MMS GST INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION QUANTITY INSTALLATION MANUFACTURER TYPE NO MATERIAL SOURCE TOTAL QUANTITY ABU ALI MARINE BUILDING AS PER MTO * NOTIFIER, SIEMENS OR APPROVED EQUIVALENT AS PER RVL * 3 ADDRESSABLE SMOKE DETECTOR SPECIFICATIONS ISSUED FOR CONSTRUCTION DESCRIPTION L1-05, L1-06, L1-08 RA-018949.001 TYPE : APPROVAL /LISTINGS : INTELLIGENT ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR UL LISTED OR FM APPROVED TECHNOLOGY ADDRESSABLE PHOTOELECTRIC DETECTOR WITH UNIQUE OPTICAL SENSING CHAMBER HOUSING LOW PROFILE WITH SURFACE MOUNTING BASE ADDRESS SETTING TYPE SENSITIVITY AND PRE-ALARM LEVELS FEATURES ROTARY DECIMAL ADDRESS SWITCHES OR BY DEVICE PROGRAMMER ADJUSTABLE THROUGH PANEL. PRE-ALARM REPORTING BASED ON FIRE PROFILE SELECTED, REMOTE SENSITIVITY MEASUREMENT CAPABILITY, AUTOMATIC ENVIRONMENTAL COMPENSATION MULTII-COLOR (RED/GREEN) FLASH GREEN WHEN NORMAL AND STEADY RED IN ALARM, BUILT IN MAGNETIC TEST SWITCH OR AUTOMATIC TEST COMMAND FROM PANEL. AS PEER DEVICES BY TYPE CODE FROM FACP SHALL USES STATE-OF-THE-ART MICROPROCESSOR CIRCUITRY WITH ERROR CHECK, DETECTOR SELF-DIAGNOSTICS AND SUPERVISION PROGRAMS A DUST RESISTANT, FIELD CLEANABLE PHOTO CHAMBER FALSE INPUT CAUSED BY RADIO FREQUENCY (RFI) AND ELECTROMAGNETIC (EMI) INTERFERENCE DUAL STATUS LEDS ON DETECTOR TEST COMMUNICATION WITH SLC INTERNAL IDENTIFYING TYPE JO/EWO 22H201 DATE DETECTOR SHALL CONSISTS OF DETECTOR SHALL IDENTIFY AND DISREGARD MECHANICAL DATA MOUNTING : COVER : AUXILIARY / OPTIONAL DEVICES 00 REV NO. 09/20/2022 OTHER OPTIONS DISCIPLINE ENGINEER WOZ X DATE: SURFACE OR PENDANT / SUSPENDED MOUNT N/A A REMOTE ALARM OUTPUT, REMOTE LED INDICATOR, REMOTE TEST STATION. SHALL INCLUDE RED ALARM LED AND MAGNET TEST SWITCH. RELAY BASE, AUDIBLE BASE, AND DUCT HOUSING DETECTOR BASE TO BE SUPPLIED BY VENDOR. SEE NOTE-1 FILTERS. TEST MAGNET WITH TELESCOPING HANDLE. PHOTO INSECT SCREEN. * REQUIRED ACCESSORIES: REPLACEMENTS SHALL BE AVAILABLE: MATERIAL: NAME PLATE: 09/20/2022 PROJECT ENGINEER MMS DATE: WIRING: 09/20/2022 CERTIFIED SHIPPING WEIGHT: DIMENSIONS: GST DATE: 09/20/2022 ELECTRICAL DATA CONSTRUCTION AGENCY HMH DATE: SINGLE CONDUCTOR WIRE SHALL BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). SEE NOTE:- 2 SEE NOTE:- 2 09/20/2022 OPERATIONS OPERATING VOLTAGE RANGE MAX STAND BY CURRENT MAX ALARM CURRENT ALARM AUXILIARY CONTACTS (DPDT): LOOP RESISTANCE LED CURRENT AMS 25 SEPTEMBER 2022 DATE: BY: OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY (DCC) NO. _____________________ 22H201-0001-001 ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ ENVIRONMENTAL CONDITION 09/20/2022 EDSD VERIFICATION DATE: 16 TO 33 VDC. 300 MICRO AMPS @ 24 VDC 6.5mA @ 24VDC --40 OHMS MAX 6.5 mA @ 24 VDC 32°F to 120°F (0°C to 49°C). 15 - 27°C/60 - 80°F. 0 % TO 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. ` ADDRESSABLE SMOKE DETECTOR RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY DWG.TYPE 302 ONSHORE FAC. OFFSHORE CRUDE ABU ALI PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO. 001 00 DAT SAUDI ARABIA J.O. / EWO: B RE-018951 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS PMT OPRNS DATA SHEET FOR ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR GENERAL INFORMATION ENGG CERT SAUDI ARABIAN OIL COMPANY HMH Saudi Aramco 2616-ENG (03/99) DATA SHEET FOR ADDRESSABLE MANUAL CALL POINT GENERAL INFORMATION MMS GST INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION QUANTITY INSTALLATION MANUFACTURER TYPE NO MATERIAL SOURCE TOTAL QUANTITY ABU ALI MARINE BUILDING AS PER MTO * NOTIFIER, SIEMENS OR APPROVED