes the limits for harmonics in component, respectively. the current—Electromagnetic compatibility (EMC)-Part 3–2: Limits for harmonics current emission. The International Electrotechnical Commission (IEC) 61727 imposes the limits for harmonics in The IEEE Single Phase Harmonics Task Force (P1495) has set similar limitations. U.S. and European the current—Electromagnetic compatibility (EMC)-Part 3–2: Limits for harmonics current emission. power systems are different from each other in many standards. Therefore, the United States should be The IEEE Single Phase Harmonics Task Force (P1495) has set similar limitations. U.S. and European different than the IEC stance. Thus, there is a flexibility to follow the certain standard (Table 3). power systems are different from each other in many standards. Therefore, the United States should be different than the IEC stance. Thus, there is a flexibility to follow the certain standard (Table 3). = H 2 Table 3. Current and Voltage total harmonic distortion allowing values and their associated risks (courtesy: Interpreting European norm (EN) 50160 and International Electrotechnical Commission (IEC) standard 61727). THD—total harmonics distortion. Electronics 2018, 7, 142 THDV <8% THDI <5% Risk normal situation considerable 5 of 15 Table 3. Current and Voltage total harmonic allowing values and their associated risks 8–15% 5–50%distortion Minor harmonic (courtesy: Interpreting European norm (EN) 50160 and International pollution with Electrotechnical Commission (IEC) standard 61727). THD—total harmonics distortion. malfunctions possibility THDV THDI <8% 8–15% >15% <5%>15% situation considerable >50% normal major harmonic 5–50% Minor harmonic pollution with malfunctions possibility pollution with >50% major harmonic pollution with malfunctions probability Risk malfunctions probability The losses in transformers can be classified as load loss (impedance loss), no-load loss (excitation loss), and totalinloss (no-load +can load-loss). Loadasloss can be (impedance subdivided loss), further into stray magnetic The losses transformers be classified load loss no-load loss (excitation losses in the core, eddy currents, and resistive losses in the windings. loss), and total loss (no-load + load-loss). Load loss can be subdivided further into stray magnetic losses in the core, eddy currents, and resistive losses in the windings. h=hmax h = hmax 2 2 Ih2h 2 pt = p f h∑ =1 I h h pt = p f (3) (3) h =1 wherePPf is theeddy eddycurrent current loss the fundamental frequency, and f and Ih are fractions of total the where loss atat the fundamental frequency, and f and Ih are the the fractions of the f isthe totalload RMScurrent load current the harmonic number h. RMS at the at harmonic number h. 2.3.Circuit CircuitOperation Operation 2.3. Figure44shows, shows,AAsingle-phase single-phase half bridge kHz) is comprised of two power MOSFET Figure half bridge (10(10 kHz) is comprised of two power MOSFET (IRF(IRF 250) 250) (Texas Instruments, Dallas, TX, USA), S1 and S2, which are driven by a DSP F28335 (Texas (Texas Instruments, Dallas, TX, USA), S1 and S2, which are driven by a DSP F28335 (Texas Instruments, Instruments, Dallas, TX, USA) chip to generate a pulse width modulated waveform andD1 feedback Dallas, TX, USA) chip to generate a pulse width modulated waveform and feedback diodes, and D2. diodes, andfreewheeling D2. These are called freewheeling withtotwo DC bus toTwo-stage stabilize These areD1 called diodes with two DC busdiodes capacitors stabilize thecapacitors DC voltage. the DCconversions voltage. Two-stage with thetransformer. help of the high-frequency power with the power help ofconversions the high-frequency High-frequency transformer. operation is High-frequency operation is possible at the first DC/DC stage and at the second modified possible at the first DC/DC stage and at the second stage modified amplitude of stage converted highamplitude of converted high-frequency AC voltage by high-frequency transformer secondary, which is frequency AC voltage by high-frequency transformer secondary, which is connected to high-frequency connected to high-frequency rectifier AC/DC and an output inverter, which converts the DC voltage rectifier AC/DC and an output inverter, which converts the DC voltage to the required frequency AC to the required frequency voltage the case of utility grid 50/60 Hz. voltage in the case of utilityAC grid 50/60 in Hz. Figure 4. Circuit layout for photovoltaic (PV) high-frequency-based medium voltage (MV) inverter Figure 4. Circuit layout for photovoltaic (PV) high-frequency-based medium voltage (MV) inverter system. system. 3. Fabrication This study examined a new design for the high-frequency link of an MV inverter, which mitigates the temperature increase occurring as a result of harmful harmonics by reducing the capacitive coupling at the high-frequency transformer. Four toroid core transformers with conventional and modified configurations, with 180◦ and 360◦ sector windings, were fabricated, and their THD, self-induced capacitance, and temperature were measured and compared. The transformer windings for all four 3. Fabrication 3. Fabrication This study examined a new design for the high-frequency link of an MV inverter, which mitigates This study examined a new design for the high-frequency link of an MV inverter, which mitigates the temperature increase occurring as a result of harmful harmonics by reducing the capacitive the temperature increase occurring as a result of harmful harmonics by reducing the capacitive coupling at the high-frequency transformer. Four toroid core transformers with conventional and Electronics 2018, 7, 142 6 ofand 15 coupling at the high-frequency transformer. Four toroid core transformers with conventional modified configurations, with 180° and 360° sector windings, were fabricated, and their THD, selfmodified configurations, with 180° and 360° sector windings, were fabricated, and their THD, selfinduced capacitance, and temperature were measured and compared. The transformer windings for all induced capacitance, and temperature were measured and compared. The transformer windings for all configurations werewere wound manually. TheThe corecore material, dimensions, copper wire, andand a number of four configurations wound manually. material, dimensions, copper wire, a number four configurations were wound manually. The core material, dimensions, copper wire, and a number ofwinding windingturns turnswere werethe thesame samefor forthe theconventional conventionaland