EQUIVALENT AS PER RVL * 7 ADDRESSABLE MANUAL CALL POINT SPECIFICATIONS ISSUED FOR CONSTRUCTION DESCRIPTION L1-01, L1-03, L1-04, L1-07, L1-09, L1-15, L1-16 RA-018949.001 TYPE : APPROVAL /LISTINGS : INTELLIGENT ADDRESSABLE MANUAL CALL POINT UL LISTED OR FM APPROVED TECHNOLOGY ADDRESSABLE DUAL ACTION MANUAL CALL POINT WITH HANDLE LATCHES IN DOWN POSITION AND THE WORD “ACTIVATED” APPEARS TO CLEARLY INDICATE THE STATION HAS BEEN OPERATED MOLDED OF DURABLE POLYCARBONATE MATERIAL WITH A TEXTURED FINISH. INCLUDES BRAILLE TEXT ON STATION HANDLE ROTARY DECIMAL ADDRESS SWITCHES OR BY DEVICE PROGRAMMER N/A CAN OPEN FOR INSPECTION AND ADDRESS SETTING WITHOUT CAUSING AN ALARM CONDITION. HANDLE LATCHES IN DOWN POSITION AND THE WORD “ACTIVATED” APPEARS TO CLEARLY INDICATE THE STATION HAS BEEN OPERATED MULTII-COLOR (RED/GREEN) FLASH GREEN WHEN NORMAL AND STEADY RED IN ALARM, N/A AS PEER DEVICES BY TYPE CODE FROM FACP HIGHLY VISIBLE DURABLE POLYCARBONATE TEXTURED BOX, DUAL ACTION HANDLE WITH WORD “ACTIVATED”. HOUSING ADDRESS SETTING TYPE SENSITIVITY AND PRE-ALARM LEVELS FEATURES DATE REV NO. TEST COMMUNICATION WITH SLC INTERNAL IDENTIFYING TYPE OTHER OPTIONS 00 09/20/2022 22H201 JO/EWO DUAL STATUS LEDS ON DETECTOR MANUAL CALL POINT SHALL CONSISTS OF MECHANICAL DATA DISCIPLINE ENGINEER WOZ X 09/20/2022 DATE: PROJECT ENGINEER MMS 09/20/2022 DATE: JZM MOUNTING : COVER : AUXILIARY / OPTIONAL DEVICES ACCESSORIES: REPLACEMENTS SHALL BE AVAILABLE: MATERIAL: NAME PLATE: WIRING: WALL SURFACE MOUNTED OR SEMI FLUSH MOUNTED PROTECTIVE COVER “OPTIONAL BASED ON DESIGN” SURFACE BACKBOX, TRIM RING, KEYS TO BE SUPPLIED BY VENDOR. SEE NOTE-1 KEYS * REQUIRED SINGLE CONDUCTOR WIRE SHALL BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). SEE NOTE:- 2 SEE NOTE:- 2 SHIPPING WEIGHT: DIMENSIONS: ELECTRICAL DATA CERTIFIED GST DATE: 09/20/2022 CONSTRUCTION AGENCY HMH DATE: 09/20/2022 OPERATIONS AMS 25 SEPTEMBER 2022 BY: DATE: (DCC) NO. _____________________ 22H201-0001-001 ISSUED FOR CONSTRUCTION (IFC) 16 TO 33 VDC. 375 MICRO AMPS @ 24 VDC 5.00 mA @ 24VDC N/A 40 OHMS MAX 5.00 mA @ 24 VDC ENVIRONMENTAL CONDITION OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY 32°F to 120°F (0°C to 49°C) 15 - 27°C/60 - 80°F. 0 % TO 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). NOTES: BY DRAWING COMPLETION CERTIFICATE OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER 09/20/2022 EDSD VERIFICATION DATE: OPERATING VOLTAGE RANGE MAX STAND BY CURRENT MAX ALARM CURRENT ALARM AUXILIARY CONTACTS (DPDT): LOOP RESISTANCE LED CURRENT * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. ` ADDRESSABLE MANUAL CALL POINT RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY DWG.TYPE DAT ONSHORE FAC. OFFSHORE CRUDE ABU ALI SAUDI ARABIA PLANT NO. INDEX 302 J.O. / EWO: B DRAWING NO. RE-018951 SHT.NO. REV.NO. 002 00 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS SAUDI ARABIAN OIL COMPANY HMH ENGG CERT PMT OPRNS Saudi Aramco 2616-ENG (03/99) AS PER MTO * AS PER RVL * * 9 HORN WITH STROBE WITH FIELD-SELECTABLE CANDELA SETTINGS UL LISTED OR FM APPROVED TECHNOLOGY FIELD-SELECTABLE CANDELA SETTINGS HORN WITH STROBE HOUSING MOLDED OF DURABLE POLYCARBONATE MATERIAL WITH A UNIVERSAL MOUNTING PLATE THAT MOUNTS TO A STANDARD 4.0" X 4.0" BACKBOX OR 2”X2” WITH THE WORD “FIRE” WRITTEN ON IT. TONE/CANDELA SETTING TYPE SENSITIVITY AND PRE-ALARM LEVELS FEATURES CANDELA SETTINGS HORN RATING COMMUNICATION WITH NAC INTERNAL IDENTIFYING TYPE OTHER OPTIONS ROTARY SWITCHES N/A FIELD-SELECTABLE TONE & CANDELA SETTINGS FIELD-SELECTABLE 15, 30, 60, 95, 110 88+ DBA AT 10 FEET AS PEER DEVICES N/A N/A 22H201 TYPE : APPROVAL /LISTINGS : MOUNTING : COVER : AUXILIARY / OPTIONAL DEVICES ACCESSORIES: REPLACEMENTS SHALL BE AVAILABLE: MATERIAL: NAME PLATE: WIRING: DISCIPLINE ENGINEER WOZ 09/20/2022 DATE: PROJECT ENGINEER X SURFACE MOUNTED OR SEMI FLUSHED AS PER DESIGN REQUIREMENT RED HOUSING WITH CLEAR LENS BACKBOX TO BE SUPPLIED BY VENDOR. SEE NOTE-1 N/A * REQUIRED SINGLE CONDUCTOR WIRE SHALL BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). SEE NOTE:- 2 SEE NOTE:- 2 SHIPPING WEIGHT: DIMENSIONS: MMS DATE: ELECTRICAL DATA 09/20/2022 CERTIFIED GST DATE: 09/20/2022 CONSTRUCTION AGENCY HMH DATE: 09/20/2022 OPERATIONS AMS 25 SEPTEMBER 2022 BY: DATE: (DCC) NO. _____________________ 22H201-0001-001 ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ 16 TO 33 VDC. N/A 79.0mA @ 15cd; 107.0mA @ 30cd; 176.0mA @ 60cd; 194.0mA @ 90cd, 212.0mA @ 110cd N/A N/A MAXIMUM IDC WIRING RESISTANCE MAX NAC CURRENT RATINGS ENVIRONMENTAL CONDITION OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY 32°F to 120°F (0°C to 49°C) 15 - 27°C/60 - 80°F. 0 % TO 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). 09/20/2022 EDSD VERIFICATION DATE: OPERATING VOLTAGE RANGE MAX STAND BY CURRENT MAX ALARM CURRENT “SEE NOTE 3” NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. 3. VENDOR TO SPECIFY EXACT CURRENT WITHDRAWL FOR PROPER VOLTAGE DROP AND BATTERY CALCULATION. ` DATA SHEET FOR HORN WITH STROBE RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY DWG.TYPE DAT ONSHORE FAC. OFFSHORE CRUDE ABU ALI SAUDI ARABIA PLANT NO. INDEX 302 J.O./ EWO: B DRAWING NO. RE-018951 SHT.NO. REV.NO. 003 00 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS GST MMS ABU ALI MARINE BUILDING MECHANICAL DATA 09/20/2022 JO/EWO H1-01, H1-02, H1-03, H1-04, H1-05, H1-06, H1-07, H1-09, H3-01 RA-018949.001 HORN WITH STROBE SPECIFICATIONS 00 REV NO. DATE INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION QUANTITY INSTALLATION MANUFACTURER TYPE NO MATERIAL SOURCE TOTAL QUANTITY ISSUED FOR CONSTRUCTION PMT OPRNS DATA SHEET FOR HORN WITH STROBE GENERAL INFORMATION DESCRIPTION ENGG CERT SAUDI ARABIAN OIL COMPANY HMH Saudi Aramco 2616-ENG (03/99) MMS GST INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION QUANTITY INSTALLATION MANUFACTURER TYPE NO MATERIAL SOURCE TOTAL QUANTITY ISSUED FOR CONSTRUCTION 22H201 DESCRIPTION JO/EWO DATE 09/20/2022 00 REV NO. FIELD-SELECTABLE CANDELA SETTINGS HORN WITH STROBE HOUSING MOLDED OF DURABLE POLYCARBONATE MATERIAL WITH A UNIVERSAL MOUNTING PLATE THAT MOUNTS TO A WEATHERPROOF BACKBOX OR 2”X2” WITH THE WORD “FIRE” WRITTEN ON IT. TONE/CANDELA SETTING TYPE SENSITIVITY AND PRE-ALARM LEVELS FEATURES CANDELA SETTINGS TEST COMMUNICATION WITH NAC INTERNAL IDENTIFYING TYPE OTHER OPTIONS ROTARY SWITCHES N/A FIELD-SELECTABLE TONE & CANDELA SETTINGS FIELD-SELECTABLE 15, 30, 60, 95, 110 N/A AS PEER DEVICES N/A N/A SURFACE MOUNTED OR SEMI FLUSHED AS PER DESIGN REQUIREMENT WEATHERPROOF RED HOUSING WITH CLEAR LENS WEATHERPROOF BACKBOX TO BE SUPPLIED BY VENDOR. SEE NOTE-1 N/A * REQUIRED SINGLE CONDUCTOR WIRE SHALL BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). SEE NOTE:- 2 SEE NOTE:- 2 ELECTRICAL DATA OPERATING VOLTAGE RANGE MAX STAND BY CURRENT MAX ALARM CURRENT “SEE NOTE 3” GST 09/20/2022 CONSTRUCTION AGENCY HMH 16 TO 33 VDC. N/A 79.0mA @ 15cd; 107.0mA @ 30cd; 176.0mA @ 60cd; 194.0mA @ 90cd, 212.0mA @ 110cd N/A N/A MAXIMUM IDC WIRING RESISTANCE MAX NAC CURRENT RATINGS 09/20/2022 ENVIRONMENTAL CONDITION OPERATIONS AMS OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY –40°F to 151°F (–40°C to 66°C). 