andmodified modifiedconfiguration, configuration,as aslisted listedin inTable Table3.3. of winding turns were the same for the conventional and modified configuration, as listed in Table 3. Thedifference differencebetween between the the conventional conventional and and modified configuration was The was aa two-part two-partmold moldthat thatwas was The difference between the conventional and modified configuration was a two-part mold that was mountedover overthe thesecondary secondary windings windings and and ferrite core. The primary mounted primary winding winding was wasthen thenwound woundover over mounted over the secondary windings and ferrite core. The primary winding was then wound over thisadditional additionalpiece pieceof ofhardware, hardware, which which altered the dimensions this dimensions of of the the primary primarywinding windingand andprovided provided this additional piece of hardware, which altered the dimensions of the primary winding and provided scopeto tounique uniquewinding winding arrangements. arrangements. The The mold was printed using scope using aa 3D 3D printer printerwith withaaPLA PLAfilament filament scope to unique winding arrangements. The mold was printed using a 3D printer with a PLA filament material.This Thiswas wascomprised comprised two parts, and bottom, each with a width of mm 0.5 mm material. ofof two parts, toptop and bottom, each with a width of 0.5 eacheach withwith very material. This was comprised of two parts, top and bottom, each with a width of 0.5 mm each with very very negligible extra weight and[35,36]. cost [35,36]. negligible extra weight and cost negligible extra weight and cost [35,36]. 3.1.Case Case1:1:Conventional ConventionalToroid ToroidCore CoreTransformer Transformerwith with180° 180◦Sector SectorWindings Windings 3.1. 3.1. Case 1: Conventional Toroid Core Transformer with 180° Sector Windings ◦ thisconfiguration, configuration,the the entire entire secondary secondary winding InInthis winding is is distributed distributedover overthe the180 180°sector sectorof ofthe thetoroid toroid In this configuration, the entire secondary winding is distributed over the 180° sector of the toroid corein inaaback-and-forth back-and-forthmanner. manner. The The other other half half of of the core the toroid toroid core core is is wound woundwith withprimary primarywindings windingsinin core in a back-and-forth manner. The other half of the toroid core is wound with primary windings in similar manner,as asshown shown inFigure Figure aasimilar manner, in 5.5. a similar manner, as shown in Figure 5. Figure. 5. The 180° (A) flux pattern in core; (B) 2D model; (C) 3D model. ◦ conventional(A) Figure Figure.5.5.The The180 180°conventional conventional (A)flux fluxpattern patterninincore; core;(B) (B)2D 2Dmodel; model;(C) (C)3D 3Dmodel. model. 3.2. Case 2: Modified Toroid Core Transformer with 180°◦ Sector Windings 3.2.Case Case2:2:Modified ModifiedToroid ToroidCore CoreTransformer Transformer with with 180° 180 Sector SectorWindings Windings 3.2. In this configuration, the secondary winding is distributed over the 180° sector of the toroid core ◦ sector thisconfiguration, configuration,the thesecondary secondary winding is distributed over 180 of the toroid InInthis winding is distributed over thethe 180° sector of the toroid core incore a back-and-forth manner, just as in the previous case. The two parts of the 3D printed mold using in a back-and-forth manner, as in the previous case. The twoofparts of the 3D printed moldaa in a back-and-forth manner, just asjust in the previous case. The two parts the 3D printed mold using PLA filament material were mounted over the ferrite toroid core and secondary windings, to usingfilament a PLA filament were mounted ferrite toroid coreand andsecondary secondary windings, PLA materialmaterial were mounted over over the the ferrite toroid core windings, toto completely encapsulate them. Owing to the assembly of the mold, the secondary secondary windingisiscompletely completely completelyencapsulate encapsulatethem. them. Owing Owing to to the the assembly assembly of of the the mold, completely mold, the the secondarywinding winding is completely hidden, which leaves an entire 360° span for the primary winding. The initial experiments were carried hidden,which whichleaves leavesan anentire entire 360° 360◦ span span for for the the primary primary winding. hidden, winding. The The initial initial experiments experimentswere werecarried carried out with the primary windings over the 360° sector and 180° sector of thethe core. On thethe other hand, the ◦ sector ◦ sector outwith withthe theprimary primarywindings windingsover overthe the360° 360sector and 180sector core. other hand, out and 180° of of the core. OnOn the other hand, the lowest leakage inductance was achieved when the primary had a 180°◦ sector winding without the lowest leakage inductance achieved when primaryhad hadaa 180° 180 sector winding lowest leakage inductance waswas achieved when thetheprimary winding without without overlapping the secondary winding, as shown in Figure 6. overlappingthe thesecondary secondarywinding, winding,as asshown shownininFigure Figure6.6. overlapping Figure 6. The 180° (A) flux pattern in core; (B) 2D model; (C) 3D model. ◦ modified (A) Figure flux pattern in in core; core; (B) (B)2D 2Dmodel; model;(C) (C)3D 3Dmodel. model. Figure6.6.The The180 180° modified modified 3.3. Case 3: A Conventional 360◦ Wound Toroid Core Transformer In this case, the secondary winding is distributed over the entire 360◦ sector of the toroid ferrite core. The primary winding is also distributed over the 360◦ sector on top of the secondary winding (Figure 7). Electronics 2018, 7, x 7 of 16 3.3. Case 3: A Conventional 360° Wound Toroid Core Transformer 3.3. Case 3: A Conventional 360° Wound Toroid Core Transformer In this case, the secondary winding is distributed over the entire 360° sector of the toroid ferrite In this case, the secondary winding is distributed over the entire 360° sector of the toroid ferrite core. The primary is also distributed over the 360° sector on top of the secondary winding Electronics 7, 142winding 7 of 15 core. The2018, primary winding is also distributed over the 360° sector on top of the secondary winding (Figure 7). (Figure 7). Figure 7. The 360° conventional (A) 2D model; (B) flux distribution; (C) 3D model. ◦ conventional Figure 7. 7. The 360 Figure The 360° conventional(A) (A)2D 2Dmodel; model;(B) (B)flux fluxdistribution; distribution; (C) (C) 3D 3D model. model. 