15 - 27°C/60 - 80°F. 0 % TO 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). 25 SEPTEMBER 2022 BY: DATE: (DCC) NO. _____________________ 22H201-0001-001 ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE OF THIS DRAWING IS COVERED, FOR ALL APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER 09/20/2022 EDSD VERIFICATION REVISION REVISIONCERTIFICATION CERTIFICATE TECHNOLOGY 09/20/2022 JZM CERTIFIED 00 THIS INDICATES THAT REV. NO.__________ WEATHERPROOF HORN WITH STROBE WITH FIELD-SELECTABLE CANDELA SETTINGS UL LISTED OR FM APPROVED SHIPPING WEIGHT: DIMENSIONS: MMS DATE: TYPE : APPROVAL /LISTINGS : MECHANICAL DATA X DATE: AS PER MTO * AS PER RVL * * 4 MOUNTING : COVER : AUXILIARY / OPTIONAL DEVICES ACCESSORIES: REPLACEMENTS SHALL BE AVAILABLE: MATERIAL: NAME PLATE: WIRING: 09/20/2022 DATE: PROJECT ENGINEER DATE: ABU ALI MARINE BUILDING WEATHERPROOF HORN WITH STROBE SPECIFICATIONS DISCIPLINE ENGINEER WOZ DATE: H2-01, H2-02, H2-03, H2-04 RA-018949.001 NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. 3. VENDOR TO SPECIFY EXACT CURRENT WITHDRAWL FOR PROPER VOLTAGE DROP AND BATTERY CALCULATION. ` WEATHERPROOF HORN WITH STROBE DWG.TYPE RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY DAT ONSHORE FAC. OFFSHORE CRUDE ABU ALI SAUDI ARABIA PLANT NO. INDEX 302 J.O. / EWO: B DRAWING NO. RE-018951 P SHT.NO. REV.NO. 004 00 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS PMT OPRNS DATA SHEET FOR WEATHERPROOF HORN WITH STROBE GENERAL INFORMATION ENGG CERT SAUDI ARABIAN OIL COMPANY HMH Saudi Aramco 2616-ENG (03/99) N/A RA-018949.001 ABU ALI MARINE BUILDING AS PER MTO * AS PER RVL * * 3 ISSUED FOR CONTRUCTION SHORT CIRCUIT ISOLATOR MODULE SPECIFICATIONS TYPE : APPROVAL /LISTINGS : SHORT CIRCUIT ISOLATOR MODULE UL LISTED OR FM APPROVED TECHNOLOGY PROVIDE PROTECTION OF SLC LOOP AGAINST SHORT CIRCUITS. IF A SHORT OCCURS BETWEEN ANY TWO ISOLATORS, THEN BOTH ISOLATORS IMMEDIATELY SWITCH TO AN OPEN CIRCUIT STATE AND ISOLATE THE GROUPS OF INITIATING DEVICES BETWEEN THEM. THE REMAINING UNITS ON THE LOOP CONTINUE TO FULLY OPERATE MOLDED OF DURABLE POLYCARBONATE MATERIAL STANDARD-SIZED MODULE MOUNTS TO A 4" [10.16 CM] SQUARE BOX ) OR AS PER VENDOR RECOMMENDATON.. THE FACE PLATE IS MADE OF OFF-WHITE HEAT-RESISTANT PLASTIC N/A N/A CAN OPEN FOR INSPECTION AND ADDRESS SETTING WITHOUT CAUSING AN ALARM CONDITION. PROVIDES A CONTROLLED CIRCUIT OF NOTIFICATION APPLIANCES. ONE LED. FLASH AMBER WHEN NORMAL AND STEADY AMBER IN SHORT CIRCUIT CONDITION N/A AS PEER DEVICES BY TYPE CODE FROM FACP N/A HOUSING ADDRESS SETTING TYPE SENSITIVITY AND PRE-ALARM LEVELS FEATURES 22H201 MECHANICAL DATA MOUNTING : 00 REV NO. DATE TEST COMMUNICATION WITH SLC INTERNAL IDENTIFYING TYPE OTHER OPTIONS 09/20/2022 JO/EWO STATUS LEDS ON MODULE DISCIPLINE ENGINEER WOZ 09/20/2022 DATE: PROJECT ENGINEER X MMS DATE: SHIPPING WEIGHT: DIMENSIONS: GST 09/20/2022 CONSTRUCTION AGENCY HMH DATE: 09/20/2022 OPERATIONS AMS 25 SEPTEMBER 2022 BY: DATE: 22H201-0001-001 (DCC) NO. _____________________ ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER 09/20/2022 EDSD VERIFICATION DATE: COVER : AUXILIARY / OPTIONAL DEVICES ACCESSORIES: REPLACEMENTS SHALL BE AVAILABLE: MATERIAL: NAME PLATE: WIRING: 09/20/2022 JZM CERTIFIED DATE: SURFACE MOUNTED TO A 4" [10.16 CM] SQUARE BOX OR AS PER VENDOR RECOMMENDATON. THE FACE PLATE IS MADE OF OFF-WHITE HEAT-RESISTANT PLASTIC BACKBOX TO BE SUPPLIED BY VENDOR. SEE NOTE-1 N/A * REQUIRED SINGLE CONDUCTOR WIRE SHALL BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). SEE NOTE:- 2 SEE NOTE:- 2 ELECTRICAL DATA OPERATING VOLTAGE RANGE MAX STAND BY CURRENT MAX ALARM CURRENT MAXIMUM IDC