3.4. Case 4: A Modified 360° Wound Toroid Core Transformer 3.4.Case Case4:4:AAModified Modified360° 360◦Wound WoundToroid ToroidCore CoreTransformer Transformer 3.4. InIn thisthis case, the secondary winding is distributed over 360° sector the toroid core in a back-andcase, secondary winding is distributed over 360◦ofof sector of the toroid in a In this case, thethe secondary winding is distributed over 360° sector the toroid core in a core back-andforth manner, as in the former case. The toroid ferrite core along with the secondary winding is back-and-forth as in the former case. The toroid with the secondary forth manner, asmanner, in the former case. The toroid ferrite coreferrite along core withalong the secondary winding is encapsulated with the 3D printed mold, over which the primary winding is wound around a 360° span winding is encapsulated the mold, 3D printed mold, over which the primary is wound around encapsulated with the 3Dwith printed over which the primary winding is winding wound around a 360° span ◦8). (Figure a 360 span (Figure 8). (Figure 8). Figure 8. The 360° modified (A) 2D model; (B) flux distribution; (C) 3D model. Figure 8. The 360° modified (A) 2D model; (B) flux distribution; (C) 3D model. Figure 8. The 360◦ modified (A) 2D model; (B) flux distribution; (C) 3D model. 4. Calculation of the Transformer Inter-Winding Capacitance 4. Calculation of the Transformer Inter-Winding Capacitance 4. Calculation of the Transformer Inter-Winding Capacitance The general structure (2D, 3D, and flux flow in core) of the four designed transformer’s prototypes The general structure (2D, 3D, and flux flow in core) of the four designed transformer’s prototypes Theare general structure (2D, 3D, and flux flow(3). in core) ofsection, the fourprototype designed transformer’s prototypes under test illustrated in the fabrication section In this transformer calculations under test are illustrated in the fabrication section (3). In this section, prototype transformer calculations under test are illustrated in the fabrication section (3). In this section, prototype transformer calculations were carried out for inter-winding capacitance. Figure 9 shows the conceptual structure of case 1 and were carried out for inter-winding capacitance. Figure 9 shows the conceptual structure of case 1 and were carried out for inter-winding capacitance.capacitance Figure 9 shows the conceptual structure of case 1 and case 2 transformer prototypes for inter-winding calculation. Likewise, the capacitance for case 2 transformer prototypes for inter-winding capacitance calculation. Likewise, the capacitance for case 2 transformer prototypes for inter-winding capacitance calculation. Likewise, the capacitance for other prototypes can be evaluated in a similar manner. other prototypes can be evaluated in a similar manner. other prototypes can be evaluated in a similar manner. Ferrite core material 77 has a negligible effect on parasitic capacitance; therefore, only winding configurations were taken into account. For the sake of simplicity, only one winding of the secondary side, which is wound on the ferrite core, is considered for calculation of inter-winding capacitance. The same position of the secondary winding is considered for all four cases. The distance between the inner secondary winding and inner primary windings can be expressed as follows: s π πi r1in,i = r1 2 + r2 2 − 2r1 r2 cos( + ) (4) 2 np where r1 is the distance from the center of the core to the inner primary windings, r2 is the distance from the center of the core to the outer primary windings, r3 is the distance from the center of the core to the inner secondary windings, r4 is the distance from the center of the core to the outer secondary windings (Figure 9), and np is the total number of primary turns. In all four cases, r3 and r4 values are the same, as secondary winding is wounded on the ferrite core and core dimension is same for all transformer prototypes. On the other hand, r1 and r2 values will vary with respect to each case, for example, r1 , for case 4 (r1, 4 ) and case 2 (r1, 2 ) will be same, but they are less than case 3 (r1, 3 ), which Electronics 2018, 7, 142 8 of 15 in turn is less than case 1 (r1, 1 ). The details of r1 , r2 , r3 , r4 for the four different configurations are given as follows: A : r1, 4 = r1, 2 < r1, 3 < r1, 1 B : r2, 1 < r2, 3 < r2, 2 = r2, 4 C : r3, 1 = r3, 2 = r3, 3 = r3, 4 D : r4, 1 = r4, 2 = r4, 3 = r4, 4 Electronics 2018, 7, x 9 of 16 The static capacitance between the inner primary and inner secondary is as follows: C1in,i = , ∈∈∘ ◦dπl1 ∈∈∘◦dπl1 = q 2r21in,i , 22 r1 2 + r2 2 − 2 r1 r2 cos( π2 + 2 πi np ) (5) (5) where Є∘◦ is free space, space, ddisisthe thediameter diameterof ofthe thewire wireused usedfor forprimary primaryand andsecondary secondary is the permittivity of free windings, and l11 is is the the overlapped overlapped length. length. Assuming that the voltage potential distribution along the primary turn varies linearly, linearly, i 1Vp np − 1 The total stored energy between the inner primary and secondary is as follows: The total stored energy between the inner primary and secondary is as follows: Vp [i ] = E1in ! 1n −1 2 1 p i = 2 ∑ C1in,i (, Vp ) 1 2 i =0 np − 1 (6) (6) (7) (7) Similarly, the capacitance capacitance between between the the inner innerprimary–outer primary–outersecondary, secondary,outer outerprimary–outer primary–outer Similarly, the secondary, and outer primary–outer secondary can be calculated. Equations (4)–(7) can be used to find secondary, and outer primary–outer secondary can be calculated. Equations (4)–(7) can be used to the and and energy for the other three cases as as well (Table 4).4). The simulation was findcapacitance the capacitance energy for the other three cases well (Table The simulation wasrun runon MATLAB to calculate thethe capacitance of simplicity simplicityand andtotoignore ignorethe the on MATLAB to calculate capacitanceininallallfour fourcases. cases. For For the the sake sake of repetitive process of inter-winding capacitance calculations, only one winding in the same position repetitive process of inter-winding capacitance calculations, only one winding in the same positionof the secondary side is considered forfor allall four cases. ToTo seesee thethe effect ofof inter-winding capacitance, we of the secondary side is considered four cases. effect inter-winding capacitance, Electronics 2018, 7, x ◦ choose three primary winding for 180° conventional and modified configurations instead