WIRING RESISTANCE MAX NAC CURRENT RATINGS LED CURRENT 16 TO 33 VDC. 450 MICRO AMPS @ 24 VDC 17.0 mA @ 24VDC 1500 Ohms 2A @ CLASS A WIRING 17.0 mA @ 24VDC ENVIRONMENTAL CONDITION OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY 32°F to 120°F (0°C to 49°C) 15 - 27°C/60 - 80°F. 0 % TO 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. ` SHORT CIRCUIT ISOLATOR MODULE RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY ONSHORE FAC. OFFSHORE CRUDE ABU ALI DWG.TYPE PLANT NO. INDEX DRAWING NO. SHT.NO. REV.NO. 005 00 DAT 302 SAUDI ARABIA J.O. / EWO: B RE-018951 P 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS GST INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION QUANTITY INSTALLATION MANUFACTURER TYPE NO MATERIAL SOURCE TOTAL QUANTITY MMS PMT OPRNS DATA SHEET FOR SHORT CIRCUIT ISOLATOR MODULE GENERAL INFORMATION DESCRIPTION ENGG CERT SAUDI ARABIAN OIL COMPANY HMH Saudi Aramco 2616-ENG (03/99) INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION QUANTITY INSTALLATION MANUFACTURER TYPE NO MATERIAL SOURCE TOTAL QUANTITY L1-11, L1-12, L1-13, L1-14 RA-018949.001 MOUNTING : COVER : AUXILIARY DEVICES: - SHIPPING WEIGHT: DIMENSIONS: OUTSIDE MOUNTING TABS. MOUNTS TO ROUND OR RECTANGULAR DUCTS FROM 1’ TO 12’ (0.3 TO 3.7 METERS) WIDE. TRANSPARENT COVER FOR CONVENIENT VISUAL INSPECTION (WEATHER PROOF TYPE) A REMOTE ALARM OUTPUT, REMOTE LED ANNUNCIATOR, REMOTE TEST STATION. SHALL INCLUDE RED ALARM LED AND MAGNET TEST SWITCH. TO BE SUPPLIED BY VENDOR SEE NOTE-1 FILTERS. TEST MAGNET WITH TELESCOPING HANDLE. PHOTO INSECT SCREEN.END CAP FOR SAMPLING TUBE. SAMPLING TUBE. * REQUIRED SINGLE CONDUCTOR WIRE BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). 3.35 LBS. (1.5 KG). OR * 14.75" (37 CM) LENGTH X 5.50" (14 CM) WIDTH X 2.75" (7 CM) DEEP. OPERATING VOLTAGE RANGE MAX STAND BY CURRENT MAX ALARM CURRENT ALARM AUXILIARY CONTACTS (DPDT): LOOP RESISTANCE LED CURRENT 16 TO 33 VDC. 300MICRO AMPS @ 24 VDC 6.5MA @ 24VDC 10 A @ 30 VDC; 10 A @ 277 VAC (0.75 POWER FACTOR) 40 OHMS MAX 6.5 MA @ 24 VDC OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY DUCT AIR VELOCITY: 32° TO 131°F (0° TO 55°C). 15 - 27°C/60 - 80°F. 10% TO 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). 300 TO 4,000 FEET/MIN (0.5 TO 20.32 M/S). ABU ALI MARINE BUILDING AS PER MTO * AS PER RVL * AS PER MTO 4 MECHANICAL DATA ACCESSORIES: REPLACEMENTS SHALL BE AVAILABLE: MATERIAL: NAME PLATE: WIRING: 22H201 09/20/2022 ENVIRONMENTAL CONDITION 00 REV NO. DATE JO/EWO ELECTRICAL DATA DISCIPLINE ENGINEER WOZ 09/20/2022 DATE: PROJECT ENGINEER MMS DATE: 09/20/2022 CERTIFIED NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. GST DATE: 09/20/2022 CONSTRUCTION AGENCY HMH DATE: 09/20/2022 OPERATIONS AMS 25 SEPTEMBER 2022 BY: DATE: (DCC) NO. 22H201-0001-001 _____________________ ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER 09/20/2022 EDSD VERIFICATION DATE: DWG.TYPE DATA SHEET FOR ADDRESSABLE DUCT SMOKE DETECTOR RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY ONSHORE FAC. OFFSHORE CRUDE ABU ALI PLANT NO. INDEX 302 B DRAWING NO. SHT.NO. REV.NO. 006 00 DAT SAUDI ARABIA J.O. / EWO: RE-018951 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. PMT OPRNS AMS MMS ENGG CERT DATA SHEET FOR ADDRESSABLE DUCT SMOKE DETECTOR GENERAL INFORMATION ISSUED FOR CONSTRUCTION DESCRIPTION SAUDI ARABIAN OIL COMPANY GST HMH Saudi Aramco 2616-ENG (03/99) INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION MANUFACTURER TOTAL QUANTITY L1-02 RA-018949.001 ABU ALI MARINE BUILDING AS PER RVL 1 DESCRIPTION ISSUED FOR CONSTRUCTION ADDRESSABLE HEAT DETECTOR SPECIFICATIONS