of 116, and we choose three primary winding for 180 conventional and modified configurations instead of 116, 68 of 16 primary windings for 360° and modified configurations instead of 220.of 220. and 6 primary windings forconventional 360◦ conventional and modified configurations instead Table 4. Detailed parameters of the transformer prototypes. PLA—polylactic acid. Prototypes Physical Properties Copper Wire standard Primary Turns Secondary Turns Core Material (Table 1) Core shape Permittivity (F/m) Case 1 Case 2 Case 3 Case 4 24 AWG 24 AWG 24 AWG 24 AWG 116 116 220 220 116 116 220 220 Ferrite 77 Ferrite 77 Ferrite77 Ferrite 77 Ring Ring Ring Ring 8.85 × 10−12 8.4190×10−12 8.85×10−12 8.419 × 10−12 (Air) (Air + PLA) (Air) (Air + PLA) Inner Radius (mm) 17.775 15.275 17.775 15.275 Outer Radius (mm) 30.5 32.5 30.5 32.5 Primary Voltage (V) 24 24 24 24 Secondary Voltage (V) ~24 ~24 ~24 ~24 Frequency (kHz) 1–30 1–30 1–30 1–30 17.265 14.765 16.755 14.765 30.5 32.5 31.01 32.5 17.265 17.265 17.265 17.265 Figure 9. Toroidal transformer with 180◦ sectored presentation 30.5 winding, Conceptual 30.5 30.5 of transformer 30.5 Figurefrom 9. Toroidal transformer with 180° winding, Conceptual presentation of transformer prototypes left to right conventional andsectored modified. PLA—polylactic acid. fromTable left to5right and modified. PLA—polylactic It canprototypes be seen from thatconventional the inter-winding capacitance would beacid. highest for case 3, followed by that for case 1, case 4, and case 2. These analytical calculations hold well with the experimental data Ferrite core material which 77 hasisashown negligible effect parasitic capacitance; therefore, only winding for inter-winding capacitance, in the nexton section. configurations were taken into account. For the sake of simplicity, only one winding of the secondary side, which is wound on the ferrite core, is considered for calculation of inter-winding capacitance. The Electronics 2018, 7, 142 9 of 15 Table 4. Detailed parameters of the transformer prototypes. PLA—polylactic acid. Prototypes Physical Properties Case 1 Case 2 Case 3 Case 4 Copper Wire standard Primary Turns Secondary Turns Core Material (Table 1) Core shape 24 AWG 116 116 Ferrite 77 Ring 8.85 × 10−12 (Air) 17.775 30.5 24 ~24 1–30 17.265 30.5 17.265 30.5 24 AWG 116 116 Ferrite 77 Ring 8.4190×10−12 (Air + PLA) 15.275 32.5 24 ~24 1–30 14.765 32.5 17.265 30.5 24 AWG 220 220 Ferrite77 Ring 8.85×10−12 (Air) 17.775 30.5 24 ~24 1–30 16.755 31.01 17.265 30.5 24 AWG 220 220 Ferrite 77 Ring 8.419 × 10−12 (Air + PLA) 15.275 32.5 24 ~24 1–30 14.765 32.5 17.265 30.5 Permittivity (F/m) Inner Radius (mm) Outer Radius (mm) Primary Voltage (V) Secondary Voltage (V) Frequency (kHz) r1 r2 r3 r4 It can be seen from Table 5 that the inter-winding capacitance would be highest for case 3, followed by that for case 1, case 4, and case 2. These analytical calculations hold well with the experimental data for inter-winding capacitance, which is shown in the next section. Table 5. Theoratical analysis of all presented prototypes, calculated energy, and inter-winding capacitance. Case 1 Energy (J) Percentage % E1 E2 E3 E4 Etotal Capacitanceeq (F) 5.63 × 10−10 35.4 3.87 × 10−10 24.3 3.54 × 10−10 22.3 2.87 × 10−10 18 1.59 × 10−10 100 2.76 × 10−12 E4 Etotal Capacitanceeq (F) Case 2 E1 Energy (J) Percentage % 10−10 5.31 × 33.9 E2 10−10 3.74 × 23.9 E3 10−10 3.66 × 23.4 10−10 2.94 × 18.8 10−9 1.57 × 100 2.72 × 10−12 Case 3 E1 Energy (J) Percentage % 10−10 5.69 × 35.5 E2 10−10 3.87 × 24.2 E3 10−10 3.56 × 22.2 E4 10−10 2.90 × 18.1 Etotal 10−9 1.60 × 100 Capacitanceeq (F) 2.78 × 10−12 Case 4 E1 Energy (J) Percentage % 10−10 5.29 × 33.6 E2 10−10 3.73 × 23.7 E3 10−10 3.73 × 23.7 E4 10−10 3.00 × 19 Etotal 10−9 1.57 × 100 Capacitanceeq (F) 2.73 × 10−12 5. Experimental Setup The high-frequency transformer temperature, capacitive coupling, and leakage inductance were measured using a Fluke VT04A (Fluke, Everett, WA, USA) Thermometer and GWInstek LCR (GWINSTEK, New Taipei City, Tucheng Dist., Taiwan) meter. The experiments were conducted at constant ambient room temperature, on the high-frequency link of a 1 kW half bridge MV inverter. Two 38 V, 350 W standalone solar modules connected in parallel served as input for the developed inverter. Owing to the addition of a 3D printed mold and sector winding, it was possible to have different winding arrangements. A number of modified toroid high-frequency transformers have been developed with different sector windings, such as 45◦ , 90◦ , 120◦ , 180◦ , 270◦ , and 360◦ . Figure 10 presents a block diagram of the experimental setup. The input and output waveforms of the constant ambient room temperature, on the high-frequency link of a 1 kW half bridge MV inverter. Two 38 V, 350 W standalone solar modules connected in parallel served as input for the developed inverter. Owing to the addition of a 3D printed mold and sector winding, it was possible to have different winding arrangements. A number of modified toroid high-frequency transformers have been Electronics 2018, 7, 142 10 of 15 developed with different sector windings, such as 45°, 90°, 120°, 180°, 270°, and 360°. Figure 10 presents a block diagram of the experimental setup. The input and output waveforms of the transformer were stored, and the harmonic contents present in thecontents waveform wereinanalyzed by Matlab-FFT (MathWorks, transformer were stored, and the harmonic present the waveform were analyzed by Matlab-FFT (MathWorks, Natick, MA, USA). Natick, MA, USA). FigureFigure 10. Block diagram for for thethe testing prototypesPV PV high frequency based MV inverter 10. Block diagram testingprocess process for for prototypes high frequency based MV inverter systems. THD— total harmonics distortion. systems. THD—total harmonics distortion. 