TYPE APPROVAL /LISTINGS INTELLIGENT ADDRESSABLE HEAT DETECTOR UL LISTED, TECHNOLOGY ADDRESSABLE DETECTOR WITH THERMISTOR SENSING CIRCUIT TO PRODUCE RATE-O-RISE THERMAL DETECTION - 15°F (8.3°C) PER MINUTE LOW PROFILE WITH SURFACE MOUNTING BASE HOUSING ADDRESS SETTING TYPE FEATURES ROTARY DECIMAL ADDRESS SWITCHES OR BY DEVICE PROGRAMMER FAST RESPONSE, REMOTE TEST FEATURE FROM THE PANEL, PLASTIC FLAMMABILITY RATING MULTII-COLOR (RED/GREEN) FLASH GREEN WHEN NORMAL AND STEADY RED IN ALARM, BUILT IN MAGNETIC TEST SWITCH OR AUTOMATIC TEST COMMAND FROM PANEL. SHALL USES STATE-OF-THE-ART MICROPROCESSOR CIRCUITRY WITH ERROR CHECK, DETECTOR SELF-DIAGNOSTICS AND SUPERVISION PROGRAMS A DUST RESISTANT, FIELD CLEANABLE PHOTO CHAMBER FALSE INPUT CAUSED BY RADIO FREQUENCY (RFI), ELECTROMAGNETIC (EMI) INTERFERENCE AND FALSE INPUT CAUSED BY DUST, LINT, AND SMALL INSECTS DUAL STATUS LEDS ON DETECTOR TEST OTHER OPTIONS DETECTOR SHALL CONSISTS OF DETECTOR SHALL IDENTIFY AND DISREGARD DATE 22H201 DISCIPLINE ENGINEER WOZ ELECTRICAL DATA 09/20/2022 DATE: PROJECT ENGINEER MMS DATE: 09/20/2022 OPERATING VOLTAGE RANGE MAX STAND BY CURRENT MAX ALARM CURRENT ALARM AUXILIARY CONTACTS (DPDT): LOOP RESISTANCE LED CURRENT 16 TO 33 VDC. 300 MICRO AMPS @ 24 VDC 6.5mA @ 24VDC N/A 40 OHMS MAX 6.5 mA @ 24 VDC ENVIRONMENTAL CONDITION CERTIFIED GST DATE: SURFACE OR PENDANT / SUSPENDED MOUNT N/A A REMOTE ALARM OUTPUT, REMOTE LED INDICATOR, REMOTE TEST STATION. SHALL INCLUDE RED ALARM LED AND MAGNET TEST SWITCH. RELAY BASE, AUDIBLE BASE, AND DUCT HOUSING TO BE SUPPLIED BY VENDOR. SEE NOTE-1 FILTERS. TEST MAGNET WITH TELESCOPING HANDLE. PHOTO INSECT SCREEN. REQUIRED SINGLE CONDUCTOR WIRE SHALL BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). ACCESSORIES REPLACEMENTS SHALL BE AVAILABLE NAME PLATE WIRING 00 REV NO. 09/20/2022 JO/EWO MECHANICAL DATA MOUNTING COVER AUXILIARY / OPTIONAL DEVICES 09/20/2022 OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY –4°F TO 100°F (–20°C TO 38°C). 15 - 27°C/60 - 80°F. 0 % TO 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). CONSTRUCTION AGENCY HMH DATE: 09/20/2022 OPERATIONS AMS 25 SEPTEMBER 2022 BY: DATE: (DCC) NO. 22H201-0001-001 _____________________ ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER 09/20/2022 EDSD VERIFICATION DATE: NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. DWG.TYPE DATA SHEET FOR ADDRESSABLE HEAT DETECTOR RELOCATE JAZAN-ABHA REFINED PRODUCTS PIPELINE FOR IN-PLANT FACILITY ONSHORE FAC. OFFSHORE CRUDE ABU ALI PLANT NO. INDEX 302 B DRAWING NO. SHT.NO. REV.NO. 007 00 DAT SAUDI ARABIA J.O. / EWO: RE-018951 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS PMT OPRNS DATA SHEET FOR ADDRESSABLE HEAT DETECTOR GENERAL INFORMATION MMS ENGG CERT SAUDI ARABIAN OIL COMPANY GST HMH Saudi Aramco 2616-ENG (03/99) GST HMH DATA SHEET FOR STROBE LIGHT GENERAL INFORMATION INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION MANUFACTURER TOTAL QUANTITY H1-08, H3-02 RA-018949.001 ABU ALI MARINE BUILDING AS PER RVL 2 JO/EWO 22H201 DATE STROBE WITH FIELD-SELECTABLE CANDELA SETTINGS UL LISTED TECHNOLOGY FIELD-SELECTABLE CANDELA SETTINGS FOR STROBE HOUSING MOLDED OF DURABLE POLYCARBONATE MATERIAL WITH A UNIVERSAL MOUNTING PLATE THAT MOUNTS TO A STANDARD 4.0" X 4.0" BACKBOX ROTARY SWITCHES FIELD-SELECTABLE TONE & CANDELA SETTINGS FIELD-SELECTABLE 15, 30, 60, 95, 110 TONE/CANDELA SETTING TYPE FEATURES CANDELA SETTINGS MECHANICAL DATA MOUNTING COVER AUXILIARY / OPTIONAL DEVICES ACCESSORIES: WIRING: SURFACE MOUNTED RED HOUSING WITH CLEAR LENS BACKBOX TO BE SUPPLIED BY VENDOR. SEE NOTE-1 SINGLE CONDUCTOR WIRE SHALL BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). ELECTRICAL DATA OPERATING VOLTAGE RANGE MAX ALARM CURRENT 16 TO 33 VDC. 41.0MA @ 15CD; 63.0MA @ 30CD; 100.0MA @ 60CD; 134.0MA @ 90CD, 158.0MA @ 110CD ENVIRONMENTAL CONDITION OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY 00 REV NO. 09/20/2022 DESCRIPTION ISSUED FOR CONSTRUCTION STROBE SPECIFICATIONS TYPE APPROVAL /LISTINGS 32°F to 120°F (0°C to 49°C) 15 - 27°C/60 - 80°F. 0 % TO 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). DISCIPLINE ENGINEER WOZ 09/20/2022 DATE: PROJECT ENGINEER MMS DATE: NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. 09/20/2022 JZM CERTIFIED GST DATE: 09/20/2022 CONSTRUCTION AGENCY HMH DATE: 09/20/2022 OPERATIONS AMS 25 SEPTEMBER 2022 BY: DATE: (DCC) NO. 22H201-0001-001 _____________________ ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER 09/20/2022 EDSD VERIFICATION DATE: DWG.TYPE DATA SHEET FOR ADDRESSABLE HEAT DETECTOR RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY ONSHORE FAC. OFFSHORE CRUDE ABU ALI PLANT NO. INDEX 302 B DRAWING NO. SHT.NO. REV.NO. 008 00 DAT SAUDI ARABIA J.O. / EWO: RE-018951 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS SAUDI ARABIAN OIL COMPANY MMS ENGG CERT PMT OPRNS Saudi Aramco 2616-ENG (03/99) MMS GST INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION QUANTITY INSTALLATION MANUFACTURER TYPE NO MATERIAL SOURCE TOTAL QUANTITY SURGE ARRESTOR SPECIFICATIONS ISSUED FOR CONSTRUCTION DESCRIPTION N/A RA-018949.001 ABU ALI MARINE BUILDING AS PER MTO * AS PER RVL * * 4 TYPE : APPROVAL /LISTINGS : LOOP CIRCUIT SURGE PROTECTOR UL LISTED 497B TECHNOLOGY FIELD REPLACEABLE WITH MODULAR EDGE CONNECTION DESIGN WITH MOUNTING BASE USING LINE-GROUND METHOD TO PROTECT THE CIRCUIT. SHALL BE SUITABLE FOR ALL NAC AND SLC LOOPS. HOUSING ADDRESS SETTING TYPE SENSITIVITY AND PRE-ALARM LEVELS FEATURES STATUS LEDS ON MODULE N/A N/A N/A ONE LED. FLASH AMBER WHEN NORMAL AND STEADY AMBER IN SHORT CIRCUIT CONDITION N/A AS PER MANUFACTURER RECOMMENDATION BY TYPE CODE FROM FACP N/A 22H201 JO/EWO TEST COMMUNICATION WITH SLC INTERNAL IDENTIFYING TYPE OTHER OPTIONS MECHANICAL DATA 00 REV NO. DATE 09/20/2022 MOUNTING : COVER : AUXILIARY / OPTIONAL DEVICES ACCESSORIES: REPLACEMENTS SHALL BE AVAILABLE: MATERIAL: NAME PLATE: WIRING: DISCIPLINE ENGINEER WOZ 09/20/2022 DATE: PROJECT ENGINEER AS PER MANUFACTURER RECOMMENDATION AS PER MANUFACTURER RECOMMENDATION TO BE SUPPLIED BY VENDOR. SEE NOTE-1 N/A * REQUIRED SINGLE CONDUCTOR WIRE SHALL BE NO SMALLER THAN 18 AWG (0.821 MM²). TERMINALS ACCOMMODATE WIRE SIZES UP TO 12 AWG (2.5 MM²). SEE NOTE:- 2 SEE NOTE:- 2 SHIPPING WEIGHT: DIMENSIONS: ELECTRICAL DATA MMS DATE: SERVICE VOLTAGE SURGE CURRENT RATING CONTINUOUS CURRENT PROTECTION MODE 09/20/2022 CERTIFIED GST DATE: ENVIRONMENTAL CONDITION 09/20/2022 CONSTRUCTION AGENCY HMH DATE: 24VDC 20,000 A 5A LINE TO GROUND OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY -40°C to 70°C 15 - 27°C/60 - 80°F. 95% NON CONDENSING 09/20/2022 OPERATIONS AMS NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. 