6. Results and Discussion 6. Results and Discussion ◦ Forcomparative the comparative analysis, wedesigned designed aa conventional conventional toroid transformer withwith the same 180 180° For the analysis, we toroid transformer the same ◦ and sector 360 sector windings samecore coredimension. dimension. The experimental studies statedstated and 360° windings andand thethe same Thecomparative comparative experimental studies that the proposed modified design succeeded in lowering the inter-winding capacitance (approximately 87%) and controlling temperature increase issues (less than 30◦ ) when compared with conventional designs; detailed discussion based on sectored winding is shown below. Table 6 compares the THD of the aforementioned transformer prototypes. By comparative analysis of normative Table 3 and experimental result Table 6, it is clearly visible that all the prototypes have a minimum risk. Although, modified designs have registered more or less similar distortion compared with conventional designs. Table 6. Voltage and current THD for all prototypes. Source Input Voltage (V) 24 24 24 24 THDV % Case 1 2 3 4 THDI % Primary Secondary Primary Secondary 45.53 34.70 11.92 9.81 22.34 22.15 16.33 14.94 5.6 12.22 48.19 43.06 7.20 11.85 49.56 44.32 6.1. Toroidal Transformer with 180◦ Sectored Winding Inter-winding Capacitance: Large inter-winding capacitance causes a significant amount of common mode noise at high-frequency operations. Figure 11 shows the comparison for parasitic capacitance from 1 to 30 kHz frequency at a high-frequency-based MV inverter. It is clearly visible that the proposed modified design has minimized the parasitic capacitance close to 20 pF, which is much lower than the conventional design. This was because of the mold, which helped increase the distance between the windings. Inter-winding Capacitance: Large inter-winding capacitance causes a significant amount of common mode noise at high-frequency operations. Figure 11 shows the comparison for parasitic capacitance from 1 to 30 kHz frequency at a high-frequency-based MV inverter. It is clearly visible that the proposed modified design has minimized the parasitic capacitance close to 20 pF, which is much lower than the conventional design. This was because of the mold, which helped increase the distance between the Electronics 2018, 7, 142 11 of 15 windings. Figure 11. Toroidal transformers sectored winding, parasitic parasitic coupling capacitance comparison Figure 11. Toroidal transformers at 180at◦ 180° sectored winding, coupling capacitance comparison between the conventional and modified design of high-frequency link based MV inverter systems. between the conventional and modified design of high-frequency link based MV inverter systems. Leakage Inductance: In a sectored wound transformer, when the winding covers only 180°, leakage path changes core. According theory, we expected inductance be higher Leakageflux Inductance: Inina the sectored woundtotransformer, whenthe theleakage winding coverstoonly 180◦in, leakage modified design when compared with the conventional design because of the distance between flux path changes in the core. According to theory, we expected the leakage inductance to be higher windings created by the PLA mold. However, the 3D printed mold using PLA filament was mounted in modified design when compared with the conventional design because of the distance between over the ferrite toroid core and secondary windings to completely encapsulate them and provided windings created the PLA mold. However, 3D printed using PLA filament was mounted scope to by increase the mean length turn of thethe primary winding, mold which is required to reduce the leakage inductance. This theory supported bywindings the experiment results [37]. Figure 12 demonstrates over the ferrite toroid core andis secondary to completely encapsulate them that andthe provided modified design recorded less leakage inductance than the conventional design. scope to increase the mean length turn of the primary winding, which is required to reduce the leakage inductance. This7,theory is supported by the experiment results [37]. Figure 12 demonstrates that the Electronics 1212ofof1616 Electronics 2018,2018, x 7, x modified design recorded less leakage inductance than the conventional design. ◦ sectored winding, leakage inductance comparison between Figure 12. Toroidal transformers at 180 Figure 12. Toroidal transformers at 180° sectored winding, leakage inductance comparison between the Figure 12. Toroidal transformers at 180° sectored winding, leakage inductance comparison between the conventional and modifieddesign design of linklink based MV inverter systems. the conventional and modified ofhigh-frequency high-frequency based MV inverter systems. conventional and modified design of high-frequency link based MV inverter systems. Temperature: By comparing modified and conventional transformers on full load, it is clearly visible Temperature: ByBy comparing modified and conventional transformers on full itvisible is clearly that lowering the interwinding capacitance and harmonicstransformers distortion helped significantly in controlling Temperature: comparing modified and conventional on full load, it isload, clearly visible that lowering the interwinding capacitance and harmonics distortion helped significantly the temperature rise issue incapacitance the transformer 13). distortion helped significantly in controlling in that lowering the interwinding and (Figure harmonics controlling the temperature rise in the transformer the temperature rise issue in theissue transformer (Figure 13). (Figure 13). Figure 13. Toroidal transformers at 180° sectored winding, temperature comparison between the conventional and modified transformer design. Figure 13. Toroidal transformers at 180° sectored winding, temperature comparison between the Figure 13. Toroidal transformers at 180◦ sectored winding, temperature comparison between the 6.2. Toroidal Transformer with 360° Sectored Winding conventional and modified transformer design. conventional and modified transformer design. The primary winding is on top of the secondary winding for the entire 360°, leakage flux is produced by the current in the windings, which are opposite in direction and equal in magnitude (The = ), thus magnetizing or leakage cancels itself in thefor core. primary winding is on top of the flux secondary winding the entire 360°, leakage flux is Capacitance: Larger values self-capacitance of the transformer, which occur producedInter-winding by the current in the windings, whichofare opposite in direction and equal in magnitude between and secondary windings, a vital roleininthe large primary current distortions. Self( = ),primary thus magnetizing or leakage fluxplay cancels itself core. capacitance value of the proposed prototypeofhas largely reduced (40occur pF) Inter-winding Capacitance: Largermodified values transformer of self-capacitance thebeen transformer, which 6.2. Toroidal Transformer with 360° Sectored Winding Electronics 2018, 7, 142 12 of 15 6.2. Toroidal Transformer with 360◦ Sectored Winding The primary winding is on top of the secondary winding for the entire 360◦ , leakage flux is produced by the current in the windings, which are opposite in direction and equal in magnitude (N1 I1 = N2 I2 ), thus magnetizing or leakage flux cancels itself in the core. Inter-winding Capacitance: Larger values of self-capacitance of the transformer, which occur between primary and secondary windings, play a vital role in large primary current distortions. Self-capacitance value of the proposed modified transformer prototype has been largely reduced (40 pF) with the help of 3D designed cover, spaces between windings, and proposed different winding arrangements compared with the conventional prototype. In Figure 14, winding capacitance for both conventional and modified transformers were plotted. It is noted that the modified design Electronics 2018, 7, x 13 of 16 succeeded in 7,minimizing the transformer self-capacitance by approximately 87% compared with Electronics 2018, x 13 of 16 conventional designs. Figure 14. Toroidal transformers at 360° sectored winding, parasitic coupling capacitance comparison ◦ Figure winding, parasitic coupling capacitance comparison Figure14. 14.Toroidal Toroidaltransformers transformersatat360 360°sectored sectored winding, parasitic coupling capacitance comparison between the conventional and modified design of high-frequency link based MV inverter systems. between betweenthe theconventional conventionaland andmodified modifieddesign designofofhigh-frequency high-frequencylink linkbased basedMV MVinverter invertersystems. systems. Leakage Inductance: The leakage inductance and primary/secondary capacitance are mutually Leakage Inductance: Inductance: The Theleakage leakageinductance inductanceand and primary/secondarycapacitance capacitanceareare mutually Leakage mutually exclusive and are governed by the distance between primary/secondary the windings and unwounded core. Therefore, it exclusive and and are aregoverned governed by by thedistance distance between between the the windings and and unwounded core. core. Therefore, Therefore, it exclusive is difficult to achieve both lowthe capacitive coupling and awindings high degree ofunwounded inductive coupling in a power achieve both low capacitive coupling andand a high degree of inductive coupling in a power itis isdifficult difficulttoto achieve both low capacitive coupling a high degree of inductive in a transformer. However, the magnetic core geometry and winding arrangements have acoupling large influence transformer. However, the magnetic core geometry and winding arrangements have a large influence power transformer. However, the magnetic core geometry and winding arrangements have a large on self-capacitance and leakage inductance of the transformer and because of the addition of a mold, it on self-capacitance and leakage of the transformer and because of the addition of a mold, influence on self-capacitance and inductance leakage inductance of the transformer and because of the addition of it enables access to various types of winding arrangements. Thus, the modified design has successfully enables access to various types of winding arrangements. Thus, the modified design has successfully alowered mold, it enables access to various types ofand winding arrangements. Thus,difference the modified designleakage has the inter-winding capacitance achieves the minimum between lowered thelowered inter-winding capacitance and achieves the minimum difference between leakage successfully the inter-winding capacitance and achieves the minimum difference between inductance. The experimental results are shown in Figure 15. inductance. The experimental results are shown Figure leakage inductance. The experimental results are in shown in 15. Figure 15. ◦ sectored winding, leakage inductance comparison of modified Figure atat 360 Figure15. 15.Toroidal Toroidaltransformers transformers 360° sectored winding, leakage inductance comparison of modified Figure 15. Toroidal transformers at 360° sectored winding, leakagesystems. inductance comparison of modified and andconventional conventionaldesign designofofhigh-frequency high-frequencylink-based link-basedMV MVinverter inverter systems. and conventional design of high-frequency link-based MV inverter systems. Temperature: Modified Modified design design shows significant control inintemperature rise by lowering the interTemperature: showssignificant significantcontrol controlin temperature rise lowering Temperature: Modified design shows temperature rise by by lowering the the interwinding capacitance and controlled leakage inductance over conventional designs (Figure 16). inter-winding capacitance and controlled leakage inductance conventional designs (Figure winding capacitance and controlled leakage inductance over over conventional designs (Figure 16). 16). An MV inverter high-frequency link-modified toroid transformer was designed differently from An MV inverter high-frequency link-modified toroid transformer was designed differently from the conventional toroid designs. Both modified prototypes, case 2 and 4, showed extremely low the conventional toroid designs. Both modified prototypes, case 2 and 4, showed extremely low coupling capacitance, that is, 20 pF and 40 pF, respectively. The toroidal transformer at 180° sectored coupling capacitance, that is, 20 pF and 40 pF, respectively. The toroidal transformer at 180° sectored winding has registered higher leakage inductance, which can be utilized in other topologies, such as winding has registered higher leakage inductance, which can be utilized in other topologies, such as dual active bridge topologies. The experimental results matched the calculated analysis quite well. Thus, dual active bridge topologies. The experimental results matched the calculated analysis quite well. Thus, Electronics 2018, 7, 142 13 of 15 An MV inverter high-frequency link-modified toroid transformer was designed differently from the conventional toroid designs. Both modified prototypes, case 2 and 4, showed extremely low coupling capacitance, that is, 20 pF and 40 pF, respectively. The toroidal transformer at 180◦ sectored winding has registered higher leakage inductance, which can be utilized in other topologies, such as dual active bridge topologies. The experimental results matched the calculated analysis quite well. Electronics 2018, x 14 of 16 Thus, the7,feasibility of the converter was validated. Figure 16. Toroidal transformers winding,temperature temperature comparison between Figure 16. Toroidal transformersatat360° 360◦ sectored sectored winding, comparison between the the conventional and and modified design of of high-frequency MVinverter inverter systems. conventional modified design high-frequency link-based link-based MV systems. 