25 SEPTEMBER 2022 BY: DATE: (DCC) NO. _____________________ 22H201-0001-001 ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE APPROVAL/CERTIFICATION REQUIREMENTS, OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ EDSD VERIFICATION CONTROL NUMBER DATE: 09/20/2022 ` LOOP CIRCUIT SURGE PROTECTOR DWG.TYPE RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY DAT 302 ONSHORE FAC. OFFSHORE CRUDE ABU ALI PLANT NO. INDEX SAUDI ARABIA J.O. / EWO: B DRAWING NO. RE-018951 SHT.NO. REV.NO. 009 00 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS PMT OPRNS DATA SHEET FOR SURGE PROTECTOR GENERAL INFORMATION ENGG CERT SAUDI ARABIAN OIL COMPANY HMH Saudi Aramco 2616-ENG (03/99) GST MMS ISSUED FOR CONSTRUCTION 22H201 DESCRIPTION FUNCTIONALITY INTELLIGENT SIGNALING LINE CIRCUITS (SLC) INTELLIGENT DEVICES ON EACH SLC LOOP SEE NOTE 3. NOTIFICATION APPLIANCE CIRCUITS TO PROVIDE SYSTEM CONTROL & MONITOR OF ALL SLC & NAC DEVICES CONNECTED TO IT 2 LOOPS 159 ADDRESSABLE DETECTOR; 159 ADDRESSABLE MODULE 04 NACS NOT LIMITED TO ALARM, PRE ALARM, TROUBLE, SUPERVISORY, SECURITY, SYSTEM NORMAL AND SYSTEM BYPASS. ACK, SIL, DRILL, RESET, LAMP-TEST, SCROLL, PRINT SCREEN/ QWERT KEY PAD FOR MONITORING AND FIELD PROGRAMMING REQUIRED AND SHALL SOUND DISTINCTIVE SIGNALS. AS REQUIRED AS REQUIRED/ PROVISION SHALL BE AVAILABLE SHALL BE AT LEAST 640-CH LCD 100 ZONES 14 ZONES LCD WITH 640 CHARACTERS NODES SUPPORT REQUIRED AT LEAST 103 FIELD PROGRAMMING ON PANEL / AUTO PROGRAM OR ON PC CHARGER FOR UP TO 24 HOURS OF STANDBY POWER. FIBER OPTIC / RS 485 OR DRY CONTACT AS NEEDED LOCAL PIEZO ELECTRIC AUDIBLE DEVICE ADDRESSABLE MONITOR CONTROL MODULES PROGRAMMABLE HARDWARE AND O/P CIRCUITS STANDARD DISPLAY PROGRAMMABLE SOFTWARE ZONES SPECIAL PROGRAMMING ZONES LCD ANNUNCIATORS NETWORK OPTION PROGRAMMING BATTERY CHARGER INTERFACE REQUIRED 09/20/2022 JO/EWO INTELLIGENT ADDRESSABLE FIRE ALARM CONTROL PANEL (HSSD COMPATIBLE) UL LISTED OR FM APPROVED OPERATOR CONTROL KEYS AND QWERT KEY PAD MECHANICAL DATA WOZ 09/20/2022 DATE: PROJECT ENGINEER X MMS 09/20/2022 CERTIFIED GST DATE: TYPE APPROVAL /LISTINGS : SYSTEM LEDS DISCIPLINE ENGINEER DATE: 302-FACP-001 RA-018949.001 ABU ALI MARINE BUILDING AS PER MTO * AS PER RVL * * 1 ADDRESSABLE FIRE ALARM CONTROL PANEL SPECIFICATIONS 00 REV NO. DATE INSTRUMENT TAG NO. LAYOUTDRAWING NUMBER/SHEET NUMBER: LOCATION :QUANTITY INSTALLATION MANUFACTURER TYPE NO MATERIAL SOURCE TOTAL QUANTITY 09/20/2022 MOUNTING : ACCESSORIES: MATERIAL: NAME PLATE: SURFACE OR SEMI FLUSH. TO BE SUPPLIED BY VENDOR SEE NOTE-1 * REQUIRED ELECTRICAL DATA PRIMARY INPUT POWER BOARD: STANDARD NOTIFICATION CIRCUITS: NON-RESETTABLE REGULATED POWER OUTPUTS: BATTERY CHARGER RANGE: OPERATING TEMPERATURE RECOMMENDED TEMP RANGE RELATIVE HUMIDITY 230 VAC, 50/60 HZ, 3.0 A. 24V 2.0A 2 x 1.5A 18 AH -200 AH. TO BE USE SEPARATE CABINET FOR BATTERIES OVER 26 AH. ENVIRONMENTAL CONDITION 32°F to 120°F (0°C to 49°C) 15 - 27°C/60 - 80°F. 93% ± 2% RH (NO CONDENSING) AT 32°C ± 2°C (90°F ± 3°F). CONSTRUCTION AGENCY HMH DATE: 09/20/2022 OPERATIONS AMS 25 SEPTEMBER 2022 BY: DATE: (DCC) NO. _____________________ 22H201-0001-001 ISSUED FOR CONSTRUCTION (IFC) BY DRAWING COMPLETION CERTIFICATE OF THIS DRAWING IS COVERED, FOR ALL REVISION REVISIONCERTIFICATION CERTIFICATE 00 THIS INDICATES THAT REV. NO.__________ APPROVAL/CERTIFICATION REQUIREMENTS, CONTROL NUMBER 09/20/2022 EDSD VERIFICATION DATE: NOTES: * VENDOR TO SPECIFY AND/OR VERIFY 1. VENDOR TO PROVIDE ALL THE ACCESSORIES REQUIRED FOR MOUNTING/INSTALLATION OF THE DEVICE. 2. VENDOR TO PROVIDE ACTUAL MANUFACTURER DATA SHEET. 3. ADDITIONAL POWER SUPPLY TO BE PROVIDED “IF REQUIRED”. VENDOR TO VERIFY ` SURGE ARRESTOR DWG.TYPE RENOVATION OF ABU ALI PIER MARINE ADMIN BLDG.JUBL INDUSTR. CITY DAT ONSHORE FAC. OFFSHORE CRUDE ABU ALI SAUDI ARABIA PLANT NO. INDEX 302 J.O. / EWO: B DRAWING NO. RE-018951 SHT.NO. REV.NO. 010 00 22H201-0001 EDSD/2616-0399.doc THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER. AMS PMT OPRNS DATA SHEET FOR ADDRESSABLE FIRE ALARM CONTROL PANEL GENERAL INFORMATION ENGG CERT SAUDI ARABIAN OIL COMPANY HMH Saudi Aramco 2616-ENG (03/99)