7. Conclusions 7. Conclusions Overall, the MV inverter withthe theproposed proposed modified design has has a minimized total total Overall, the MV inverter with modifiedtransformer transformer design a minimized circuit input–output capacitance to approximately 20 pF, while the temperature increase was kept circuit input–output capacitance to approximately 20 pF, while the temperature increase was kept ◦ C, without using any extra circuitry or cooling agent. The modified design is certainly a belowbelow 29.5 29.5 °C, without using any extra circuitry or cooling agent. The modified design is certainly a powerful solution to reduce thedistortion distortion in This leads to anto improved power quality powerful solution to reduce the inthe thewaveform. waveform. This leads an improved power of quality renewable power sources and an increase in the operational lifetime of the devices and loads involved of renewable power sources and an increase in the operational lifetime of the devices and loads in power systems. Hence, the MV inverter with the modified design transformer is more robust than involved in power systems. Hence, the MV inverter with the modified design transformer is more other available power inverters of the same power rate. These experimental measurements, which robustagree thanwith other available power inverters of the same power rate. These experimental measurements, the mathematical derivation, prove that the transformer shape and winding arrangements whichhave agree with the on mathematical derivation, prove that the transformer andwhen winding a huge impact the inter-winding capacitance, and cannot be ignored in powershape inverters arrangements haveimprovement a huge impact the inter-winding capacitance, and cannot be ignored in power power quality is ofon concern. inverters when power quality improvement is ofthe concern. Finally, the overall result achieved with prototype provides a very high resistance to the common the mode noise current by rapid transients,provides which makes the MV inverter feasibleto the Finally, overall result caused achieved withvoltage the prototype a very high resistance for renewable energy sources applications. For future research, a study of the optimal design method common mode noise current caused by rapid voltage transients, which makes the MV inverter feasible on advanced prototypes with higher inductive with more THD will be conducted. for renewable energy sources applications. For coupling future research, a controlled study of the optimal design method on advanced prototypes with higher inductive coupling with more controlled THD will be conducted. Author Contributions: H.-J.K., G.S.P., H.S., and H. conceptualized the idea of this research project. H.-J.K. and G.S.P. developed the proposal to the funding body. Finally, the project was awarded the funding. H., P.S., and H.S. discuss the design for the MV inverter high-frequency toroid transformer. H. this and H.Y.L. developed 3D and Author Contributions: H.-J.K., G.S.P., H.S., and H. conceptualized the idea of research project.the H.-J.K. design model including material selection. The fabrication and integration of the experimental setup were mostly G.S.P.carried developed the to and the M.U.A., fundingunder body.the Finally, the project was awarded the funding. H., P.S.,and and H.S. out by theproposal H., M.A.K. supervision of H.J.K. and G.S.P. Mathematics derivation real-time data for wasthe analyzed by H.S.high-frequency and H. The papertoroid was written by H. and discuss the design MV inverter transformer. H.H.J.K. and H.Y.L. developed the 3D design This researchselection. was supported by Basic Research Laboratoryof through the National Research Foundations modelFunding: including material The fabrication and integration the experimental setup were mostly carried of Korea. Funded by the Ministry of Science, ICT, and Future Planning (NRF-2015R1A4A1041584). out by the H., M.A.K. and M.U.A., under the supervision of H.J.K. and G.S.P. Mathematics derivation and realConflicts of Interest: The authors declare no conflict of interest. time data was analyzed by H.S. and H. The paper was written by H. and H.J.K. Funding: This research was supported by Basic Research Laboratory through the National Research Foundations of Korea. Funded by the Ministry of Science, ICT, and Future Planning (NRF-2015R1A4A1041584). Conflicts of interest: The authors declare no conflict of interest. References 1. 2. Gu, W.J.; Liu, R. A study of volume and weight vs. frequency for high-frequency transformers. In Proceedings of IEEE Power Electronics Specialist Conference (PESC 1993), Seattle, WA, USA, 20–24 June 1993; pp. 1123–1129. Leibl, M.; Ortiz, G.; Kolar, J.W. Design and experimental analysis of a medium-frequency transformer for Electronics 2018, 7, 142 14 of 15 References 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. Gu, W.J.; Liu, R. A study of volume and weight vs. frequency for high-frequency transformers. In Proceedings of the IEEE Power Electronics Specialist Conference (PESC 1993), Seattle, WA, USA, 20–24 June 1993; pp. 1123–1129. Leibl, M.; Ortiz, G.; Kolar, J.W. Design and experimental analysis of a medium-frequency transformer for solid-state transformer applications. IEEE J. Emerg. Sel. Top. Power Electron. 2017, 5, 110–123. [CrossRef] Kulkarni, A.; John, V. New start-up scheme for HF transformer link photovoltaic inverter. IEEE Trans. Ind. Appl. 2017, 53, 232–241. [CrossRef] Basu, K.; Mohan, N. A high-frequency link single-stage PWM inverter with common-mode voltage suppression and source-based commutation of leakage energy. IEEE Trans. Power Electron. 2014, 29, 3907–3918. [CrossRef] De, D.; Ramanarayanan, V. A proportional $bm +$ multiresonant controller for three-phase four-wire high-frequency link inverter. IEEE Trans. Power Electron. 2010, 25, 899–906. [CrossRef] Hayashi, Y.; Matsugaki, Y.; Ninomiya, T. Design Consideration for High Step-up Nonisolated Multicellular dc-dc Converter for PV Micro Converters. Available online: https://www.hindawi.com/journals/je/2018/ 5098083/ (accessed on 11 June 2018). Kouro, S.; Leon, J.I.; Vinnikov, D.; Franquelo, L.G. Grid-connected photovoltaic systems: an overview of recent research and emerging PV converter technology. IEEE Ind. Electron. Mag. 2015, 9, 47–61. [CrossRef] Sathishkumar, P.; Krishna, T.N.V.; Himanshu; Khan, M.A.; Zeb, K.; Kim, H.-J. Digital soft start implementation for minimizing start up transients in high power DAB-IBDC converter. Energies 2018, 11, 956. [CrossRef] Alexander, S. Development of solar photovoltaic inverter with reduced harmonic distortions suitable for Indian sub-continent. Renew. Sustain. Energy Rev. 2016, 56, 694–704. [CrossRef] Sathishkumar, P.; Himanshu; Piao, S.; Khan, M.A.; Kim, D.-H.; Kim, M.-S.; Jeong, D.-K.; Lee, C.; Kim, H.-J. A blended SPS-ESPS control DAB-IBDC converter for a standalone solar power system. Energies 2017, 10, 1431. [CrossRef] Singh, R.; Taghizadeh, S.; Tan, N.M.L.; Pasupuleti, J. Battery energy storage system for PV output power leveling. J. Eng. 2018, 2018, 5098083. Available online: https://www.hindawi.com/journals/ape/2014/ 796708/ (accessed on 11 June 2018). [CrossRef] Bolduc, P.; Lehmicke, D.; Smith, J. Performance of a grid-connected PV system with energy storage. In Proceedings of the 23th IEEE Photovoltaic Specialists Conference (Cat. No.93CH3283-9), Louisville, KY, USA, 10–14 May 1993; pp. 1159–1162. Tan, N.M.L.; Abe, T.; Akagi, H. Design and performance of a bidirectional isolated DC–DC converter for a battery energy storage system. IEEE Trans. Power Electron. 2012, 27, 1237–1248. [CrossRef] McBee, K.D. Transformer aging due to high penetrations of PV, EV charging, and energy storage applications. In Proceedings of the 2017 Ninth Annual IEEE Green Technologies Conference (GreenTech), Denver, CO, USA, 29–31 March 2017; pp. 163–170. Bojoi, R.I.; Limongi, L.R.; Roiu, D.; Tenconi, A. Enhanced power quality control strategy for single-phase inverters in distributed generation systems. IEEE Trans. Power Electron. 2011, 26, 798–806. [CrossRef] Eltawil, M.A.; Zhao, Z. Grid-connected photovoltaic power systems: Technical and potential problems—A review. Renew. Sustain. Energy Rev. 2010, 14, 112–129. [CrossRef] Popavath, L.N.; Kaliannan, P. Photovoltaic-STATCOM with Low Voltage Ride through Strategy and Power Quality Enhancement in a Grid Integrated Wind-PV System. Electronics 2018, 7, 51. [CrossRef] Real-Calvo, R.; Moreno-Munoz, A.; Gonzalez-De-La-Rosa, J.J.; Pallares-Lopez, V.; Gonzalez-Redondo, M.J.; Moreno-Garcia, I.M. An embedded system in smart inverters for power quality and safety functionality. Energies 2016, 9, 219. [CrossRef] Li, Y.; Oruganti, R. A flyback-CCM inverter scheme for photovoltaic AC module application. Aust. J. Electr. Electron. Eng. 2009, 6, 301–309. [CrossRef] Pairodamonchai, P.; Suwankawin, S.; Sangwongwanich, S. Design and implementation of a hybrid output EMI filter for high-frequency common-mode voltage compensation in PWM inverters. IEEE Trans. Ind. Appl. 2009, 45, 1647–1659. [CrossRef] Electronics 2018, 7, 142 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 15 of 15 Wang, F.; Duarte, J.L.; Hendrix, M.A.M.; Ribeiro, P.F. Modeling and analysis of grid harmonic distortion impact of aggregated DG inverters. IEEE Trans. Power Electron. 2011, 26, 786–797. [CrossRef] Grady, W.M.; Santoso, S. Understanding power system hannonics. IEEE Power Eng. Rev. 2001, 21, 8–11. [CrossRef] Abdi, B.; Ranjbar, A.H.; Farabi, V.; Yazdanparast, M.S. Effect of transformer’s parameters on harmonic generation. Energy Procedia 2011, 12, 679–685. [CrossRef] Murthy-Bellur, D.; Kazimierczuk, M.K. Winding losses caused by harmonics in high-frequency flyback transformers for pulse-width modulated dc-dc converters in discontinuous conduction mode. IET Power Electron. 2010, 3, 804–817. [CrossRef] Zolfaghari, A.; Chan, A.; Razavi, B. Stacked inductors and transformers in CMOS technology. IEEE J. Solid-State Circuits 2001, 36, 620–628. [CrossRef] Portolan, A.; Hofsajer, I.W. The analysis and design of an inter-winding shielding structure of a high frequency transformer. In Proceedings of the 2007 IEEE Power Engineering Society Conference and Exposition in Africa-PowerAfrica, Johannesburg, South Africa, 16–20 July 2007; pp. 1–6. Nguyen-Duy, K.; Ouyang, Z.; Knott, A.; Andersen, M.A.E. Minimization of the transformer inter-winding parasitic capacitance for modular stacking power supply applications. In Proceedings of the 2014 16th IEEE European Conference on Power Electronics and Applications, Lappeenranta, Finland, 26–28 August 2014; pp. 1–10. Ali, M.U.; Nengroo, S.H.; Khan, M.A.; Zeb, K.; Kamran, M.A.; Kim, H.J. A real-time simulink interfaced fast-charging methodology of lithium-ion batteries under temperature feedback with fuzzy logic control. Energies 2018, 11, 1122. Ajami, A.; Farakhor, A.; Ardi, H. Minimisations of total harmonic distortion in cascaded transformers multilevel inverter by modifying turn ratios of the transformers and input voltage regulation. IET Power Electron. 2014, 7, 2687–2694. [CrossRef] Kashyap, M.; Kansal, S. Temperature control in transformer using intelligent system. In Proceedings of the 2015 2nd IEEE International Conference on Recent Advances in Engineering Computational Sciences (RAECS), Chandigarh, India, 21–22 December 2015; pp. 1–6. Hurezeanu, I.; Nicola, C.I.; Sacerdoţianu, D.; Nicola, M.; Aciu, A.M.; Niţu, M.C. Temperature control and monitoring system for power transformer windings using fiber optic sensors. In Proceedings of the 2016 IEEE International Symposium on Fundamentals of Electrical Engineering (ISFEE), Bucharest, Romania, 30 June–2 July 2016; pp. 1–4. Blache, F.; Keradec, J.P.; Cogitore, B. Stray capacitances of two winding transformers: equivalent circuit, measurements, calculation and lowering. In Proceedings of the 1994 IEEE Industry Applications Society Annual Meeting, Denver, CO, USA, 2–6 October 1994; pp. 1211–1217. Conway, D.W. Shielded Electrical Wire Construction, and Transformer Utilizing the same for Reduction of Capacitive Coupling. U.S. Patent 5,012,125, 30 April 1991. De León, F.; Purushothaman, S.; Qaseer, L. Leakage inductance design of toroidal transformers by sector winding. IEEE Trans. Power Electron. 2014, 29, 473–480. [CrossRef] Mathew, A.P.; Oksman, K.; Sain, M. Mechanical properties of biodegradable composites from poly lactic acid (PLA) and microcrystalline cellulose (MCC). J. Appl. Polym. Sci. 2005, 97, 2014–2025. [CrossRef] Silverajah, V.S.G.; Ibrahim, N.A.; Zainuddin, N.; Yunus, W.M.Z.W.; Hassan, H.A. Mechanical, thermal and morphological properties of poly (lactic acid)/epoxidized palm olein blend. Molecules 2012, 17, 11729–11747. [CrossRef] [PubMed] Mclyman, C.W. Transformer and Inductor Design Handbook; CRC Press: Boca Raton, FL, USA, 2004. Available online: https://www.taylorfrancis.com/books/9780203913598 (accessed on 31 March 2004). © 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).